Running EnergyPlus, Building Envelope, Internal Loads, Reports[LINK]
Rectangular single story building
Windows in east and west walls
Single zone with no interior partitions
Lightweight construction
The details of the building construction and operation are shown in the following tables and description. For tutorial purposes, the building is located in Chicago Illinois, one of the weather files supplied with EnergyPlus. These details are listed in a fashion to make for easy entry into EnergyPlus.
Details of the exercise[LINK]
Surface Constructions[LINK]
| Walls |
|
|
|
|
|
|
| WOOD SIDING-1 |
0.140 |
0.009 |
15.556 |
0.064 |
530 |
900 |
| FIBERGLASS QUILT-1 |
0.040 |
0.066 |
0.606 |
1.650 |
12 |
840 |
| PLASTERBOARD-1 |
0.160 |
0.012 |
13.333 |
0.075 |
950 |
840 |
| Roof |
|
|
|
|
|
|
|
ROOF DECK |
0.140 |
0.019 |
7.368 |
0.136 |
530 |
900 |
| FIBERGLASS QUILT-2 |
0.040 |
0.066 |
0.606 |
1.650 |
12 |
840 |
| PLASTERBOARD-2 |
0.160 |
0.010 |
1.60 |
0.625 |
950 |
840 |
| Floor |
|
|
|
|
|
|
| C5 CONCRETE |
1.73 |
0.1015 |
17.04 |
0.059 |
2243 |
837 |
Window Properties[LINK]
| Number of panes |
2 |
| Pane thickness |
0.006 m |
| Air-gap thickness |
0.0032 m |
| Conductivity of glass |
0.9 W/m-K |
Refers to specific glass type included in the EnergyPlus datasets directory
(WindowGlassMaterials.idf)
Additional Model Details
| Internal Loads |
Lights (1000 W), Office Lighting schedule, surface mount fluorescent |
|
Space Conditioning |
Heating setpoint 20C, cooling setpoint 24C, no setback |
| Location |
Chicago, Illinois, USA; Summer and Winter design days |
| Simulation Period |
Annual, Jan 1 - Dec 31 |
| Ground Temperatures |
18.2 C to 22.5 C (from Slab preprocessor, vary monthly) |
Running EnergyPlus, Building Envelope, Internal Loads, Reports[LINK]
Overview[LINK]
Rectangular single story building
Windows in east and west walls
Single zone with no interior partitions
Lightweight construction
Schematic for Exercise 1
The details of the building construction and operation are shown in the following tables and description. For tutorial purposes, the building is located in Chicago Illinois, one of the weather files supplied with EnergyPlus. These details are listed in a fashion to make for easy entry into EnergyPlus.
Details of the exercise[LINK]
Surface Constructions[LINK]
Window Properties[LINK]
Refers to specific glass type included in the EnergyPlus datasets directory
(WindowGlassMaterials.idf)
Documentation content copyright © 1996-2022 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.