Air System Humidifiers[LINK]
Air system humidifiers are components that add moisture to
the supply air stream. They fall into 2 broad categories:
spray type humidifiers which act like direct evaporative
coolers, cooling the supply air as well as humidifying it; and
dry steam humidifiers, which humidify the supply air stream
while causing almost no change to the supply air stream
temperature. The EnergyPlus electric steam humidifier uses
electrical energy to convert ordinary tap water to steam which
it then injects into the supply air stream by means of a
blower fan. The actual unit might be an electrode-type
humidifier or a resistance-type humidifier.
Electric Steam
Humidifier[LINK]
The electric steam humidifier model (object name:
Humidifier:Steam:Electric) is based on moisture and enthalpy
balance equations plus standard psychrometric relationships.
The approach is similar to that taken in the ASHRAE HVAC 2
Toolkit, page 4-112 (ASHRAE 1993). EnergyPlus contains its own
module of psychrometric routines; the psychrometric theory and
relations are given in the 2001 edition of ASHRAE
Fundamentals, Chapter 6 (ASHRAE 2001). The model contains both
an ideal controller and the component. The control model
assumes that there is a minimum humidity setpoint on the
component air outlet node. This setpoint is established by a
setpoint manager described elsewhere.
The component model is a forward model: its inputs are its
inlet conditions; its outputs are its outlet conditions and
its energy consumption. The inputs are the temperature,
humidity ratio, and mass flow rate of the inlet air stream,
which are known; and the water addition rate (kg/s) which is
determined by the controller.
The controller first decides whether the humidifier is on
or off. For the humidifier to be on:
- the humidifier schedule value must be nonzero;
- the inlet air mass flow must be greater than zero;
- the inlet air humidity ratio must be less than the minimum
humidity ratio setpoint.
If the humidifier is off, the water addition rate is set to
zero. If the humidifier is on, the water addition rate needed
to meet the humidity setpoint is calculated.
where
= the air mass flow rate
[kg/s]
= the inlet air humidity
ratio [kg/kg]
= water addition rate
needed to meet the setpoint [kg/s]
= the humidity ratio
setpoint [kg/kg]
Equation is the moisture balance equation for the
component. It is solved for
(the other variables are known) which is passed to the
humidifier component model as its desired inlet water addition
rate.
The inputs to the component model are the air inlet
conditions and mass flow rate and the water addition rate set
by the controller. The outputs are the air outlet conditions.
First the desired water addition rate is checked against
component capacity.
where
= the humidifier nominal
capacity [kg/s], a user input.
If
is zero, the outlet
conditions are set to the inlet conditions and the water
addition rate is set to zero. If the humidifier is scheduled
on the component power consumption is set to the standby power
consumption:
. Otherwise
= 0.
If
> 0, then the
moisture and enthalpy balance equations
with
set equal to
are solved for
and
. Here
= the air mass flow rate
[kg/s]
= the inlet air humidity
ratio [kg/kg]
= the inlet water
addition rate [kg/s]
= the outlet air humidity
ratio [kg/kg]
= the inlet air specific
enthalpy [J/kg]
= the steam specific
enthalpy = 2676125. [J/kg] at 100 oC
= the outlet air specific
enthalpy [J/kg]
The outlet temperature is obtained from
where
= outlet air temperature
[^o^C],
is an EnergyPlus
psychrometric function.
The humidity ratio at saturation at the outlet temperature
is
where
= the barometric pressure
[Pa],
1.0 is the relative humidity at saturation,
is an EnergyPlus
psychrometric function.
IF
then the outlet
condition is below the saturation curve and the desired
moisture addition rate can be met.
is set to
and the calculation of outlet
conditions is done. But if
then it is assumed that this condition will be detected and
the steam addition rate throttled back to bring the outlet
conditions back to the saturation condition. We need to find
the point where the line drawn between state 1 (inlet) and
state 2 (our desired outlet) crosses the saturation curve.
This will be the new outlet condition. Rather than iterate to
obtain this point, we find it approximately by solving for the
point where 2 lines cross: the first drawn from state 1 to
state 2, the second from
,
to
,
; where
is the inlet temperature
[^o^C],
is the humidity ratio at
saturation at temperature
[kg/kg],
is the desired outlet
temperature [^o^C],
is the humidity ratio at
saturation at temperature
[kg/kg].
The 2 lines are given by the equations:
Solving for the point (state 3) where the lines cross:
This point isn’t quite on the saturation curve since we
made a linear approximation of the curve, but the temperature
should be very close to the correct outlet temperature. We
will use this temperature as the outlet temperature and move
to the saturation curve for the outlet humidity and enthalpy.
