System Node Setpoints[LINK]
A series of actuators is available for all the setpoints
that can be placed on system nodes. System nodes are used to
define air and plant loops, and a natural application of EMS
is to control the setpoints at these nodes. The node actuators
are all called “System Node Setpoint.” There are nine control
types:
Temperature Setpoint, (°C)
Temperature Minimum Setpoint (°C)
Temperature Maximum Setpoint (°C)
Humidity Ratio Setpoint (kgWater/kgDryAir)
Humidity Ratio Minimum Setpoint
(kgWater/kgDryAir)
Humidity Ratio Maximum Setpoint
(kgWater/kgDryAir)
Mass Flow Rate Setpoint (kg/s)
Mass Flow Rate Minimum Setpoint (kg/s)
Mass Flow Rate Maximum Setpoint (units kg/s)
Using these actuators is natural with an EMS. Typically,
the controller would place the setpoint on the outlet node.
Then the component’s low-level controller should operate to
meet the leaving setpoint. Setting the setpoints on nodes
should be a common application for the EMS.
Although all nine possible setpoints are available as EMS
actuators, it does not follow that EnergyPlus can use all of
them. Most components can use only one or two setpoints. If a
component cannot control to meet the setpoints on a node, the
actuator will do nothing.
Zone HVAC Control[LINK]
Several actuators relate to HVAC zone controls for
temperature, humidity, and comfort.
Two actuators called “Zone Temperature Control” are
available with the control types of “Heating Setpoint” and
“Cooling Setpoint.” These enable you to directly override the
zone-by-zone heating and cooling setpoints. The units are in
degrees Celsius. The unique identifier is the zone
name.
Two actuators called “Zone Humidity Control” are
available with the control types “Relative Humidity
Humidifying Setpoint” and “Relative Humidity Dehumidifying
Setpoint.” These enable you to directly override the
zone-by-zone humidity control setpoints. The units are in
percent relative humidity. The unique identifier is the zone
name.
Two actuators called “Zone Comfort Control” are
available with the control types “Heating Setpoint” and
“Cooling Setpoint.” These enable you to directly override the
zone-by-zone comfort control setpoints. The units are
predicted mean vote (PMV). The unique identifier is the zone
name.
Plant Supervisory
Control[LINK]
Several levels of actuators are available for on/off
supervisory control of Plant systems.
Each plant (and condenser) loop has an actuator called
“Plant Loop Overall” available with the control type “On/Off
Supervisory.” Setting the value of this actuator to 1.0
directs the overall plant to loop to run normally based on
other controls. Setting the value of this actuator to 0.0
directs the overall plant loop to shut down regardless of what
other controls indicate.
Each plant (and condenser) loop has actuators called
“Supply Side Half Loop” and “Demand Side Half Loop” that are
available with the control type “On/Off Supervisory.” Setting
the value of this actuator to 1.0 directs the plant’s loop
side to run normally based on other controls. Setting the
value of this actuator to 0.0 directs the plant’s loop side to
shut down regardless of what other controls indicate.
Each plant (and condenser) loop has a series of
actuators called “Supply Side Branch” and “Demand Side Branch”
that are available with the control type “On/Off
Supervisory.” These are available for each individual branch
in a loop. Setting the value of this actuator to 1.0 directs
the plant’s branch to run normally based on other controls.
Setting the value of this actuator to 0.0 directs the plant’s
branch to shut down regardless of what other controls
indicate.
Each plant (and condenser) loop has a series of
actuators called “Plant Component *” that are available with
the control type “On/Off Supervisory.” These are available
for each individual component on a loop. Setting the value of
this actuator to 1.0 directs the component to run normally
based on other controls. Setting the value of this actuator to
0.0 directs the component to shut down regardless of what
other controls indicate.
Outdoor Air System
Node Conditions[LINK]
Actuators called “Outdoor Air System Node” are available
with control types called “Drybulb Temperature” and “Wetbulb
Temperature.” The units are degrees Celsius. These actuators
are available for all system nodes that are listed in either
an OutdoorAir:Node
or OutdoorAir:NodeList
input object. You should probably set both the drybulb and
wetbulb temperatures to ensure a full description of the moist
air conditions.
The air system and many component models require you to
specify a node as an outdoor air node to obtain values for the
outdoor conditions. For example, outdoor air nodes are used at
the inlet to an outdoor air mixer or at the inlet of the heat
rejection side of a component model. Typically this is the
weather data value for outdoor conditions. But local
variations in microclimate may shift the local outdoor air
temperature to differ slightly from the weather data.
