The primary cooling system is constructed by using a PlantLoop
object. It uses an electric chiller that generates chilled
water which is used to charge the TES tank at night. The
chilled water stored in the TES tank is later used during the
peak hours to satisfy the demand loads. Therefore, the supply
side of the loop contains the electric chiller and the charge
side of the TES tank. The demand side loop contains the
cooling coil. The loop is operated by using plant equipment
operation schemes, and schedules. Refer to Figure #ref/fig
simple-line-diagram-for-the-primary-cooling-system for a
simple diagram of the Primary Cooling Loop.
Simple line diagram for the
primary cooling system
Flowcharts
for the Primary Cooling Loop Input Process[LINK]
This series of flowcharts serve as a guide for identifying
and inputting the CoolSysPrimary loop and its components into
the input file. The working fluid in this loop is water. The
important area for this loop is its controls. The EnergyPlus
line diagram for this loop is provided in Figure #ref/fig
energyplus-line-diagram-for-the-primary-cooling-system. A
simple flowchart for the separation of the half loops is
provided in Figure #ref/fig
simple-flowchart-for-the-separation-of-halfloops-in-the-primary-cooling-system.
EnergyPlus line diagram for the
primary cooling systemSimple flowchart for the
separation of half-loops in the primary cooling
system
CoolSysPrimary
Supply Side Loop Construction[LINK]
The main components on the supply side half loop for the
primary cooling system are the electric chiller that supplies
the chilled water, the variable speed pump that circulates the
chilled water through the loop, and the TES tank that stores
the supplied chilled water. This half loop supplies chilled
water to the cooling coil which is placed on the demand side
half loop. The supply side half loop contains five components,
four branches, nine nodes, and one splitter-mixer pair. The
EnergyPlus line diagram for the primary cooling loop supply
side is provided in Figure #ref/fig
energyplus-line-diagram-for-the-supply-side-of-the-primary-cooling-loop.
The flowchart for supply side branches and components is
provided in Figure #ref/fig
flowchart-for-primary-cooling-loop-supply-side-branches-and-components.
The flowchart for supply side connectors is provided in Figure
#ref/fig
flowchart-for-primary-cooling-loop-supply-side-connectors.
EnergyPlus line diagram for the
supply side of the primary cooling loopFlowchart for primary cooling
loop supply side branches and componentsFlowchart for primary cooling
loop supply side connectors
CoolSysPrimary
Demand Side Loop Construction[LINK]
The main component on the demand side half loop is the
cooling coil which cools the air in the building by using the
chilled water that is supplied by the supply side half loop.
This side of the loop has eight nodes, four components, four
branches, and one splitter mixer pair. An EnergyPlus line
diagram for the demand side is provided in Figure #ref/fig
energyplus-line-diagram-for-the-demand-side-of-the-primary-cooling-loop.
The flowchart for demand side branch definition is provided in
Figure #ref/fig
flowchart-for-primary-cooling-loop-demand-side-branches-and-components.
The flowchart for the demand side connectors is provided in
Figure #ref/fig
flowchart-for-primary-cooling-loop-demand-side-connectors.
EnergyPlus line diagram for the
demand side of the primary cooling loopFlowchart for primary cooling
loop demand side branches and componentsFlowchart for primary cooling
loop demand side connectors
Flowcharts
for Primary Cooling Loop Controls[LINK]
The Primary Cooling loop is operated by using set-points,
plant equipment operation schemes and schedules. The TES tank
charging schedule is one of the most important schedules in
this system.
The flowchart for Primary Cooling loop schedule definition
is provided in Figure #ref/fig
flowchart-for-primary-cooling-loop-schedules. The Primary
Cooling loop uses five different schedules to operate
properly. The PlantOnSchedule is a compact schedule
that keeps the chiller and the TES tank ON at all times of the
day, this compact schedule uses a discrete
ScheduleTypeLimit (On/Off) which defines
that the value of On is 1 and that of Off is 0. This plant
loop also uses another compact schedule named CW Primary
Loop Temp Schedule declare that the temperature of the
chilled water loop outlet flow is 6.7 degrees Celsius at all
times. This schedule is used by the setpoint manager
(CoolSysPrimary Loop Setpoint Manager). This schedule
uses a schedule type limit named Temperature, which
defines the upper and lower loop temperature limits
The compact schedule ALWAYS_ON dictates that the
use/discharge side of the TES tank is On at all times of the
day. This schedule uses the ScheduleTypeLimit
(Fraction) to set the fractional flow rate of the use
side. This schedule is used to define the use side
availability of the TES tank. The compact schedule CW Tank
Temp Schedule is input in the TES tank object class to
define the limits of the temperature for the chilled water
storage tank outlet. This schedule uses the
ScheduleTypeLimit (Temperature) to define that the
temperature at that outlet should be 7.5 degrees Celsius at
all times of the day.
