Infiltration/Ventilation[LINK]
Any outdoor air that enters by way of infiltration is
assumed to be immediately mixed with the zone air. The
determination of the amount of infiltration air is quite
complicated and subject to significant uncertainty. In the
most common procedure, the infiltration quantity is converted
from a number of air changes per hour (ACH) and included in
the zone air heat balance using the outside temperature at the
current simulation time step.
EnergyPlus contains three models for infiltration. The
first is the “Design Flow Rate” model that was inherited from
EnergyPlus’ predecessor programs. It is accessed through the
ZoneInfiltration:DesignFlowRate
object and is based on environmental conditions modifying a
design flow rate. The second is the “Effective Leakage Area”
model based on Sherman and Grimsrud (1980) and accessed using
the ZoneInfiltration:EffectiveLeakageArea
input object. The third is the “Flow Coefficient” model based
on Walker and Wilson (1998) and accessed using the ZoneInfiltration:FlowCoefficient
input object. The model formulations for the Effective Leakage
Area and Flow Coefficient models are from the ASHRAE Handbook
of Fundamentals (2001 Chapter 26; 2005 Chapter 27) where they
are referred to as “Basic” and “Enhanced”, respectively.
Infiltration Design
Flow Rate[LINK]
Infiltration (Ref Object: ZoneInfiltration:DesignFlowRate)
is the unintended flow of air from the outdoor environment
directly into a thermal zone. Infiltration is generally caused
by the opening and closing of exterior doors, cracks around
windows, and even in very small amounts through building
elements. In this model, the user defines a design flow rate
that can be modified by temperature differences and windspeed.
The basic equation (Coblenz and Achenbach 1963) used to
calculate infiltration with this model is:
\[Infiltration = \left(
{{I_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A
+ B\left| {\left( {{T_{zone}} - {T_{odb}}} \right)} \right| +
C\left( {WindSpeed} \right) + D\left( {Windspee{d^2}} \right)}
\right]\]
The \(Infiltration\)
volume flow rate is converted to mass flow rate using the
density basis specified in the input: outdoor (the default),
standard, or indoor.
More advanced infiltration calculations are possible using
the EnergyPlus AirflowNetwork model for natural infiltration
driven by wind when the HVAC system does not operate and/or
driven by wind and forced air for times when the HVAC system
operates. Exfiltration (the leakage of zone air to the
outside) is generally handled better as zone exhaust air in
the zone equipment description.
The question of typical values for these coefficients is
subject to debate. Ideally, one should do a detailed analysis
of the infiltration situation and then determine a custom set
of coefficients using methods such as those laid out in
Chapter 26 of the ASHRAE Handbook of Fundamentals. The
EnergyPlus defaults are 1,0,0,0 which gives a constant volume
flow of infiltration under all conditions.
BLAST (one of the EnergyPlus predecessors) used the
following values as defaults: 0.606, 0.03636, 0.1177, 0.
These coefficients produce a value of 1.0 at 0\(^{\circ}\)C deltaT and 3.35 m/s
(7.5 mph) windspeed, which corresponds to a typical summer
condition. At a winter condition of 40\(^{\circ}\)C deltaT and 6 m/s
(13.4 mph) windspeed, these coefficients would increase the
infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change
method defaults are (adjusted to SI units) 0, 0, 0.224
(windspeed), 0. With these coefficients, the summer conditions
above would give a factor of 0.75, and the winter conditions
would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a
factor of 1.0.
The source of the BLAST defaults is noted in the BLAST
documentation as:
“Empirical equation and the coefficient default were
determined from ASHRAE journal articles and other data on the
effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the
infiltration relationships described in the ASHRAE Handbook of
Fundamentals.
The EnergyPlus example files use all of the above, the
BLAST defaults in some (e.g., GeometryTest), the DOE-2
defaults in some (e.g., 5ZoneAirCooled), and the EnergyPlus
defaults in some (e.g., LgOffVAVDetCoil).
Infiltration
by Effective Leakage Area[LINK]
The Effective Leakage Area model is based on Sherman and
Grimsrud (1980) and accessed using the ZoneInfiltration:EffectiveLeakageArea
input object. The model formulation used in EnergyPlus is
from the ASHRAE Handbook of Fundamentals (2001 Chapter 26;
2005 Chapter 27) where it is referred to as the “Basic”
model.
