EMS Actuator Interface[LINK]
New component models may need to register certain control
variables with the Energy Management System. In many cases, a
component model will be controlled by setpoints placed on a
system node, such as the component outlet, and the setpoints
placed on the nodes can already be actuated by the EMS. But a
given new component may have internal controls that should be
made to work with EMS. When this is the case, the developer
needs to register the control point as an actuator that EMS
users can reference. The content of registered actuators is
reported to the EDD file when EMS is used in a model and the
Output:EnergyManagementSystem
object is configured to do so.
The EMS actuator interface is similar to
SetupOutputVariable. Here is the syntax:
CALL SetupEMSActuator(<component type>, <component unique name>,
<control type name>, <units>, <logical variable on flag>,
< variable to be controlled> )
is a string representing
the type of component or entity being registered. This is
usually the class name of the IDF object. Or it could be
another identifying string, if not directly associated with an
object. For example the call to setup actuator for nodes uses
“System Node Setpoint.’
is the local
user-specified object name that identifies a unique instance
among a set of the same or similar components.
is the string
identifying the type of actuator. A model may have more than
one type of control and this argument clarifys which one is
being registered. A thermostat object could, for instance,
have several actuators for that object type: “On/Off”,
“Heating Set Point Temperature”, and “Cooling Set Point
Temperature”.
is the string for the units of the
control variable, used for reporting.
is a local
variable attached to the object data structure that says
whether or not the actuator value should be used (see below).
This becomes a pointer in the EMS data structure so that the
EMS can set the value of this variable remotely. The variable
type needs to be LOGICAL.
is another
variable attached to the object data structure that specifies
the value or state of the actuator, used in conjunction with
the flag above. Similar to above, this also becomes a pointer
in the EMS data structure so that the EMS can set the value of
this variable remotely. A Fortran INTERFACE is used to
overload the call the SetupEMSActuator so that this can be
either a real, integer, or logical value.
However, it is not desirable to register EMS actuators in
every simulation because if there is no use of the EMS then
this just adds to memory and computation. Therefore, we wrap
calls to SetupEMSActuator inside logical checks using a global
variable called “AnyEnergyManagementSystemInModel.”
Here is an example to create an actuator that can set the
power on EXTERIORLIGHTS:
if (AnyEnergyManagementSystemInModel) Then
CALL SetupEMSActuator('ExteriorLights', ExteriorLights(Item)%Name, &
'Electric Power', 'W', ExteriorLights(Item)%PowerActuatorOn, &
ExteriorLights(Item)%PowerActuatorValue)
ENDIF
Variables analogous to “PowerActuatorOn” and
“PowerActuatorValue” are added to data structure for the
component model.
Code must then be written at the object or component level
to react to the variables that are being actuated by the EMS
Manager. Often it only requires one or two lines of code per
actuator. ExteriorLights is particularly simple:
IF (ExteriorLights(Item)%PowerActuatorOn) THEN
ExteriorLights(Item)%Power = &
ExteriorLights(Item)%PowerActuatorValue
END IF
Finally, once SetupEMSActuator is called, several things
happen:
Two pointers are created in the EMS Manager
The actuator is made available for use Erl
programs.
The actuator name and associated information are logged
in the EDD output file
All of the available actuators that can be accessed are
shown in the EDD output file. Like the RDD, the list changes
depending on what objects you have in your input file.
In addition to setting up actuators, component model
developers can also register design data for components and
systems to be made available for possible use in Erl programs.
These are generally static data that do not vary across an
environment period but might vary from one run to the next.
These are registered using calls to SetupEMSInternalVariable
such as:
CALL SetupEMSInternalVariable('Zone Floor Area', Zone(ZoneNum)%Name, '[m2]', &
Zone(ZoneNum)%FloorArea )
CALL SetupEMSInternalVariable('Zone Air Volume', Zone(ZoneNum)%Name, '[m3]', &
Zone(ZoneNum)%Volume )
The calls to SetupEMSInternalVariable should also be
protected by logic that uses the
AnyEnergyManagementSystemInModel logic flag. The internal data
available can also be listed in the EDD output file.
EMS Actuator Interface[LINK]
New component models may need to register certain control variables with the Energy Management System. In many cases, a component model will be controlled by setpoints placed on a system node, such as the component outlet, and the setpoints placed on the nodes can already be actuated by the EMS. But a given new component may have internal controls that should be made to work with EMS. When this is the case, the developer needs to register the control point as an actuator that EMS users can reference. The content of registered actuators is reported to the EDD file when EMS is used in a model and the Output:EnergyManagementSystem object is configured to do so.
The EMS actuator interface is similar to SetupOutputVariable. Here is the syntax:
However, it is not desirable to register EMS actuators in every simulation because if there is no use of the EMS then this just adds to memory and computation. Therefore, we wrap calls to SetupEMSActuator inside logical checks using a global variable called “AnyEnergyManagementSystemInModel.”
Here is an example to create an actuator that can set the power on EXTERIORLIGHTS:
Variables analogous to “PowerActuatorOn” and “PowerActuatorValue” are added to data structure for the component model.
Code must then be written at the object or component level to react to the variables that are being actuated by the EMS Manager. Often it only requires one or two lines of code per actuator. ExteriorLights is particularly simple:
Finally, once SetupEMSActuator is called, several things happen:
Two pointers are created in the EMS Manager
The actuator is made available for use Erl programs.
The actuator name and associated information are logged in the EDD output file
All of the available actuators that can be accessed are shown in the EDD output file. Like the RDD, the list changes depending on what objects you have in your input file.
In addition to setting up actuators, component model developers can also register design data for components and systems to be made available for possible use in Erl programs. These are generally static data that do not vary across an environment period but might vary from one run to the next. These are registered using calls to SetupEMSInternalVariable such as:
The calls to SetupEMSInternalVariable should also be protected by logic that uses the AnyEnergyManagementSystemInModel logic flag. The internal data available can also be listed in the EDD output file.