The “branch node details” (bnd) file is intended to give
enough information that one could (with a chosen software)
diagram the nodes and components of the HVAC system. It may or
may not achieve that objective. Of more use may be its
illustration of node connection/branch errors that aren’t
detected by the software. This file has the details to support
any “node connection” errors that will be noted in the
eplusout.err file. Branch
validation is shown in this file. Branches are checked to
assure that each output node of the branch element is an input
node to the next branch element. Cross-branch checking is not
done directly within the program though the details will
illustrate some problems of that nature.
Supply and Return Air Paths are also checked and feedback
about each item are shown.
As is standard with many EnergyPlus output files, this file
is CSV (comma-delimited) such that it can be read by
spreadsheet programs for further manipulation by the user.
An example will illustrate. Notes about the reporting are
highlighted in green.
Program Version,EnergyPlus, <version>
! This file shows details about the branches, nodes, and
other
! elements of the flow connections.
! This file is intended for use in “debugging” potential
problems
! that may also be detected by the program, but may be more
easily
! identified by “eye”.
! This file is also intended to support software which
draws a
! schematic diagram of the HVAC system.
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
! #Nodes,<Number of Unique Nodes>
#Nodes,11
List of all nodes follows. # references may be an
indication of faulty node spec (or not)
! <Node>,<NodeNumber>,<Node
Name>,<Node Fluid Type>,<# Times Node Referenced
After Definition>
Node,1,SUPPLY INLET NODE,Air,3
Node,2,FAN INLET NODE,Air,4
<reduced for brevity>
Node,10,ZONE EQUIPMENT OUTLET NODE,Air,2
Node,11,RELIEF AIR OUTLET NODE,Air,1
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
! Suspicious nodes have 0 references. It is normal for some
nodes, however.
! Suspicious nodes have 0 references. It is normal for
some nodes, however.
! Listing nodes with 0 references (culled from previous
list):
! <Suspicious Node>,<NodeNumber>,<Node
Name>,<Node Fluid Type>,<# Times Node Referenced
After Definition>
Suspicious Node,7,MAIN ZONE NODE,Air,0
List of branches follow.
! <#Branch Lists>,<Number of Branch
Lists>
#Branch Lists,1
! <Branch List>,<Branch List Count>,<Branch
List Name>,<Loop Name>,<Loop Type>,<Number
of Branches>
! <Branch>,<Branch Count>,<Branch
Name>,<Loop Name>,<Loop Type>,<Branch Inlet
Node Name>,<Branch Outlet Node Name>
Branch List,1,AIR LOOP BRANCHES,EVAP COOLER
SYSTEM,Air,1
Branch,1,AIR LOOP MAIN BRANCH,EVAP COOLER
SYSTEM,Air,SUPPLY INLET NODE,SUPPLY OUTLET NODE
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
! <#Supply Air Paths>,<Number of Supply Air
Paths>
! <#Supply Air Paths>,<Number of Supply Air
Paths>
#Supply Air Paths,1
! <Supply Air Path>,<Supply Air Path
Count>,<Supply Air Path Name>,<AirLoopHVAC
Name>
! <#Components on Supply Air Path>,<Number of
Components>
! <Supply Air Path Component>,<Component
Count>,<Component Type>,<Component
Name>,<AirLoopHVAC Name>
! <#Outlet Nodes on Supply Air Path
Component>,<Number of Nodes>
! <Supply Air Path Component Nodes>,<Node
Count>,<Component Type>,<Component