The Effective Leakage Area, or Sherman-Grimsrud, model
is:
\[Infiltration = \left(
{{F_{Schedule}}} \right)\frac{{{A_L}}}{{1000}}\sqrt
{{C_s}\Delta T + {C_w}{{\left( {WindSpeed}
\right)}^2}}\]
where,
\({F_{schedule}}\) is a
value from a user-defined schedule,
\({A_L}\) is the
effective air leakage area in cm\(^{2}\) that corresponds to a 4 Pa
pressure differential,
\({C_s}\) is the
coefficient for stack-induced infiltration in (L/s)\(^{2}\)/(cm\(^{4}\cdot\)K),
\(\Delta T\) is the
absolute temperature difference between zone air and outdoor
air,
\({C_w}\) is the
coefficient for wind-induced infiltration in (L/s)\(^{2}\)/(cm\(^{4}\cdot\)(m/s)\(^{2}\)), and
\(WindSpeed\) is the
local wind speed.
Infiltration by Flow
Coefficient[LINK]
The Flow Coefficient model is based on Walker and Wilson
(1998) and accessed using the ZoneInfiltration:FlowCoefficient
input object. The model formulation used in EnergyPlus is
from the ASHRAE Handbook of Fundamentals (2001 Chapter 26;
2005 Chapter 27) where it is referred to as the “Enhanced” or
“AIM-2” model.
The Enhanced, or AIM-2, model is:
\[Infiltration = \left(
{{F_{Schedule}}} \right)\sqrt {{{\left( {c\,{C_s}\Delta {T^n}}
\right)}^2} + {{\left( {c\,{C_w}{{\left( {s * WindSpeed}
\right)}^{2n}}} \right)}^2}}\]
where,
\({F_{schedule}}\) is a
value from a user-defined schedule,
\(c\) is the flow
coefficient in m\(^{3}\)/(s\(\cdot\)Pa\(^{n}\)),
\({C_s}\) is the
coefficient for stack-induced infiltration in (Pa/K)\(^{n}\),
\(n\) is the pressure
exponent,
\({C_w}\) is the
coefficient for wind-induced infiltration in (Pa\(\cdot\)s\(^{2}\)/m\(^{2}\))\(^{n}\), and
\(s\) is the shelter
factor.
Coblenz, C. W. and Achenbach, P. R. 1963. Field Measurement
of Ten Electrically-Heated Houses. ASHRAE Transactions pp
358-365.
Sherman, M.H. and D.T. Grimsrud. 1980.
Infiltration-pressurization correlation: Simplified physical
modeling. ASHRAE Transactions 86(2):778
Walker, I.S., and D.J. Wilson. 1998. Field validation of
equations for stack and wind driven air infiltration
calculations. International Journal of HVAC&R Research
4(2).
ASHRAE Handbook of Fundamentals. 2005. Chapter 27. (and
2001 Chapter 26).
EnergyPlus contains two models for ventilation. The
“Design Flow Rate” model, inherited from EnergyPlus’
predecessor programs, is accessed through the ZoneVentilation:DesignFlowRate
object and is based on environmental conditions modifying a
design flow rate. The “Wind and Stack with Open Area” model,
based on equations defined in Chapter 16 of the 2009 ASHRAE
Handbook of Fundamentals, is accessed using the ZoneVentilation:WindandStackOpenArea
input object. Since the “Wind and Stack with Open Area” object
requires the height difference between the midpoint of the
lower opening and the neutral pressure level, which is
difficult to estimate, this object should be used with care
(e.g., research only).
These two ventilation objects can be used alone or in
combination to determine ventilation air for a zone. If
multiple ZoneVentilation:* objects are specified for a zone,
then the total zone ventilation flow rate is the sum of the
ventilation air flow rates calculated by each ZoneVentilation
object.
Ventilation Design Flow
Rate[LINK]
Ventilation (Ref Object: ZoneVentilation:DesignFlowRate) is
the purposeful flow of air from the outdoor environment
directly into a thermal zone in order to provide some amount
of non-mechanical cooling. Ventilation as specified by this
input syntax is intended to model “simple” ventilation as
opposed to the more detailed ventilation investigations that
can be performed with the AirflowNetwork model. Simple
ventilation in EnergyPlus can be controlled by a schedule and
through the specification of minimum, maximum and delta
temperatures. The temperatures can be either single constant
values for the entire simulation or schedules which can vary
over time. Specific details are given in the Input/Output
reference document. As with infiltration, the actual flow rate
of ventilation can be modified by the temperature difference
between the inside and outside environment and the wind speed.
The basic equation used to calculate ventilation using this
model is:
\[Ventilation = \left(
{{V_{design}}} \right)\left( {{F_{schedule}}}
\right)\left\lfloor {A + B\left| {{T_{zone}} - {T_{odb}}}
\right| + C\left( {WindSpeed} \right) + D\left(
{WindSpee{d^2}} \right)} \right\rfloor\]
The \(Ventilation\) volume
flow rate is converted to mass flow rate using the density
basis specified in the input: outdoor (the default), standard,
or indoor.
More advanced ventilation calculations are possible using
the EnergyPlus AirflowNetwork model.
