Begin Timestep Before
Predictor[LINK]
The calling point called “BeginTimestepBeforePredictor”
occurs near the beginning of each timestep but before the
predictor executes. “Predictor” refers to the step in
EnergyPlus modeling when the zone loads are calculated. This
calling point is useful for controlling components that affect
the thermal loads the HVAC systems will then attempt to meet.
Programs called from this point might actuate the building
envelope or internal gains based on current weather or on the
results from the previous timestep. Demand management routines
might use this calling point to reduce lighting or process
loads, change thermostat settings, operate window shades,
etc.
Begin Timestep Before Predictor[LINK]
The calling point called “BeginTimestepBeforePredictor” occurs near the beginning of each timestep but before the predictor executes. “Predictor” refers to the step in EnergyPlus modeling when the zone loads are calculated. This calling point is useful for controlling components that affect the thermal loads the HVAC systems will then attempt to meet. Programs called from this point might actuate the building envelope or internal gains based on current weather or on the results from the previous timestep. Demand management routines might use this calling point to reduce lighting or process loads, change thermostat settings, operate window shades, etc.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.