Interfacing with Plant[LINK]
Beginning with Version
7.0, EnergyPlus’s plant routines were reengineered and this
section discusses protocols for how component models should
interact with plant loop modeling. Component models that
reject or obtain heat from a liquid fluid stream, such as hot
or chilled water, condenser water, and steam (but not
refrigeration), are “plant components” that will need to
interface with the central plant solver routines. This section
describes a number of utility routines and concepts for
developers of plant component models.
The node structure discussed above is reused for plant.
Each component model related to plant has inlet and outlet
nodes that describe how it is connected to the loop. Many of
the routines pass in node indexes as arguments as well as
other indexes into the main plant data structure.
Plant Loop Data
Structure[LINK]
For plant components, in addition to inlet nodes, outlet
nodes, and the component’s internal data structure, there is a
fourth aspect to data flow that includes central data
structures defined in DataPlant.f90. The main data structure
is called PlantLoop.
Both condenser loops and plant loops are treated the same and
share the PlantLoop
structure. The PlantLoop
structure stores information on the loop topology as well as
various control and dispatch input and operational data. The
data structure is nested and component information is stored
at this level:
PlantLoop()%LoopSide()%Branch()%Comp()%xxx
Where,
PlantLoop
is the top level and will be sized to the total number of
plant and condenser loops.
LoopSide is the second level and will be sized to two, one
loop side is for the demand side and one loop side is for the
supply side.
Branch
is the third level and will be sized to the total number of
branches on that loop side
Comp is the fourth level and will be sized to the total
number of components on the branch.
There are four indices that indentify each component’s
location for each of the plant loops it is connected with: :
loop number, loop side number, branch number, and component
number. A water cooled chiller will be connected to two loops
and so the component itself will appear twice in the data
structure and one set of indices will identify its location on
the chilled water loop while a second set of indices will
locate it on the condenser loop.
Initialization[LINK]
Component models should store indexes that describe their
location in the plant data structure. To obtain these indices,
call the routine ScanPlantLoopsForObject once for each
instance of the component. The component model’s data
structure should store a set of indices for: loop number, loop
side number, branch number, and component number. If the
component is connected to more than one plant loop, then there
should be set of indices and a call to ScanPlantLoopsForObject
for each plant loop it is connected to. If a component model
only has a single node name, the required indices can be
similarly obtained using the a call to
ScanPlantLoopsForNodeNum.
Component models generally need to do a thorough
re-initialization at the start of each new environment.
Component models can call InitComponentNodes to coordinate
initializing inlet and outlet nodes. This routine has
arguments for the minimum and maximum flow and these should be
mass flow rates, in kg/s, that correspond to the “hardware”
limits of the device.
Some components are connected to more than one plant loop
creating dependencies between loops. For example a
water-cooled chiller is connected to both a chilled water loop
and a condenser water loop. The chilled water loop places
demands on the condenser water loop so it is beneficial to
model the chilled water loop’s supply side before the
condenser water loop’s demand side is modeled. An
initialization routine called InterConnectTwoPlantLoopSides is
used by the component models to inform the central plant
routines of these situations. One call to this routine
describes a connection between two half-loops. The component
model developer needs to decide which of the half loops places
demands on the other and set the logical argument
Loop1DemandsOnLoop2 appropriately. The central plant routines
use this information to determine an appropriate calling order
for simulating individual half-loops.
Component models need to interact with centralized routines
that relate to sizes. This section provides an overview of how
EnergyPlus performs automatic sizing of plant systems and
components so that the broader context can be understood when
implementing plant components. As of EnergyPlus version 7, the
plant sizing methods were changed significantly. We first
describe some of the variables involved, then describe the
overall process steps, and finally discuss implications for
component models.
The following variables are used to help control plant
sizing:
PlantSizeNotComplete This public logical flag is declared
in DataPlant. It starts out FALSE TRUE and is set to TRUE
FALSE only after all plant sizing actions have been completed
and finalized.
PlantSizesOkayToFinalize This public logical flag is
declared in DataPlant. It starts out false FALSE and is set to
TRUE after the main iterative phase of sizing is completed but
before the final finishing passes are made. Component models
should delay final reporting and filling of autosized values
until this is set to TRUE. The -9999 values that indicate an
autosized variable are not filled until this is TRUE. Calls to
report the outcome of sizing are not made until this is
TRUE.
