Example 10.
Plant Loop Override Control[LINK]
Problem Statement[LINK]
A common occurrence in EnergyPlus central plant simulations
is for a component to be designed well, but during the course
of an annual simulation, it is operated outside of its
allowable region. This is due to the governing control
strategies (operating schemes). These operation schemes may
not have the intelligence to say, turn off a cooling tower
when the outdoor temperature is too low.
Within the EnergyPlus example files, the cooling tower
offers warnings stating that the tower temperature is going
below a low temperature limit. We should ask, can we use a
simple EMS addition to an input file to override the loop and
turn off the cooling tower to avoid these situations and
therefore the warnings?
EMS Design Discussion[LINK]
For this example, we will start with the example file that
is packaged with EnergyPlus called EcoRoofOrlando.idf. This
is one example of an input file where a cooling tower throws
warnings due to operating at too low of a temperature.
Although the input file has many aspects related to zone and
HVAC, we will only be interested in the loop containing the
tower, which is a CondenserLoop
named Chiller Plant Condenser Loop. The loop has a
minimum loop temperature of 5 degrees Celsius, as specified by
the CondenserLoop
object.
In order to avoid these warnings and properly shut off the
tower, EMS will be used to check the outdoor temperature and
shut down the whole loop. Special care must be taken when
manipulating plant and condenser loops with EMS. The most
robust way found is to both disable the loop equipment and
also override (turn off) the loop. Skipping either of these
can cause mismatches where either components are still
expecting flow but the pump is not running, or the pump is
trying to force flow through components which are disabled.
Either of these cases can cause unstable conditions and
possibly fatal flow errors.
The outdoor air temperature must be checked in order to
determine what the EMS needs to do at a particular point in
the simulation. This is handled by use of an EMS sensor
monitoring the Outdoor Dry Bulb standard E+ output
variable.
To manage the loop and pump, actuators are employed on
both. The pump actuator is a mass flow rate override. This
can be used to set the flow to zero, effectively shutting off
the pump. The loop actuator is an on/off supervisory control,
which allows you to “shut the entire loop down.” This
actuator will not actually shut the loop down, it effectively
empties the equipment availability list, so that there is no
equipment available to reject/absorb load on the supply side.
If you use this actuator alone to “shut down the loop,” you
may find that the pump is still flowing fluid around the loop,
but the equipment will not be running.
The EMS calling point chosen is
“InsideHVACSystemIterationLoop,” so that the
operation will be updated every time the plant loops are
simulated.
The Erl program is quite simple for this case. If the
outdoor dry bulb temperature goes below a certain value, the
loop and pump actuators are set to zero. If the outdoor
temperature is equal to or above this value, the actuators are
set to Null, relinquishing control back to the
regular operation schemes. In modifying this specific input
file it was found that the outdoor dry bulb temperature which
removed these warnings was six degrees Celsius. We also
create a custom output variable called “EMS Condenser Flow
Override On” to easily record when the overrides have
occurred.
The main input objects that implement this example of plant
loop control are listed below and are included in the example
file called “EMSPlantLoopOverrideControl.idf.” The addition
of the EMS objects properly shuts down the loop as the outdoor
temperature go below the transition value, and the simulation
error file shows no warnings for the tower outlet
temperature.
