Psychrometric services[LINK]
EnergyPlus has a full complement of psychrometric
functions. All the routines are Fortran functions returning a
single precision real value. All arguments and results are in
SI units.
Note that each of the psychrometric routines has a
“calledfrom” optional parameter – this has been implemented in
some of the calling routines and is useful when errors are
detected during simulation for support personnel to figure out
where the psych routine is called from.
The Names for the different Psychrometric Routines are
based on the following self-explanatory format; the different
variables used in the Psych Routine taxonomy are as
follows.
H = Enthalpy
W = Humidity Ratio
Rh = Relative Humidity
V = Specific Volume
Rhov = Vapor Density of Air
Hfg = Latent energy (heat of vaporization for moist
air)
Hg = Enthalpy of gaseous moisture
Pb = Barometric Pressure
Twb = Temperature Wet Bulb
Twd = Temperature Dry Bulb
Tdp = Temperature Dew Point
Tsat and Psat = Saturation Temperature and Saturation
Pressure
Psy## Fn ## = Psy {## is a Function of
##}
Note: Each of the two capital alphabets together have
different meaning
Eg: {Psy ## Fn HW} = {Psy ## Function
of Enthalpy and Humidity Ratio}
PsyRhoAirFnPbTdbW
(Pb,Tdb,W,calledfrom)[LINK]
Returns the density of air in kilograms per cubic meter as
a function of barometric pressure [Pb] (in Pascals) and
humidity ratio [W] (kilograms of water per kilogram of dry
air).
PsyCpAirFnW
(W,calledfrom)[LINK]
Returns the specific heat of air in Joules per kilogram
degree Celsius as a function of humidity ratio [W] (kilograms
of water per kilogram of dry air) and dry bulb temperature
[Tdb] (Celsius).
PsyHfgAirFnWTdb
(W,Tdb,calledfrom)[LINK]
Returns the Latent energy of air Hfg as a function of
humidity ratio [W] (kilograms of water per kilogram of dry
air) and dry bulb temperature [Tdb] (Celsius). It calculates
hg and then hf and the difference is Hfg.
PsyHgAirFnWTdb
(W,Tdb,calledfrom)[LINK]
Returns the specific enthalpy of the moisture as a gas in
the air in Joules per kilogram as a function of humidity ratio
[W] (kilograms of water per kilogram of dry air) and dry bulb
temperature [Tdb] (Celsius).
PsyTdpFnTdbTwbPb
(Tdb,Twb,Pb,calledfrom)[LINK]
Returns the dew point temperature in Celsius as a function
of dry bulb temperature [Tdb] (Celsius), wet bulb temperature
[Twb] (Celsius), and barometric pressure [Pb] (Pascals).
PsyTdpFnWPb
(W,Pb,calledfrom)[LINK]
Returns the dew point temperature in Celsius as a function
of humidity ratio [W] (kilograms of water per kilogram of dry
air) and barometric pressure [Pb] (Pascals).
PsyHFnTdbW
(Tdb,W,calledfrom)[LINK]
Returns the specific enthalpy of air in Joules per kilogram
as a function of dry bulb temperature [Tdb] (Celsius) and
humidity ratio [W] (kilograms of water per kilogram of dry
air).
PsyHFnTdbRhPb
(Tdb,Rh,Pb,calledfrom)[LINK]
Returns the specific enthalpy of air in Joules per kilogram
as a function of dry bulb temperature [Tdb] (Celsius),
relative humidity [Rh] (fraction), and barometric pressure
[Pb] (Pascals).
PsyTdbFnHW
(H,W,calledfrom)[LINK]
Returns the air temperature in Celsius as a function of air
specific enthalpy [H] (Joules per kilogram) and humidity ratio
[W] (kilograms of water per kilogram of dry air).
PsyRhovFnTdbRh
(Tdb,Rh,calledfrom)[LINK]
Returns the Vapor Density in air RhoVapor
as a function of dry bulb temperature Tdb, Relative Humidity [Rh] (fraction).