Thus we set
=
and
where
is an EnergyPlus
psychrometric function. The water addition rate is set to
We now have the outlet conditions and the adjusted steam
addition rate for the case where the desired outlet humidity
results in an outlet state above the saturation curve.
Finally, the electricity consumption is given by
where
= nominal fan power [W],
a user input,
= standby power [W], a
user input.
and the water consumption rate is
where
= the water consumption
rate [m3],
= water density (998.2
kg/m3).
ASHRAE. 1993. HVAC 2 Toolkit: A Toolkit for Secondary HVAC
System Energy Calculations. Atlanta: American Society of
Heating, Refrigerating and Air-Conditioning Engineers,
Inc.
ASHRAE. 2001. 2001 ASHRAE Handbook Fundamentals. Atlanta:
American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.
Air System Humidifiers[LINK]
Overview[LINK]
Air system humidifiers are components that add moisture to the supply air stream. They fall into 2 broad categories: spray type humidifiers which act like direct evaporative coolers, cooling the supply air as well as humidifying it; and dry steam humidifiers, which humidify the supply air stream while causing almost no change to the supply air stream temperature. The EnergyPlus electric steam humidifier uses electrical energy to convert ordinary tap water to steam which it then injects into the supply air stream by means of a blower fan. The actual unit might be an electrode-type humidifier or a resistance-type humidifier.
Electric Steam Humidifier[LINK]
The electric steam humidifier model (object name: Humidifier:Steam:Electric) is based on moisture and enthalpy balance equations plus standard psychrometric relationships. The approach is similar to that taken in the ASHRAE HVAC 2 Toolkit, page 4-112 (ASHRAE 1993). EnergyPlus contains its own module of psychrometric routines; the psychrometric theory and relations are given in the 2001 edition of ASHRAE Fundamentals, Chapter 6 (ASHRAE 2001). The model contains both an ideal controller and the component. The control model assumes that there is a minimum humidity setpoint on the component air outlet node. This setpoint is established by a setpoint manager described elsewhere.
Model[LINK]
The component model is a forward model: its inputs are its inlet conditions; its outputs are its outlet conditions and its energy consumption. The inputs are the temperature, humidity ratio, and mass flow rate of the inlet air stream, which are known; and the water addition rate (kg/s) which is determined by the controller.
Controller[LINK]
The controller first decides whether the humidifier is on or off. For the humidifier to be on:
If the humidifier is off, the water addition rate is set to zero. If the humidifier is on, the water addition rate needed to meet the humidity setpoint is calculated.
where
Equation is the moisture balance equation for the component. It is solved for
(the other variables are known) which is passed to the
humidifier component model as its desired inlet water addition
rate.
Component[LINK]
The inputs to the component model are the air inlet conditions and mass flow rate and the water addition rate set by the controller. The outputs are the air outlet conditions. First the desired water addition rate is checked against component capacity.
where
If
is zero, the outlet
conditions are set to the inlet conditions and the water
addition rate is set to zero. If the humidifier is scheduled
on the component power consumption is set to the standby power
consumption:
. Otherwise
= 0.
If
> 0, then the
moisture and enthalpy balance equations
with
set equal to
are solved for
and
. Here
The outlet temperature is obtained from
where
The humidity ratio at saturation at the outlet temperature is
where
1.0 is the relative humidity at saturation,
IF
then the outlet
condition is below the saturation curve and the desired
moisture addition rate can be met.
is set to
and the calculation of outlet
conditions is done. But if
then it is assumed that this condition will be detected and
the steam addition rate throttled back to bring the outlet
conditions back to the saturation condition. We need to find
the point where the line drawn between state 1 (inlet) and
state 2 (our desired outlet) crosses the saturation curve.
This will be the new outlet condition. Rather than iterate to
obtain this point, we find it approximately by solving for the
point where 2 lines cross: the first drawn from state 1 to
state 2, the second from
,
to
,
; where
The 2 lines are given by the equations:
Solving for the point (state 3) where the lines cross:
This point isn’t quite on the saturation curve since we made a linear approximation of the curve, but the temperature should be very close to the correct outlet temperature. We will use this temperature as the outlet temperature and move to the saturation curve for the outlet humidity and enthalpy. Thus we set
=
and
where
is an EnergyPlus
psychrometric function. The water addition rate is set to
We now have the outlet conditions and the adjusted steam addition rate for the case where the desired outlet humidity results in an outlet state above the saturation curve.
Finally, the electricity consumption is given by
where
and the water consumption rate is
where
References[LINK]
ASHRAE. 1993. HVAC 2 Toolkit: A Toolkit for Secondary HVAC System Energy Calculations. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE. 2001. 2001 ASHRAE Handbook Fundamentals. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.