Tabular Summary Reports[LINK]
Several predefined reports are available from the Output
Table:Predefined object including the following.
Annual Building
Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outside Air Summary
Object Count Summary
In addition, specifying “All Summary” will enable all the
reports in this category (more than are shown here).
First and foremost, the Annual Building
Utility Performance Summary gives a good overview of the
energy use by category:
Report:
AnnualBuildingUtilityPerformanceSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Values gathered over 8760.00 hours
Site and Source Energy
| |
Total Energy [GJ] |
Energy Per Total Building Area
[MJ/m2] |
Energy Per Conditioned Building
Area [MJ/m2] |
| Total Site Energy |
180.73 |
194.92 |
194.92 |
| Net Site Energy |
180.73 |
194.92 |
194.92 |
| Total Source Energy |
1141.64 |
1231.28 |
1231.28 |
| Net Source Energy |
1141.64 |
1231.28 |
1231.28 |
Source to Site Energy Conversion Factors
| |
Source= > Site Conversion
Factor |
| Electricity |
0.293 |
| Natural Gas |
0.010 |
| District Cooling |
0.098 |
| District Heating |
0.033 |
| Steam |
0.250 |
| Gasoline |
1.050 |
| Diesel |
1.050 |
| Coal |
1.050 |
| Fuel Oil #1 |
1.050 |
| Fuel Oil #2 |
1.050 |
| Propane |
1.050 |
Building
Area
| |
Area [m2] |
| Total Building Area |
927.20 |
| Net Conditioned Building
Area |
927.20 |
| Unconditioned Building Area |
0.00 |
End Uses
| |
Electricity [GJ] |
Natural Gas [GJ] |
Other Fuel [GJ] |
District Cooling [GJ] |
District Heating [GJ] |
Water [m3] |
| Heating |
0.00 |
28.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
16.56 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
6.59 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
0.48 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
|
| Total End Uses |
152.57 |
28.16 |
0.00 |
0.00 |
0.00 |
0.00 |
Note: Natural gas appears to be the principal heating
source based on energy usage.
End Uses By Subcategory
| |
Subcategory |
Electricity [GJ] |
Natural Gas [GJ] |
Other Fuel [GJ] |
District Cooling [GJ] |
District Heating [GJ] |
Water [m3] |
| Heating |
Boiler |
0.00 |
28.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
Boiler Parasitic |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
General |
16.56 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
GeneralLights |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
General |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
General |
6.59 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
General |
0.48 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Normalized Metrics
Utility Use Per Conditioned Floor Area
| |
Electricity Intensity
[MJ/m2] |
Natural Gas Intensity
[MJ/m2] |
Other Fuel Intensity
[MJ/m2] |
District Cooling Intensity
[MJ/m2] |
District Heating Intensity
[MJ/m2] |
Water Intensity [m3/m2] |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
25.49 |
30.37 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
164.55 |
30.37 |
0.00 |
0.00 |
0.00 |
0.00 |
Utility Use Per Total Floor Area
| |
Electricity Intensity
[MJ/m2] |
Natural Gas Intensity
[MJ/m2] |
Other Fuel Intensity