PsyRhovFnTdbWP
(Tdb,W,Pb,calledfrom)[LINK]
Returns the Vapor Density in air RhoVapor
as a function of dry bulb temperature Tdb, humidity ratio [W] (kilograms of water
per kilogram of dry air) and barometric pressure [Pb]
(Pascals).
PsyRhFnTdbRhov
(Tdb,Rhov,calledfrom)[LINK]
Returns the Relative Humidity [Rh] (fraction) in air as a
function of dry bulb temperature [Tdb] (Celcius) and Vapor
Density in air RhoVapor.
PsyRhFnTdbWPb
(Tdb,W,Pb,calledfrom)[LINK]
Returns the relative humidity (fraction) as a function of
of dry bulb temperature [Tdb] (Celsius), humidity ratio [W]
(kilograms of water per kilogram of dry air) and barometric
pressure [Pb] (Pascals).
PsyTwbFnTdbWPb
(Tdb,W,Pb,calledfrom)[LINK]
Returns the air wet bulb temperatute in Celsius as a
function of dry bulb temperature [Tdb] (Celsius), humidity
ratio [W] (kilograms of water per kilogram of dry air) and
barometric pressure [Pb] (Pascals).
PsyVFnTdbWPb
(Tdb,W,Pb,calledfrom)[LINK]
Returns the specific volume in cubic meters per kilogram as
a function of dry bulb temperature [Tdb] (Celsius), humidity
ratio [W] (kilograms of water per kilogram of dry air) and
barometric pressure [Pb] (Pascals).
PsyWFnTdpPb
(Tdp,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per
kilogram of dry air as a function of the dew point temperature
[Tdp] (Celsius) and barometric pressure [Pb] (Pascals).
PsyWFnTdbH
(Tdb,H,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per
kilogram of dry air as a function of dry bulb temperature
[Tdb] (Celsius) and air specific enthalpy [H] (Joules per
kilogram).
PsyWFnTdbTwbPb
(Tdb,Twb,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per
kilogram of dry air as a function of dry bulb temperature
[Tdb] (Celsius), wet bulb temperature [Twb] (Celsius), and
barometric pressure [Pb] (Pascals).
PsyWFnTdbRhPb
(Tdb,Rh,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per
kilogram of dry air as a function of dry bulb temperature
[Tdb] (Celsius), relative humidity [RH] (fraction), and
barometric pressure [Pb] (Pascals).
PsyPsatFnTemp
(T,calledfrom)[LINK]
Returns the saturation pressure in Pascals as a function of
the air saturation temperature [T] (Celsius).
PsyTsatFnHPb
(H,Pb,calledfrom)[LINK]
Returns the air saturation temperature in Celsius as a
function of air specific enthalpy [H] (Joules per kilogram)
and barometric pressure [Pb] (Pascals).
PsyTsatFnPb
(P,calledfrom)[LINK]
Returns the air saturation temperature in Celsius as a
function of saturation pressure [P] (Pascals).
CPCW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin)
for chilled water as function of temperature [T]
(Celsius).
CPHW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin) for
hot water as function of temperature [T] (Celsius).
CVHW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin) for
hot water at constant volume as function of temperature [T]
(Celsius).
RhoH2O (Temp,calledfrom)[LINK]
Returns density of water (kg/m3) as function of Temperature
[T] (Celsius).
PsyDeltaHSenFnTdb2W2Tdb1W1
(Tdb2,W2, Tdb1, W1,calledfrom)[LINK]
Returns sensible enthalpy difference of moist air going
from state 1 to state 2 in Joules per kilogram as a function
of state 2 dry bulb temperature [Tdb2] (Celsius), state 2
humidity ratio [W2] (kilograms of water per kilogram of dry
air), state 1 dry bulb temperature [Tdb1] (Celsius), and state
1 humidity ratio [W1] (kilograms of water per kilogram of dry
air).
PsyHfgAvgFnTdb2Tdb1
(Tdb2,Tdb1,calledfrom)[LINK]
Returns average latent of vaporization of water for use in
moist air calculation in Joules per kilogram of water as a
function of state 2 dry bulb temperature [Tdb2] (Celsius), and
state 1 dry bulb temperature [Tdb1] (Celsius).
