Statement Keywords[LINK]
Every programming language has instructions or commands that
tell the processor what to do. Erl supports a few types of
program statements. Each line of an Erl program begins with a
statement keyword. The syntax for each line depends on the
keyword that starts that line. Only those listed in Table 1
are allowed.
|
Keyword
|
Syntax
|
Statement Description
|
|
RUN
|
RUN <program name>
|
Calls another Erl program or subroutine. Returns to the
calling point when completed. Recursive calling is allowed.
|
|
RETURN
|
RETURN,
|
Prematurely exits a subroutine or program and returns control
to the caller.
|
|
SET
|
SET <variable> = <expression>,
|
Assigns the right-hand side to the left-hand side. If
has not been used before, it is dynamically
declared (with local scope). Note: <variables>
should NOT start with numerics.
|
|
IF
|
IF <expression>,
|
Begins an “IF block.” Conditional decision. If
<expression> evaluates to anything other than zero, the
block of statements after the IF is executed.
|
|
ELSEIF
|
ELSEIF <expression>
|
Conditional decision that follows a regular IF block of
instructions. If <expression> evaluates to anything
other than zero, the block of instructions after the ELSEIF is
executed.
|
|
ELSE
|
ELSE,
|
Conditional decision. Associated with an IF statement, the
block of statements after the ELSE is executed if
<expression> evaluates to zero for preceding IF and
ELSEIF statements.
|
|
ENDIF
|
ENDIF,
|
Terminates IF block (required).
|
|
WHILE
|
WHILE <expression>
|
Begins a “WHILE block.” Conditional decision. If
<expression> evaluates to anything other than zero, the
block of statements after the WHILE is repeatedly executed.
|
|
ENDWHILE
|
ENDWHILE,
|
Terminates WHILE block (required).
|
Rules for IF blocks:[LINK]
IF blocks can be nested, but only up to five
deep.
ELSE is optional. If omitted, the IF block is
terminated by ENDIF.
IF-ELSEIF-ELSE-ENDIF blocks are allowed. If there are many
ELSEIF statements, the first in the list that evaluates to
true (1.0) is applied and the execution jumps to the ENDIF for
that IF block. If no IF or ELSEIF is true, the ELSE condition
(if any) is applied. A single IF block currently has a limit
of 199 ELSEIF statements plus one ELSE statement.
Rules for WHILE blocks:[LINK]
WHILE blocks cannot be nested.
A WHILE block must be terminated by an
ENDWHILE
The block is repeated until the expression following
the WHILE statement evaluates to 0.0 (false).
Once the WHILE loop is entered, there is a maximum
limit on the number of times the loop can be repeated. The
limit is set at one million repetitions to protect against the
possibility of an Erl program entering an infinite loop if the
WHILE loop’s expression is malformed so as to never evaluate
to 0.0 (false).
Erl programs are entered into the input data file (IDF)
using the input objects called EnergyManagementSystem:Program
and EnergyManagementSystem:Subroutine.
These objects use individual fields to store the statements
for an Erl program. As with most EnergyPlus objects, each
field is separated by a comma and typically given a separate
line of text for readability. In this case, each field can be
considered a separate line of Erl program code. Every input
field (line of code) must conform to the following rules:
Every input field contains only one statement.
Every field begins with a statement keyword that
identifies what that particular line of code is
doing.
The syntax for each statement depends on the
keyword.
All field content (keywords, variable names, etc.) is
case insensitive.
A comma (or semicolon if it is the last field) marks
the end of every statement.
The maximum length for a field is 100 characters. If
you enter a longer field, it will be truncated to the first
100 characters. This can have subtle effects if the remaining
portion forms a viable expression.
The “!” character is for comments.
REMEMBER, every line needs to end in a comma or, if it is
the last in the program, a semicolon.
Statement Keywords[LINK]
Every programming language has instructions or commands that tell the processor what to do. Erl supports a few types of program statements. Each line of an Erl program begins with a statement keyword. The syntax for each line depends on the keyword that starts that line. Only those listed in Table 1 are allowed.Rules for IF blocks:[LINK]
IF blocks can be nested, but only up to five deep.
ELSE is optional. If omitted, the IF block is terminated by ENDIF.
IF-ELSEIF-ELSE-ENDIF blocks are allowed. If there are many ELSEIF statements, the first in the list that evaluates to true (1.0) is applied and the execution jumps to the ENDIF for that IF block. If no IF or ELSEIF is true, the ELSE condition (if any) is applied. A single IF block currently has a limit of 199 ELSEIF statements plus one ELSE statement.
Rules for WHILE blocks:[LINK]
WHILE blocks cannot be nested.
A WHILE block must be terminated by an ENDWHILE
The block is repeated until the expression following the WHILE statement evaluates to 0.0 (false).
Once the WHILE loop is entered, there is a maximum limit on the number of times the loop can be repeated. The limit is set at one million repetitions to protect against the possibility of an Erl program entering an infinite loop if the WHILE loop’s expression is malformed so as to never evaluate to 0.0 (false).
Erl programs are entered into the input data file (IDF) using the input objects called EnergyManagementSystem:Program and EnergyManagementSystem:Subroutine. These objects use individual fields to store the statements for an Erl program. As with most EnergyPlus objects, each field is separated by a comma and typically given a separate line of text for readability. In this case, each field can be considered a separate line of Erl program code. Every input field (line of code) must conform to the following rules:
Every input field contains only one statement.
Every field begins with a statement keyword that identifies what that particular line of code is doing.
The syntax for each statement depends on the keyword.
All field content (keywords, variable names, etc.) is case insensitive.
A comma (or semicolon if it is the last field) marks the end of every statement.
The maximum length for a field is 100 characters. If you enter a longer field, it will be truncated to the first 100 characters. This can have subtle effects if the remaining portion forms a viable expression.
The “!” character is for comments.
REMEMBER, every line needs to end in a comma or, if it is the last in the program, a semicolon.