[MJ/m2] |
District Cooling Intensity
[MJ/m2] |
District Heating Intensity
[MJ/m2] |
Water Intensity [m3/m2] |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
25.49 |
30.37 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
164.55 |
30.37 |
0.00 |
0.00 |
0.00 |
0.00 |
Electric Loads Satisfied
| |
Electricity [GJ] |
Percent Electricity [%] |
| Fuel-Fired Power Generation |
0.00 |
0.00 |
| High Temperature
Geothermal* |
0.00 |
0.00 |
| Photovoltaic Power |
0.00 |
0.00 |
| Wind Power* |
0.00 |
0.00 |
| Net Decrease in On-Site
Storage |
0.00 |
0.00 |
| Total On-Site Electric
Sources |
0.00 |
0.00 |
| |
|
|
| Electricity Coming From
Utility |
152.57 |
100.00 |
| Surplus Electricity Going To
Utility |
0.00 |
0.00 |
| Net Electricity From
Utility |
152.57 |
100.00 |
| |
|
|
| Total On-Site and Utility
Electric Sources |
152.57 |
100.00 |
| Total Electricity End Uses |
152.57 |
100.00 |
On-Site Thermal Sources
| |
Heat [GJ] |
Percent Heat [%] |
| Water-Side Heat Recovery |
0.00 |
|
| Air to Air Heat Recovery for
Cooling |
0.00 |
|
| Air to Air Heat Recovery for
Heating |
0.00 |
|
| High-Temperature
Geothermal* |
0.00 |
|
| Solar Water Thermal |
0.00 |
|
| Solar Air Thermal |
0.00 |
|
| Total On-Site Thermal
Sources |
0.00 |
|
Water Source Summary
| |
Water [m3] |
Percent Water [%] |
| Rainwater Collection |
0.00 |
- |
| Condensate Collection |
0.00 |
- |
| Groundwater Well |
0.00 |
- |
| Total On Site Water Sources |
0.00 |
- |
Initial Storage 0.00 - Final Storage 0.00 - Change in
Storage 0.00 - - - - Water Supplied by Utility 0.00 - - - -
Total On Site, Change in Storage, and Utility Water Sources
0.00 - Total Water End Uses 0.00 -
Comfort and Setpoint Not Met Summary
| |
Facility [Hours] |
| Time Set Point Not Met During
Occupied Heating |
0.00 |
| Time Set Point Not Met During
Occupied Cooling |
213.25 |
| Time Not Comfortable Based on
Simple ASHRAE 55-2004 |
72.50 |
Note 1: An asterisk (*) indicates that the feature is not
yet implemented.
The input verification summary gives a good overview of the
facility being simulated:
Report:
InputVerificationandResultsSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
General
| |
Value |
| Program Version and Build |
EnergyPlus 4.0.0.017, 9/17/2009
5:30 PM |
| Weather |
Climate Zone 6 CA USA
WYEC2-C-00006 WMO#=722970 |
| Latitude [deg] |
33.90 |
| Longitude [deg] |
-118.5 |
| Elevation [m] |
30.00 |
| Time Zone |
-8.0 |
| North Axis Angle [deg] |
30.00 |
| Rotation for Appendix G
[deg] |
0.00 |
| Hours Simulated [hrs] |
8760.00 |
ENVELOPE
Window-Wall Ratio
| |
Total |
North (315 to 45 deg) |
East (45 to 135 deg) |
South (135 to 225 deg) |
West (225 to 315 deg) |
| Gross Wall Area [m2] |
274.20 |
91.50 |
45.60 |
91.50 |
45.60 |
| Window Opening Area [m2] |
60.90 |
20.85 |
9.12 |
21.81 |
9.12 |
| Window-Wall Ratio [%] |
22.21 |
22.79 |
20.00 |
23.84 |
20.00 |
Skylight-Roof Ratio
| |
Total |
| Gross Roof Area [m2] |
463.60 |
| Skylight Area [m2] |
0.00 |
| Skylight-Roof Ratio [%] |
0.00 |
PERFORMANCE
Zone
Summary
| |
Area [m2] |
Conditioned (Y/N) |
Volume [m3] |
Multipliers |
Gross Wall Area [m2] |
Window Glass Area [m2] |
Lighting [W/m2] |