(Currently the only local variation model for this effect in
EnergyPlus varies the outdoor air conditions as a function of
height.) If you want to experiment with other models for
local variations in outdoor air conditions, this EMS actuator
allows you to override the outdoor temperature at a particular
system node with any model that can be implemented in an Erl
program. For example (although better models for the changes
in conditions may need be developed), this actuator could be
used to examine the energy impacts of warmer outdoor air
temperatures experienced by a rooftop packaged HVAC system
sitting on a black roof or the cooler conditions experienced
by a unit that is located on the shaded side of a building.
Another example is to make use of a separate model, outside of
EnergyPlus, for some unique type of component (such as a
labyrinth or earth-tube) that preconditions outdoor air; the
results of that model could be fed into the air system model
in EnergyPlus using these actuators.
AirLoopHVAC
Availability Status[LINK]
This actuator is available in all models with central, or
primary, air systems that are entered with the object
“AirLoopHVAC.” Various availability managers use the air
loop’s availability status to override control of the central
air system fan. The fan may be scheduled to be unavailable
during certain times to shut down the system when it is not
needed. However, there may be times when the air system should
be started to protect from freezing, for example. This
actuator can force an air system to start up or shut down.
The control is actuated by setting values for the
availability status. The settings are numeric, but represent
discrete states the status can take. The following settings
are valid:
0.0 ( = NoAction). This tells the air system to do
whatever it would usually do without any special override
status.
1.0 ( = ForceOff). This overrides the air system to
shut down when it would normally want to run.
2.0 ( = CycleOn). This overrides the air system to
start up when it would normally be off.
3.0 ( = CycleOnZoneFansOnly). This overrides only the
zone fans (not the central fans) if they would normally be
off.
Ideal Loads Air System[LINK]
An actuator called “Ideal Loads Air System” is available
with control types called “Air Mass Flow Rate” (supply air),
“Outdoor Air Mass Flow Rate,” “Air Temperature,” and “Air
Humidity Ratio.” These are available in models that use the
ideal loads air system, formerly known as purchased air. The
units are kg/s for mass flow rate, C for temperature and
kgWater/kgDryAir for humidity ratio. The unique identifier is
the user-defined name of the ZoneHVAC:IdealLoadsAirSystem
input object.
For Air Temperature and Air Humidity Ratio, the overrides
are absolute. They are applied after all other limits have
been checked. For mass flow rate, the overrides are not
absolute, in that the model has additional internal controls
that may not always be overridden. The internal controls will
still apply the capacity and flow rate limits if defined in
the input object. The EMS override affects the flow rate only
if the air system is on. If the air system is “off,” the mass
flow is zero regardless of the actuator setting. The internal
model controls will turn off the air system if the zone is in
the dead band or if it is scheduled “off” by availability
managers. This behavior allows you to use the internal
controls to determine when the air should cycle on, as for a
constant volume system that cycles to achieve control. If both
the Air Mass Flow Rate and Outdoor Air Mass Flow Rate are
overridden, the Outdoor Air Mass Flow Rate will not be allowed
to be greater than the override value for Air Mass Flow
Rate.
Actuators called “Fan” are available with the control types
“Fan Air Mass Flow Rate,” “Fan Pressure Rise,” and “Fan Total
Efficiency.” These provide direct control over the fan
operation in an air system. The EMS program can override the
flow rate by using kg/s. It can override the total pressure
rise at the fan by using Pascals. And it can override the fan
efficiency on a scale from 0.0 to 1.0. The unique identifier
is the name of the fan in the Fan input objects.
An actuator is also available for overriding the autosize
value for the fan’s design air flow rate. This actuator is
called “Fan” and the control type is “’Fan Autosized Air Flow
Rate” with units in m\(^{3}\)/s. It is only useful from
the calling point named AfterComponentInputReadIn.
DX Cooling Coils[LINK]
Actuators are available for overriding the autosize values
related to the size of single speed DX coils. Actuators
called “Coil:Cooling:DX:SingleSpeed” are available with
control types “Autosized Rated Air Flow Rate” (in m3/s),
“Autosized Rated Sensible Heat Ratio” (in W/W), and “Autosized
Rated Total Cooling Capacity” (in W). These are only useful
from the calling point named AfterComponentInputReadIn.