The following description is copied from the Infiltration
discussion above. The question of typical values for these
coefficients is subject to debate. Ideally, one should do a
detailed analysis of the ventilation situation and then
determine a custom set of coefficients using methods such as
those laid out in Chapter 26 of the ASHRAE Handbook of
Fundamentals. The EnergyPlus defaults are 1,0,0,0 which gives
a constant volume flow of ventilation under all
conditions.
BLAST (one of the EnergyPlus predecessors) used the
following values as defaults: 0.606, 0.03636, 0.1177, 0.
These coefficients produce a value of 1.0 at 0\(^{\circ}\)C deltaT and 3.35 m/s
(7.5 mph) windspeed, which corresponds to a typical summer
condition. At a winter condition of 40\(^{\circ}\)C deltaT and 6 m/s
(13.4 mph) windspeed, these coefficients would increase the
ventilation rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change
method defaults are (adjusted to SI units) 0, 0, 0.224
(windspeed), 0. With these coefficients, the summer conditions
above would give a factor of 0.75, and the winter conditions
would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a
factor of 1.0.
The source of the BLAST defaults is noted in the BLAST
documentation as:
“Empirical equation and the coefficient default were
determined from ASHRAE journal articles and other data on the
effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the
infiltration relationships described in the ASHRAE Handbook of
Fundamentals.
The EnergyPlus example files use all of the above, the
BLAST defaults in some (e.g., AirflowNetwork_Simple_house),
the DOE-2 defaults in some (e.g., VentilationSimpleTest – has
all 3), and the EnergyPlus defaults in some (e.g.,
5ZoneNightVent2).
Ventilation
by Wind and Stack with Open Area[LINK]
For this model (Ref Object:
ZoneVentilation:WindandStackOpenArea), the ventilation air
flow rate is a function of wind speed and thermal stack
effect, along with the area of the opening being modeled. This
object can be used alone or in combination with ZoneVentilation:DesignFlowRate
objects. This model is intended for simplified ventilation
calculations as opposed to the more detailed ventilation
investigations that can be performed with the AirflowNetwork
model. Using the “Wind and Stack with Open Area” model, the
natural ventilation flow rate can be controlled by a
multiplier fraction schedule applied to the user-defined
opening area and through the specification of minimum, maximum
and delta temperatures. The temperatures can be either single
constant values for the entire simulation or schedules which
can vary over time. The equation used to calculate the
ventilation rate driven by wind is given by Equation 37 in
Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals:
\[{Q_w} =
{C_w}{A_{opening}}{F_{schedule}}V\]
where
Q\(_{w}\) =
Volumetric air flow rate driven by wind [m\(^{3}\)/s]
C\(_{w}\) =
Opening effectiveness [dimensionless]
A\(_{opening}\)
= Opening area [m\(^{2}\)]
F\(_{schedule}\)
= Open area fraction [user-defined schedule value,
dimensionless]
V = Local wind speed [m/s]
If the user specifies “Autocalculate” for the Opening
Effectiveness input field, the opening effectiveness is
calculated for each simulation time step based on the angle
between the actual wind direction and the Effective Angle (a
user-defined input) using the following equation:
\[{C_w} = 0.55 - \frac{{\left|
{EffectiveAngle - WindDirection}
\right|}}{{180}}*0.25\]
The difference EffectiveAngle – WindDirection should be
between 0 and 180 degrees. If the difference EffectivAngle –
WindDirection is greater than 180, the difference is reset to
be minus 180 degrees. This equation is a linear interpolation
using the values recommended by the 2009 ASHRAE Handbook of
Fundamentals (page 16.13): 0.5 to 0.6 for perpendicular winds
and 0.25 to 0.35 for diagonal winds.
The equation used for calculating the ventilation rate due
to stack effect is given by Equation 38 in Chapter 16 of the
2009 ASHRAE Handbook of Fundamentals:
\[{Q_s} =
{C_D}{A_{opening}}{F_{schedule}}\sqrt {2g\Delta
{H_{NPL}}(|{T_{zone}} - {T_{odb}}|/{T_{zone}})}\]
where,
Q\(_{s}\) =
Volumetric air flow rate due to stack effect [m\(^{3}\)/s]
C\(_{D}\) =
Discharge coefficient for opening [dimensionless]
A\(_{opening}\)
= Opening area [m\(^{2}\)]
F\(_{schedule}\)
= Open area fraction [user-defined schedule value,
dimensionless]
\(\Delta\)H\(_{NPL}\) = Height from
midpoint of lower opening to the neutral pressure level [m].
Estimation of this value is difficult; refer to Chapter 16 of
the 2009 ASHRAE Handbook of Fundamentals for guidance.
