eplusout.sql is an optional output format for EnergyPlus.
The eplusout.sql output file is a sqlite3 database file (see
http://www.sqlite.org) and includes all of the
data found in EnergyPlus’ eplustbl.* files, eplusout.eso and
eplusout.mtr output files (i.e., EnergyPlus’ standard variable
and meter output files) plus a number of reports that are
found in the eplusout.eio output file.
A discussion of the individual data tables is presented
below followed by a discussion about how to access data within
the SQL file.
List of Available
SQLite Tables[LINK]
This initial release of the SQL database output option
includes a variety of data in the following tables:
ComponentSizes Table
ConstructionLayers Table
Constructions Table
Materials Table
NominalBaseboardHeaters Table
NominalElectricEquipment Table
NominalGasEquipment Table
NominalHotWaterEquipment Table
NominalInfiltration Table
NominalLighting Table
NominalOtherEquipment Table
NominalPeople Table
NominalSteamEquipment Table
NominalVentilation Table
ReportData Table
ReportDataDictionary Table
ReportExtendedData Table
RoomAirModels Table
Schedules Table
Surfaces Table
SystemSizes Table
Time Table
ZoneGroups Table
Zones Table
ZoneLists Table
ZoneSizes Table
ZoneInfoLists Table
Simulations Table
EnvironmentPeriods Table
TabularData Table
Strings Table
StringTypes Table
TabularDataWithStrings Table
Errors Table
A short discussion of contents of each of the above SQL
tables is given in the sections that follow.
Data in the following four tables are also found in
EnergyPlus’ standard output file (i.e., eplusout.eso – see
that section for more information) or in EnergyPlus’
eplusout.mtr (i.e. meter) output file. As with the standard
output file, the “Report Variable” and “Report Meter” commands
control the data in these tables.
ReportDataDictionary
Table[LINK]
The ReportDataDictionary table provides the equivalent of
the dictionary portion of the ESO file (i.e., the first
section of the .eso file) or eplusout.mtr. Please see the
Report Variable section of the Input-Output Reference for more
information. Like in the eplusout.mtr file (see the
eplusout.mtr section), only data requested by “Report Meter”
commands will set isMeter to 1 or True.
SQL ReportDataDictionary Contents
| Field Name |
Field Type |
Description |
Enumeration |
| ReportDataDictionaryIndex |
INTEGER PRIMARY KEY |
The ReportDataDictionaryIndex
links the dictionary data to the variable data (see ReportData
table) |
|
| IsMeter |
INTEGER |
Boolean flag whether dictionary
data is report of meter data |
0, 1 |
| Type |
TEXT |
Nature of data type with respect
to state, (e.g. average or sum type of data). |
“Sum” “Avg” |
| IndexGroup |
TEXT |
The reporting group (e.g., Zone,
Plant, etc.) |
|
| TimestepType |
TEXT |
Type of timestep for data |
“Zone” “HVAC System” |
| KeyValue |
TEXT |
The identifying “key name” for
the data |
|
| Name |
TEXT |
The actual report data name |
|
| ReportingFrequency |
TEXT |
The reporting frequency of the
variable, e.g. |
“HVAC System Timestep”, “Zone
Timestep”, “Hourly”, “Daily”, “Monthly”, “Run Period”. |
| ScheduleName |
TEXT |
The name of the schedule that
controls reporting frequency |
|
| Units |
TEXT |
The data units |
|
ReportData Table[LINK]
The ReportData table contains the report or meter variable
data (e.g., the hourly, daily, and monthly report variable
data). Please see the Report Variable section of the
Input-Output Reference for more information.
SQL ReportData Table Contents
| Field Name |
Field Type |
Description |
| ReportDataIndex |
INTEGER PRIMARY KEY |
|
| TimeIndex |
INTEGER |
This index links the record to
its time record (see the Time table below) |
| ReportDataDictionaryIndex |
INTEGER |
The ReportDataDictionaryIndex
links the data to the respective data dictionary record (see
ReportDataDictionary table above) |
| Value |
REAL |
The data value |
ReportExtendedData
Table[LINK]
The ReportExtendedData table contains additional data
(e.g., monthly maximums and minimums) that is available for
certain report or meter variables.
