Guide for Interface Developers — EnergyPlus 8.5

<< Prev | Table of Contents | Object Index | Next >>

Appendix A.  Simple IDF file[LINK]

!1ZoneUncontrolled.idf
  ! Basic file description:  Basic test for EnergyPlus.  Resistive Walls.  Regular (no ground contact) floor.
  !                          Regular roof.  No Windows.
  !
  ! Highlights:              Very basic test to see that EnergyPlus "works".
  !
  !
  ! Simulation Location/Run: DENVER_STAPLETON_CO_USA_WMO_724690, 2 design days, 1 run period,
  !                          Run Control executes two design days (see RUN PERIOD object)
  !
  ! Location:                Denver, CO
  !
  ! Design Days:             DENVER_STAPLETON_CO_USA Annual Heating 99%, MaxDB = -16°C
  !                          DENVER_STAPLETON_CO_USA Annual Cooling (DB = >MWB) 1%, MaxDB = 32.6°C MWB = 15.5°C
  !
  ! Run Period (Weather File): Full Annual Simulation, DENVER_STAPLETON_CO_USA_WMO_724690
  !
  ! Run Control:             No zone or system sizing, design day run control (no weather file simulation)
  !
  ! Building: Fictional 1 zone building with resistive walls.
  !
  !           The building is oriented due north.
  !
  ! Floor Area:        232.25 m2
  ! Number of Stories: 1
  !
  ! Zone Description Details:
  !
  !       (0,15.24,0)                 (15.24,15.24,0)
  !              _____________________________
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |                             |
  !             |_____________________________|
  !
  !          (0,0,0)                      (15.24,0,0)
  !
  ! Internal gains description:     NA
  !
  ! Interzone Surfaces:             None
  ! Internal Mass:                  None
  ! People:                         None
  ! Lights:                         None
  ! Equipment:                      None
  ! Windows:                        0
  ! Detached Shading:               None
  ! Daylight:                       None
  ! Natural Ventilation:            None
  ! Compact Schedules:              NA (Example of non-Compact Schedules)
  ! Solar Distribution:             MinimalShadowing
  !
  ! HVAC:                           NA
  !
  ! Zonal Equipment:                NA
  ! Central Air Handling Equipment: No
  ! System Equipment Autosize:      No
  ! Purchased Cooling:              No
  ! Purchased Heating:              No
  ! Purchased Chilled Water:        No
  ! Purchased Hot Water:            No
  ! Coils:                          None
  ! Pumps:                          None
  ! Boilers:                        None
  ! Chillers:                       None
  ! Towers:                         None
  !
  ! Results:
  ! Standard Reports:               Variable Dictionary, Surfaces (dxf-wireframe), Meter File
  ! Timestep or Hourly Variables:   Hourly and Daily
  ! Time bins Report:               None
  ! HTML Report:                    None
  ! Environmental Emissions:        None
  ! Utility Tariffs:                None


    Output:PreprocessorMessage,
      No Preprocessor Used,    !- Preprocessor Name
      Information,             !- Error Severity
      Illustrative Message,    !- Message Line 1
      No problems for processing;  !- Message Line 2


    Version,
      3.0;                     !- Version Identifier


    Timestep,
      4;                       !- Number of Timesteps per Hour


    Building,
      Simple One Zone (Wireframe DXF),  !- Name
      0.0000000E+00,           !- North Axis {deg}
      Suburbs,                 !- Terrain
      .04,                     !- Loads Convergence Tolerance Value
      .004,                    !- Temperature Convergence Tolerance Value {deltaC}
      MinimalShadowing,        !- Solar Distribution
      30;                      !- Maximum Number of Warmup Days


    HeatBalanceAlgorithm,
      ConductionTransferFunction;  !- Algorithm


    SurfaceConvectionAlgorithm:Inside,
      Detailed;                !- Algorithm


    SurfaceConvectionAlgorithm:Outside,
      Detailed;                !- Algorithm


    SimulationControl,
      No,                      !- Do Zone Sizing Calculation
      No,                      !- Do System Sizing Calculation
      No,                      !- Do Plant Sizing Calculation
      Yes,                     !- Run Simulation for Sizing Periods
      Yes;                     !- Run Simulation for Weather File Run Periods