InitLoopEquip This logical flag is passed as an argument
with SimPlantEquip and carries through to the main simulation
calls for component models. This argument is set to TRUE when
the plant sizing is being conducted. The component model needs
to handle this argument such that when TRUE the get input,
initialization and sizing routines are run, but the
calculation routine does not. When TRUE most supply side
component models need to return values for the minimum,
maximum, and optimal capacities (in terms of loop loads that
the device can meet).
GetSizingFactor This logical flag is passed as an argument
with SimPlantEquip and carries through to the main simulation
calls for component models. This is arguementargument set TRUE
during some portions of the plant sizing calls and signals the
intent to obtain the value of a component-level sizing factor.
When this argument is TRUE, InitLoopEquip will also be TRUE.
It can be ignored if the component model has no
component-level sizing factor as part of its input. If the
component does offer a sizing factor, then the implementation
needs to handle this argument such that when TRUE the model
returns the value of the SizingFactor as an argument to the
simulation routine that is called from SimPlantEquip.
CurLoopNum This public integer variable is declared in
DataSizing. It is used to communicate to the component models
which of the plant loops is actively being sized at the
moment.
LoopNum and LoopSide These arguments are optional to the
main simulation routine
Plant sizing routines use the approach outlined in the
following steps. These steps occur at a point during the
program’s procedural flow when: zone and system sizing is
completed, much of the plant loop input has been read in and
processed but the main plant manager is being called for the
first time, none of the pure plant component’s simulation
routines have yet been called (but components on the air side
may have been), and an initial attempt at determining loop
calling order has been made in
SetupInitialPlantCallingOrder.
Initialize the indices that map between the central plant
sizing data structures and the PlantLoop
data structure. This uses the subroutine called
InitOneTimePlantSizingInfo. This ensures that the
PlantLoop%PlantSizNum variable is filled before any component
models are called.
(steps 2 thru 4 are sequentially repeated for four
iterations)
Call each component model in calling order. InitLoopEquip
is TRUE. The components on each half loop are called in flow
order. Each half loop in the model is called in the order set
up for simulation. These calls are typically the first time
certain component models have been called and should trigger
input processing and plant loop topology processing including
loop interconnections.
Revise the calling order for the sequence with which the
various plant loop sides are called for sizing and normal
simulation. Components that connect two loops will have been
processed in Step 2 and that information is now available to
refine loop side calling order
Call loop sizing routines in calling order. Component will
have registered their design flow rates in step 2 and now the
overall loop sizes are determined from the sum of the
components on the loop.
A final pass thru each loop side is made in calling order
with the flag PlantSizesOkayToFinalize set to true. At this
point the findings are not expected to change. Component
models now finalize their findings and store the results for
use during the simulation. Overall plant loops are finalized.
Sizing reporting occurs.
Sizing finished and PlantSizeNotComplete set FALSE
Previous to version 7, component sizing routines were only
called once and one had to take care not call them repeatedly
(or else their flow request would get doubled each time).
However, now plant component models should be designed for
multiple executions of their component-level sizing routine.
This allows for an iterative approach to plant sizing that is
used to solve complex problems raised by inter-connected loops
and the interdependence of sizing information.
After the component model has determined a design value for
the flow rate, this flow rate needs to be registered with the
larger plant routines by calling RegisterPlantCompDesignFlow.
This is a volume flow rate in m3/s. The flow rate
is associated with the inlet node. This call can be repeated
and the design flow will be updated with the latest
request.
Calls to InitComponentNodes should be done after sizing is
complete so that valid sizes are passed for initialing
nodes.
Component Flow Rates[LINK]
Plant components models need knowledge of the rate of plant
fluid flows through the device for each of loops involved.
Some components will need to request the flow they desire
while others just need to know the mass flow rate. However,
components do not necessarily have complete control over the
resulting flow rates because they depend on the state of the
entire plant and not just on the individual component model.