SQL ReportExtendedData Table Contents
| Field Name |
Field Type |
Description |
| ReportExtendedDataIndex |
INTEGER PRIMARY KEY |
|
| ReportDataIndex |
INTEGER |
Associates ReportData record
with ReportExtendedData record |
| MaxValue |
REAL |
The maximum value during the
reporting interval |
| MaxMonth |
INTEGER |
The month in which the maximum
value occurred |
| MaxDay |
INTEGER |
The day on which the maximum
value occurred |
| MaxHour |
INTEGER |
The hour in which the maximum
value occurred |
| MaxStartMinute |
INTEGER |
The starting minute of the
interval in which the maximum value occurred |
| MaxMinute |
INTEGER |
The minute that the maximum
value occurred |
| MinValue |
REAL |
The minimum value |
| MinMonth |
INTEGER |
The month in which the minimum
value occurred |
| MinDay |
INTEGER |
The day on which the minimum
value occurred |
| MinHour |
INTEGER |
The hour in which the minimum
value occurred |
| MinStartMinute |
INTEGER |
The starting minute of the
interval in which the minimum value occurred |
| MinMinute |
INTEGER |
The minute that the minimum
value occurred |
The Time table provides the time information for both the
“report variable” and “report meter” variables (the ReportData
table).
Time Table Contents
| Field Name |
Field Type |
Description |
| TimeIndex |
INTEGER PRIMARY KEY |
Connects the time information
with the report variables and meter variables (see the
ReportData table) |
| Month |
INTEGER |
Month |
| Day |
INTEGER |
Day |
| Hour |
INTEGER |
Hour |
| Minute |
INTEGER |
Minute |
| DST |
INTEGER |
Daylight saving time
indicator |
| Interval |
INTEGER |
Length of the reporting
interval |
| IntervalType |
INTEGER |
The index for the type of
reporting interval. (enum: -1=detailed HVAC system timestep;
0=zone timestep, 1=hourly, 2=daily, 3=monthly,
4=runperiod) |
| SimulationDays |
INTEGER |
Day of simulation. This number
resets after warmup and at the beginning of an environment
period |
| DayType |
TEXT |
The type of day. (enum:
“Sunday”, “Monday”, “Tuesday”, Wednesday”, “Thursday”,
“Friday”, “Saturday”, “Holiday”, “SummerDesignDay”,
“WinterDesignDay”, “CustomDay1”, “CustomDay2”) |
| EnvironmentPeriodIndex |
INTEGER |
Foreign Key to the
EnvironmentPeriods table |
| WarmupFlag |
INTEGER |
1 during warmup, 0
otherwise |
One time (EIO) File Data[LINK]
Data in the tables below can also be found in EnergyPlus
input output file (i.e., in the eplusout.eio output file).
The Zones table provides a variety of information about the
zones specified within EnergyPlus. One of its most common uses
is to provide zone name and area information for the other
tables within the SQL database (e.g., use the ZoneIndex to
look up the ZoneName).
SQL Zones Table Contents
| Field Name |
Field Type |
Description |
| ZoneIndex |
INTEGER PRIMARY KEY |
The ZoneIndex is used to link
this table to related tables |
| ZoneName |
TEXT |
Zone Name |
| RelNorth |
REAL |
Relative North, in degrees |
| OriginX |
REAL |
X origin, in meters |
| OriginY |
REAL |
Y origin, in meters |
| OriginZ |
REAL |
Z origin, in meters |
| CentroidX |
REAL |
X position of zone Centroid, in
meters |
| CentroidY |
REAL |
Y position of zone Centroid, in
meters |
| CentroidZ |
REAL |
Z position of zone Centroid, in
meters |
| OfType |
INTEGER |
(not used yet) |
| Multiplier |
REAL |
Zone multiplier |
| ListMultiplier |
REAL |
Zone Group multiplier |
| MinimumX |
REAL |
Minimum X value, in meters |
| MaximumX |
REAL |
Maximum X value, in meters |
| MinimumY |
REAL |
Minimum Y value, in meters |
| MaximumY |
REAL |
Maximum Y value, in meters |
| MinimumZ |
REAL |
Minimum Z value, in meters |
| MaximumZ |
REAL |
Maximum Z value, in meters |
| CeilingHeight |
REAL |
Ceiling height, in meters |
| Volume |
REAL |
Zone volume, in cubic
meters |
| InsideConvectionAlgo |
INTEGER |
Inside convection algorithm
(enum: 1=simple, 2=detailed, 3=Ceiling diffuser,
4=TrombeWall) |
| OutsideConvectionAlgo |
INTEGER |
Outside convection algorithm
(enum: 1=simple, 2=detailed, 6=MoWitt, 7=DOE-2) |
| FloorArea |
REAL |
Zone floor area, in square
meters |
| ExtGrossWallArea |
REAL |
Zone external gross wall area
(includes windows and doors), in square meters |
| ExtNetWallArea |
REAL |
Zone net wall area (excludes
windows and doors), and square meters |
| ExtWindowArea |
REAL |
Zone window area (includes glass
doors), and square meters |
| IsPartOfTotalArea |
INTEGER |
See Zone input object
documentation |
Please see the Zone
object in the Group-Thermal Zone
Description/Geometry section of the Input-Output Reference for
more information.
