The following list of steps will outline the process for
converting an engineering line diagram into an EnergyPlus line
diagram. Throughout the process, the components in the systems
should be identified and named properly. It is easier to input
the system if a list of components and their names is
available.
1. Obtain an engineering line diagram for the
system.
2. Identify all the loops in the
system. Some systems may be very complex, but an
effort should be made to separate the system into its
constituent plant loops. A system may have multiple plant
loops. Therefore, proper documentation of the loops and their
components should be a priority.
3. Identify the demand side and supply side of
the individual loops. EnergyPlus expects the demand
side loop and supply side loop to be entered separately. Some
examples of simple plant loops are: a hot water heater (supply
component) connected to a heating coil (demand component), a
chiller (supply component) connected to a cooling coil (demand
component) or a cooling tower (supply component) connected to
a water cooled chiller (demand component). These loops may
have multiple supply components and multiple demand
components. A chiller may also be a supply or demand component
depending on the loop.
4. Identify the components in the
system. All the operating/active components, such as
chillers, pumps, cooling towers, thermal energy storage tanks,
heating and cooling coils, and other components should be
identified and named properly. It should be noted that even
though EnergyPlus has objects for modeling valves, they are
not often used. Instead the flow through a component is
regulated by using schedules, plant equipment operation
schemes and set points. Passive components such as inlet and
outlet pipes for each side of the loop should also be
identified, as they will help in modeling the loop
connectors.
5. Identify all the nodes in the
system. Nodes are necessary to connect the different
components in the system. Nodes define the starting and ending
points of branches as well as intermediate nodes on
multi-component branches. A good method to pin-point nodes on
the line diagram would be to put a node on either side of an
active or passive component. Note: If the outlet of one
component does not feed into a splitter or a mixer, then the
outlet node will be the same as the inlet node of the
downstream component.
6. Identify all the branches in the
loops. A good way to define a branch would be to
include at least one of the components in the branch. Branches
can accommodate multiple components in series, but parallel
components should be modeled on separate branches.
Operating/active components (except pumps) should be bypassed
by adding a bypass branch parallel to the branch containing
the active component. Multiple bypass branches in parallel can
be replaced by a single bypass branch.
7. Identify the position of the connectors in
the system. Connectors are an integral part of the
system and are important in constructing the loop. There are
two types of connectors, splitters and mixers. Splitters can
distribute the flow from a single branch into multiple
parallel branches. Mixers can combine the flow from multiple
branches into a single branch. As mentioned above, most
systems have multiple supply and demand side components, so
splitters and mixers play a crucial role in distributing and
recombining the flow of the working fluid through all the
components.
8. Generate an EnergyPlus diagram of
the whole system as well as the individual loops by using the
information gathered from the preceding steps.
A flowchart for this process is provided in Figure 1.1
.
Generating an EnergyPlus Line Diagram[LINK]
The following list of steps will outline the process for converting an engineering line diagram into an EnergyPlus line diagram. Throughout the process, the components in the systems should be identified and named properly. It is easier to input the system if a list of components and their names is available.
1. Obtain an engineering line diagram for the system.
2. Identify all the loops in the system. Some systems may be very complex, but an effort should be made to separate the system into its constituent plant loops. A system may have multiple plant loops. Therefore, proper documentation of the loops and their components should be a priority.
3. Identify the demand side and supply side of the individual loops. EnergyPlus expects the demand side loop and supply side loop to be entered separately. Some examples of simple plant loops are: a hot water heater (supply component) connected to a heating coil (demand component), a chiller (supply component) connected to a cooling coil (demand component) or a cooling tower (supply component) connected to a water cooled chiller (demand component). These loops may have multiple supply components and multiple demand components. A chiller may also be a supply or demand component depending on the loop.
4. Identify the components in the system. All the operating/active components, such as chillers, pumps, cooling towers, thermal energy storage tanks, heating and cooling coils, and other components should be identified and named properly. It should be noted that even though EnergyPlus has objects for modeling valves, they are not often used. Instead the flow through a component is regulated by using schedules, plant equipment operation schemes and set points. Passive components such as inlet and outlet pipes for each side of the loop should also be identified, as they will help in modeling the loop connectors.
5. Identify all the nodes in the system. Nodes are necessary to connect the different components in the system. Nodes define the starting and ending points of branches as well as intermediate nodes on multi-component branches. A good method to pin-point nodes on the line diagram would be to put a node on either side of an active or passive component. Note: If the outlet of one component does not feed into a splitter or a mixer, then the outlet node will be the same as the inlet node of the downstream component.
6. Identify all the branches in the loops. A good way to define a branch would be to include at least one of the components in the branch. Branches can accommodate multiple components in series, but parallel components should be modeled on separate branches. Operating/active components (except pumps) should be bypassed by adding a bypass branch parallel to the branch containing the active component. Multiple bypass branches in parallel can be replaced by a single bypass branch.
7. Identify the position of the connectors in the system. Connectors are an integral part of the system and are important in constructing the loop. There are two types of connectors, splitters and mixers. Splitters can distribute the flow from a single branch into multiple parallel branches. Mixers can combine the flow from multiple branches into a single branch. As mentioned above, most systems have multiple supply and demand side components, so splitters and mixers play a crucial role in distributing and recombining the flow of the working fluid through all the components.
8. Generate an EnergyPlus diagram of the whole system as well as the individual loops by using the information gathered from the preceding steps.
A flowchart for this process is provided in Figure 1.1 .