Component models need to be implemented to handle situations
where they do not get the exact flow rate they requested or
expected to get. For example there could be a shortage of flow
and components are starved and get less than they desire. Or a
component could be in series with another that is making a
larger flow request and therefore a component receives more
flow than expected. Even if a component is usually passive and
takes what flow it gets, the user might have placed a
component on a branch that is in parallel with other branches
making it necessary for even a passive component to make a
flow “request” in order for its parallel branch to receive
flow when a splitter distributes flow across a set of
branches.
SetComponentFlowRate collects code for how to properly deal
with plant flow rates. The idea is to use a central routine
that actually changes the various mass flow rate variables on
the node and checks against all the constraints. As of Version
7, component models should no longer assign flows to the Node
data structure. (Component models can get data from Node data
structure but should not set flow rate data on the Node
directly.) The SetComponentFlowRate subroutine’s argument for
fluid mass flow is INOUT; the component model makes a request
and if it cannot be satisfied, the mass flow rate variable
will be returned with the corrected flow that the plant can
actually provide at the moment.
Some models, such as a water coil controller, may only have
information about one control node. If a model does not really
represent a single device with inlet and outlet nodes, then
there is another useful routine called
SetActuatedBranchFlowRate which serves a role similar to
SetComponentFlowRate. This routine handles mass flow issues
for all the components on the branch that contains the
actuated node but is otherwise similar in concept.
Plant component models have different types of control
interactions depending on the type of component. Plant
components that are led by the air side of HVAC models will
generally be controlled by circumstances on the air side. A
water-based cooling coil will be targeting the achievement of
certain air conditions and while the state of the chilled
water plant serving the coil will matter in the model
calculations, the component itself is not controlled by plant
but things outside of plant.
Components that need to be operated to meet the loads
placed on plant loops will often be controlled based on some
combination of node setpoints and dispatched loads. The main
entry routine (called from PlantLoopEquipment.f90) for most
such primary components should include and use arguments for
“MyLoad” and “RunFlag.” Central routines for operation schemes
and availability managers will determine if a component is
available (e.g. RunFlag) and what power level the device is
being asked to provide (e.g. MyLoad). MyLoad is now signed as
of version 7; a negative value of MyLoad is a cooling load; a
positive value of MyLoad is a heating load.
Plant component update routines should no longer be setting
mass flow rates in the update routine. The flow setting
routines should be called during initialization or calculation
routines and should not need to be called again during update.
The state of the outlet node should be updated, such as outlet
temperature, but mass flow rate should not be. Prior to
version 7 it was common in EnergyPlus to write
Node(OutletNode) = Node(InletNode)
However this is no longer acceptable practice and is not
allowed for plant nodes. Instead this can be replaced with a
call to SafeCopyPlantNode. This avoids problems when two
components are in series and the outlet of one is the inlet of
another. We cannot allow unsafe node copying because it will
wipe out information stored on the inlet node of the second
component.
A component model connected to plant via nodes will inherit
a great deal of reporting that already occurs for each node.
The output variables that start out “System Node” will already
be available to the user. In general, the focus of reporting
should be on data that are internal to the component
model.
Central Routine
Modifications[LINK]
When adding a new plant component, there are several places
where the central routines’ code needs to be modified so that
the new model can properly interact with them. The following
sections of the code should be expanded when adding a new
plant component:
DataPlant.f90. A new component will need to modify
DataPlant.f90 in these places:
Parameter NumSimPlantEquipTypes. Increment up to include
new component.
Array SimPlantEquipTypes. Add array element with new
object’s class name in upper case.
Array ccSimPlantEquipTypes. Add array element with new
object’s class name in camel case.
Array ValidLoopEquipTypes. Add array element with
classification for what type of loop this component is
intended for, primarily with respect to the type of loop it is
intended to meet loads.
Parameter TypeOf_xxxx . Add an integer parameter to
identify “TypeOf” number for subsequent use to identify
component type without having to do string comparisions.
PlantManager.f90
GetPlantInput. There is a large IF-ELSEIF block in this
routine that will need to be extended to process the new
component. This is where the “TypeOf” number gets set for
subsequent use. Choose a general equipment type for the
component. Initialize the value for Comp%CurOpSchemeType
depending on which loop side is involved and/or the nature of
the component
SetupBranchControlTypes. There is a large Case block in
this routine that will need to be extended to process the new
component. Prior to Version
7, the user had to input a branch control type in the IDF. Now
this information is set in code in this routine. There are
three different control classifications that need to be set in
this routine:
Comp%FlowCtrl. This is the branch control type input for
versions prior to version 7. Plant components that have some
influence over the mass flows should be set to
ControlType_Active. There are also ControlType_Passive and
ControlType_ByPass options that may apply. The branches are
further processed by routines that automatically detect series
active situations.
