Air Loop Simulation[LINK]
A complete simulation of each primary air system - zone
equipment air loop is done in the following manner.
If this is the first simulation this system time-step,
just call ManageAirLoops (simulates the primary air
systems) and ManageZoneEquipment (simulates the zone
equipment sets) once and quit. This initial pass is simulated
with full design air flow rates and allows the zone equipment
to set the flow rates for each zone that will meet the zone
loads.
Otherwise loop over primary air systems and zone
equipment sets until the temperatures, flow rates, enthalpies,
humidity ratios etc. agree to within tolerance at each primary
air system - zone equipment gap.
DO WHILE ((SimAirLoops .OR. SimZoneEquipment) .AND. (IterAir.LE.MaxAir) )
IF (SimAirLoops) THEN
CALL ManageAirLoops(FirstHVACIteration,SimAirLoops,SimZoneEquipment)
SimPlantDemandLoops = .TRUE
SimElecCircuits =.TRUE.
END IF
IF (SimZoneEquipment) THEN
CALL ResolveAirLoopFlowLimits(IterAir+1)
CALL ManageZoneEquipment(FirstHVACIteration,SimZoneEquipment,SimAirLoops)
SimPlantDemandLoops = .TRUE.
SimElecCircuits =.TRUE.
END IF
IterAir = IterAir + 1
END DO
CALL ResolveLockoutFlags(SimAirLoops)
The logical flags SimAirLoops and
SimZoneEquipment are used to signal whether the
primary air systems or the zone equipment sets need to be
resimulated. These flags are set by the subroutine
UpdateHVACInterface which is called from within
ManageAirLoops and ManageZoneEquipment at
the end of each half-loop simulation.
UpdateHVACInterface (when called from
ManageAirLoops) passes the values at the
outlet nodes of a primary air system on to the inlet nodes of
the corresponding zone equipment half-loop and similarly (when
called from ManageZoneEquipment) passes the
values of the outlet nodes of a zone equipment half-loop on to
the inlet nodes of its corresponding primary air system. Each
time UpdateHVACInterface is called it also checks
whether the values at the half-loop outlet nodes are in
agreement with the values at the downstream half-loop inlet
nodes. If they are not it sets the simulate flag of the
downstream half-loop to true. The values checked by
UpdateHVACInterface and their tolerances are as
follows.
| Quantities |
Tolerances |
| specific enthalpy [J/kg} |
10.0 |
| mass flow rate [kg/s] |
0.01 |
| humidity ratio [kg
H2O / kg dry air] |
0.0001 |
| quality |
0.01 |
| air pressure [Pa] |
10.0 |
| temperature [C] |
0.01 |
| energy [J] |
10.0 |
ResolveAirLoopFlowLimits is invoked to deal with
zone equipment - primary air system flow mismatches. For
instance the zone air terminal units (ATUs) may be asking for
more air than the central fan can supply. In this case
ResolveAirLoopFlowLimits takes the air flow that the
fan can supply and apportions it among the ATUs in proportion
to their design maximum air flow rates
(ResolveAirLoopFlowLimits sets the \({\dot m_{\max avail,node}}\) at
the entering node of each ATU in the system).
At the end of the air loop simulation
ResolveLockoutFlags is called. This subroutine checks
if any air system component has requested that the economizer
be locked out. If such a request has been made and if the
economizer is active, ResolveLockoutFlags sets
SimAirLoops to true and the
EconoLockout flag to true to ensure that the
air loop will be resimulated with the economizer forced
off.
Air Loop Simulation[LINK]
A complete simulation of each primary air system - zone equipment air loop is done in the following manner.
If this is the first simulation this system time-step, just call ManageAirLoops (simulates the primary air systems) and ManageZoneEquipment (simulates the zone equipment sets) once and quit. This initial pass is simulated with full design air flow rates and allows the zone equipment to set the flow rates for each zone that will meet the zone loads.
Otherwise loop over primary air systems and zone equipment sets until the temperatures, flow rates, enthalpies, humidity ratios etc. agree to within tolerance at each primary air system - zone equipment gap.
The logical flags SimAirLoops and SimZoneEquipment are used to signal whether the primary air systems or the zone equipment sets need to be resimulated. These flags are set by the subroutine UpdateHVACInterface which is called from within ManageAirLoops and ManageZoneEquipment at the end of each half-loop simulation. UpdateHVACInterface (when called from ManageAirLoops) passes the values at the outlet nodes of a primary air system on to the inlet nodes of the corresponding zone equipment half-loop and similarly (when called from ManageZoneEquipment) passes the values of the outlet nodes of a zone equipment half-loop on to the inlet nodes of its corresponding primary air system. Each time UpdateHVACInterface is called it also checks whether the values at the half-loop outlet nodes are in agreement with the values at the downstream half-loop inlet nodes. If they are not it sets the simulate flag of the downstream half-loop to true. The values checked by UpdateHVACInterface and their tolerances are as follows.
ResolveAirLoopFlowLimits is invoked to deal with zone equipment - primary air system flow mismatches. For instance the zone air terminal units (ATUs) may be asking for more air than the central fan can supply. In this case ResolveAirLoopFlowLimits takes the air flow that the fan can supply and apportions it among the ATUs in proportion to their design maximum air flow rates (ResolveAirLoopFlowLimits sets the \({\dot m_{\max avail,node}}\) at the entering node of each ATU in the system).
At the end of the air loop simulation ResolveLockoutFlags is called. This subroutine checks if any air system component has requested that the economizer be locked out. If such a request has been made and if the economizer is active, ResolveLockoutFlags sets SimAirLoops to true and the EconoLockout flag to true to ensure that the air loop will be resimulated with the economizer forced off.