NominalPeople Table[LINK]
An overview of the NominalPeople SQL table is shown
below.
SQL NominalPeople Table Contents
| Field Name |
Field Type |
Description |
| NominalPeopleIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The name of the People
object |
| ZoneIndex |
INTEGER |
Connects the NominalPeople table
to the Zones table |
| NumberOfPeople |
INTEGER |
Nominal number of people in the
zone |
| NumberOfPeopleScheduleIndex |
INTEGER |
Number of people schedule number
(see Schedule table) |
| ActivityScheduleIndex |
INTEGER |
Activity level schedule (see
People object documentation) |
| FractionRadiant |
REAL |
see People object
documentation |
| FractionConvected |
REAL |
see People object
documentation |
| WorkEfficiencyScheduleIndex |
INTEGER |
Work efficiency schedule number
(see schedule table and people object documentation) |
| ClothingEfficiencyScheduleIndex |
INTEGER |
Clothing efficiency schedule
number (see schedule table and people object
documentation) |
| AirVelocityScheduleIndex |
INTEGER |
Air velocity schedule number
(see schedule table and people object documentation) |
| Fanger |
INTEGER |
Flag indicating whether Fanger
calculations are active |
| Pierce |
INTEGER |
Flag indicating whether Pierce
calculations are active |
| KSU |
INTEGER |
Flag indicating whether KSU
calculations are active |
| MRTCalcType |
INTEGER |
see People object
documentation |
| SurfaceIndex |
INTEGER |
see Surfaces table and People
object documentation |
| UserSpecifeidSensibleFraction |
REAL |
see People object
documentation |
| Show55Warning |
INTEGER |
see People object
documentation |
Please see the People
object in the Group-Internal Gains section of the Input-Output
Reference for more information.
NominalLighting Table[LINK]
An overview of the NominalLighting SQL table is shown
below.
SQL NominalLighting Table Contents
| Field Name |
Field Type |
Description |
| NominalLightingIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The LIGHTS object name |
| ZoneIndex |
INTEGER |
Connects the NominalLighting
table to the Zones table |
| ScheduleIndex |
INTEGER |
Lighting schedule number (see
Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionReturnAir |
REAL |
User-specified return air
fraction |
| FractionRadiant |
REAL |
User-specified radiant
fraction |
| FractionReplaceable |
REAL |
Defines the daylighting control
for the LIGHTS object |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the LIGHTS object in the Group-Internal Gains
section of the Input-Output Reference for more
information.
NominalElectricEquipment
Table[LINK]
An overview of the NominalElectricEquipment SQL table is
shown below.
SQL NominalElectricEquipment Table Contents
| Field Name |
Field Type |
Description |
| NominalElectricEquipmentIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Electric Equipment object
name |
| ZoneIndex |
INTEGER |
Connects the
NominalElectricEquipment table to the Zones table |
| ScheduleIndex |
INTEGER |
Electric equipment schedule
number (see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionLatent |
REAL |
User-specified latent heat
fraction |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionLost |
REAL |
User-specified lost heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Electric Equipment object in the
Group-Internal Gains section of the Input-Output Reference for
more information.
NominalGasEquipment
Table[LINK]
An overview of the NominalGasEquipment SQL table is shown
below.
SQL NominalGasEquipment Table Contents
| Field Name |
Field Type |
Description |
| NominalGasEquipmentIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Gas Equipment object
name |
| ZoneIndex |
INTEGER |
Connects the NominalGasEquipment
table to the Zones table |
| ScheduleIndex |
INTEGER |
Gas equipment schedule number
(see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionLatent |
REAL |
User-specified latent heat
fraction |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionLost |
REAL |
User-specified lost heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Gas Equipment object in the Group-Internal
Gains section of the Input-Output Reference for more
information.
NominalSteamEquipment
Table[LINK]
An overview of the NominalSteamEquipment SQL table is shown
below.