People [m2] per person |
Plug and Process [W/m2] |
| PLENUM-1 |
463.60 |
Yes |
283.20 |
1.00 |
54.84 |
0.00 |
0.0000 |
|
0.0000 |
| SPACE1-1 |
99.16 |
Yes |
239.25 |
1.00 |
73.20 |
21.81 |
15.9742 |
9.01 |
10.6495 |
| SPACE2-1 |
42.73 |
Yes |
103.31 |
1.00 |
36.48 |
9.12 |
16.0056 |
8.55 |
10.6704 |
| SPACE3-1 |
96.48 |
Yes |
239.25 |
1.00 |
73.20 |
20.85 |
16.4179 |
8.77 |
10.9453 |
| SPACE4-1 |
42.73 |
Yes |
103.31 |
1.00 |
36.48 |
9.12 |
16.0056 |
8.55 |
10.6704 |
| SPACE5-1 |
182.49 |
Yes |
447.68 |
1.00 |
0.00 |
0.00 |
16.2420 |
9.12 |
10.8280 |
| Total |
927.20 |
|
1416.00 |
|
274.20 |
60.90 |
8.0889 |
17.83 |
5.3926 |
| Conditioned Total |
927.20 |
|
1416.00 |
|
274.20 |
60.90 |
8.0889 |
17.83 |
5.3926 |
| Unconditioned Total |
0.00 |
|
0.00 |
|
0.00 |
0.00 |
|
|
|
Source
Energy End Use Components Summary[LINK]
The source energy end use components summary gives a good
overview of the source energy consumption broken down by end
uses for the facility being simulated:
Report:
SourceEnergyEndUseComponentsSummary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components
Summary
|
Source Electricity [GJ] |
Source Natural Gas [GJ] |
Source Other Fuel [GJ] |
Source District Cooling
[GJ] |
Source District Heating
[GJ] |
| Heating |
0.00 |
140.03 |
0.00 |
0.00 |
0.00 |
| Cooling |
167.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
569.39 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
325.49 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
55.72 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
7.57 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1125.82 140.03 0.00
0.00 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned
Floor Area
|
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1214.22 151.02 0.00
0.00 0.00
Source Energy End Use Components Per Total Floor
Area
|
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1214.22 151.02 0.00
0.00 0.00
Other Summary Reports[LINK]
The Climatic Data Summary, Envelope Summary and Equipment
Summary reports might be quite important to some reporting or
presentation.
Report: ClimaticDataSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
SizingPeriod:DesignDay
| |
Maximum Dry Bulb [C] |
Daily Temperature Range [C] |
Humidity Value |
Humidity Type |
Wind Speed [m/s] |
Wind Direction |
| LOS_ANGELES_CA_USA HEATING 99%
CONDITIONS |
7.40 |
0.00 |
7.40 |
0 |
2.80 |
70.00 |
| LOS_ANGELES_CA_USA COOLING 1%
CONDITIONS DB= > MWB |
27.00 |
6.10 |
17.60 |
0 |
4.40 |
250.00 |
Weather Statistics File
| |
Value |
| Reference |
CZ06RV2 |
| Site:Location |
Climate Zone 6 CA USA |
| Latitude |
N 33° 54’ |
| Longitude |
W 118° 30’ |
| Time Zone |
GMT -8.0 Hours |
| Elevation |
30m above sea level |
| Standard Pressure at
Elevation |
100965Pa |
| Data Source |
WYEC2-C-00006 |
| WMO Station |
722970 |
| Design Conditions |
Climate Design Data 2005 ASHRAE
Handbook |
| Heating Design Temperature 99.6%
(C) |
4.9 |
| Heating Design Temperature 99%
(C) |
6.2 |
| Cooling Design Temperature 0.4%
(C) |
33.1 |
| Cooling Design Temperature 1%
(C) |
30.9 |
| Cooling Design Temperature 2%
(C) |
29.2 |
| Maximum Dry Bulb Temperature