    RunPeriod,
      1,                       !- Begin Month
      1,                       !- Begin Day of Month
      12,                      !- End Month
      31,                      !- End Day of Month
      Tuesday,                 !- Day of Week for Start Day
      Yes,                     !- Use Weather File Holidays and Special Days
      Yes,                     !- Use Weather File Daylight Saving Period
      No,                      !- Apply Weekend Holiday Rule
      Yes,                     !- Use Weather File Rain Indicators
      Yes;                     !- Use Weather File Snow Indicators


    Site:Location,
      DENVER_STAPLETON_CO_USA_WMO_724690,  !- Name
      39.77,                   !- Latitude {deg}
      -104.87,                 !- Longitude {deg}
      -7.00,                   !- Time Zone {hr}
      1611.00;                 !- Elevation {m}


   !  WMO = 724690 Time Zone = NAM        (GMT-07:00) Mountain Time (US & Canada)
   !  Data Source = ASHRAE 2005 Annual Design Conditions
   ! Using Design Conditions from "Climate Design Data 2005 ASHRAE Handbook"
   ! DENVER_STAPLETON_CO_USA Extreme Annual Wind Speeds, 1% = 10.9m/s, 2.5% = 8.8m/s, 5% = 7.7m/s
   ! DENVER_STAPLETON_CO_USA Extreme Annual Temperatures, Max Drybulb = 37.2°C Min Drybulb = -24.6°C
   ! DENVER_STAPLETON_CO_USA Annual Heating Design Conditions Wind Speed = 2.3m/s Wind Dir = 180
   ! Coldest Month = December
   ! DENVER_STAPLETON_CO_USA Annual Heating 99%, MaxDB = -16°C


    SizingPeriod:DesignDay,
      DENVER_STAPLETON Ann Htg 99% Condns DB,  !- Name
      -16,                     !- Maximum Dry-Bulb Temperature {C}
      0.0,                     !- Daily Temperature Range {deltaC}
      -16,                     !- Humidity Indicating Conditions at Maximum Dry-Bulb
      83411.,                  !- Barometric Pressure {Pa}
      2.3,                     !- Wind Speed {m/s}
      180,                     !- Wind Direction {deg}
      0.00,                    !- Sky Clearness
      0,                       !- Rain Indicator
      0,                       !- Snow Indicator
      21,                      !- Day of Month
      12,                      !- Month
      WinterDesignDay,         !- Day Type
      0,                       !- Daylight Saving Time Indicator
      WetBulb;                 !- Humidity Indicating Type


   ! DENVER_STAPLETON Annual Cooling Design Conditions Wind Speed = 4m/s Wind Dir = 120
   ! Hottest Month = July
   ! DENVER_STAPLETON_CO_USA Annual Cooling (DB = >MWB) 1%, MaxDB = 32.6°C MWB = 15.5°C


    SizingPeriod:DesignDay,
      DENVER_STAPLETON Ann Clg 1% Condns DB = >MWB,  !- Name
      32.6,                    !- Maximum Dry-Bulb Temperature {C}
      15.2,                    !- Daily Temperature Range {deltaC}
      15.5,                    !- Humidity Indicating Conditions at Maximum Dry-Bulb
      83411.,                  !- Barometric Pressure {Pa}
      4,                       !- Wind Speed {m/s}
      120,                     !- Wind Direction {deg}
      1.00,                    !- Sky Clearness
      0,                       !- Rain Indicator
      0,                       !- Snow Indicator
      21,                      !- Day of Month
      7,                       !- Month
      SummerDesignDay,         !- Day Type
      0,                       !- Daylight Saving Time Indicator
      WetBulb;                 !- Humidity Indicating Type


    Material:NoMass,
      R13LAYER,                !- Name
      Rough,                   !- Roughness
      2.290965,                !- Thermal Resistance {m2-K/W}
      0.9000000,               !- Thermal Absorptance
      0.7500000,               !- Solar Absorptance
      0.7500000;               !- Visible Absorptance


