Tips and Tricks for Using EnergyPlus — EnergyPlus 8.4

<< Prev | Table of Contents | Object Index | Next >>

Rain Flag[LINK]

Why is my exterior convection coefficient value 1000?

When the outside environment indicates that it is raining, the exterior surfaces (exposed to wind) are assumed to be wet. The convection coefficient is set to a very high number (1000) and the outside temperature used for the surface will be the wet-bulb temperature. (If you choose to report this variable, you will see 1000 as its value.)