Unitary Equipment[LINK]
Actuators called “Unitary HVAC” are available with the
control types “Sensible Load Request” and “Moisture Load
Request.” These control the operation of unitary equipment.
Normally these systems operate to meet zone loads, but these
actuators allow you to override the controls of unitary
systems. The units are in Watts. The unique identifier is the
name of the unitary equipment in the input objects.
Actuators are available for overriding the autosize values
related to supply air flow rates some unitary HVAC equipment.
These actuators allow selectively altering the outcome of
sizing routines and are used from the calling point named
AfterComponentInputReadIn. The units are m\(^{3}\)/s.
An actuator called
“AirLoopHVAC:Unitary:Furnace:HeatOnly” is available with
control type “Autosized Supply Air Flow Rate.”
An actuator called “AirLoopHVAC:UnitaryHeatOnly” is
available with control type “Autosized Supply Air Flow
Rate.”
Actuators called “AirLoopHVAC:Unitary:Furnace:HeatCool”
and “AirLoopHVAC:UnitaryHeatCool”are available with control
types “Autosized Supply Air Flow Rate,” “Autosized Supply Air
Flow Rate During Cooling Operation,” “Autosized Supply Air
Flow Rate During Heating Operation,” and “Autosized Supply Air
Flow Rate During No Heating or Cooling Operation.”
An actuator called
“AirLoopHVAC:UnitaryHeatPump:AirToAir” is available with
control type “Autosized Supply Air Flow Rate.”
An actuator called
“AirLoopHVAC:UnitaryHeatPump:WaterToAir” is available with
control type “Autosized Supply Air Flow Rate.”
AirTerminal:SingleDuct:Uncontrolled[LINK]
An actuator called “AirTerminal:SingleDuct:Uncontrolled” is
available with a control type called “Mass Flow Rate.” This
actuator is available in models that use the direct air
terminal. The units are kg/s. This actuator is used to control
the flow rate. Normally, the flow rate of direct air terminals
is fixed by the input or sizing results, but this actuator
provides a way to override the flow with Erl programs.
Outdoor Air Controller[LINK]
An actuator called “Outdoor Air Controller” is available
with the control type called “Air Mass Flow Rate.” This
provides override control over the rate of outdoor air. The
units are kg/s. The unique identifier is the name of the Controller:OutdoorAir
input object.
Plant Load Profile[LINK]
Actuators called “Plant Load Profile” are available with
the control types called “Mass Flow Rate” (in kg/s) and
“Power” (in W). The unique identifier is the name of the LoadProfile:Plant
input object. These actuators provide override control over
the loads placed on a plant system by a plant load
profile.
An actuator called “Pump” is available with the control
type “Pump Mass Flow Rate” (in kg/s). This allows you to
override the flow rate produced by a pump. The unique
identifier is the name of Pump Input object.
Window Air Conditioner[LINK]
An actuator called “Window Air Conditioner” is available
with a control type called “Part Load Ratio.” This is
nondimensional and takes numbers between 0.0 and 1.0. The
unique identifier is the name of the ZoneHVAC:WindowAirConditioner
input object.
Low Temperature
Radiant Hydronic[LINK]
Actuators called “Hydronic Low Temp Radiant” and “Constant
Flow Low Temp Radiant” are available with the control type
“Water Mass Flow Rate” (in kg/s). This allows you to override
the flow of water through hydronic radiant systems. The unique
identifier is the name of either the ZoneHVAC:LowTemperatureRadiant:VariableFlow
or ZoneHVAC:LowTemperature
Radiant:ConstantFlow input objects.
Variable
Refrigerant Flow Heat Pump Air Conditioner[LINK]
An actuator called “Variable Refrigerant Flow Heat Pump” is
available with a control type called “Operating Mode.” This
is nondimensional and takes numbers between 0.0 and 2.0 where
0.0 means the system is off, 1.0 means the system is in
cooling mode, and 2.0 means the system is in heating mode. The
unique identifier is the name of the AirConditioner:VariableRefrigerantFlow
input object.
Variable
Refrigerant Flow Terminal Unit[LINK]
An actuator called “Variable Refrigerant Flow Terminal
Unit” is available with a control type called “Part Load
Ratio.” This is nondimensional and takes numbers between 0.0
and 1.0. The unique identifier is the name of the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow
input object. This control over rides the part-load ratio of
the terminal unit and can be applied only when the cooling or
heating minimum and maximum outdoor temperature limits of the
condenser (i.e., the AirConditioner:VariableRefrigerantFlow
object) are not exceeded.