    Material:NoMass,
      R31LAYER,                !- Name
      Rough,                   !- Roughness
      5.456,                   !- Thermal Resistance {m2-K/W}
      0.9000000,               !- Thermal Absorptance
      0.7500000,               !- Solar Absorptance
      0.7500000;               !- Visible Absorptance


    Material,
      C5 - 4 IN HW CONCRETE,   !- Name
      MediumRough,             !- Roughness
      0.1014984,               !- Thickness {m}
      1.729577,                !- Conductivity {W/m-K}
      2242.585,                !- Density {kg/m3}
      836.8000,                !- Specific Heat {J/kg-K}
      0.9000000,               !- Thermal Absorptance
      0.6500000,               !- Solar Absorptance
      0.6500000;               !- Visible Absorptance


    Construction,
      R13WALL,                 !- Name
      R13LAYER;                !- Outside Layer


    Construction,
      FLOOR,                   !- Name
      C5 - 4 IN HW CONCRETE;   !- Outside Layer


    Construction,
      ROOF31,                  !- Name
      R31LAYER;                !- Outside Layer


    Site:GroundTemperature:BuildingSurface,
      18.89,                   !- January Ground Temperature {C}
      18.92,                   !- February Ground Temperature {C}
      19.02,                   !- March Ground Temperature {C}
      19.12,                   !- April Ground Temperature {C}
      19.21,                   !- May Ground Temperature {C}
      19.23,                   !- June Ground Temperature {C}
      19.07,                   !- July Ground Temperature {C}
      19.32,                   !- August Ground Temperature {C}
      19.09,                   !- September Ground Temperature {C}
      19.21,                   !- October Ground Temperature {C}
      19.13,                   !- November Ground Temperature {C}
      18.96;                   !- December Ground Temperature {C}


    Zone,
      ZONE ONE,                !- Name
      0.0000000E+00,           !- Direction of Relative North {deg}
      0.0000000E+00,           !- X Origin {m}
      0.0000000E+00,           !- Y Origin {m}
      0.0000000E+00,           !- Z Origin {m}
      1,                       !- Type
      1,                       !- Multiplier
      autocalculate,           !- Ceiling Height {m}
      autocalculate;           !- Volume {m3}


    ScheduleTypeLimits,
      Fraction,                !- Name
      0.0 : 1.0,               !- Range
      CONTINUOUS;              !- Numeric Type


    GlobalGeometryRules,
      UpperLeftCorner,         !- Starting Vertex Position
      CounterClockWise,        !- Vertex Entry Direction
      WorldCoordinateSystem;   !- Coordinate System


    BuildingSurface:Detailed,
      Zn001:Wall001,           !- Name
      Wall,                    !- Surface Type
      R13WALL,                 !- Construction Name
      ZONE ONE,                !- Zone Name
      Outdoors,                !- Outside Boundary Condition
      ,                        !- Outside Boundary Condition Object
      SunExposed,              !- Sun Exposure
      WindExposed,             !- Wind Exposure
      0.5000000,               !- View Factor to Ground
      4,                       !- Number of Vertices
      0.0000000E+00,0.0000000E+00,4.572000,  !- X,Y,Z = = > Vertex 1
      0.0000000E+00,0.0000000E+00,0.0000000E+00,  !- X,Y,Z = = > Vertex 2
      15.24000,0.0000000E+00,0.0000000E+00,  !- X,Y,Z = = > Vertex 3
      15.24000,0.0000000E+00,4.572000;  !- X,Y,Z = = > Vertex 4