Psychrometric services[LINK]
EnergyPlus has a full complement of psychrometric functions. All the routines are Fortran functions returning a single precision real value. All arguments and results are in SI units.
Note that each of the psychrometric routines has a “calledfrom” optional parameter – this has been implemented in some of the calling routines and is useful when errors are detected during simulation for support personnel to figure out where the psych routine is called from.
The Names for the different Psychrometric Routines are based on the following self-explanatory format; the different variables used in the Psych Routine taxonomy are as follows.
H = Enthalpy
W = Humidity Ratio
Rh = Relative Humidity
V = Specific Volume
Rhov = Vapor Density of Air
Hfg = Latent energy (heat of vaporization for moist air)
Hg = Enthalpy of gaseous moisture
Pb = Barometric Pressure
Twb = Temperature Wet Bulb
Twd = Temperature Dry Bulb
Tdp = Temperature Dew Point
Tsat and Psat = Saturation Temperature and Saturation Pressure
Psy## Fn ## = Psy {## is a Function of ##}
Note: Each of the two capital alphabets together have different meaning
Eg: {Psy ## Fn HW} = {Psy ## Function of Enthalpy and Humidity Ratio}
PsyRhoAirFnPbTdbW (Pb,Tdb,W,calledfrom)[LINK]
Returns the density of air in kilograms per cubic meter as a function of barometric pressure [Pb] (in Pascals) and humidity ratio [W] (kilograms of water per kilogram of dry air).
PsyCpAirFnW (W,calledfrom)[LINK]
Returns the specific heat of air in Joules per kilogram degree Celsius as a function of humidity ratio [W] (kilograms of water per kilogram of dry air) and dry bulb temperature [Tdb] (Celsius).
PsyHfgAirFnWTdb (W,Tdb,calledfrom)[LINK]
Returns the Latent energy of air Hfg as a function of humidity ratio [W] (kilograms of water per kilogram of dry air) and dry bulb temperature [Tdb] (Celsius). It calculates hg and then hf and the difference is Hfg.
PsyHgAirFnWTdb (W,Tdb,calledfrom)[LINK]
Returns the specific enthalpy of the moisture as a gas in the air in Joules per kilogram as a function of humidity ratio [W] (kilograms of water per kilogram of dry air) and dry bulb temperature [Tdb] (Celsius).
PsyTdpFnTdbTwbPb (Tdb,Twb,Pb,calledfrom)[LINK]
Returns the dew point temperature in Celsius as a function of dry bulb temperature [Tdb] (Celsius), wet bulb temperature [Twb] (Celsius), and barometric pressure [Pb] (Pascals).
PsyTdpFnWPb (W,Pb,calledfrom)[LINK]
Returns the dew point temperature in Celsius as a function of humidity ratio [W] (kilograms of water per kilogram of dry air) and barometric pressure [Pb] (Pascals).
PsyHFnTdbW (Tdb,W,calledfrom)[LINK]
Returns the specific enthalpy of air in Joules per kilogram as a function of dry bulb temperature [Tdb] (Celsius) and humidity ratio [W] (kilograms of water per kilogram of dry air).
PsyHFnTdbRhPb (Tdb,Rh,Pb,calledfrom)[LINK]
Returns the specific enthalpy of air in Joules per kilogram as a function of dry bulb temperature [Tdb] (Celsius), relative humidity [Rh] (fraction), and barometric pressure [Pb] (Pascals).
PsyTdbFnHW (H,W,calledfrom)[LINK]
Returns the air temperature in Celsius as a function of air specific enthalpy [H] (Joules per kilogram) and humidity ratio [W] (kilograms of water per kilogram of dry air).
PsyRhovFnTdbRh (Tdb,Rh,calledfrom)[LINK]
Returns the Vapor Density in air RhoVapor as a function of dry bulb temperature Tdb, Relative Humidity [Rh] (fraction).
PsyRhovFnTdbWP (Tdb,W,Pb,calledfrom)[LINK]
Returns the Vapor Density in air RhoVapor as a function of dry bulb temperature Tdb, humidity ratio [W] (kilograms of water per kilogram of dry air) and barometric pressure [Pb] (Pascals).