Comp%FlowPriority. New for version 7 is a plant modeling
concept that treats flow requests differently depending on the
nature of the component’s priority. The idea is that when
determining the overall flow rate in a loop, some mass flow
requests need to be handled differently than others. The three
flow priority options for components are
LoopFlowStatus_NeedyAndTurnsLoopOn,
LoopFlowStatus_NeedyIfLoopOn, and
LoopFlowStatus_TakesWhatGets. The first is typically a demand
side component that when it requests flow will dictate that
the loop operate and try to meet its request. The second is
typically a supply side component with a minimum flow
requirement that should necessarily turn on the loop, but if
it is running already then the overall flow rate needs to
satisfy the minimum on the component. The third is typically a
passive device like a water tank.
Comp%HowLoadServed. This variable informs the load dispatch
routines about the component. Some components are intended to
serve loads in slightly different ways and this information is
stored in the plant data structure as different parameters for
HowLoadsServed. HowMet_NoneDemand is used for demand
components or others than never meet a load. HowMet_PassiveCap
is used for components that can meet a load but are not
generally explicitly controllable to meet a certain level of
load, such as a ground heat exchanger. HowMet_ByNominalCap is
used for components that can be controlled to meet a desired
load and do not have any additional layers of constraints.
HowMet_ByNominalCapLowOutLimit is used for components that can
be controlled to meet a desired load but have low temperature
limit on their outlet node. HowMet_ByNominalCapHiOutLimit is
used for components that can be controlled to meet a desired
load but have a hi temperature limit on their outlet node.
PlantLoopEquipment.f90. The routine SimPlantEquip includes
a large Case statement that will need to expanded to include
the new component. Some demand components, such as a water
coil, may not need to actually call a routine from here but a
placeholder must be added to the Case statement. Most plant
components will call the main simulation entry point for the
component model from SimPlantEquip and new components need to
add that call here. Note that the Case statement are broken up
into General equipment and the specific equipment. Code should
support use of InitLoopEquip and GetCompSizFac as
appropriate.
Interfacing with Plant[LINK]
Beginning with Version 7.0, EnergyPlus’s plant routines were reengineered and this section discusses protocols for how component models should interact with plant loop modeling. Component models that reject or obtain heat from a liquid fluid stream, such as hot or chilled water, condenser water, and steam (but not refrigeration), are “plant components” that will need to interface with the central plant solver routines. This section describes a number of utility routines and concepts for developers of plant component models.
The node structure discussed above is reused for plant. Each component model related to plant has inlet and outlet nodes that describe how it is connected to the loop. Many of the routines pass in node indexes as arguments as well as other indexes into the main plant data structure.
Plant Loop Data Structure[LINK]
For plant components, in addition to inlet nodes, outlet nodes, and the component’s internal data structure, there is a fourth aspect to data flow that includes central data structures defined in DataPlant.f90. The main data structure is called PlantLoop. Both condenser loops and plant loops are treated the same and share the PlantLoop structure. The PlantLoop structure stores information on the loop topology as well as various control and dispatch input and operational data. The data structure is nested and component information is stored at this level:
PlantLoop()%LoopSide()%Branch()%Comp()%xxx
Where,
PlantLoop is the top level and will be sized to the total number of plant and condenser loops.
LoopSide is the second level and will be sized to two, one loop side is for the demand side and one loop side is for the supply side.
Branch is the third level and will be sized to the total number of branches on that loop side
Comp is the fourth level and will be sized to the total number of components on the branch.
There are four indices that indentify each component’s location for each of the plant loops it is connected with: : loop number, loop side number, branch number, and component number. A water cooled chiller will be connected to two loops and so the component itself will appear twice in the data structure and one set of indices will identify its location on the chilled water loop while a second set of indices will locate it on the condenser loop.