    BuildingSurface:Detailed,
      Zn001:Wall002,           !- Name
      Wall,                    !- Surface Type
      R13WALL,                 !- Construction Name
      ZONE ONE,                !- Zone Name
      Outdoors,                !- Outside Boundary Condition
      ,                        !- Outside Boundary Condition Object
      SunExposed,              !- Sun Exposure
      WindExposed,             !- Wind Exposure
      0.5000000,               !- View Factor to Ground
      4,                       !- Number of Vertices
      15.24000,0.0000000E+00,4.572000,  !- X,Y,Z = = > Vertex 1
      15.24000,0.0000000E+00,0.0000000E+00,  !- X,Y,Z = = > Vertex 2
      15.24000,15.24000,0.0000000E+00,  !- X,Y,Z = = > Vertex 3
      15.24000,15.24000,4.572000;  !- X,Y,Z = = > Vertex 4


    BuildingSurface:Detailed,
      Zn001:Wall003,           !- Name
      Wall,                    !- Surface Type
      R13WALL,                 !- Construction Name
      ZONE ONE,                !- Zone Name
      Outdoors,                !- Outside Boundary Condition
      ,                        !- Outside Boundary Condition Object
      SunExposed,              !- Sun Exposure
      WindExposed,             !- Wind Exposure
      0.5000000,               !- View Factor to Ground
      4,                       !- Number of Vertices
      15.24000,15.24000,4.572000,  !- X,Y,Z = = > Vertex 1
      15.24000,15.24000,0.0000000E+00,  !- X,Y,Z = = > Vertex 2
      0.0000000E+00,15.24000,0.0000000E+00,  !- X,Y,Z = = > Vertex 3
      0.0000000E+00,15.24000,4.572000;  !- X,Y,Z = = > Vertex 4


    BuildingSurface:Detailed,
      Zn001:Wall004,           !- Name
      Wall,                    !- Surface Type
      R13WALL,                 !- Construction Name
      ZONE ONE,                !- Zone Name
      Outdoors,                !- Outside Boundary Condition
      ,                        !- Outside Boundary Condition Object
      SunExposed,              !- Sun Exposure
      WindExposed,             !- Wind Exposure
      0.5000000,               !- View Factor to Ground
      4,                       !- Number of Vertices
      0.0000000E+00,15.24000,4.572000,  !- X,Y,Z = = > Vertex 1
      0.0000000E+00,15.24000,0.0000000E+00,  !- X,Y,Z = = > Vertex 2
      0.0000000E+00,0.0000000E+00,0.0000000E+00,  !- X,Y,Z = = > Vertex 3
      0.0000000E+00,0.0000000E+00,4.572000;  !- X,Y,Z = = > Vertex 4


    BuildingSurface:Detailed,
      Zn001:Flr001,            !- Name
      Floor,                   !- Surface Type
      FLOOR,                   !- Construction Name
      ZONE ONE,                !- Zone Name
      Surface,                 !- Outside Boundary Condition
      Zn001:Flr001,            !- Outside Boundary Condition Object
      NoSun,                   !- Sun Exposure
      NoWind,                  !- Wind Exposure
      1.000000,                !- View Factor to Ground
      4,                       !- Number of Vertices
      15.24000,0.000000,0.0,  !- X,Y,Z = = > Vertex 1
      0.000000,0.000000,0.0,  !- X,Y,Z = = > Vertex 2
      0.000000,15.24000,0.0,  !- X,Y,Z = = > Vertex 3
      15.24000,15.24000,0.0;  !- X,Y,Z = = > Vertex 4


    BuildingSurface:Detailed,
      Zn001:Roof001,           !- Name
      Roof,                    !- Surface Type
      ROOF31,                  !- Construction Name
      ZONE ONE,                !- Zone Name
      Outdoors,                !- Outside Boundary Condition
      ,                        !- Outside Boundary Condition Object
      SunExposed,              !- Sun Exposure
      WindExposed,             !- Wind Exposure
      0.0000000E+00,           !- View Factor to Ground
      4,                       !- Number of Vertices
      0.000000,15.24000,4.572,  !- X,Y,Z = = > Vertex 1
      0.000000,0.000000,4.572,  !- X,Y,Z = = > Vertex 2
      15.24000,0.000000,4.572,  !- X,Y,Z = = > Vertex 3
      15.24000,15.24000,4.572;  !- X,Y,Z = = > Vertex 4