HVAC Systems[LINK]
System Node Setpoints[LINK]
A series of actuators is available for all the setpoints that can be placed on system nodes. System nodes are used to define air and plant loops, and a natural application of EMS is to control the setpoints at these nodes. The node actuators are all called “System Node Setpoint.” There are nine control types:
Temperature Setpoint, (°C)
Temperature Minimum Setpoint (°C)
Temperature Maximum Setpoint (°C)
Humidity Ratio Setpoint (kgWater/kgDryAir)
Humidity Ratio Minimum Setpoint (kgWater/kgDryAir)
Humidity Ratio Maximum Setpoint (kgWater/kgDryAir)
Mass Flow Rate Setpoint (kg/s)
Mass Flow Rate Minimum Setpoint (kg/s)
Mass Flow Rate Maximum Setpoint (units kg/s)
Using these actuators is natural with an EMS. Typically, the controller would place the setpoint on the outlet node. Then the component’s low-level controller should operate to meet the leaving setpoint. Setting the setpoints on nodes should be a common application for the EMS.
Although all nine possible setpoints are available as EMS actuators, it does not follow that EnergyPlus can use all of them. Most components can use only one or two setpoints. If a component cannot control to meet the setpoints on a node, the actuator will do nothing.
Zone HVAC Control[LINK]
Several actuators relate to HVAC zone controls for temperature, humidity, and comfort.
Two actuators called “Zone Temperature Control” are available with the control types of “Heating Setpoint” and “Cooling Setpoint.” These enable you to directly override the zone-by-zone heating and cooling setpoints. The units are in degrees Celsius. The unique identifier is the zone name.
Two actuators called “Zone Humidity Control” are available with the control types “Relative Humidity Humidifying Setpoint” and “Relative Humidity Dehumidifying Setpoint.” These enable you to directly override the zone-by-zone humidity control setpoints. The units are in percent relative humidity. The unique identifier is the zone name.
Two actuators called “Zone Comfort Control” are available with the control types “Heating Setpoint” and “Cooling Setpoint.” These enable you to directly override the zone-by-zone comfort control setpoints. The units are predicted mean vote (PMV). The unique identifier is the zone name.
Plant Supervisory Control[LINK]
Several levels of actuators are available for on/off supervisory control of Plant systems.
Each plant (and condenser) loop has an actuator called “Plant Loop Overall” available with the control type “On/Off Supervisory.” Setting the value of this actuator to 1.0 directs the overall plant to loop to run normally based on other controls. Setting the value of this actuator to 0.0 directs the overall plant loop to shut down regardless of what other controls indicate.
Each plant (and condenser) loop has actuators called “Supply Side Half Loop” and “Demand Side Half Loop” that are available with the control type “On/Off Supervisory.” Setting the value of this actuator to 1.0 directs the plant’s loop side to run normally based on other controls. Setting the value of this actuator to 0.0 directs the plant’s loop side to shut down regardless of what other controls indicate.
Each plant (and condenser) loop has a series of actuators called “Supply Side Branch” and “Demand Side Branch” that are available with the control type “On/Off Supervisory.” These are available for each individual branch in a loop. Setting the value of this actuator to 1.0 directs the plant’s branch to run normally based on other controls. Setting the value of this actuator to 0.0 directs the plant’s branch to shut down regardless of what other controls indicate.
Each plant (and condenser) loop has a series of actuators called “Plant Component *” that are available with the control type “On/Off Supervisory.” These are available for each individual component on a loop. Setting the value of this actuator to 1.0 directs the component to run normally based on other controls. Setting the value of this actuator to 0.0 directs the component to shut down regardless of what other controls indicate.
Outdoor Air System Node Conditions[LINK]
Actuators called “Outdoor Air System Node” are available with control types called “Drybulb Temperature” and “Wetbulb Temperature.” The units are degrees Celsius. These actuators are available for all system nodes that are listed in either an OutdoorAir:Node or OutdoorAir:NodeList input object. You should probably set both the drybulb and wetbulb temperatures to ensure a full description of the moist air conditions.
