The Basement idd[LINK]

The basement idd objects and fields are shown below. These objects also appear in the main Energy+.IDD file with the prefix “GroundHeatTransfer:Basement:”

    ! Basement foundation heat transfer module Input Data Dictionary file
    ! Created:    August 18, 2000
    ! Written by: Edward Clements
    ! Modified for EnergyPlus Auxiliary Application by C. O. Pedersen 10/04
    ! Description format: FORTRAN var.: description, units, typ. values
    !
    SimParameters,
          N1,\field F: Multiplier for the ADI solution:
             \note 0<F<1.0,
             \note typically 0.1 (0.5 for high k soil]
          N2; \field IYRS: Maximum number of yearly iterations:
             \note typically 15-30]

    MatlProps,
         N1, \field NMAT: Number of materials in this domain
             \maximum 6
         N2, \field Density for Foundation Wall
             \note typical value 2243
             \units kg/m3
         N3, \field density for Floor Slab
             \note typical value 2243
             \units kg/m3
         N4, \field density for Ceiling
             \note typical value 311
             \units kg/m3
         N5, \field density for Soil
             \note typical value 1500
             \units kg/m3
         N6, \field density for Gravel
             \note typical value 2000
             \units kg/m3
         N7, \field density for Wood
             \note typical value 449
             \units kg/m3
         N8,  \field Specific heat for foundation wall
              \note typical value 880
              \units J/kg-K
         N9,  \field Specific heat for floor slab
              \note typical value 880
              \units J/kg-K
         N10, \field Specific heat for ceiling
              \note typical value 1530
              \units J/kg-K
         N11, \field Specific heat for soil
              \note typical value 840
              \units J/kg-K
         N12, \field Specific heat for gravel
              \note typical value 720
              \units J/kg-K
         N13, \field Specific heat for wood
              \note typical value 1530
              \units J/kg-K
         N14, \field Thermal conductivity for foundation wall
              \note typical value 1.4
              \units W/m-K
         N15, \field Thermal conductivity for floor slab
              \note typical value 1.4
              \units W/m-K
         N16, \field Thermal conductivity for ceiling
              \note typical value 0.09
              \units W/m-K
         N17,  \field thermal conductivity for soil
              \note typical value 1.1
              \units W/m-K
         N18, \field thermal conductivity for gravel
              \note typical value 1.9
              \units W/m-K
         N19; \field thermal conductivity for wood
              \note typical value 0.12
              \units W/m-K

    Insulation,
         N1, \field REXT: R Value of any exterior insulation, K/(W/m2)]
             \units m2-K/W
         A1; \field INSFULL: Flag: Is the wall fully insulated?
             \note  True for full insulation
             \note  False for insulation half way down side wall from grade line

    SurfaceProps,
         N1, \field ALBEDO: Surface albedo for No snow conditions
             \note typical value 0.16
         N2, \field ALBEDO: Surface albedo for snow conditions
             \note typical value 0.40
         N3, \field EPSLN: Surface emissivity No Snow
             \note typical value 0.94
         N4, \field EPSLN: Surface emissivity  with Snow
             \note typical value 0.86
         N5, \field VEGHT: Surface roughness No snow conditions,cm
             \note typical value 6.0
             \units cm
         N6, \field VEGHT: Surface roughness Snow conditions, cm, ]
             \note typical value 0.25
             \units cm
         A1; \field PET: Flag, Potential evapotranspiration on? T/F]
             \note  Typically, PET is True

    BldgData,
         N1, \field DWALL: Wall thickness,
             \note typical value .2]
             \units m
         N2, \field DSLAB: Floor slab thickness,
             \units m
             \maximum 0.25
         N3, \field DGRAVXY: Width of gravel pit beside basement wall
             \units  m
         N4, \field DGRAVZN: Gravel depth extending above the floor slab
             \units m
         N5; \field DGRAVZP: Gravel depth below the floor slab,
             \units m
             \note typical value 0.1
    !
    Interior,
       A1, \field COND: Flag: Is the basement conditioned?
           \note TRUE or FALSE
           \note for EnergyPlus this should be TRUE
       N1, \field HIN: Downward convection only heat transfer coefficient
           \units W/m2-K
       N2, \field HIN: Upward convection only heat transfer coefficient
           \units W/m2-K
       N3, \field HIN: Horizontal convection only heat transfer coefficient
           \units W/m2-K
       N4, \field HIN: Downward combined (convection and radiation) heat transfer coefficient
           \units W/m2-K
       N5, \field HIN: Upward combined (convection and radiation) heat transfer coefficient
           \units W/m2-K
       N6; \field HIN: Horizontal combined (convection and radiation) heat transfer coefficient
           \units W/m2-K
    !

