The eplusmap.csv (or txt or tab extension) is a file that
is generated by the Output:IlluminanceMap
object. These are calculated for the Daylighting:Controls
daylighting option. By default, this is a comma delimited text
file (csv) that can be imported into a spreadsheet program.
For example, the input for the Output:IlluminanceMap
object shown below:
Output:IlluminanceMap,
Daylit Map, !- Map Name
Daylit Zone, !- Zone Name
0.8, !- Z height {m}
0.1, !- X minimum coordinate {m}
4.9, !- X maximum coordinate {m}
10, !- Number of X grid points
0.1, !- Y minimum coordinate {m}
9.9, !- Y maximum coordinate {m}
10; !- Number of Y grid points
generates the following output in csv format
when viewed with Microsoft Excel. Note that
if the point is outside the zone a “*” will be
shown.
Spreadsheet view of Daylight
Map output
Each cell reports the illuminance (in lux) at the location
specified by the (X;Y) coordinates in the column and row
headers. These are XY pairs separated by a semi-colon for ease
in importing into the spreadsheet. The Z coordinate of the map
is shown in the title (the illuminance map is set in a plane).
The date and time are indicated in the upper left cell of the
map. One map is reported for every hour of the simulation.
The illuminance values are organized to allow the user to
rapidly plot a visualization of the data using Microsoft
Excel’s standard “3-D Column” graph. A 3-D graph is shown
below for the data in a single day similar to the earlier
example.
3D Graph of Illuminance
Map
The following figure illustrates a similar map for the
tubular daylighting device example file that is included with
the installation.
A 3D illuminance map for the
tubular daylighting device file
Individual 3-D graphs can be generated for each hour of a
given day and collected to generate a sequence of graphs
representing the progression of daylighting conditions over
the course of the day. Using additional software tools (not
provided with EnergyPlus) the user can do further
post-processing to link screenshots of the graphs into an
animated sequence.
eplusmap. [LINK]
The eplusmap.csv (or txt or tab extension) is a file that is generated by the Output:IlluminanceMap object. These are calculated for the Daylighting:Controls daylighting option. By default, this is a comma delimited text file (csv) that can be imported into a spreadsheet program. For example, the input for the Output:IlluminanceMap object shown below:
generates the following output in csv format when viewed with Microsoft Excel. Note that if the point is outside the zone a “*” will be shown.
Each cell reports the illuminance (in lux) at the location specified by the (X;Y) coordinates in the column and row headers. These are XY pairs separated by a semi-colon for ease in importing into the spreadsheet. The Z coordinate of the map is shown in the title (the illuminance map is set in a plane). The date and time are indicated in the upper left cell of the map. One map is reported for every hour of the simulation.
The illuminance values are organized to allow the user to rapidly plot a visualization of the data using Microsoft Excel’s standard “3-D Column” graph. A 3-D graph is shown below for the data in a single day similar to the earlier example.
The following figure illustrates a similar map for the tubular daylighting device example file that is included with the installation.
Individual 3-D graphs can be generated for each hour of a given day and collected to generate a sequence of graphs representing the progression of daylighting conditions over the course of the day. Using additional software tools (not provided with EnergyPlus) the user can do further post-processing to link screenshots of the graphs into an animated sequence.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.