The air system and many component models require you to specify a node as an outdoor air node to obtain values for the outdoor conditions. For example, outdoor air nodes are used at the inlet to an outdoor air mixer or at the inlet of the heat rejection side of a component model. Typically this is the weather data value for outdoor conditions. But local variations in microclimate may shift the local outdoor air temperature to differ slightly from the weather data. (Currently the only local variation model for this effect in EnergyPlus varies the outdoor air conditions as a function of height.) If you want to experiment with other models for local variations in outdoor air conditions, this EMS actuator allows you to override the outdoor temperature at a particular system node with any model that can be implemented in an Erl program. For example (although better models for the changes in conditions may need be developed), this actuator could be used to examine the energy impacts of warmer outdoor air temperatures experienced by a rooftop packaged HVAC system sitting on a black roof or the cooler conditions experienced by a unit that is located on the shaded side of a building. Another example is to make use of a separate model, outside of EnergyPlus, for some unique type of component (such as a labyrinth or earth-tube) that preconditions outdoor air; the results of that model could be fed into the air system model in EnergyPlus using these actuators.
AirLoopHVAC Availability Status[LINK]
This actuator is available in all models with central, or primary, air systems that are entered with the object “AirLoopHVAC.” Various availability managers use the air loop’s availability status to override control of the central air system fan. The fan may be scheduled to be unavailable during certain times to shut down the system when it is not needed. However, there may be times when the air system should be started to protect from freezing, for example. This actuator can force an air system to start up or shut down.
The control is actuated by setting values for the availability status. The settings are numeric, but represent discrete states the status can take. The following settings are valid:
0.0 ( = NoAction). This tells the air system to do whatever it would usually do without any special override status.
1.0 ( = ForceOff). This overrides the air system to shut down when it would normally want to run.
2.0 ( = CycleOn). This overrides the air system to start up when it would normally be off.
3.0 ( = CycleOnZoneFansOnly). This overrides only the zone fans (not the central fans) if they would normally be off.
Ideal Loads Air System[LINK]
An actuator called “Ideal Loads Air System” is available with control types called “Air Mass Flow Rate” (supply air), “Outdoor Air Mass Flow Rate,” “Air Temperature,” and “Air Humidity Ratio.” These are available in models that use the ideal loads air system, formerly known as purchased air. The units are kg/s for mass flow rate, C for temperature and kgWater/kgDryAir for humidity ratio. The unique identifier is the user-defined name of the ZoneHVAC:IdealLoadsAirSystem input object.
For Air Temperature and Air Humidity Ratio, the overrides are absolute. They are applied after all other limits have been checked. For mass flow rate, the overrides are not absolute, in that the model has additional internal controls that may not always be overridden. The internal controls will still apply the capacity and flow rate limits if defined in the input object. The EMS override affects the flow rate only if the air system is on. If the air system is “off,” the mass flow is zero regardless of the actuator setting. The internal model controls will turn off the air system if the zone is in the dead band or if it is scheduled “off” by availability managers. This behavior allows you to use the internal controls to determine when the air should cycle on, as for a constant volume system that cycles to achieve control. If both the Air Mass Flow Rate and Outdoor Air Mass Flow Rate are overridden, the Outdoor Air Mass Flow Rate will not be allowed to be greater than the override value for Air Mass Flow Rate.
Fan[LINK]
Actuators called “Fan” are available with the control types “Fan Air Mass Flow Rate,” “Fan Pressure Rise,” and “Fan Total Efficiency.” These provide direct control over the fan operation in an air system. The EMS program can override the flow rate by using kg/s. It can override the total pressure rise at the fan by using Pascals. And it can override the fan efficiency on a scale from 0.0 to 1.0. The unique identifier is the name of the fan in the Fan input objects.
An actuator is also available for overriding the autosize value for the fan’s design air flow rate. This actuator is called “Fan” and the control type is “’Fan Autosized Air Flow Rate” with units in m\(^{3}\)/s. It is only useful from the calling point named AfterComponentInputReadIn.
DX Cooling Coils[LINK]
Actuators are available for overriding the autosize values related to the size of single speed DX coils. Actuators called “Coil:Cooling:DX:SingleSpeed” are available with control types “Autosized Rated Air Flow Rate” (in m3/s), “Autosized Rated Sensible Heat Ratio” (in W/W), and “Autosized Rated Total Cooling Capacity” (in W). These are only useful from the calling point named AfterComponentInputReadIn.