SQL NominalSteamEquipment Table Contents
| Field Name |
Field Type |
Description |
| NominalSteamEquipmentIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Steam Equipment object
name |
| ZoneIndex |
INTEGER |
Connects the
NominalSteamEquipment table to the Zones table |
| ScheduleIndex |
INTEGER |
Steam equipment schedule number
(see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionLatent |
REAL |
User-specified latent heat
fraction |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionLost |
REAL |
User-specified lost heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Steam Equipment object in the Group-Internal
Gains section of the Input-Output Reference for more
information.
NominalHotWaterEquipment
Table[LINK]
An overview of the NominalHotWaterEquipment SQL table is
shown below.
SQL NominalHotWaterEquipment Table Contents
| Field Name |
Field Type |
Description |
| NominalHotWaterEquipmentIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Hot Water Equipment object
name |
| ZoneIndex |
INTEGER |
Connects the
NominalHotWaterEquipment table to the Zones table |
| ScheduleIndex |
INTEGER |
Hot water equipment schedule
number (see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionLatent |
REAL |
User-specified latent heat
fraction |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionLost |
REAL |
User-specified lost heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Hot Water Equipment object in the
Group-Internal Gains section of the Input-Output Reference for
more information.
NominalOtherEquipment
Table[LINK]
An overview of the NominalOtherEquipment SQL table is shown
below.
SQL NominalOtherEquipment Table Contents
| Field Name |
Field Type |
Description |
| NominalOtherEquipmentIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Other Equipment object
name |
| ZoneIndex |
INTEGER |
Connects the
NominalOtherEquipment table to the Zones table |
| ScheduleIndex |
INTEGER |
Other equipment schedule number
(see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
Watts |
| FractionLatent |
REAL |
User-specified latent heat
fraction |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionLost |
REAL |
User-specified lost heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Other Equipment object in the Group-Internal
Gains section of the Input-Output Reference for more
information.
NominalBaseboardHeaters
Table[LINK]
An overview of the NominalBaseboardHeaters SQL table is
shown below.
SQL NominalBaseboardHeaters Table Contents
| Field Name |
Field Type |
Description |
| NominalBaseboardHeaterIndex |
INTEGER |
The internal statement
number |
| ObjectName |
TEXT |
The Baseboard Heat object
name |
| ZoneIndex |
INTEGER |
Connects the
NominalBaseboardHeat table to the Zones table |
| ScheduleIndex |
INTEGER |
Baseboard heat schedule number
(see Schedules table) |
| CapatLowTemperature |
REAL |
Capacity at low temperature, in
Watts |
| LowTemperature |
REAL |
Low temperature capacity
setpoint |
| CapatHighTemperature |
REAL |
Capacity at high temperature, in
Watts |
| HighTemperature |
REAL |
High temperature capacity
setpoint |
| FractionRadiant |
REAL |
User-specified radiant heat
fraction |
| FractionConvected |
REAL |
User-specified convicted heat
fraction |
| EndUseSubcategory |
TEXT |
User-specified end-use
subcategory |
Please see the Baseboard Heat object in the Group-Internal
Gains section of the Input-Output Reference for more
information.
NominalInfiltration
Table[LINK]
An overview of the NominalInfiltration SQL table is shown
below.
SQL NominalInfiltration Table Contents
| Field Name |
Field Type |
Description |
| NominalInfiltrationIndex |
INTEGER PRIMARY KEY |
The internal statement
number |
| ObjectName |
TEXT |
The Infiltration object
name |
| ZoneIndex |
INTEGER |
Connects the NominalInfiltration
table to the Zones table |
| ScheduleIndex |
INTEGER |
Infiltration schedule number
(see Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
m3/s |
Please see the Infiltration object in the Group-Airflow
section of the Input-Output Reference for more
information.
NominalVentilation
Table[LINK]
An overview of the NominalVentilation SQL table is shown
below.
SQL NominalVentilation Table Contents
| Field Name |
Field Type |
Description |
| NominalVentilationIndex |
INTEGER PRIMARY KEY |
The internal statement
number |
| ObjectName |
TEXT |
The Ventilation object name |
| ZoneIndex |
INTEGER |
Connects the NominalVentilation
table to the Zones table |
| ScheduleIndex |
INTEGER |
Ventilation schedule number (see
Schedule table) |
| DesignLevel |
REAL |
Nominal design level, in
m3/s |
Please see the Ventilation object in the Group-Airflow
section of the Input-Output Reference for more
information.
Surfaces Table[LINK]
An overview of the Surfaces SQL table is shown below.