(C) |
31.7° |
| Maximum Dry Bulb Occurs on |
Sep 24 |
| Minimum Dry Bulb Temperature
(C) |
3.5° |
| Minimum Dry Bulb Occurs on |
Jan 8 |
| Maximum Dew Point Temperature
(C) |
20.9 |
| Maximum Dew Point Occurs on |
Jun 20 |
| Minimum Dew Point Temperature
(C) |
-21.7 |
| Minimum Dew Point Occurs on |
Dec 27 |
| Heating Degree-Days (base
10°C) |
2 |
| Cooling Degree-Days (base
18°C) |
216 |
| Köppen Classification |
Csb |
| Köppen Description |
Mediterranean climate (dry warm
summer, mild winter, lat. 30-45°N) |
| Köppen Recommendation |
|
| ASHRAE Climate Zone |
3C |
| ASHRAE Description |
Warm-Marine |
Report: EnvelopeSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Opaque Exterior
| |
Construction |
Reflectance |
U-Factor with Film [W/m2-K] |
U-Factor no Film [W/m2-K] |
Gross Area [m2] |
Azimuth [deg] |
Tilt [deg] |
Cardinal Direction |
| WALL-1PF |
WALL-1 |
0.22 |
0.384 |
0.408 |
18.30 |
210.00 |
90.00 |
S |
| WALL-1PR |
WALL-1 |
0.22 |
0.384 |
0.408 |
9.12 |
120.00 |
90.00 |
E |
| WALL-1PB |
WALL-1 |
0.22 |
0.384 |
0.408 |
18.30 |
30.00 |
90.00 |
N |
| WALL-1PL |
WALL-1 |
0.22 |
0.384 |
0.408 |
9.12 |
300.00 |
90.00 |
W |
| TOP-1 |
ROOF-1 |
0.35 |
0.268 |
0.282 |
463.60 |
210.00 |
0.00 |
|
| FRONT-1 |
WALL-1 |
0.22 |
0.384 |
0.408 |
73.20 |
210.00 |
90.00 |
S |
| F1-1 |
FLOOR-SLAB-1 |
0.35 |
3.119 |
12.894 |
99.16 |
30.00 |
180.00 |
|
| RIGHT-1 |
WALL-1 |
0.22 |
0.384 |
0.408 |
36.48 |
120.00 |
90.00 |
E |
| F2-1 |
FLOOR-SLAB-1 |
0.35 |
3.119 |
12.894 |
42.73 |
300.00 |
180.00 |
|
| BACK-1 |
WALL-1 |
0.22 |
0.384 |
0.408 |
73.20 |
30.00 |
90.00 |
N |
| F3-1 |
FLOOR-SLAB-1 |
0.35 |
3.119 |
12.894 |
96.48 |
74.22 |
180.00 |
|
| LEFT-1 |
WALL-1 |
0.22 |
0.384 |
0.408 |
36.48 |
300.00 |
90.00 |
W |
| F4-1 |
FLOOR-SLAB-1 |
0.35 |
3.119 |
12.894 |
42.73 |
120.00 |
180.00 |
|
| F5-1 |
FLOOR-SLAB-1 |
0.35 |
3.119 |
12.894 |
182.49 |
30.00 |
180.00 |
|
Fenestration
| |
Construction |
Area of One Opening [m2] |
Area of Openings [m2] |
U-Factor [W/m2-K] |
SHGC |
Visible Transmittance |
Shade Control |
Parent Surface |
Azimuth [deg] |
Cardinal Direction |
| WF-1 |
DBL CLR 3MM/13MM AIR |
16.56 |
16.56 |
2.720 |
0.764 |
0.812 |
No |
FRONT-1 |
210.00 |
S |
| DF-1 |
SGL GREY 3MM |
5.25 |
5.25 |
5.894 |
0.716 |
0.611 |
No |
FRONT-1 |
210.00 |
S |
| WR-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.720 |
0.764 |
0.812 |
No |
RIGHT-1 |
120.00 |
E |
| WB-1 |
DBL CLR 3MM/13MM AIR |
16.44 |
16.44 |
2.720 |
0.764 |
0.812 |
No |
BACK-1 |
30.00 |
N |
| DB-1 |
SGL GREY 3MM |
4.41 |
4.41 |
5.894 |
0.716 |
0.611 |
No |
BACK-1 |
30.00 |
N |
| WL-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.720 |
0.764 |
0.812 |
No |
LEFT-1 |
300.00 |
W |
| Total or Average |
|
|
60.90 |
3.22 |
0.756 |
0.780 |
|
|
|
|
| North Total or Average |
|
|
20.85 |
3.39 |
0.754 |
0.769 |
|
|
|
|
| Non-North Total or Average |
|
|
40.05 |
3.14 |
0.757 |
0.785 |
|
|
|
|
Report: ShadingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Sunlit Fraction
| |
March 21 9am |
March 21 noon |
March 21 3pm |
June 21 9am |
June 21 noon |
June 21 3pm |
December 21 9am |
December 21 noon |
December 21 3pm |
| WF-1 |
0.00 |
0.00 |