Name>,<Inlet Node Name>,<Outlet Node
Name>,<AirLoopHVAC Name>
Supply Air Path,1,ZONE SUPPLY AIR PATH,EVAP COOLER
SYSTEM
#Components on Supply Air Path,1
Supply Air Path
Component,1,AIRLOOPHVAC:ZONESPLITTER,ZONE SUPPLY AIR
SPLITTER,EVAP COOLER SYSTEM
#Outlet Nodes on Supply Air Path Component,1
Supply Air Path Component
Nodes,1,AIRLOOPHVAC:ZONESPLITTER,ZONE SUPPLY AIR SPLITTER,ZONE
EQUIPMENT INLET NODE,MAIN ZONE INLET NODE,EVAP COOLER
SYSTEM
! <#Nodes on Supply Air Path>,<Number of
Nodes>
! <Supply Air Path Node>,<Node Type>,<Node
Count>,<Node Name>,<AirLoopHVAC Name>
#Nodes on Supply Air Path,2
Supply Air Path Node,Inlet Node,1,ZONE EQUIPMENT INLET
NODE,EVAP COOLER SYSTEM
Supply Air Path Node,Outlet Node,2,MAIN ZONE INLET
NODE,EVAP COOLER SYSTEM
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
! <#Return Air Paths>,<Number of Return Air
Paths>
! <#Return Air Paths>,<Number of Return Air
Paths>
#Return Air Paths,1
! <Return Air Path>,<Return Air Path
Count>,<Return Air Path Name>,<AirLoopHVAC
Name>
! <#Components on Return Air Path>,<Number of
Components>
! <Return Air Path Component>,<Component
Count>,<Component Type>,<Component
Name>,<AirLoopHVAC Name>
! <#Inlet Nodes on Return Air Path
Component>,<Number of Nodes>
! <Return Air Path Component Nodes>,<Node
Count>,<Component Type>,<Component
Name>,<Inlet Node Name>,<Outlet Node
Name>,<AirLoopHVAC Name>
Return Air Path,1,ZONE RETURN AIR PATH,EVAP COOLER
SYSTEM
#Components on Return Air Path,1
Return Air Path Component,1,AIRLOOPHVAC:ZONEMIXER,ZONE
RETURN AIR MIXER,EVAP COOLER SYSTEM
#Inlet Nodes on Return Air Path Component,1
Return Air Path Component
Nodes,1,AIRLOOPHVAC:ZONEMIXER,ZONE RETURN AIR MIXER,MAIN ZONE
OUTLET NODE,ZONE EQUIPMENT OUTLET NODE,EVAP COOLER SYSTEM
! <#Nodes on Return Air Path>,<Number of
Nodes>
! <Return Air Path Node>,<Node Type>,<Node
Count>,<Node Name>,<AirLoopHVAC Name>
#Nodes on Return Air Path,2
Return Air Path Node,Outlet Node,1,ZONE EQUIPMENT OUTLET
NODE,EVAP COOLER SYSTEM
Return Air Path Node,Inlet Node,2,MAIN ZONE OUTLET
NODE,EVAP COOLER SYSTEM
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
! #Outside Air Nodes,<Number of Outside Air
Nodes>
! #Outdoor Air Nodes,<Number of Outdoor Air
Nodes>
#Outdoor Air Nodes,1
! <Outdoor Air Node>,<NodeNumber>,<Node
Name>
Outdoor Air Node,5,OUTSIDE AIR INLET NODE
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
= = =
Component sets. Very important for node connection
error detection.
! <#Component Sets>,<Number of Component
Sets>
#Component Sets,4
! <Component Set>,<Component Set
Count>,<Parent Object Type>,<Parent Object
Name>,<Component Type>,<Component
Name>,<Inlet Node ID>,<Outlet Node
ID>,<Description>
Component Set,1,BRANCH,AIR LOOP MAIN
BRANCH,AIRLOOPHVAC:OUTDOORAIRSYSTEM,OUTSIDE AIR SYSTEM,SUPPLY
INLET NODE,FAN INLET NODE,Air Nodes
Component Set,2,BRANCH,AIR LOOP MAIN
BRANCH,FAN:CONSTANTVOLUME,SUPPLY FAN,FAN INLET NODE,EVAP
COOLER INLET NODE,Air Nodes
Component Set,3,BRANCH,AIR LOOP MAIN
BRANCH,EVAPORATIVECOOLER:DIRECT:CELDEKPAD,EVAPORATIVE
COOLER,EVAP COOLER INLET NODE,SUPPLY OUTLET NODE,Evap Air
Nodes
Component Set,4,AIRLOOPHVAC:OUTDOORAIRSYSTEM,OUTSIDE AIR
SYSTEM,OUTDOORAIR:MIXER,OUTSIDE AIR MIXING BOX,OUTSIDE AIR
INLET NODE,FAN INLET NODE,Air Nodes
Similar details for Plant Loops, Condenser Loops,
Controlled Zones, etc.
