System not Cooling[LINK]
I built a very simple system 5 zones VAV no reheat to
understand how a E+ system is put together. The results show
that the cooling coil is not seeing a load. I then build the
same HVACTemplate system and made sure all the details are
exactly the same. The template works but not my
system.
It is much easier to use HVACTemplate objects to set up
your system. All required supporting objects are set up for
you. Notice in your 5Zone input file, you have specified
AHU1CCController for BOTH cooling coil controller lists. The
second controller list should use controller name
AHU2CCController. The 5Zone file worked when I used the
correct controller name.
AirLoopHVAC:ControllerList,
AHU1SystemController, !- Name
Controller:WaterCoil, !- Controller Type 1
AHU1CCController; !- Controller Name 1
AirLoopHVAC:ControllerList,
AHU2SystemController, !- Name
Controller:WaterCoil, !- Controller Type 1
AHU1CCController; !- Controller Name 1
System not Cooling[LINK]
I built a very simple system 5 zones VAV no reheat to understand how a E+ system is put together. The results show that the cooling coil is not seeing a load. I then build the same HVACTemplate system and made sure all the details are exactly the same. The template works but not my system.
It is much easier to use HVACTemplate objects to set up your system. All required supporting objects are set up for you. Notice in your 5Zone input file, you have specified AHU1CCController for BOTH cooling coil controller lists. The second controller list should use controller name AHU2CCController. The 5Zone file worked when I used the correct controller name.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.