0.26 |
0.00 |
0.00 |
0.00 |
0.00 |
0.30 |
0.74 |
| DF-1 |
0.75 |
0.13 |
0.59 |
0.00 |
0.00 |
0.35 |
0.92 |
0.62 |
0.94 |
| WR-1 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
| WB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| DB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| WL-1 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
Window
Control
| |
Name |
Type |
Shaded Construction |
Control |
Glare Control |
| None |
|
|
|
|
|
Report: LightingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Interior Lighting
| |
Zone |
Lighting Power Density
[W/m2] |
Zone Area [m2] |
Total Power [W] |
End Use Subcategory |
Schedule Name |
Average Hours/Week [hr] |
Return Air Fraction |
Conditioned (Y/N) |
| SPACE1-1 LIGHTS 1 |
SPACE1-1 |
15.9742 |
99.16 |
1584.00 |
GeneralLights |
LIGHTS-1 |
0.00 |
0.2000 |
Y |
| SPACE2-1 LIGHTS 1 |
SPACE2-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
LIGHTS-1 |
0.00 |
0.2000 |
Y |
| SPACE3-1 LIGHTS 1 |
SPACE3-1 |
16.4179 |
96.48 |
1584.00 |
GeneralLights |
LIGHTS-1 |
0.00 |
0.2000 |
Y |
| SPACE4-1 LIGHTS 1 |
SPACE4-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
LIGHTS-1 |
0.00 |
0.2000 |
Y |
| SPACE5-1 LIGHTS 1 |
SPACE5-1 |
16.2420 |
182.49 |
2964.00 |
GeneralLights |
LIGHTS-1 |
0.00 |
0.2000 |
Y |
| Interior Lighting Total |
|
16.1777 |
463.60 |
7500.00 |
|
|
|
|
|
Daylighting
| |
Zone |
Daylighting Type |
Control Type |
Fraction Controlled |
Lighting Installed in Zone
[W] |
Lighting Controlled [W] |
| None |
|
|
|
|
|
|
Exterior Lighting
| |
Total Watts |
Astronomical Clock/Schedule |
Schedule Name |
Average Annual Hours/Week |
| Exterior Lighting Total |
0.00 |
|
|
|
Report: EquipmentSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Central Plant
| |
Type |
Nominal Capacity [W] |
Nominal Efficiency [W/W] |
| CENTRAL CHILLER |
Chiller:Electric |
25311.64 |
3.20 |
| CENTRAL BOILER |
Boiler:HotWater |
56191.29 |
0.80 |
Cooling Coils
| |
Type |
Nominal Total Capacity [W] |
Nominal Sensible Capacity
[W] |
Nominal Latent Capacity [W] |
Nominal Sensible Heat Ratio |
Nominal Efficiency [W/W] |
| MAIN COOLING COIL 1 |
Coil:Cooling:Water |
28159.12 |
19476.53 |
8682.60 |
0.69 |
- |
Heating Coils
| |
Type |
Nominal Total Capacity [W] |
Nominal Efficiency [W/W] |
| SPACE1-1 ZONE COIL |
Coil:Heating:Water |
10384.85 |
- |
| SPACE2-1 ZONE COIL |
Coil:Heating:Water |
8470.48 |
- |
| SPACE3-1 ZONE COIL |
Coil:Heating:Water |
10477.88 |
- |
| SPACE4-1 ZONE COIL |
Coil:Heating:Water |
11334.29 |
- |
| SPACE5-1 ZONE COIL |
Coil:Heating:Water |
11391.33 |
- |
| MAIN HEATING COIL 1 |
Coil:Heating:Water |
4061.83 |
- |
Fans
| |
Type |
Total Efficiency [W/W] |
Delta Pressure [pa] |
Max Flow Rate [m3/s] |
Rated Power [W] |
Motor Heat In Air Fraction |
End Use |
| SUPPLY FAN 1 |
Fan:VariableVolume |
0.70 |
600.00 |
1.28 |
1099.23 |
1.00 |
General |
Pumps
| |
Type |
Control |
Head [pa] |
Power [W] |
Motor Efficiency [W/W] |
| HW CIRC PUMP |
Pump:VariableSpeed |
INTERMITTENT |
179352.00 |
312.23 |
0.90 |
| CW CIRC PUMP |
Pump:VariableSpeed |
INTERMITTENT |
179352.00 |
231.95 |
0.90 |
Service Water Heating
| |
Type |
Storage Volume [m3] |
Input [W] |