Initialization[LINK]
Component models should store indexes that describe their location in the plant data structure. To obtain these indices, call the routine ScanPlantLoopsForObject once for each instance of the component. The component model’s data structure should store a set of indices for: loop number, loop side number, branch number, and component number. If the component is connected to more than one plant loop, then there should be set of indices and a call to ScanPlantLoopsForObject for each plant loop it is connected to. If a component model only has a single node name, the required indices can be similarly obtained using the a call to ScanPlantLoopsForNodeNum.
Component models generally need to do a thorough re-initialization at the start of each new environment. Component models can call InitComponentNodes to coordinate initializing inlet and outlet nodes. This routine has arguments for the minimum and maximum flow and these should be mass flow rates, in kg/s, that correspond to the “hardware” limits of the device.
Some components are connected to more than one plant loop creating dependencies between loops. For example a water-cooled chiller is connected to both a chilled water loop and a condenser water loop. The chilled water loop places demands on the condenser water loop so it is beneficial to model the chilled water loop’s supply side before the condenser water loop’s demand side is modeled. An initialization routine called InterConnectTwoPlantLoopSides is used by the component models to inform the central plant routines of these situations. One call to this routine describes a connection between two half-loops. The component model developer needs to decide which of the half loops places demands on the other and set the logical argument Loop1DemandsOnLoop2 appropriately. The central plant routines use this information to determine an appropriate calling order for simulating individual half-loops.
Sizing[LINK]
Component models need to interact with centralized routines that relate to sizes. This section provides an overview of how EnergyPlus performs automatic sizing of plant systems and components so that the broader context can be understood when implementing plant components. As of EnergyPlus version 7, the plant sizing methods were changed significantly. We first describe some of the variables involved, then describe the overall process steps, and finally discuss implications for component models.
The following variables are used to help control plant sizing:
PlantSizeNotComplete This public logical flag is declared in DataPlant. It starts out FALSE TRUE and is set to TRUE FALSE only after all plant sizing actions have been completed and finalized.
PlantSizesOkayToFinalize This public logical flag is declared in DataPlant. It starts out false FALSE and is set to TRUE after the main iterative phase of sizing is completed but before the final finishing passes are made. Component models should delay final reporting and filling of autosized values until this is set to TRUE. The -9999 values that indicate an autosized variable are not filled until this is TRUE. Calls to report the outcome of sizing are not made until this is TRUE.
InitLoopEquip This logical flag is passed as an argument with SimPlantEquip and carries through to the main simulation calls for component models. This argument is set to TRUE when the plant sizing is being conducted. The component model needs to handle this argument such that when TRUE the get input, initialization and sizing routines are run, but the calculation routine does not. When TRUE most supply side component models need to return values for the minimum, maximum, and optimal capacities (in terms of loop loads that the device can meet).
GetSizingFactor This logical flag is passed as an argument with SimPlantEquip and carries through to the main simulation calls for component models. This is arguementargument set TRUE during some portions of the plant sizing calls and signals the intent to obtain the value of a component-level sizing factor. When this argument is TRUE, InitLoopEquip will also be TRUE. It can be ignored if the component model has no component-level sizing factor as part of its input. If the component does offer a sizing factor, then the implementation needs to handle this argument such that when TRUE the model returns the value of the SizingFactor as an argument to the simulation routine that is called from SimPlantEquip.
CurLoopNum This public integer variable is declared in DataSizing. It is used to communicate to the component models which of the plant loops is actively being sized at the moment.
LoopNum and LoopSide These arguments are optional to the main simulation routine
Plant sizing routines use the approach outlined in the following steps. These steps occur at a point during the program’s procedural flow when: zone and system sizing is completed, much of the plant loop input has been read in and processed but the main plant manager is being called for the first time, none of the pure plant component’s simulation routines have yet been called (but components on the air side may have been), and an initial attempt at determining loop calling order has been made in SetupInitialPlantCallingOrder.
Initialize the indices that map between the central plant sizing data structures and the PlantLoop data structure. This uses the subroutine called InitOneTimePlantSizingInfo. This ensures that the PlantLoop%PlantSizNum variable is filled before any component models are called.
