Use of Set Point
Managers[LINK]
A coil will check its inlet air temperature compared to the
set point temperature. For cooling, if the inlet air
temperature is above the set point temp, the coil turns on.
It’s opposite that for heating. In the 5ZoneAutoDXVAV example
file, a schedule temperature set point is placed at the system
outlet node. This is the temperture the designer wants at the
outlet. The mixed air SP manager is used to account for fan
heat and places the required SP at the outlet of the cooling
coil so the coil slightly overcools the air to overcome fan
heat and meet the system outlet node set point.
You don’t blindly place the SP’s at the coil outlet node,
but this is a likely starting point in most cases. If there is
a fan after the coil’s, the “actual” SP will need to be placed
on a different node (other than the coils). Then a mixed air
manager will be used to reference that SP and the fan’s
inlet/outlet node to calculate the correct SP to place
wherever you want (at the coil outlet, the mixed air node,
etc.). Place it at the mixed air node if you want the outside
air system to try and meet that setpoint through mixing. Place
it at the cooling coil outlet if you want the coil control to
account for fan heat. Place it at both locations if you want
the outside air system to try and meet the load with the coil
picking up the remainder of the load.
See if the coils are fully on when the SP is not met. If
they are the coils are too small. If they are at part-load,
the control SP is calculated incorrectly.
Relationship
of Set Point Managers and Controllers[LINK]
Could you elaborate further on the relation between
SetPoint managers and Controllers?
SetpointManager objects place a setpoint on a node, for
example, one might place a setpoint of 12C on the node named
“Main Cooling Coil Air Outlet Node”.
In the case of Controler:WaterCoil which controls a hot
water or chilled water coil, the controller reads the setpoint
and tries to adjust the water flow so that the air temperature
at the controlled node matches the current setpoint.
Continuing the example above:
Controller:WaterCoil,
Main Cooling Coil Controller, !- Name
Temperature, !- Control variable
Reverse, !- Action
Flow, !- Actuator variable
Main Cooling Coil Air Outlet Node, !- Control_Node
Main Cooling Coil Water Inlet Node, !- Actuator_Node
0.002, !- Controller Convergence Tolerance:
!- delta temp from setpoint temp {deltaC}
autosize, !- Max Actuated Flow {m3/s}
0.0; !- Min Actuated Flow {m3/s}
It is possible to place the control node downstream of the
actual object being controlled, for example after other coils
and the supply fan, but I recommend using the coil leaving air
node as the control node for tighter control.
Use of Set Point Managers[LINK]
A coil will check its inlet air temperature compared to the set point temperature. For cooling, if the inlet air temperature is above the set point temp, the coil turns on. It’s opposite that for heating. In the 5ZoneAutoDXVAV example file, a schedule temperature set point is placed at the system outlet node. This is the temperture the designer wants at the outlet. The mixed air SP manager is used to account for fan heat and places the required SP at the outlet of the cooling coil so the coil slightly overcools the air to overcome fan heat and meet the system outlet node set point.
You don’t blindly place the SP’s at the coil outlet node, but this is a likely starting point in most cases. If there is a fan after the coil’s, the “actual” SP will need to be placed on a different node (other than the coils). Then a mixed air manager will be used to reference that SP and the fan’s inlet/outlet node to calculate the correct SP to place wherever you want (at the coil outlet, the mixed air node, etc.). Place it at the mixed air node if you want the outside air system to try and meet that setpoint through mixing. Place it at the cooling coil outlet if you want the coil control to account for fan heat. Place it at both locations if you want the outside air system to try and meet the load with the coil picking up the remainder of the load.
See if the coils are fully on when the SP is not met. If they are the coils are too small. If they are at part-load, the control SP is calculated incorrectly.
Relationship of Set Point Managers and Controllers[LINK]
Could you elaborate further on the relation between SetPoint managers and Controllers?
SetpointManager objects place a setpoint on a node, for example, one might place a setpoint of 12C on the node named “Main Cooling Coil Air Outlet Node”.
In the case of Controler:WaterCoil which controls a hot water or chilled water coil, the controller reads the setpoint and tries to adjust the water flow so that the air temperature at the controlled node matches the current setpoint. Continuing the example above:
It is possible to place the control node downstream of the actual object being controlled, for example after other coils and the supply fan, but I recommend using the coil leaving air node as the control node for tighter control.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.