    Output:Variable,
      *,                       !- Key Value
      outdoor dry bulb,        !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Daylight Saving Time Indicator,  !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      DayType Index,           !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Zone Mean Air Temperature,  !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Zone Total Internal Latent Gain,  !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Zone Mean Radiant Temperature,  !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Zone Air Balance Surface Convection Rate,  !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Zone Air Balance Air Energy Storage Rate,  !- Variable Name
      hourly;                  !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Surface Inside Temperature,  !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Surface Outside Temperature,  !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Surface Int Convection Coeff,  !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Variable,
      *,                       !- Key Value
      Surface Ext Convection Coeff,  !- Variable Name
      daily;                   !- Reporting Frequency


    Output:Reports,
      VariableDictionary,      !- Type of Report
      IDF;                     !- Report Name


    Output:Reports,
      surfaces,                !- Type of Report
      dxf:wireframe;           !- Report Name


    Output:Reports,
      construction;            !- Type of Report


    Output:Meter:MeterFileOnly,
      ExteriorLights:Electricity,  !- Name
      hourly;                  !- Reporting Frequency


    Output:Meter:MeterFileOnly,
      Carbon Equivalent:Facility,  !- Name
      hourly;                  !- Reporting Frequency


    Output:Meter:MeterFileOnly,
      EnergyTransfer:Building, !- Name
      hourly;                  !- Reporting Frequency


    Output:Meter:MeterFileOnly,
      EnergyTransfer:Facility, !- Name
      hourly;                  !- Reporting Frequency


    OutputControl:Table:Style,
      HTML;                    !- Column Separator


    Output:Table:SummaryReports,
      AllSummary;              !- Report 1 Name


    Exterior:Lights,
      ExtLights,               !- Name
      AlwaysOn,                !- Schedule Name
      5250,                    !- Design Level {W}
      AstronomicalClock,       !- Control Option
      Grounds Lights;          !- End-Use Subcategory


    ScheduleTypeLimits,
      On/Off,                  !- Name
      0:1,                     !- Range
      DISCRETE;                !- Numeric Type


    Schedule:Day:Hourly,
      On,                      !- Name
      On/Off,                  !- Schedule Type Limits Name
      1.,                      !- Hour 1
      1.,                      !- Hour 2
      1.,                      !- Hour 3
      1.,                      !- Hour 4
      1.,                      !- Hour 5
      1.,                      !- Hour 6
      1.,                      !- Hour 7
      1.,                      !- Hour 8
      1.,                      !- Hour 9
      1.,                      !- Hour 10
      1.,                      !- Hour 11
      1.,                      !- Hour 12
      1.,                      !- Hour 13
      1.,                      !- Hour 14
      1.,                      !- Hour 15
      1.,                      !- Hour 16
      1.,                      !- Hour 17
      1.,                      !- Hour 18
      1.,                      !- Hour 19
      1.,                      !- Hour 20
      1.,                      !- Hour 21
      1.,                      !- Hour 22
      1.,                      !- Hour 23
      1.;                      !- Hour 24


    Schedule:Week:Daily,
      On Weeks,                !- Name
      On,                      !- Sunday Schedule:Day Name
      On,                      !- Monday Schedule:Day Name
      On,                      !- Tuesday Schedule:Day Name
      On,                      !- Wednesday Schedule:Day Name
      On,                      !- Thursday Schedule:Day Name
      On,                      !- Friday Schedule:Day Name
      On,                      !- Saturday Schedule:Day Name
      On,                      !- Holiday Schedule:Day Name
      On,                      !- SummerDesignDay Schedule:Day Name
      On,                      !- WinterDesignDay Schedule:Day Name
      On,                      !- CustomDay1 Schedule:Day Name
      On;                      !- CustomDay2 Schedule:Day Name


    Schedule:Year,
      AlwaysOn,                !- Name
      On/Off,                  !- Schedule Type Limits Name
      On Weeks,                !- Schedule:Week Name 1
      1,                       !- Start Month 1
      1,                       !- Start Day 1
      12,                      !- End Month 1
      31;                      !- End Day 1