eplusout.bnd[LINK]
The “branch node details” (bnd) file is intended to give enough information that one could (with a chosen software) diagram the nodes and components of the HVAC system. It may or may not achieve that objective. Of more use may be its illustration of node connection/branch errors that aren’t detected by the software. This file has the details to support any “node connection” errors that will be noted in the eplusout.err file. Branch validation is shown in this file. Branches are checked to assure that each output node of the branch element is an input node to the next branch element. Cross-branch checking is not done directly within the program though the details will illustrate some problems of that nature.
Supply and Return Air Paths are also checked and feedback about each item are shown.
As is standard with many EnergyPlus output files, this file is CSV (comma-delimited) such that it can be read by spreadsheet programs for further manipulation by the user.
An example will illustrate. Notes about the reporting are highlighted in green.
Program Version,EnergyPlus, <version>
! This file shows details about the branches, nodes, and other
! elements of the flow connections.
! This file is intended for use in “debugging” potential problems
! that may also be detected by the program, but may be more easily
! identified by “eye”.
! This file is also intended to support software which draws a
! schematic diagram of the HVAC system.
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
! #Nodes,<Number of Unique Nodes>
#Nodes,11
List of all nodes follows. # references may be an indication of faulty node spec (or not)
! <Node>,<NodeNumber>,<Node Name>,<Node Fluid Type>,<# Times Node Referenced After Definition>
Node,1,SUPPLY INLET NODE,Air,3
Node,2,FAN INLET NODE,Air,4
<reduced for brevity>
Node,10,ZONE EQUIPMENT OUTLET NODE,Air,2
Node,11,RELIEF AIR OUTLET NODE,Air,1
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
! Suspicious nodes have 0 references. It is normal for some nodes, however.
! Suspicious nodes have 0 references. It is normal for some nodes, however.
! Listing nodes with 0 references (culled from previous list):
! <Suspicious Node>,<NodeNumber>,<Node Name>,<Node Fluid Type>,<# Times Node Referenced After Definition>
Suspicious Node,7,MAIN ZONE NODE,Air,0
List of branches follow.
! <#Branch Lists>,<Number of Branch Lists>
#Branch Lists,1
! <Branch List>,<Branch List Count>,<Branch List Name>,<Loop Name>,<Loop Type>,<Number of Branches>
! <Branch>,<Branch Count>,<Branch Name>,<Loop Name>,<Loop Type>,<Branch Inlet Node Name>,<Branch Outlet Node Name>
Branch List,1,AIR LOOP BRANCHES,EVAP COOLER SYSTEM,Air,1
Branch,1,AIR LOOP MAIN BRANCH,EVAP COOLER SYSTEM,Air,SUPPLY INLET NODE,SUPPLY OUTLET NODE
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
! <#Supply Air Paths>,<Number of Supply Air Paths>
! <#Supply Air Paths>,<Number of Supply Air Paths>
#Supply Air Paths,1
! <Supply Air Path>,<Supply Air Path Count>,<Supply Air Path Name>,<AirLoopHVAC Name>
! <#Components on Supply Air Path>,<Number of Components>
! <Supply Air Path Component>,<Component Count>,<Component Type>,<Component Name>,<AirLoopHVAC Name>
! <#Outlet Nodes on Supply Air Path Component>,<Number of Nodes>
! <Supply Air Path Component Nodes>,<Node Count>,<Component Type>,<Component Name>,<Inlet Node Name>,<Outlet Node Name>,<AirLoopHVAC Name>