PsyRhFnTdbRhov (Tdb,Rhov,calledfrom)[LINK]
Returns the Relative Humidity [Rh] (fraction) in air as a function of dry bulb temperature [Tdb] (Celcius) and Vapor Density in air RhoVapor.
PsyRhFnTdbWPb (Tdb,W,Pb,calledfrom)[LINK]
Returns the relative humidity (fraction) as a function of of dry bulb temperature [Tdb] (Celsius), humidity ratio [W] (kilograms of water per kilogram of dry air) and barometric pressure [Pb] (Pascals).
PsyTwbFnTdbWPb (Tdb,W,Pb,calledfrom)[LINK]
Returns the air wet bulb temperatute in Celsius as a function of dry bulb temperature [Tdb] (Celsius), humidity ratio [W] (kilograms of water per kilogram of dry air) and barometric pressure [Pb] (Pascals).
PsyVFnTdbWPb (Tdb,W,Pb,calledfrom)[LINK]
Returns the specific volume in cubic meters per kilogram as a function of dry bulb temperature [Tdb] (Celsius), humidity ratio [W] (kilograms of water per kilogram of dry air) and barometric pressure [Pb] (Pascals).
PsyWFnTdpPb (Tdp,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per kilogram of dry air as a function of the dew point temperature [Tdp] (Celsius) and barometric pressure [Pb] (Pascals).
PsyWFnTdbH (Tdb,H,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per kilogram of dry air as a function of dry bulb temperature [Tdb] (Celsius) and air specific enthalpy [H] (Joules per kilogram).
PsyWFnTdbTwbPb (Tdb,Twb,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per kilogram of dry air as a function of dry bulb temperature [Tdb] (Celsius), wet bulb temperature [Twb] (Celsius), and barometric pressure [Pb] (Pascals).
PsyWFnTdbRhPb (Tdb,Rh,Pb,calledfrom)[LINK]
Returns the humidity ratio in kilograms of water per kilogram of dry air as a function of dry bulb temperature [Tdb] (Celsius), relative humidity [RH] (fraction), and barometric pressure [Pb] (Pascals).
PsyPsatFnTemp (T,calledfrom)[LINK]
Returns the saturation pressure in Pascals as a function of the air saturation temperature [T] (Celsius).
PsyTsatFnHPb (H,Pb,calledfrom)[LINK]
Returns the air saturation temperature in Celsius as a function of air specific enthalpy [H] (Joules per kilogram) and barometric pressure [Pb] (Pascals).
PsyTsatFnPb (P,calledfrom)[LINK]
Returns the air saturation temperature in Celsius as a function of saturation pressure [P] (Pascals).
CPCW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin) for chilled water as function of temperature [T] (Celsius).
CPHW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin) for hot water as function of temperature [T] (Celsius).
CVHW (Temp,calledfrom)[LINK]
Returns Specific heat capacity (Joule/kilogram/kelvin) for hot water at constant volume as function of temperature [T] (Celsius).
RhoH2O (Temp,calledfrom)[LINK]
Returns density of water (kg/m3) as function of Temperature [T] (Celsius).
PsyDeltaHSenFnTdb2W2Tdb1W1 (Tdb2,W2, Tdb1, W1,calledfrom)[LINK]
Returns sensible enthalpy difference of moist air going from state 1 to state 2 in Joules per kilogram as a function of state 2 dry bulb temperature [Tdb2] (Celsius), state 2 humidity ratio [W2] (kilograms of water per kilogram of dry air), state 1 dry bulb temperature [Tdb1] (Celsius), and state 1 humidity ratio [W1] (kilograms of water per kilogram of dry air).
PsyHfgAvgFnTdb2Tdb1 (Tdb2,Tdb1,calledfrom)[LINK]
Returns average latent of vaporization of water for use in moist air calculation in Joules per kilogram of water as a function of state 2 dry bulb temperature [Tdb2] (Celsius), and state 1 dry bulb temperature [Tdb1] (Celsius).
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.