Loop, Equipment Sizing and other Design Data[LINK]

The importance of correct equipment sizing is often ignored in discussions of building simulation methods. The lack of reliable, efficient and flexible sizing calculations can present a serious barrier to the adoption and acceptance of building simulation programs. This section describes the sizing methodology implemented in EnergyPlus. This method includes:

A zone by zone heat balance load and air-flow calculation for multiple design days;

Significant user control with modest input requirements;

Zone, system and plant level calculations of design heating and cooling capacities and fluid flow rates;

Modular, component-specific sizing algorithms for each HVAC component.