T\(_{zone}\) =
Zone
air dry-bulb temperature [K]
T\(_{odb}\) =
Local outdoor air dry-bulb temperature [K]
The following equation, given by Equation 39 in Chapter 16
of the 2009 ASHRAE Handbook of Fundamentals, is used to
calculate the Discharge Coefficient for Opening when the user
sets the value for this input field to “Autocalculate”:
\[{C_D} = 0.40 + 0.0045\left|
{{T_{zone}} - {T_{odb}}} \right|\]
The total ventilation rate calculated by this model is the
quadrature sum of the wind and stack air flow components:
\[Ventilatio{n_{WindAndStack}} =
\sqrt {{Q_s}^2 + {Q_w}^2}\]
If desired, a simple summation, instead of quadrature
summation, can be realized by inputting two
ZoneVentilation:WindAndStackOpenArea objects. One object can
be defined with only a wind-driven component by setting C\(_{D}\) = 0, and the other object
can have only stack-effect inputs specified and set C\(_{w}\) = 0.
Zone
Air Balance Outdoor Airflow (ZoneAirBalance:OutdoorAir)[LINK]
ASHRAE 2009 Handbook of Fundamentals specifies that any
unbalanced supply or exhaust ventilation air, Q\(_{u,v}\), to a zone causes
pressurization/depressurization that influences the flow of
infiltration air and thus should be combined with natural
infiltration, Q\(_{n}\),
(and, if present, unbalanced duct leakage, Qu,l) in
superposition. Balanced ventilation airflow, Q\(_{b,v}\), to a zone (such as an
ERV or HRV with balanced exhaust and intake air flows) does
not interact with infiltration air and is added in whole:
\[Q = \sqrt {{Q_n}^2 +
{Q_{u,v}}^2 + ({Q_{u,l}}^2)} + {Q_{b,v}}\]
where,
Q = Combined outdoor airflow with infiltration,
balanced and unbalanced outdoor air flows, and unbalanced duct
leakage [m\(^{3}\)/s]
Q\(_{n}\) =
Natural infiltration airflow [m\(^{3}\)/s]
Q\(_{b,v}\) =
Balanced ventilation airflow, excluding infiltration [m\(^{3}\)/s]
Q\(_{u,v}\) =
Unbalanced ventilation airflow, excluding infiltration [m\(^{3}\)/s]
Q\(_{u,l}\) =
Unbalanced duct leakage: the difference between supply and
return leaks [m\(^{3}\)/s]
The natural infiltration airflow includes all outdoor
airflows from all ZoneInfiltration objects for the same
zone.
\[{Q_n} = \sum\limits_i
{{Q_{Infiltration,i}}}\]
where
Q\(_{Infiltration,i}\) =
Outdoor airflow rate given in the ith ZoneInfiltration objects
for the same zone
The balanced ventilation airflow is the sum of outdoor
airflows from all ZoneVentilation: DesignFlowRate objects with
Ventilation Type = Balanced:
\[{Q_{b,v}} = \sum\limits_i
{{Q_{v,Balanced,i}}}\]
where
Q\(_{v,Balanced,i}\) =
Ventilation rate with “Balanced” ventilation type defined in
the ith ZoneVentilation:DesignFlowRate
object for the same zone
The unbalanced ventilation airflow is given by the
following equation:
\[{Q_{u,v}} = {\left[ {{{\left(
{\sum\limits_i {{Q_{v,Natural,i}}} + \sum\limits_i
{{Q_{v,Wind,i}}} } \right)}^2} + {{\left( {\sum\limits_i
{{Q_{v,Intake,i}}} } \right)}^2} + {{\left( {\sum\limits_i
{{Q_{v,Exhaust,i}}} } \right)}^2} + {{\left( {\sum\limits_i
{Max\left( {0,\;({Q_{ERV,Exh,i}} - {Q_{ERV,Sup,i}})} \right)}
} \right)}^2}} \right]^{0.5}}\]
where
Q\(_{v,Exhaust,i}\) =
Ventilation rate with “Exhaust” type in the ith ZoneVentilation:DesignFlowRate
object for the same zone
Q\(_{v,Intake,i}\) =
Ventilation rate with “Intake” type in the ith ZoneVentilation:DesignFlowRate
object for the same zone
Q\(_{v,Natural,i}\) =
Ventilation rate with “Natural” type in the ith ZoneVentilation:DesignFlowRate
object for the same zone
Q\(_{v,Wind,v}\)
= Ventilation rate in the ith ZoneVentilation:WindandStackOpenArea
object for the same zone
Q\(_{ERV,Sup,i}\) = Supply
flow rate given in the ith ZoneHVAC:EnergyRecoveryVentilator
object
Q\(_{ERV,Exh,i}\) = Exhaust
flow rate given in the ith ZoneHVAC:EnergyRecoveryVentilator
object
For Ventilation Type = Intake in the ZoneVentilation:DesignFlowRate
object, an appropriate amount of fan heat will be ignored and
the outdoor temperature will be used in the zone air heat
balance equation.