Supply Air Path,1,ZONE SUPPLY AIR PATH,EVAP COOLER SYSTEM
#Components on Supply Air Path,1
Supply Air Path Component,1,AIRLOOPHVAC:ZONESPLITTER,ZONE SUPPLY AIR SPLITTER,EVAP COOLER SYSTEM
#Outlet Nodes on Supply Air Path Component,1
Supply Air Path Component Nodes,1,AIRLOOPHVAC:ZONESPLITTER,ZONE SUPPLY AIR SPLITTER,ZONE EQUIPMENT INLET NODE,MAIN ZONE INLET NODE,EVAP COOLER SYSTEM
! <#Nodes on Supply Air Path>,<Number of Nodes>
! <Supply Air Path Node>,<Node Type>,<Node Count>,<Node Name>,<AirLoopHVAC Name>
#Nodes on Supply Air Path,2
Supply Air Path Node,Inlet Node,1,ZONE EQUIPMENT INLET NODE,EVAP COOLER SYSTEM
Supply Air Path Node,Outlet Node,2,MAIN ZONE INLET NODE,EVAP COOLER SYSTEM
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
! <#Return Air Paths>,<Number of Return Air Paths>
! <#Return Air Paths>,<Number of Return Air Paths>
#Return Air Paths,1
! <Return Air Path>,<Return Air Path Count>,<Return Air Path Name>,<AirLoopHVAC Name>
! <#Components on Return Air Path>,<Number of Components>
! <Return Air Path Component>,<Component Count>,<Component Type>,<Component Name>,<AirLoopHVAC Name>
! <#Inlet Nodes on Return Air Path Component>,<Number of Nodes>
! <Return Air Path Component Nodes>,<Node Count>,<Component Type>,<Component Name>,<Inlet Node Name>,<Outlet Node Name>,<AirLoopHVAC Name>
Return Air Path,1,ZONE RETURN AIR PATH,EVAP COOLER SYSTEM
#Components on Return Air Path,1
Return Air Path Component,1,AIRLOOPHVAC:ZONEMIXER,ZONE RETURN AIR MIXER,EVAP COOLER SYSTEM
#Inlet Nodes on Return Air Path Component,1
Return Air Path Component Nodes,1,AIRLOOPHVAC:ZONEMIXER,ZONE RETURN AIR MIXER,MAIN ZONE OUTLET NODE,ZONE EQUIPMENT OUTLET NODE,EVAP COOLER SYSTEM
! <#Nodes on Return Air Path>,<Number of Nodes>
! <Return Air Path Node>,<Node Type>,<Node Count>,<Node Name>,<AirLoopHVAC Name>
#Nodes on Return Air Path,2
Return Air Path Node,Outlet Node,1,ZONE EQUIPMENT OUTLET NODE,EVAP COOLER SYSTEM
Return Air Path Node,Inlet Node,2,MAIN ZONE OUTLET NODE,EVAP COOLER SYSTEM
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
! #Outside Air Nodes,<Number of Outside Air Nodes>
! #Outdoor Air Nodes,<Number of Outdoor Air Nodes>
#Outdoor Air Nodes,1
! <Outdoor Air Node>,<NodeNumber>,<Node Name>
Outdoor Air Node,5,OUTSIDE AIR INLET NODE
! = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
Component sets. Very important for node connection error detection.
! <#Component Sets>,<Number of Component Sets>
#Component Sets,4
! <Component Set>,<Component Set Count>,<Parent Object Type>,<Parent Object Name>,<Component Type>,<Component Name>,<Inlet Node ID>,<Outlet Node ID>,<Description>
Component Set,1,BRANCH,AIR LOOP MAIN BRANCH,AIRLOOPHVAC:OUTDOORAIRSYSTEM,OUTSIDE AIR SYSTEM,SUPPLY INLET NODE,FAN INLET NODE,Air Nodes
Component Set,2,BRANCH,AIR LOOP MAIN BRANCH,FAN:CONSTANTVOLUME,SUPPLY FAN,FAN INLET NODE,EVAP COOLER INLET NODE,Air Nodes
Component Set,3,BRANCH,AIR LOOP MAIN BRANCH,EVAPORATIVECOOLER:DIRECT:CELDEKPAD,EVAPORATIVE COOLER,EVAP COOLER INLET NODE,SUPPLY OUTLET NODE,Evap Air Nodes
Component Set,4,AIRLOOPHVAC:OUTDOORAIRSYSTEM,OUTSIDE AIR SYSTEM,OUTDOORAIR:MIXER,OUTSIDE AIR MIXING BOX,OUTSIDE AIR INLET NODE,FAN INLET NODE,Air Nodes
Similar details for Plant Loops, Condenser Loops, Controlled Zones, etc.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.