Thermal Efficiency [W/W] |
Recovery Efficiency [W/W] |
Energy Factor |
| None |
|
|
|
|
|
|
Tabular Summary Reports[LINK]
Several predefined reports are available from the Output Table:Predefined object including the following.
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outside Air Summary
Object Count Summary
In addition, specifying “All Summary” will enable all the reports in this category (more than are shown here).
Annual Building Utility Performance Summary[LINK]
First and foremost, the Annual Building Utility Performance Summary gives a good overview of the energy use by category:
Report: AnnualBuildingUtilityPerformanceSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Values gathered over 8760.00 hours
Site and Source Energy
Source to Site Energy Conversion Factors
Building Area
End Uses
Note: Natural gas appears to be the principal heating source based on energy usage.
End Uses By Subcategory
Normalized Metrics
Utility Use Per Conditioned Floor Area
Utility Use Per Total Floor Area
Electric Loads Satisfied
On-Site Thermal Sources
Water Source Summary
Initial Storage 0.00 - Final Storage 0.00 - Change in Storage 0.00 - - - - Water Supplied by Utility 0.00 - - - - Total On Site, Change in Storage, and Utility Water Sources 0.00 - Total Water End Uses 0.00 -
Comfort and Setpoint Not Met Summary
Note 1: An asterisk (*) indicates that the feature is not yet implemented.
Input Verification Summary[LINK]
The input verification summary gives a good overview of the facility being simulated:
Report: InputVerificationandResultsSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
General
ENVELOPE
Window-Wall Ratio
Skylight-Roof Ratio
PERFORMANCE
Zone Summary
Source Energy End Use Components Summary[LINK]
The source energy end use components summary gives a good overview of the source energy consumption broken down by end uses for the facility being simulated:
Report: SourceEnergyEndUseComponentsSummary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components Summary
Total Source Energy End Use Components 1125.82 140.03 0.00 0.00 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned Floor Area
Total Source Energy End Use Components 1214.22 151.02 0.00 0.00 0.00
Source Energy End Use Components Per Total Floor Area
Total Source Energy End Use Components 1214.22 151.02 0.00 0.00 0.00
Other Summary Reports[LINK]
The Climatic Data Summary, Envelope Summary and Equipment Summary reports might be quite important to some reporting or presentation.
Report: ClimaticDataSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
SizingPeriod:DesignDay
Weather Statistics File
Report: EnvelopeSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Opaque Exterior
Fenestration
Report: ShadingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Sunlit Fraction
Window Control
Report: LightingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Interior Lighting
Daylighting
Exterior Lighting
Report: EquipmentSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Central Plant
Cooling Coils
Heating Coils
Fans
Pumps
Service Water Heating
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.