Internal Gains[LINK]
An actuator called “People”
is available with a control type called “Number of People.”
This allows you to dictate the number of people in a zone. The
units are persons. The unique identifier is the name of the
people input object. Because you cannot really control people,
this is an example the EMS in EnergyPlus departing from the
real world of building EMS.
An actuator called “Lights”
is available with a control type called “Electric Power Level”
(in W) This allows you to set the lighting power associated
with each Lights
input object. The unique identifier is the name of the Lights
input object.
Electric Equipment[LINK]
An actuator called “ElectricEquipment”
is available with a control type called “Electric Power Level”
(in W). This allows you to set the power associated with each
ElectricEquipment
input object. The unique identifier is the name of the ElectricEquipment
input object.
Gas Equipment[LINK]
An actuator called “GasEquipment”
is available with a control type called “Gas Power Level” (in
W). This allows you to set the power associated with each GasEquipment
input object. The unique identifier is the name of the GasEquipment
input object.
Hot Water Equipment[LINK]
An actuator called “HotWaterEquipment”
is available with a control type called “District Heating
Power Level” (in W). This allows you to set the power
associated with each HotWaterEquipment
input object. The unique identifier is the name of the HotWaterEquipment
input object.
Steam Equipment[LINK]
An actuator called “SteamEquipment”
is available with a control type called “District Heating
Power Level” (in W). This allows you to set the power
associated with each SteamEquipment
input object. The unique identifier is the name of the SteamEquipment
input object.
Other Equipment[LINK]
An actuator called “OtherEquipment”
is available with a control type called “Power Level” (in W).
This allows you to set the power associated with each OtherEquipment
input object. The unique identifier is the name of the OtherEquipment
input object.
Other equipment offers a way to adjust the zone air energy
balance without consuming any energy resources.
An actuator called “ZoneBaseboard:OutdoorTemperatureControlled”
is available with a control type called “Power Level” (in W).
The unique identifier is the name of the ZoneBaseboard:OutdoorTemperatureControlled
input object.
Internal Gains[LINK]
People[LINK]
An actuator called “People” is available with a control type called “Number of People.” This allows you to dictate the number of people in a zone. The units are persons. The unique identifier is the name of the people input object. Because you cannot really control people, this is an example the EMS in EnergyPlus departing from the real world of building EMS.
Lights[LINK]
An actuator called “Lights” is available with a control type called “Electric Power Level” (in W) This allows you to set the lighting power associated with each Lights input object. The unique identifier is the name of the Lights input object.
Electric Equipment[LINK]
An actuator called “ElectricEquipment” is available with a control type called “Electric Power Level” (in W). This allows you to set the power associated with each ElectricEquipment input object. The unique identifier is the name of the ElectricEquipment input object.
Gas Equipment[LINK]
An actuator called “GasEquipment” is available with a control type called “Gas Power Level” (in W). This allows you to set the power associated with each GasEquipment input object. The unique identifier is the name of the GasEquipment input object.
Hot Water Equipment[LINK]
An actuator called “HotWaterEquipment” is available with a control type called “District Heating Power Level” (in W). This allows you to set the power associated with each HotWaterEquipment input object. The unique identifier is the name of the HotWaterEquipment input object.
Steam Equipment[LINK]
An actuator called “SteamEquipment” is available with a control type called “District Heating Power Level” (in W). This allows you to set the power associated with each SteamEquipment input object. The unique identifier is the name of the SteamEquipment input object.
Other Equipment[LINK]
An actuator called “OtherEquipment” is available with a control type called “Power Level” (in W). This allows you to set the power associated with each OtherEquipment input object. The unique identifier is the name of the OtherEquipment input object.
Other equipment offers a way to adjust the zone air energy balance without consuming any energy resources.
Baseboard[LINK]
An actuator called “ZoneBaseboard:OutdoorTemperatureControlled” is available with a control type called “Power Level” (in W). The unique identifier is the name of the ZoneBaseboard:OutdoorTemperatureControlled input object.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.