    ComBldg,
    \memo ComBldg contains the monthly average temperatures (C) and possibility of daily variation amplitude
       N1,  \field January average temperature
            \units C
       N2,  \field February average temperature
            \units C
       N3,  \field March average temperature
            \units C
       N4,  \field April average temperature
            \units C
       N5,  \field May average temperature
            \units C
       N6,  \field June average temperature
            \units C
       N7,  \field July average temperature
            \units C
       N8,  \field August average temperature
            \units C
       N9,  \field September average temperature
            \units C
       N10, \field October average temperature
            \units C
       N11, \field November average temperature
            \units C
       N12, \field December average temperature
            \units C
       N13; \field Daily variation sine wave amplitude
            \units C
            \note (Normally zero, just for checking)
    !
    EquivSlab,  !  Supplies the EquivSizing Flag
        ! Using an equivalent slab allows non-rectangular shapes to be
        !    modeled accurately.
        ! The simulation default should be EquivSizing=True
       N1, \field APRatio: The area to perimeter ratio for this slab
           \ units m
       A1; \field EquivSizing: Flag
             \note Will the dimensions of an equivalent slab be calculated (TRUE)
             \note or will the dimensions be input directly? (FALSE)]
             \note Only advanced special simulations should use FALSE.
    !
    EquivAutoGrid,
         \memo EquivAutoGrid necessary when EquivSizing=TRUE, TRUE is is the normal case.
           N1, \field CLEARANCE: Distance from outside of wall to edge of 3-D ground domain
             \units m
             \note typical value 15m
           N2, \field SlabDepth: Thickness of the floor slab
             \units m
             \note typical value 0.1m
           N3; \field BaseDepth: Depth of the basement wall below grade
             \units m
    !
    !
    ! ******** The following input objects are required only for special cases.
    !
    AutoGrid,   ! NOTE: AutoGrid only necessary when EquivSizing is false
    ! If the modelled building is not a rectangle or square, Equivalent
    ! sizing MUST be used to get accurate results
           N1, \field CLEARANCE: Distance from outside of wall to edge, 15m]
           N2, \field SLABX: X dimension of the building slab, 0-60.0 m]
           N3, \field SLABY: Y dimension of the building slab, 0-60.0 m]
           N4, \field ConcAGHeight: Height of the fndn wall above grade, m]
           N5, \field SlabDepth: Thickness of the floor slab, m, 0.1]
           N6; \field BaseDepth: Depth of the basement wall below grade, m]
    !

    ManualGrid, ! NOTE: Manual Grid only necessary using manual gridding
    !  (not recommended)
           N1, \field NX: Number of cells in the X direction: 20]
           N2, \field NY: Number of cells in the Y direction: 20]
           N3, \field NZAG: Number of cells in the Z direction
    !              above grade: 4 Always]
           N4, \field NZBG: Number of cells in Z dir. below grade: 10-35]
           N5, \field IBASE: X direction cell indicator of slab edge: 5-20]
           N6, \field JBASE: Y direction cell indicator of slab edge: 5-20]
           N7; \field KBASE: Z direction cell indicator
    !              of the top of the floor slab: 5-20]
    !
    XFACE,       ! NOTE: This is only needed when using manual gridding
    !  (not recommended)
    !       [XFACE: X Direction cell face coordinates: m]
           N1, N2, N3, N4, N5, N6, N7, N8, N9, N10, N11, N12, N13, N14,
           N15, N16, N17, N18, N19, N20, N21, N22, N23, N24, N25, N26,
           N27, N28, N29, N30, N31, N32, N33, N34, N35, N36, N37, N38,
           N39, N40, N41, N42, N43, N44;
    !
    YFACE,  ! NOTE: This is only needed when using manual gridding
    !  (not recommended)
    !       [YFACE: Y Direction cell face coordinates: m],
           N1, N2, N3, N4, N5, N6, N7, N8, N9, N10, N11, N12, N13, N14,
           N15, N16, N17, N18, N19, N20, N21, N22, N23, N24, N25, N26,
           N27, N28, N29, N30, N31, N32, N33, N34, N35, N36, N37, N38,
           N39, N40, N41, N42, N43, N44;
    !
    ZFACE,  ! NOTE: This is only needed when using manual gridding
    !  (not recommended)
    !       [ZFACE: Z Direction cell face coordinates: m]
           N1, N2, N3, N4, N5, N6, N7, N8, N9, N10, N11, N12, N13, N14,
           N15, N16, N17, N18, N19, N20, N21, N22, N23, N24, N25, N26,
           N27, N28, N29, N30, N31, N32, N33, N34, N35, N36, N37, N38,
           N39, N40;