EnergyManagementSystem:Sensor,
OutdoorTemp, !- Name
Environment, !- Output:Variable Index Key Name
Site Outdoor Air Drybulb Temperature; !- Output:Variable Name
EnergyManagementSystem:Actuator,
Actuator_Loop, !- Name
Chiller Plant Condenser Loop, !- Actuated Component Unique Name
Plant Loop Overall, !- Actuated Component Type
On/Off Supervisory; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
PumpFlowOverride, !- Name
Chiller Plant Cnd Circ Pump, !- Actuated Component Unique Name
Pump, !- Actuated Component Type
Pump Mass Flow Rate; !- Actuated Component Control Type
EnergyManagementSystem:GlobalVariable,
PumpFlowOverrideReport;
EnergyManagementSystem:OutputVariable,
EMS Condenser Flow Override On [On/Off], !- Name
PumpFlowOverrideReport, !- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep; !- Update Frequency
EnergyManagementSystem:ProgramCallingManager,
Condenser OnOff Management,
InsideHVACSystemIterationLoop,
TowerControl;
EnergyManagementSystem:Program,
TowerControl,
IF (OutdoorTemp < 6.0),
SET Actuator_Loop = 0.0,
SET PumpFlowOverride = 0.0,
SET PumpFlowOverrideReport = 1.0,
ELSE,
SET Actuator_Loop = Null,
SET PumpFlowOverride = Null,
SET PumpFlowOverrideReport = 0.0,
ENDIF;
Output:Variable,
*,
EMS Condenser Flow Override On,
Hourly;
Example 10. Plant Loop Override Control[LINK]
Problem Statement[LINK]
A common occurrence in EnergyPlus central plant simulations is for a component to be designed well, but during the course of an annual simulation, it is operated outside of its allowable region. This is due to the governing control strategies (operating schemes). These operation schemes may not have the intelligence to say, turn off a cooling tower when the outdoor temperature is too low.
Within the EnergyPlus example files, the cooling tower offers warnings stating that the tower temperature is going below a low temperature limit. We should ask, can we use a simple EMS addition to an input file to override the loop and turn off the cooling tower to avoid these situations and therefore the warnings?
EMS Design Discussion[LINK]
For this example, we will start with the example file that is packaged with EnergyPlus called EcoRoofOrlando.idf. This is one example of an input file where a cooling tower throws warnings due to operating at too low of a temperature. Although the input file has many aspects related to zone and HVAC, we will only be interested in the loop containing the tower, which is a CondenserLoop named Chiller Plant Condenser Loop. The loop has a minimum loop temperature of 5 degrees Celsius, as specified by the CondenserLoop object.
In order to avoid these warnings and properly shut off the tower, EMS will be used to check the outdoor temperature and shut down the whole loop. Special care must be taken when manipulating plant and condenser loops with EMS. The most robust way found is to both disable the loop equipment and also override (turn off) the loop. Skipping either of these can cause mismatches where either components are still expecting flow but the pump is not running, or the pump is trying to force flow through components which are disabled. Either of these cases can cause unstable conditions and possibly fatal flow errors.
The outdoor air temperature must be checked in order to determine what the EMS needs to do at a particular point in the simulation. This is handled by use of an EMS sensor monitoring the Outdoor Dry Bulb standard E+ output variable.
To manage the loop and pump, actuators are employed on both. The pump actuator is a mass flow rate override. This can be used to set the flow to zero, effectively shutting off the pump. The loop actuator is an on/off supervisory control, which allows you to “shut the entire loop down.” This actuator will not actually shut the loop down, it effectively empties the equipment availability list, so that there is no equipment available to reject/absorb load on the supply side. If you use this actuator alone to “shut down the loop,” you may find that the pump is still flowing fluid around the loop, but the equipment will not be running.
The EMS calling point chosen is “InsideHVACSystemIterationLoop,” so that the operation will be updated every time the plant loops are simulated.
The Erl program is quite simple for this case. If the outdoor dry bulb temperature goes below a certain value, the loop and pump actuators are set to zero. If the outdoor temperature is equal to or above this value, the actuators are set to Null, relinquishing control back to the regular operation schemes. In modifying this specific input file it was found that the outdoor dry bulb temperature which removed these warnings was six degrees Celsius. We also create a custom output variable called “EMS Condenser Flow Override On” to easily record when the overrides have occurred.
EMS Input Objects[LINK]
The main input objects that implement this example of plant loop control are listed below and are included in the example file called “EMSPlantLoopOverrideControl.idf.” The addition of the EMS objects properly shuts down the loop as the outdoor temperature go below the transition value, and the simulation error file shows no warnings for the tower outlet temperature.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.