Rectangular single story building with 5 occupied zones
and a ceiling plenum
Packaged DX cooling with gas heat serving one
zone
VAV with reheat and return plenum serving the other 4
zones
All equipment autosized using summer and winter design
days

Figure 20. Schematic for Exercise 2.
Details of the Exercise[LINK]
Building Description[LINK]
Single floor rectangular building 30.5 m (100 ft) by
15.2 m (50 ft) by 3m (10 ft) high.
Building
is oriented with the long axis running east-west.
Floor Area 463.6 m2 (5000 ft2).
5 occupied zones - 4 exterior, 1 interior, zone height
2.4 m (8 ft). Exterior zone depth is 3.7 m (12 ft).
1 plenum zone 0.6 m (2 ft) high.
Windows on all 4 facades
South and north facades have glass doors.
South facing glass is shaded by overhangs.
Walls are wood shingle over plywood, insulation, and
gypsum board.
Roof
is gravel built up roof with mineral board insulation and
plywood sheathing.
Floor slab is 0.1 m (4 in) heavy concrete.
Windows and glass doors are double pane Low-e clear
glass with argon gap.
Window
to wall ratio is approximately 0.3.
Lighting is 16 W/m2 (1.5 W/ft2).
Office electric equipment is 10.8 W/m2 (1.0
W/ft2).
1 occupant per 9.3 m2 (100 ft2) of floor area.
Infiltration is 0.25 air changes per hour (always on,
proportional to wind speed).
* Refers to specific glass type included in the
EnergyPlus datasets directory
(WindowGlassMaterials.idf)
Space Conditioning[LINK]
Heating setpoints: 21.1C (70F) occupied, 12.8C (55F)
unoccupied
Cooling setpoints: 23.9C (75F) occupied, 40.0C (104F,
system off) unoccupied
Plenum zone not controlled
Location: Chicago, Illinois,
USA
Design Days: Summer, Winter
Annual Simulation Period: Jan 1 – Dec 31
Ground Temperatures: from Slab preprocessor
(20.4 to 23.0 C)
Unitary System and VAV using HVACTemplate Inputs[LINK]
Overview[LINK]
Rectangular single story building with 5 occupied zones and a ceiling plenum
Packaged DX cooling with gas heat serving one zone
VAV with reheat and return plenum serving the other 4 zones
All equipment autosized using summer and winter design days
Figure 20. Schematic for Exercise 2.
Details of the Exercise[LINK]
Building Description[LINK]
Single floor rectangular building 30.5 m (100 ft) by 15.2 m (50 ft) by 3m (10 ft) high.
Building is oriented with the long axis running east-west.
Floor Area 463.6 m2 (5000 ft2).
5 occupied zones - 4 exterior, 1 interior, zone height 2.4 m (8 ft). Exterior zone depth is 3.7 m (12 ft).
1 plenum zone 0.6 m (2 ft) high.
Windows on all 4 facades
South and north facades have glass doors.
South facing glass is shaded by overhangs.
Walls are wood shingle over plywood, insulation, and gypsum board.
Roof is gravel built up roof with mineral board insulation and plywood sheathing.
Floor slab is 0.1 m (4 in) heavy concrete.
Windows and glass doors are double pane Low-e clear glass with argon gap.
Window to wall ratio is approximately 0.3.
Lighting is 16 W/m2 (1.5 W/ft2).
Office electric equipment is 10.8 W/m2 (1.0 W/ft2).
1 occupant per 9.3 m2 (100 ft2) of floor area.
Infiltration is 0.25 air changes per hour (always on, proportional to wind speed).
* Refers to specific glass type included in the EnergyPlus datasets directory
(WindowGlassMaterials.idf)
Space Conditioning[LINK]
Heating setpoints: 21.1C (70F) occupied, 12.8C (55F) unoccupied
Cooling setpoints: 23.9C (75F) occupied, 40.0C (104F, system off) unoccupied
Plenum zone not controlled
Environment[LINK]
Location: Chicago, Illinois, USA
Design Days: Summer, Winter
Annual Simulation Period: Jan 1 – Dec 31
Ground Temperatures: from Slab preprocessor (20.4 to 23.0 C)
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.