The TES Charge Schedule is a very important
schedule for the functioning of the CoolSysPrimary Loop the
schedule from the input file is provided in Figure #ref/fig
tes-charge-schedule. The schedule shows that, the on/off
ScheduleTypeLimit is used to determine if the TES
schedule is On or off for a certain period of time. A value of
1.0 means On and a value of 0 means Off. For example, it can
be observed from the figure that, for the weekdays the TES
tank is charged until 10:00AM, then it is operated during the
day from 10:00 AM to 5:00 PM and then it is charged until
midnight. The schedule for the other days is also shown in the
figure.
TES Charge
ScheduleFlowchart for primary cooling
loop schedules
This loop has two plant equipment operation schemes, one
for the chiller and one for the TES tank. The
PlantEquipmentOperationschemes object uses the
PlantOnSchedule and the CoolSysPrimary Operation
Scheme objects to set the range of demand loads for which
the chiller is operated during the simulation period.
Operation schemes are especially useful and crucial when using
multiple active components. For example, the performance of
multiple chillers can be optimized by carefully managing the
load ranges on each of the chillers. It should be noted that
it is required to enter a plant equipment operation scheme for
every plant loop in the system. A flowchart detailing the
chilled water loop plant equipment operation schemes is
provided in Figure #ref/fig
flowchart-for-chiller-plant-equipment-operation-schemes.
Flowchart for Chiller plant
equipment operation schemes
The TES tank operation is modeled here. The
PlantEquipmentOperationschemes object uses the
PlantOnSchedule and the TES Operation Scheme
objects to set the range of the demand loads for which the TES
tank is operated during the simulation period. A flowchart
detailing the Secondary Cooling Loop plant equipment operation
schemes is provided in Figure #ref/fig
flowchart-for-thermal-energy-storage-plant-equipment-operation-schemes.
Flowchart for Thermal Energy
Storage plant equipment operation schemes
The CoolSysPrimary Loop Setpoint Manager uses the
CoolSysPrimary Loop Temp Schedule to set a
temperature control point at the CoolSysPrimary Supply
Outlet Node. This setpoint allows the program to control
the temperature at the node by operating the components in the
Primary Cooling loop. A flowchart for Secondary Cooling loop
setpoints is provided in Figure #ref/fig
flowchart-for-primary-cooling-loop-setpoints.
The chilled water loop is sized such a way that the design
loop exit temperature is 6.7 degrees Celsius, and the loop
design temperature difference is 5 degrees Celsius. A
flowchart for the Secondary Cooling loop sizing is provided in
Figure #ref/fig flowchart-for-primary-cooling-loop-sizing.
Primary Cooling Loop (CoolSysPrimary) - Chiller[LINK]
The primary cooling system is constructed by using a PlantLoop object. It uses an electric chiller that generates chilled water which is used to charge the TES tank at night. The chilled water stored in the TES tank is later used during the peak hours to satisfy the demand loads. Therefore, the supply side of the loop contains the electric chiller and the charge side of the TES tank. The demand side loop contains the cooling coil. The loop is operated by using plant equipment operation schemes, and schedules. Refer to Figure #ref/fig simple-line-diagram-for-the-primary-cooling-system for a simple diagram of the Primary Cooling Loop.
Flowcharts for the Primary Cooling Loop Input Process[LINK]
This series of flowcharts serve as a guide for identifying and inputting the CoolSysPrimary loop and its components into the input file. The working fluid in this loop is water. The important area for this loop is its controls. The EnergyPlus line diagram for this loop is provided in Figure #ref/fig energyplus-line-diagram-for-the-primary-cooling-system. A simple flowchart for the separation of the half loops is provided in Figure #ref/fig simple-flowchart-for-the-separation-of-halfloops-in-the-primary-cooling-system.
CoolSysPrimary Supply Side Loop Construction[LINK]
The main components on the supply side half loop for the primary cooling system are the electric chiller that supplies the chilled water, the variable speed pump that circulates the chilled water through the loop, and the TES tank that stores the supplied chilled water. This half loop supplies chilled water to the cooling coil which is placed on the demand side half loop. The supply side half loop contains five components, four branches, nine nodes, and one splitter-mixer pair. The EnergyPlus line diagram for the primary cooling loop supply side is provided in Figure #ref/fig energyplus-line-diagram-for-the-supply-side-of-the-primary-cooling-loop. The flowchart for supply side branches and components is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-supply-side-branches-and-components. The flowchart for supply side connectors is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-supply-side-connectors.
