The generated curves are post-processed to make sure that
the curve value is 1.0 at the rated condition. The post
processing is applied only if the curve value at the rated
condition deviates by a value less than or equal to 0.025 and
the performance data set contains the rated data set as one
the data points. The coefficients of these curves are
displayed on the “OUTPUT” tab as shown in Figure [fig:delta-db-trigger-selection].
Curve Fit Tool Output Interface
[fig:curve-fit-tool-output-interface]
Besides the curve coefficients, the goodness of curve fit
indicator statistical parameters R\(^{2}\) is also reported. The
R\(^{2}\) is the
ratio of the sum of the squared deviations of the curve fit
values from the mean to the sum of the squared deviations of
the original data from the mean. R squared values closer to
1.0 are good. The tool has an option to save the curve objects
to an output file by running another macro
(SaveCurveObjToTextFile). The option output files and the
directory path are specified in the OUPUT tab in cells C2 and
C3, respectively, as shown in Figure 1. If
the output file name and path are left blank, then default
names, “EplusCurveObjects.IDF” and the local directory where
the tool is located are used. The local directory where the
tool is located must not have write restriction.
Sample EnergyPlus curve objects output file generated using
this auxiliary tool.
Curve:Biquadratic,
HeatPumpCoolingCAPFTemp, !- Name
1.4248528695, !- Coefficient1 Constant
-0.0554469607, !- Coefficient2 x
0.0027506982, !- Coefficient3 x**2
-0.0017453896, !- Coefficient4 y
-0.0000081, !- Coefficient5 y**2
-0.0004638975, !- Coefficient6 x*y
13.8888888889, !- Minimum Value of x
22.2222222222, !- Maximum Value of x
29.4444444444, !- Minimum Value of y
46.1111111111, !- Maximum Value of y
0.7875, !- Minimum Curve Output
1.1725, !- Maximum Curve Output
Temperature, !- Input Unit Type for X
Temperature, !- Input Unit Type for Y
Dimensionless; !- Output Unit Type
Curve:Biquadratic,
HeatPump1CoolingEIRFTemp, !- Name
0.1566419771, !- Coefficient1 Constant
0.0522807347, !- Coefficient2 x
-0.0017986792, !- Coefficient3 x**2
0.009523995, !- Coefficient4 y
0.0002405903, !- Coefficient5 y**2
-0.0001781171, !- Coefficient6 x*y
13.8888888889, !- Minimum Value of x
22.2222222222, !- Maximum Value of x
29.4444444444, !- Minimum Value of y
46.1111111111, !- Maximum Value of y
0.8216, !- Minimum Curve Output
1.3703, !- Maximum Curve Output
Temperature, !- Input Unit Type for X
Temperature, !- Input Unit Type for Y
Dimensionless; !- Output Unit Type
Outputs[LINK]
The generated curves are post-processed to make sure that the curve value is 1.0 at the rated condition. The post processing is applied only if the curve value at the rated condition deviates by a value less than or equal to 0.025 and the performance data set contains the rated data set as one the data points. The coefficients of these curves are displayed on the “OUTPUT” tab as shown in Figure [fig:delta-db-trigger-selection].
Besides the curve coefficients, the goodness of curve fit indicator statistical parameters R\(^{2}\) is also reported. The R\(^{2}\) is the ratio of the sum of the squared deviations of the curve fit values from the mean to the sum of the squared deviations of the original data from the mean. R squared values closer to 1.0 are good. The tool has an option to save the curve objects to an output file by running another macro (SaveCurveObjToTextFile). The option output files and the directory path are specified in the OUPUT tab in cells C2 and C3, respectively, as shown in Figure 1. If the output file name and path are left blank, then default names, “EplusCurveObjects.IDF” and the local directory where the tool is located are used. The local directory where the tool is located must not have write restriction.
Sample EnergyPlus curve objects output file generated using this auxiliary tool.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.