(steps 2 thru 4 are sequentially repeated for four iterations)
Call each component model in calling order. InitLoopEquip is TRUE. The components on each half loop are called in flow order. Each half loop in the model is called in the order set up for simulation. These calls are typically the first time certain component models have been called and should trigger input processing and plant loop topology processing including loop interconnections.
Revise the calling order for the sequence with which the various plant loop sides are called for sizing and normal simulation. Components that connect two loops will have been processed in Step 2 and that information is now available to refine loop side calling order
Call loop sizing routines in calling order. Component will have registered their design flow rates in step 2 and now the overall loop sizes are determined from the sum of the components on the loop.
A final pass thru each loop side is made in calling order with the flag PlantSizesOkayToFinalize set to true. At this point the findings are not expected to change. Component models now finalize their findings and store the results for use during the simulation. Overall plant loops are finalized. Sizing reporting occurs.
Sizing finished and PlantSizeNotComplete set FALSE
Previous to version 7, component sizing routines were only called once and one had to take care not call them repeatedly (or else their flow request would get doubled each time). However, now plant component models should be designed for multiple executions of their component-level sizing routine. This allows for an iterative approach to plant sizing that is used to solve complex problems raised by inter-connected loops and the interdependence of sizing information.
After the component model has determined a design value for the flow rate, this flow rate needs to be registered with the larger plant routines by calling RegisterPlantCompDesignFlow. This is a volume flow rate in m3/s. The flow rate is associated with the inlet node. This call can be repeated and the design flow will be updated with the latest request.
Calls to InitComponentNodes should be done after sizing is complete so that valid sizes are passed for initialing nodes.
Component Flow Rates[LINK]
Plant components models need knowledge of the rate of plant fluid flows through the device for each of loops involved. Some components will need to request the flow they desire while others just need to know the mass flow rate. However, components do not necessarily have complete control over the resulting flow rates because they depend on the state of the entire plant and not just on the individual component model. Component models need to be implemented to handle situations where they do not get the exact flow rate they requested or expected to get. For example there could be a shortage of flow and components are starved and get less than they desire. Or a component could be in series with another that is making a larger flow request and therefore a component receives more flow than expected. Even if a component is usually passive and takes what flow it gets, the user might have placed a component on a branch that is in parallel with other branches making it necessary for even a passive component to make a flow “request” in order for its parallel branch to receive flow when a splitter distributes flow across a set of branches.
SetComponentFlowRate collects code for how to properly deal with plant flow rates. The idea is to use a central routine that actually changes the various mass flow rate variables on the node and checks against all the constraints. As of Version 7, component models should no longer assign flows to the Node data structure. (Component models can get data from Node data structure but should not set flow rate data on the Node directly.) The SetComponentFlowRate subroutine’s argument for fluid mass flow is INOUT; the component model makes a request and if it cannot be satisfied, the mass flow rate variable will be returned with the corrected flow that the plant can actually provide at the moment.
Some models, such as a water coil controller, may only have information about one control node. If a model does not really represent a single device with inlet and outlet nodes, then there is another useful routine called SetActuatedBranchFlowRate which serves a role similar to SetComponentFlowRate. This routine handles mass flow issues for all the components on the branch that contains the actuated node but is otherwise similar in concept.
Controls[LINK]
Plant component models have different types of control interactions depending on the type of component. Plant components that are led by the air side of HVAC models will generally be controlled by circumstances on the air side. A water-based cooling coil will be targeting the achievement of certain air conditions and while the state of the chilled water plant serving the coil will matter in the model calculations, the component itself is not controlled by plant but things outside of plant.
Components that need to be operated to meet the loads placed on plant loops will often be controlled based on some combination of node setpoints and dispatched loads. The main entry routine (called from PlantLoopEquipment.f90) for most such primary components should include and use arguments for “MyLoad” and “RunFlag.” Central routines for operation schemes and availability managers will determine if a component is available (e.g. RunFlag) and what power level the device is being asked to provide (e.g. MyLoad). MyLoad is now signed as of version 7; a negative value of MyLoad is a cooling load; a positive value of MyLoad is a heating load.
