Undisturbed
Ground Temperature Model: Xing[LINK]
This model uses the correlation developed by Xing, 2014 to
predict undisturbed ground temperature. The correlation
parameters for 4000+ international locations can be found in
Xing, 2014. The parameters were first determined by creating
and validating a finite difference numerical model which used
local weather data for boundary conditions. From the numerical
model, the correlation parameters were determined to provide
for this simplified design model.
\[T(z,t) = \bar{T}_{s} - \sum_{n
= 1}^{2} \Delta\bar{T}_{s,n} \cdot e^{-z \cdot
\sqrt{\frac{n\pi}{\alpha\tau}}} \cdot cos\left[ \frac{2 \pi
n}{\tau} \left(t - \theta_{n} \right) - z \sqrt{\frac{n
\pi}{\alpha \tau}} \right]\]
\(T(z,t)\) is the
undisturbed ground temperature as a function of time and
depth
\(\bar{T}_{s}\) is the
average annual soil surface temperature, in deg C
\(\Delta\bar{T}_{s,n}\) is
the n-th amplitude of the soil temperature change throughout
the year, in deg C
\(\theta_{n}\) is the n-th
phase shift, or day of minimum surface temperature
\(\alpha\) is the thermal
diffusivity of the ground
\(\tau\) is time constant,
365.
Xing, L. 2014. Estimations of Undisturbed Ground
Temperatures using Numerical and Analytical Modeling.
Ph.D. Diss. Oklahoma State University, Stillwater, OK.
Undisturbed Ground Temperature Model: Xing[LINK]
Approach[LINK]
This model uses the correlation developed by Xing, 2014 to predict undisturbed ground temperature. The correlation parameters for 4000+ international locations can be found in Xing, 2014. The parameters were first determined by creating and validating a finite difference numerical model which used local weather data for boundary conditions. From the numerical model, the correlation parameters were determined to provide for this simplified design model.
\[T(z,t) = \bar{T}_{s} - \sum_{n = 1}^{2} \Delta\bar{T}_{s,n} \cdot e^{-z \cdot \sqrt{\frac{n\pi}{\alpha\tau}}} \cdot cos\left[ \frac{2 \pi n}{\tau} \left(t - \theta_{n} \right) - z \sqrt{\frac{n \pi}{\alpha \tau}} \right]\]
\(T(z,t)\) is the undisturbed ground temperature as a function of time and depth
\(\bar{T}_{s}\) is the average annual soil surface temperature, in deg C
\(\Delta\bar{T}_{s,n}\) is the n-th amplitude of the soil temperature change throughout the year, in deg C
\(\theta_{n}\) is the n-th phase shift, or day of minimum surface temperature
\(\alpha\) is the thermal diffusivity of the ground
\(\tau\) is time constant, 365.
References[LINK]
Xing, L. 2014. Estimations of Undisturbed Ground Temperatures using Numerical and Analytical Modeling. Ph.D. Diss. Oklahoma State University, Stillwater, OK.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.