This object provides a simple airflow interaction model
without having to use the AirflowNetwork capabilities, when
the Air Balance Method is specified as Quadrature.
ASHRAE. 2009. 2009 ASHRAE Handbook – Fundamentals, Chapter
16, Atlanta: American Society of Heating, Refrigerating, and
Air-Conditioning Engineers, Inc.
Infiltration/Ventilation[LINK]
Infiltration[LINK]
Any outdoor air that enters by way of infiltration is assumed to be immediately mixed with the zone air. The determination of the amount of infiltration air is quite complicated and subject to significant uncertainty. In the most common procedure, the infiltration quantity is converted from a number of air changes per hour (ACH) and included in the zone air heat balance using the outside temperature at the current simulation time step.
EnergyPlus contains three models for infiltration. The first is the “Design Flow Rate” model that was inherited from EnergyPlus’ predecessor programs. It is accessed through the ZoneInfiltration:DesignFlowRate object and is based on environmental conditions modifying a design flow rate. The second is the “Effective Leakage Area” model based on Sherman and Grimsrud (1980) and accessed using the ZoneInfiltration:EffectiveLeakageArea input object. The third is the “Flow Coefficient” model based on Walker and Wilson (1998) and accessed using the ZoneInfiltration:FlowCoefficient input object. The model formulations for the Effective Leakage Area and Flow Coefficient models are from the ASHRAE Handbook of Fundamentals (2001 Chapter 26; 2005 Chapter 27) where they are referred to as “Basic” and “Enhanced”, respectively.
Infiltration Design Flow Rate[LINK]
Infiltration (Ref Object: ZoneInfiltration:DesignFlowRate) is the unintended flow of air from the outdoor environment directly into a thermal zone. Infiltration is generally caused by the opening and closing of exterior doors, cracks around windows, and even in very small amounts through building elements. In this model, the user defines a design flow rate that can be modified by temperature differences and windspeed. The basic equation (Coblenz and Achenbach 1963) used to calculate infiltration with this model is:
\[Infiltration = \left( {{I_{design}}} \right)\left( {{F_{schedule}}} \right)\left[ {A + B\left| {\left( {{T_{zone}} - {T_{odb}}} \right)} \right| + C\left( {WindSpeed} \right) + D\left( {Windspee{d^2}} \right)} \right]\]
The \(Infiltration\) volume flow rate is converted to mass flow rate using the density basis specified in the input: outdoor (the default), standard, or indoor.
More advanced infiltration calculations are possible using the EnergyPlus AirflowNetwork model for natural infiltration driven by wind when the HVAC system does not operate and/or driven by wind and forced air for times when the HVAC system operates. Exfiltration (the leakage of zone air to the outside) is generally handled better as zone exhaust air in the zone equipment description.
The question of typical values for these coefficients is subject to debate. Ideally, one should do a detailed analysis of the infiltration situation and then determine a custom set of coefficients using methods such as those laid out in Chapter 26 of the ASHRAE Handbook of Fundamentals. The EnergyPlus defaults are 1,0,0,0 which gives a constant volume flow of infiltration under all conditions.
BLAST (one of the EnergyPlus predecessors) used the following values as defaults: 0.606, 0.03636, 0.1177, 0. These coefficients produce a value of 1.0 at 0\(^{\circ}\)C deltaT and 3.35 m/s (7.5 mph) windspeed, which corresponds to a typical summer condition. At a winter condition of 40\(^{\circ}\)C deltaT and 6 m/s (13.4 mph) windspeed, these coefficients would increase the infiltration rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change method defaults are (adjusted to SI units) 0, 0, 0.224 (windspeed), 0. With these coefficients, the summer conditions above would give a factor of 0.75, and the winter conditions would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a factor of 1.0.
The source of the BLAST defaults is noted in the BLAST documentation as:
“Empirical equation and the coefficient default were determined from ASHRAE journal articles and other data on the effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the infiltration relationships described in the ASHRAE Handbook of Fundamentals.
The EnergyPlus example files use all of the above, the BLAST defaults in some (e.g., GeometryTest), the DOE-2 defaults in some (e.g., 5ZoneAirCooled), and the EnergyPlus defaults in some (e.g., LgOffVAVDetCoil).
Infiltration by Effective Leakage Area[LINK]
The Effective Leakage Area model is based on Sherman and Grimsrud (1980) and accessed using the ZoneInfiltration:EffectiveLeakageArea input object. The model formulation used in EnergyPlus is from the ASHRAE Handbook of Fundamentals (2001 Chapter 26; 2005 Chapter 27) where it is referred to as the “Basic” model.