Updating[LINK]
Plant component update routines should no longer be setting mass flow rates in the update routine. The flow setting routines should be called during initialization or calculation routines and should not need to be called again during update. The state of the outlet node should be updated, such as outlet temperature, but mass flow rate should not be. Prior to version 7 it was common in EnergyPlus to write
Node(OutletNode) = Node(InletNode)
However this is no longer acceptable practice and is not allowed for plant nodes. Instead this can be replaced with a call to SafeCopyPlantNode. This avoids problems when two components are in series and the outlet of one is the inlet of another. We cannot allow unsafe node copying because it will wipe out information stored on the inlet node of the second component.
Reporting[LINK]
A component model connected to plant via nodes will inherit a great deal of reporting that already occurs for each node. The output variables that start out “System Node” will already be available to the user. In general, the focus of reporting should be on data that are internal to the component model.
Central Routine Modifications[LINK]
When adding a new plant component, there are several places where the central routines’ code needs to be modified so that the new model can properly interact with them. The following sections of the code should be expanded when adding a new plant component:
DataPlant.f90. A new component will need to modify DataPlant.f90 in these places:
Parameter NumSimPlantEquipTypes. Increment up to include new component.
Array SimPlantEquipTypes. Add array element with new object’s class name in upper case.
Array ccSimPlantEquipTypes. Add array element with new object’s class name in camel case.
Array ValidLoopEquipTypes. Add array element with classification for what type of loop this component is intended for, primarily with respect to the type of loop it is intended to meet loads.
Parameter TypeOf_xxxx . Add an integer parameter to identify “TypeOf” number for subsequent use to identify component type without having to do string comparisions.
PlantManager.f90
GetPlantInput. There is a large IF-ELSEIF block in this routine that will need to be extended to process the new component. This is where the “TypeOf” number gets set for subsequent use. Choose a general equipment type for the component. Initialize the value for Comp%CurOpSchemeType depending on which loop side is involved and/or the nature of the component
SetupBranchControlTypes. There is a large Case block in this routine that will need to be extended to process the new component. Prior to Version 7, the user had to input a branch control type in the IDF. Now this information is set in code in this routine. There are three different control classifications that need to be set in this routine:
Comp%FlowCtrl. This is the branch control type input for versions prior to version 7. Plant components that have some influence over the mass flows should be set to ControlType_Active. There are also ControlType_Passive and ControlType_ByPass options that may apply. The branches are further processed by routines that automatically detect series active situations.
Comp%FlowPriority. New for version 7 is a plant modeling concept that treats flow requests differently depending on the nature of the component’s priority. The idea is that when determining the overall flow rate in a loop, some mass flow requests need to be handled differently than others. The three flow priority options for components are LoopFlowStatus_NeedyAndTurnsLoopOn, LoopFlowStatus_NeedyIfLoopOn, and LoopFlowStatus_TakesWhatGets. The first is typically a demand side component that when it requests flow will dictate that the loop operate and try to meet its request. The second is typically a supply side component with a minimum flow requirement that should necessarily turn on the loop, but if it is running already then the overall flow rate needs to satisfy the minimum on the component. The third is typically a passive device like a water tank.
Comp%HowLoadServed. This variable informs the load dispatch routines about the component. Some components are intended to serve loads in slightly different ways and this information is stored in the plant data structure as different parameters for HowLoadsServed. HowMet_NoneDemand is used for demand components or others than never meet a load. HowMet_PassiveCap is used for components that can meet a load but are not generally explicitly controllable to meet a certain level of load, such as a ground heat exchanger. HowMet_ByNominalCap is used for components that can be controlled to meet a desired load and do not have any additional layers of constraints. HowMet_ByNominalCapLowOutLimit is used for components that can be controlled to meet a desired load but have low temperature limit on their outlet node. HowMet_ByNominalCapHiOutLimit is used for components that can be controlled to meet a desired load but have a hi temperature limit on their outlet node.
PlantLoopEquipment.f90. The routine SimPlantEquip includes a large Case statement that will need to expanded to include the new component. Some demand components, such as a water coil, may not need to actually call a routine from here but a placeholder must be added to the Case statement. Most plant components will call the main simulation entry point for the component model from SimPlantEquip and new components need to add that call here. Note that the Case statement are broken up into General equipment and the specific equipment. Code should support use of InitLoopEquip and GetCompSizFac as appropriate.