Unitary Equipment[LINK]
Actuators called “Unitary HVAC” are available with the control types “Sensible Load Request” and “Moisture Load Request.” These control the operation of unitary equipment. Normally these systems operate to meet zone loads, but these actuators allow you to override the controls of unitary systems. The units are in Watts. The unique identifier is the name of the unitary equipment in the input objects.
Actuators are available for overriding the autosize values related to supply air flow rates some unitary HVAC equipment. These actuators allow selectively altering the outcome of sizing routines and are used from the calling point named AfterComponentInputReadIn. The units are m\(^{3}\)/s.
An actuator called “AirLoopHVAC:Unitary:Furnace:HeatOnly” is available with control type “Autosized Supply Air Flow Rate.”
An actuator called “AirLoopHVAC:UnitaryHeatOnly” is available with control type “Autosized Supply Air Flow Rate.”
Actuators called “AirLoopHVAC:Unitary:Furnace:HeatCool” and “AirLoopHVAC:UnitaryHeatCool”are available with control types “Autosized Supply Air Flow Rate,” “Autosized Supply Air Flow Rate During Cooling Operation,” “Autosized Supply Air Flow Rate During Heating Operation,” and “Autosized Supply Air Flow Rate During No Heating or Cooling Operation.”
An actuator called “AirLoopHVAC:UnitaryHeatPump:AirToAir” is available with control type “Autosized Supply Air Flow Rate.”
An actuator called “AirLoopHVAC:UnitaryHeatPump:WaterToAir” is available with control type “Autosized Supply Air Flow Rate.”
AirTerminal:SingleDuct:Uncontrolled[LINK]
An actuator called “AirTerminal:SingleDuct:Uncontrolled” is available with a control type called “Mass Flow Rate.” This actuator is available in models that use the direct air terminal. The units are kg/s. This actuator is used to control the flow rate. Normally, the flow rate of direct air terminals is fixed by the input or sizing results, but this actuator provides a way to override the flow with Erl programs.
Outdoor Air Controller[LINK]
An actuator called “Outdoor Air Controller” is available with the control type called “Air Mass Flow Rate.” This provides override control over the rate of outdoor air. The units are kg/s. The unique identifier is the name of the Controller:OutdoorAir input object.
Plant Load Profile[LINK]
Actuators called “Plant Load Profile” are available with the control types called “Mass Flow Rate” (in kg/s) and “Power” (in W). The unique identifier is the name of the LoadProfile:Plant input object. These actuators provide override control over the loads placed on a plant system by a plant load profile.
Pump[LINK]
An actuator called “Pump” is available with the control type “Pump Mass Flow Rate” (in kg/s). This allows you to override the flow rate produced by a pump. The unique identifier is the name of Pump Input object.
Window Air Conditioner[LINK]
An actuator called “Window Air Conditioner” is available with a control type called “Part Load Ratio.” This is nondimensional and takes numbers between 0.0 and 1.0. The unique identifier is the name of the ZoneHVAC:WindowAirConditioner input object.
Low Temperature Radiant Hydronic[LINK]
Actuators called “Hydronic Low Temp Radiant” and “Constant Flow Low Temp Radiant” are available with the control type “Water Mass Flow Rate” (in kg/s). This allows you to override the flow of water through hydronic radiant systems. The unique identifier is the name of either the ZoneHVAC:LowTemperatureRadiant:VariableFlow or ZoneHVAC:LowTemperature
Radiant:ConstantFlow input objects.
Variable Refrigerant Flow Heat Pump Air Conditioner[LINK]
An actuator called “Variable Refrigerant Flow Heat Pump” is available with a control type called “Operating Mode.” This is nondimensional and takes numbers between 0.0 and 2.0 where 0.0 means the system is off, 1.0 means the system is in cooling mode, and 2.0 means the system is in heating mode. The unique identifier is the name of the AirConditioner:VariableRefrigerantFlow input object.
Variable Refrigerant Flow Terminal Unit[LINK]
An actuator called “Variable Refrigerant Flow Terminal Unit” is available with a control type called “Part Load Ratio.” This is nondimensional and takes numbers between 0.0 and 1.0. The unique identifier is the name of the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow input object. This control over rides the part-load ratio of the terminal unit and can be applied only when the cooling or heating minimum and maximum outdoor temperature limits of the condenser (i.e., the AirConditioner:VariableRefrigerantFlow object) are not exceeded.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.