The Effective Leakage Area, or Sherman-Grimsrud, model is:
\[Infiltration = \left( {{F_{Schedule}}} \right)\frac{{{A_L}}}{{1000}}\sqrt {{C_s}\Delta T + {C_w}{{\left( {WindSpeed} \right)}^2}}\]
where,
\({F_{schedule}}\) is a value from a user-defined schedule,
\({A_L}\) is the effective air leakage area in cm\(^{2}\) that corresponds to a 4 Pa pressure differential,
\({C_s}\) is the coefficient for stack-induced infiltration in (L/s)\(^{2}\)/(cm\(^{4}\cdot\)K),
\(\Delta T\) is the absolute temperature difference between zone air and outdoor air,
\({C_w}\) is the coefficient for wind-induced infiltration in (L/s)\(^{2}\)/(cm\(^{4}\cdot\)(m/s)\(^{2}\)), and
\(WindSpeed\) is the local wind speed.
Infiltration by Flow Coefficient[LINK]
The Flow Coefficient model is based on Walker and Wilson (1998) and accessed using the ZoneInfiltration:FlowCoefficient input object. The model formulation used in EnergyPlus is from the ASHRAE Handbook of Fundamentals (2001 Chapter 26; 2005 Chapter 27) where it is referred to as the “Enhanced” or “AIM-2” model.
The Enhanced, or AIM-2, model is:
\[Infiltration = \left( {{F_{Schedule}}} \right)\sqrt {{{\left( {c\,{C_s}\Delta {T^n}} \right)}^2} + {{\left( {c\,{C_w}{{\left( {s * WindSpeed} \right)}^{2n}}} \right)}^2}}\]
where,
\({F_{schedule}}\) is a value from a user-defined schedule,
\(c\) is the flow coefficient in m\(^{3}\)/(s\(\cdot\)Pa\(^{n}\)),
\({C_s}\) is the coefficient for stack-induced infiltration in (Pa/K)\(^{n}\),
\(n\) is the pressure exponent,
\({C_w}\) is the coefficient for wind-induced infiltration in (Pa\(\cdot\)s\(^{2}\)/m\(^{2}\))\(^{n}\), and
\(s\) is the shelter factor.
References:[LINK]
Coblenz, C. W. and Achenbach, P. R. 1963. Field Measurement of Ten Electrically-Heated Houses. ASHRAE Transactions pp 358-365.
Sherman, M.H. and D.T. Grimsrud. 1980. Infiltration-pressurization correlation: Simplified physical modeling. ASHRAE Transactions 86(2):778
Walker, I.S., and D.J. Wilson. 1998. Field validation of equations for stack and wind driven air infiltration calculations. International Journal of HVAC&R Research 4(2).
ASHRAE Handbook of Fundamentals. 2005. Chapter 27. (and 2001 Chapter 26).
Ventilation[LINK]
EnergyPlus contains two models for ventilation. The “Design Flow Rate” model, inherited from EnergyPlus’ predecessor programs, is accessed through the ZoneVentilation:DesignFlowRate object and is based on environmental conditions modifying a design flow rate. The “Wind and Stack with Open Area” model, based on equations defined in Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals, is accessed using the ZoneVentilation:WindandStackOpenArea input object. Since the “Wind and Stack with Open Area” object requires the height difference between the midpoint of the lower opening and the neutral pressure level, which is difficult to estimate, this object should be used with care (e.g., research only).
These two ventilation objects can be used alone or in combination to determine ventilation air for a zone. If multiple ZoneVentilation:* objects are specified for a zone, then the total zone ventilation flow rate is the sum of the ventilation air flow rates calculated by each ZoneVentilation object.
Ventilation Design Flow Rate[LINK]
Ventilation (Ref Object: ZoneVentilation:DesignFlowRate) is the purposeful flow of air from the outdoor environment directly into a thermal zone in order to provide some amount of non-mechanical cooling. Ventilation as specified by this input syntax is intended to model “simple” ventilation as opposed to the more detailed ventilation investigations that can be performed with the AirflowNetwork model. Simple ventilation in EnergyPlus can be controlled by a schedule and through the specification of minimum, maximum and delta temperatures. The temperatures can be either single constant values for the entire simulation or schedules which can vary over time. Specific details are given in the Input/Output reference document. As with infiltration, the actual flow rate of ventilation can be modified by the temperature difference between the inside and outside environment and the wind speed. The basic equation used to calculate ventilation using this model is:
\[Ventilation = \left( {{V_{design}}} \right)\left( {{F_{schedule}}} \right)\left\lfloor {A + B\left| {{T_{zone}} - {T_{odb}}} \right| + C\left( {WindSpeed} \right) + D\left( {WindSpee{d^2}} \right)} \right\rfloor\]
The \(Ventilation\) volume flow rate is converted to mass flow rate using the density basis specified in the input: outdoor (the default), standard, or indoor.
More advanced ventilation calculations are possible using the EnergyPlus AirflowNetwork model.
