Life-Cycle Cost
Computations[LINK]
The objects used for performing a life-cycle cost analysis
are:
- LifeCycleCost:Parameters
- LifeCycleCost:RecurringCosts
- LifeCycleCost:NonrecurringCost
- LifeCycleCost:UsePriceEscalation
- LifeCycleCost:UseAdjustment
The computation of life-cycle costs is broken into three
main routines which are described below.
ExpressAsCashFlows[LINK]
Step 1. If the input file has ComponentCost:* items, then
create an additional instance of a nonrecurring cost to hold
the total.
Step 2. Get the costs for each resource that has non-zero
utility costs.
Step 3. Compute the inflation on a monthly basis. For cases
where the inflation approach is constant dollars, the
inflation is set to 1.0 for all months. For current dollar
analyses, compute the inflation rate on a monthly basis. Just
using 1/12 of the annual inflation is almost correct but
introduces a small error so instead the inverse of the formula
4-32 from Newnan (Engineering Economic Analysis Ninth Edition
by Donald Newnan, Ted Eschenbach, and Jerome Lavelle):
inflationPerMonth = ((inflation + 1.00) ** (1.0/12.0)) -
1
Then the inflation is applied for each month:
monthlyInflationFactor(jMonth) = (1 + inflationPerMonth) **
(jMonth - 1)
Step 4. Put the nonrecurring, nonrecurring, and utility
costs into a monthly array for the entire length of the study
period.
Step 5. Multiply the monthly costs by the monthly inflation
which was set to 1.0 for constant dollar analyses.
Step 6. Multiply the monthly costs for resources with use
adjustments.
Step 7. Sum the monthly costs by category.
Step 8. Based on the base date, accumulate the monthly
costs into yearly costs.
ComputePresentValue[LINK]
Step 1. For each year of the study compute the discount
factor (SPV) using the following formula:
SPVyr = 1 / ((1 + curDiscountRate) **
effectiveYear)
This formula is based on formula D.2.1.1 from NIST Handbook
135 Life Cycle Costing Manual for the Federal Energy
Management Program by Sieglinde K. Fuller and Stephen R.
Petersen.
Where the effectiveYear depends on the discount convention.
If end of year discounting is used than the effectiveYear is
the year. If middle of the year discounting is used than the
effectiveYear is reduced by 0.5. If the beginning of year
discounting is used, than the effectiveYear is reduced by
1.0.
For energy costs, the use price escalations are multiplied
by the discount factors.
Step 2. Compute the present value for each month by
multiply the monthly costs by the discount factor for each
year.
Step 3. Sum the costs by category.
ComputeTaxAndDepreciation[LINK]
Step 1. Depending on the depreciation method selected the
depreciation factors are set to various constants.
Depreciation factors are based on IRS Publication 946 for 2009
“How to Depreciate Property.” The MACRS values are based on
Modified Accelerated Cost Recovery System GDS for 3, 5, 7, 10
year property are based on 200% depreciation method shown in
Appendix A of IRS Publication 946 using half year. 15 and 20
are based on 150% (Chart 1 of IRS Publication 946). For
Straight Line depreciation GDS is used for 27 years (actually
27.5) 31 years (actually 31.5 years) and 39 years using mid
month. For 40 years ADS is used (chart 2) Table A-1 is used
for 3, 4, 5, 10, 15 and 20 years. Table A-6 is for 27 years.
Table A-7 for 31 years. Table A-7a for 39 years. Table A-13
for 40 years. These years are a classification of property and
should not be confused with the length of the study. For 27
years, 31 years, 39 years and 40 years the June value was
used. All references in this paragraph are to IRS Publication
946.
Step 2. Apply the annual depreciation factors to the
capital costs.
Step 3. For each year the taxable income is the grand total
of all costs minus the depreciated capital costs.
Step 4. Taxes are the taxable income times the tax
rate.
Step 5. The after tax present value is
AfterTaxPresentValueyr = GrandTotalyr
- Taxesyr * SPVyr
All major results are presented on the tabular report.
Life-Cycle Cost Computations[LINK]
The objects used for performing a life-cycle cost analysis are:
The computation of life-cycle costs is broken into three main routines which are described below.
ExpressAsCashFlows[LINK]
Step 1. If the input file has ComponentCost:* items, then create an additional instance of a nonrecurring cost to hold the total.
Step 2. Get the costs for each resource that has non-zero utility costs.
Step 3. Compute the inflation on a monthly basis. For cases where the inflation approach is constant dollars, the inflation is set to 1.0 for all months. For current dollar analyses, compute the inflation rate on a monthly basis. Just using 1/12 of the annual inflation is almost correct but introduces a small error so instead the inverse of the formula 4-32 from Newnan (Engineering Economic Analysis Ninth Edition by Donald Newnan, Ted Eschenbach, and Jerome Lavelle):
inflationPerMonth = ((inflation + 1.00) ** (1.0/12.0)) - 1
Then the inflation is applied for each month:
monthlyInflationFactor(jMonth) = (1 + inflationPerMonth) ** (jMonth - 1)
Step 4. Put the nonrecurring, nonrecurring, and utility costs into a monthly array for the entire length of the study period.
Step 5. Multiply the monthly costs by the monthly inflation which was set to 1.0 for constant dollar analyses.
Step 6. Multiply the monthly costs for resources with use adjustments.
Step 7. Sum the monthly costs by category.
Step 8. Based on the base date, accumulate the monthly costs into yearly costs.
ComputePresentValue[LINK]
Step 1. For each year of the study compute the discount factor (SPV) using the following formula:
SPVyr = 1 / ((1 + curDiscountRate) ** effectiveYear)
This formula is based on formula D.2.1.1 from NIST Handbook 135 Life Cycle Costing Manual for the Federal Energy Management Program by Sieglinde K. Fuller and Stephen R. Petersen.
Where the effectiveYear depends on the discount convention. If end of year discounting is used than the effectiveYear is the year. If middle of the year discounting is used than the effectiveYear is reduced by 0.5. If the beginning of year discounting is used, than the effectiveYear is reduced by 1.0.
For energy costs, the use price escalations are multiplied by the discount factors.
Step 2. Compute the present value for each month by multiply the monthly costs by the discount factor for each year.
Step 3. Sum the costs by category.
ComputeTaxAndDepreciation[LINK]
Step 1. Depending on the depreciation method selected the depreciation factors are set to various constants. Depreciation factors are based on IRS Publication 946 for 2009 “How to Depreciate Property.” The MACRS values are based on Modified Accelerated Cost Recovery System GDS for 3, 5, 7, 10 year property are based on 200% depreciation method shown in Appendix A of IRS Publication 946 using half year. 15 and 20 are based on 150% (Chart 1 of IRS Publication 946). For Straight Line depreciation GDS is used for 27 years (actually 27.5) 31 years (actually 31.5 years) and 39 years using mid month. For 40 years ADS is used (chart 2) Table A-1 is used for 3, 4, 5, 10, 15 and 20 years. Table A-6 is for 27 years. Table A-7 for 31 years. Table A-7a for 39 years. Table A-13 for 40 years. These years are a classification of property and should not be confused with the length of the study. For 27 years, 31 years, 39 years and 40 years the June value was used. All references in this paragraph are to IRS Publication 946.
Step 2. Apply the annual depreciation factors to the capital costs.
Step 3. For each year the taxable income is the grand total of all costs minus the depreciated capital costs.
Step 4. Taxes are the taxable income times the tax rate.
Step 5. The after tax present value is
AfterTaxPresentValueyr = GrandTotalyr - Taxesyr * SPVyr
All major results are presented on the tabular report.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.