Building
heat transfer surfaces, such as roofs and walls, only cast
shadows in a hemisphere in the direction of the outward facing
normal (see Figure 1).
Because roof surfaces generally face upward, a roof surface
which extends beyond the walls of the building will not cast
shadows on the walls below it (see Figure 2).
Building heat transfer surfaces
cast shadows in the direction of outward facing
normal.Extended roof surface will not
shade the walls below.
Figure 3
shows the proper surface configurations for two types of attic
construction. In all cases, the roof surface should only
include the area of the roof which contacts the zone below it.
In these drawings, this is an unconditioned attic space, but
it could also be a conditioned zone. Any extensions of the
roof which are exposed to the outdoors on both sides should be
described as a shading surface.
For the configuration on the left, the overhang should be a
shading surface which will cast shadows in both directions (if
the default mirroring is disabled the shading surface must
face downward). This ensures that the correct shading will be
modeled, and it also avoids overstating the heat transfer
through the roof into the attic.
For the configuration on the right, the attic is fully
enclosed with building heat transfer surfaces for the roof and
soffits. The soffits would be described as floor surfaces in
the attic and would face downward. The central portion of the
attic floor would be described as an interzone floor surface
where the outside boundary condition is the ceiling surface in
the zone below.
Proper surface configurations
for roof overhangs for two types of attic
construction.
Describing Roof Overhangs[LINK]
Building heat transfer surfaces, such as roofs and walls, only cast shadows in a hemisphere in the direction of the outward facing normal (see Figure 1). Because roof surfaces generally face upward, a roof surface which extends beyond the walls of the building will not cast shadows on the walls below it (see Figure 2).
Figure 3 shows the proper surface configurations for two types of attic construction. In all cases, the roof surface should only include the area of the roof which contacts the zone below it. In these drawings, this is an unconditioned attic space, but it could also be a conditioned zone. Any extensions of the roof which are exposed to the outdoors on both sides should be described as a shading surface.
For the configuration on the left, the overhang should be a shading surface which will cast shadows in both directions (if the default mirroring is disabled the shading surface must face downward). This ensures that the correct shading will be modeled, and it also avoids overstating the heat transfer through the roof into the attic.
For the configuration on the right, the attic is fully enclosed with building heat transfer surfaces for the roof and soffits. The soffits would be described as floor surfaces in the attic and would face downward. The central portion of the attic floor would be described as an interzone floor surface where the outside boundary condition is the ceiling surface in the zone below.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.