The following description is copied from the Infiltration discussion above. The question of typical values for these coefficients is subject to debate. Ideally, one should do a detailed analysis of the ventilation situation and then determine a custom set of coefficients using methods such as those laid out in Chapter 26 of the ASHRAE Handbook of Fundamentals. The EnergyPlus defaults are 1,0,0,0 which gives a constant volume flow of ventilation under all conditions.
BLAST (one of the EnergyPlus predecessors) used the following values as defaults: 0.606, 0.03636, 0.1177, 0. These coefficients produce a value of 1.0 at 0\(^{\circ}\)C deltaT and 3.35 m/s (7.5 mph) windspeed, which corresponds to a typical summer condition. At a winter condition of 40\(^{\circ}\)C deltaT and 6 m/s (13.4 mph) windspeed, these coefficients would increase the ventilation rate by a factor of 2.75.
In DOE-2 (the other EnergyPlus predecessor), the air change method defaults are (adjusted to SI units) 0, 0, 0.224 (windspeed), 0. With these coefficients, the summer conditions above would give a factor of 0.75, and the winter conditions would give 1.34. A windspeed of 4.47 m/s (10 mph) gives a factor of 1.0.
The source of the BLAST defaults is noted in the BLAST documentation as:
“Empirical equation and the coefficient default were determined from ASHRAE journal articles and other data on the effects of outdoor weather conditions.”
The source of the DOE-2 defaults is based on examining the infiltration relationships described in the ASHRAE Handbook of Fundamentals.
The EnergyPlus example files use all of the above, the BLAST defaults in some (e.g., AirflowNetwork_Simple_house), the DOE-2 defaults in some (e.g., VentilationSimpleTest – has all 3), and the EnergyPlus defaults in some (e.g., 5ZoneNightVent2).
Ventilation by Wind and Stack with Open Area[LINK]
For this model (Ref Object: ZoneVentilation:WindandStackOpenArea), the ventilation air flow rate is a function of wind speed and thermal stack effect, along with the area of the opening being modeled. This object can be used alone or in combination with ZoneVentilation:DesignFlowRate objects. This model is intended for simplified ventilation calculations as opposed to the more detailed ventilation investigations that can be performed with the AirflowNetwork model. Using the “Wind and Stack with Open Area” model, the natural ventilation flow rate can be controlled by a multiplier fraction schedule applied to the user-defined opening area and through the specification of minimum, maximum and delta temperatures. The temperatures can be either single constant values for the entire simulation or schedules which can vary over time. The equation used to calculate the ventilation rate driven by wind is given by Equation 37 in Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals:
\[{Q_w} = {C_w}{A_{opening}}{F_{schedule}}V\]
where
Q\(_{w}\) = Volumetric air flow rate driven by wind [m\(^{3}\)/s]
C\(_{w}\) = Opening effectiveness [dimensionless]
A\(_{opening}\) = Opening area [m\(^{2}\)]
F\(_{schedule}\) = Open area fraction [user-defined schedule value, dimensionless]
V = Local wind speed [m/s]
If the user specifies “Autocalculate” for the Opening Effectiveness input field, the opening effectiveness is calculated for each simulation time step based on the angle between the actual wind direction and the Effective Angle (a user-defined input) using the following equation:
\[{C_w} = 0.55 - \frac{{\left| {EffectiveAngle - WindDirection} \right|}}{{180}}*0.25\]
The difference EffectiveAngle – WindDirection should be between 0 and 180 degrees. If the difference EffectivAngle – WindDirection is greater than 180, the difference is reset to be minus 180 degrees. This equation is a linear interpolation using the values recommended by the 2009 ASHRAE Handbook of Fundamentals (page 16.13): 0.5 to 0.6 for perpendicular winds and 0.25 to 0.35 for diagonal winds.
The equation used for calculating the ventilation rate due to stack effect is given by Equation 38 in Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals:
\[{Q_s} = {C_D}{A_{opening}}{F_{schedule}}\sqrt {2g\Delta {H_{NPL}}(|{T_{zone}} - {T_{odb}}|/{T_{zone}})}\]
where,
Q\(_{s}\) = Volumetric air flow rate due to stack effect [m\(^{3}\)/s]
C\(_{D}\) = Discharge coefficient for opening [dimensionless]
A\(_{opening}\) = Opening area [m\(^{2}\)]
F\(_{schedule}\) = Open area fraction [user-defined schedule value, dimensionless]
\(\Delta\)H\(_{NPL}\) = Height from midpoint of lower opening to the neutral pressure level [m]. Estimation of this value is difficult; refer to Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals for guidance.