CoolSysPrimary Demand Side Loop Construction[LINK]
The main component on the demand side half loop is the cooling coil which cools the air in the building by using the chilled water that is supplied by the supply side half loop. This side of the loop has eight nodes, four components, four branches, and one splitter mixer pair. An EnergyPlus line diagram for the demand side is provided in Figure #ref/fig energyplus-line-diagram-for-the-demand-side-of-the-primary-cooling-loop. The flowchart for demand side branch definition is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-demand-side-branches-and-components. The flowchart for the demand side connectors is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-demand-side-connectors.
Flowcharts for Primary Cooling Loop Controls[LINK]
The Primary Cooling loop is operated by using set-points, plant equipment operation schemes and schedules. The TES tank charging schedule is one of the most important schedules in this system.
CoolSysPrimary Schedules[LINK]
The flowchart for Primary Cooling loop schedule definition is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-schedules. The Primary Cooling loop uses five different schedules to operate properly. The PlantOnSchedule is a compact schedule that keeps the chiller and the TES tank ON at all times of the day, this compact schedule uses a discrete ScheduleTypeLimit (On/Off) which defines that the value of On is 1 and that of Off is 0. This plant loop also uses another compact schedule named CW Primary Loop Temp Schedule declare that the temperature of the chilled water loop outlet flow is 6.7 degrees Celsius at all times. This schedule is used by the setpoint manager (CoolSysPrimary Loop Setpoint Manager). This schedule uses a schedule type limit named Temperature, which defines the upper and lower loop temperature limits
The compact schedule ALWAYS_ON dictates that the use/discharge side of the TES tank is On at all times of the day. This schedule uses the ScheduleTypeLimit (Fraction) to set the fractional flow rate of the use side. This schedule is used to define the use side availability of the TES tank. The compact schedule CW Tank Temp Schedule is input in the TES tank object class to define the limits of the temperature for the chilled water storage tank outlet. This schedule uses the ScheduleTypeLimit (Temperature) to define that the temperature at that outlet should be 7.5 degrees Celsius at all times of the day.
The TES Charge Schedule is a very important schedule for the functioning of the CoolSysPrimary Loop the schedule from the input file is provided in Figure #ref/fig tes-charge-schedule. The schedule shows that, the on/off ScheduleTypeLimit is used to determine if the TES schedule is On or off for a certain period of time. A value of 1.0 means On and a value of 0 means Off. For example, it can be observed from the figure that, for the weekdays the TES tank is charged until 10:00AM, then it is operated during the day from 10:00 AM to 5:00 PM and then it is charged until midnight. The schedule for the other days is also shown in the figure.
CoolSysPrimary Plant Equipment Operation Schemes[LINK]
This loop has two plant equipment operation schemes, one for the chiller and one for the TES tank. The PlantEquipmentOperationschemes object uses the PlantOnSchedule and the CoolSysPrimary Operation Scheme objects to set the range of demand loads for which the chiller is operated during the simulation period. Operation schemes are especially useful and crucial when using multiple active components. For example, the performance of multiple chillers can be optimized by carefully managing the load ranges on each of the chillers. It should be noted that it is required to enter a plant equipment operation scheme for every plant loop in the system. A flowchart detailing the chilled water loop plant equipment operation schemes is provided in Figure #ref/fig flowchart-for-chiller-plant-equipment-operation-schemes.
The TES tank operation is modeled here. The PlantEquipmentOperationschemes object uses the PlantOnSchedule and the TES Operation Scheme objects to set the range of the demand loads for which the TES tank is operated during the simulation period. A flowchart detailing the Secondary Cooling Loop plant equipment operation schemes is provided in Figure #ref/fig flowchart-for-thermal-energy-storage-plant-equipment-operation-schemes.
CoolSysPrimary Setpoints[LINK]
The CoolSysPrimary Loop Setpoint Manager uses the CoolSysPrimary Loop Temp Schedule to set a temperature control point at the CoolSysPrimary Supply Outlet Node. This setpoint allows the program to control the temperature at the node by operating the components in the Primary Cooling loop. A flowchart for Secondary Cooling loop setpoints is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-setpoints.
CoolSysPrimary Sizing[LINK]
The chilled water loop is sized such a way that the design loop exit temperature is 6.7 degrees Celsius, and the loop design temperature difference is 5 degrees Celsius. A flowchart for the Secondary Cooling loop sizing is provided in Figure #ref/fig flowchart-for-primary-cooling-loop-sizing.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.