T\(_{zone}\) = Zone air dry-bulb temperature [K]
T\(_{odb}\) = Local outdoor air dry-bulb temperature [K]
The following equation, given by Equation 39 in Chapter 16 of the 2009 ASHRAE Handbook of Fundamentals, is used to calculate the Discharge Coefficient for Opening when the user sets the value for this input field to “Autocalculate”:
\[{C_D} = 0.40 + 0.0045\left| {{T_{zone}} - {T_{odb}}} \right|\]
The total ventilation rate calculated by this model is the quadrature sum of the wind and stack air flow components:
\[Ventilatio{n_{WindAndStack}} = \sqrt {{Q_s}^2 + {Q_w}^2}\]
If desired, a simple summation, instead of quadrature summation, can be realized by inputting two ZoneVentilation:WindAndStackOpenArea objects. One object can be defined with only a wind-driven component by setting C\(_{D}\) = 0, and the other object can have only stack-effect inputs specified and set C\(_{w}\) = 0.
Zone Air Balance Outdoor Airflow (ZoneAirBalance:OutdoorAir)[LINK]
ASHRAE 2009 Handbook of Fundamentals specifies that any unbalanced supply or exhaust ventilation air, Q\(_{u,v}\), to a zone causes pressurization/depressurization that influences the flow of infiltration air and thus should be combined with natural infiltration, Q\(_{n}\), (and, if present, unbalanced duct leakage, Qu,l) in superposition. Balanced ventilation airflow, Q\(_{b,v}\), to a zone (such as an ERV or HRV with balanced exhaust and intake air flows) does not interact with infiltration air and is added in whole:
\[Q = \sqrt {{Q_n}^2 + {Q_{u,v}}^2 + ({Q_{u,l}}^2)} + {Q_{b,v}}\]
where,
Q = Combined outdoor airflow with infiltration, balanced and unbalanced outdoor air flows, and unbalanced duct leakage [m\(^{3}\)/s]
Q\(_{n}\) = Natural infiltration airflow [m\(^{3}\)/s]
Q\(_{b,v}\) = Balanced ventilation airflow, excluding infiltration [m\(^{3}\)/s]
Q\(_{u,v}\) = Unbalanced ventilation airflow, excluding infiltration [m\(^{3}\)/s]
Q\(_{u,l}\) = Unbalanced duct leakage: the difference between supply and return leaks [m\(^{3}\)/s]
The natural infiltration airflow includes all outdoor airflows from all ZoneInfiltration objects for the same zone.
\[{Q_n} = \sum\limits_i {{Q_{Infiltration,i}}}\]
where
Q\(_{Infiltration,i}\) = Outdoor airflow rate given in the ith ZoneInfiltration objects for the same zone
The balanced ventilation airflow is the sum of outdoor airflows from all ZoneVentilation: DesignFlowRate objects with Ventilation Type = Balanced:
\[{Q_{b,v}} = \sum\limits_i {{Q_{v,Balanced,i}}}\]
where
Q\(_{v,Balanced,i}\) = Ventilation rate with “Balanced” ventilation type defined in the ith ZoneVentilation:DesignFlowRate object for the same zone
The unbalanced ventilation airflow is given by the following equation:
\[{Q_{u,v}} = {\left[ {{{\left( {\sum\limits_i {{Q_{v,Natural,i}}} + \sum\limits_i {{Q_{v,Wind,i}}} } \right)}^2} + {{\left( {\sum\limits_i {{Q_{v,Intake,i}}} } \right)}^2} + {{\left( {\sum\limits_i {{Q_{v,Exhaust,i}}} } \right)}^2} + {{\left( {\sum\limits_i {Max\left( {0,\;({Q_{ERV,Exh,i}} - {Q_{ERV,Sup,i}})} \right)} } \right)}^2}} \right]^{0.5}}\]
where
Q\(_{v,Exhaust,i}\) = Ventilation rate with “Exhaust” type in the ith ZoneVentilation:DesignFlowRate object for the same zone
Q\(_{v,Intake,i}\) = Ventilation rate with “Intake” type in the ith ZoneVentilation:DesignFlowRate object for the same zone
Q\(_{v,Natural,i}\) = Ventilation rate with “Natural” type in the ith ZoneVentilation:DesignFlowRate object for the same zone
Q\(_{v,Wind,v}\) = Ventilation rate in the ith ZoneVentilation:WindandStackOpenArea object for the same zone
Q\(_{ERV,Sup,i}\) = Supply flow rate given in the ith ZoneHVAC:EnergyRecoveryVentilator object
Q\(_{ERV,Exh,i}\) = Exhaust flow rate given in the ith ZoneHVAC:EnergyRecoveryVentilator object
For Ventilation Type = Intake in the ZoneVentilation:DesignFlowRate object, an appropriate amount of fan heat will be ignored and the outdoor temperature will be used in the zone air heat balance equation.
This object provides a simple airflow interaction model without having to use the AirflowNetwork capabilities, when the Air Balance Method is specified as Quadrature.
Reference[LINK]
ASHRAE. 2009. 2009 ASHRAE Handbook – Fundamentals, Chapter 16, Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.