SQL Surfaces Table Contents
| Field Name |
Field Type |
Description |
| SurfaceIndex |
INTEGER PRIMARY KEY |
Surface number (used for
cross-referencing) |
| SurfaceName |
TEXT |
Surface name |
| ConstructionIndex |
INTEGER |
Construction Index |
| ClassName |
TEXT |
Surface class name (e.g.,
shading, wall) |
| Area |
REAL |
Surface area (excluding
cutouts) |
| GrossArea |
REAL |
Surface area (including
cutouts) |
| Perimeter |
REAL |
Surface perimeter, in
meters |
| Azimuth |
REAL |
As news angle, in degrees |
| Height |
REAL |
Surface height, in meters |
| Reveal |
REAL |
Reveal depth, in meters |
| Shape |
INTEGER |
Shape index |
| Sides |
INTEGER |
Number of sides |
| Tilt |
REAL |
Tilt angle, in degrees |
| Width |
REAL |
Surface width, in meters |
| HeatTransferSurf |
INTEGER |
Flag indicating whether the
surface is a heat transfer surface |
| BaseSurfaceIndex |
INTEGER |
Based surface index |
| ZoneIndex |
INTEGER |
Zone index |
| ExtBoundCond |
INTEGER |
External boundary condition
index. For interzone surface, this is the adjacent surface
number. For an internal/adiabatic surface this is the current
surface number. 0=external environment, -1=ground, -2=other
side coefficients, -3=other side conditions model. |
| ExtSolar |
INTEGER |
Flag indicating whether the
surface is exposed to solar |
| ExtWind |
INTEGER |
Flag indicating whether the
surface is exposed to wind |
Please see the Surface(s) object in the Group-Thermal Zone
Description/Geometry section of the Input-Output Reference for
more information.
Constructions Table[LINK]
An overview of the Constructions SQL table is shown
below.
SQL Constructions Table Contents
| Field Name |
Field Type |
Description |
| ConstructionIndex |
INTEGER PRIMARY KEY |
Construction Index |
| Name |
TEXT |
Construction name |
| TotalLayers |
INTEGER |
Total number of layers |
| TotalSolidLayers |
INTEGER |
Total number of solid
layers |
| TotalGlassLayers |
INTEGER |
Total number of glass
layers |
| InsideAbsorpVis |
REAL |
The visible absorptance of the
inside layer (see Materials table) |
| OutsideAbsorpVis |
REAL |
The visible absorptance of the
outside layer (see Materials table) |
| InsideAbsorpSolar |
REAL |
The solar absorptance of the
inside layer (see Materials table) |
| OutsideAbsorpSolar |
REAL |
The solar absorptance of the
outside layer (see Materials table) |
| InsideAbsorpThermal |
REAL |
The thermal absorptance of the
inside layer (see Materials table) |
| OutsideAbsorpThermal |
REAL |
The thermal absorptance of the
outside layer (see Materials table) |
| OutsideRoughness |
INTEGER |
The roughness of the outside
layer |
| TypeIsWindow |
INTEGER |
Flag indicating whether the
construction is a window or glass door |
| Uvalue |
REAL |
Nominal U-value for the
construction |
Please see the Construction
object in the Group-Surface Construction
Elements section of the Input-Output Reference for more
information.
ConstructionLayers
Table[LINK]
An overview of the ConstructionLayers SQL table is shown
below.
SQL ConstructionLayers Table Contents
| Field Name |
Field Type |
Description |
| ConstructionLayersIndex |
INTEGER PRIMARY KEY |
Construction Layers Index |
| ConstructionIndex |
INTEGER |
Construction Index (see
Constructions table) |
| LayerIndex |
INTEGER |
Layer number (layer 1 is the
outside layer) |
| MaterialIndex |
INTEGER |
Material index (see Materials
table) |
Please see the Construction
object in the Group-Surface Construction
Elements section of the Input-Output Reference for more
information.
Materials Table[LINK]
An overview of the Materials SQL table is shown below.
SQL Materials Table Contents
| Field Name |
Field Type |
Description |
| MaterialIndex |
INTEGER PRIMARY KEY |
Material Index (links the
Materials table with the ConstructionLayers and Constructions
tables) |
| Name |
TEXT |
Material name |
| MaterialType |
INTEGER |
Material type |
| Roughness |
INTEGER |
Roughness index |
| Conductivity |
REAL |
Conductivity, in W/(m-K) |
| Density |
REAL |
Density, in kg/m3 |
| Porosity |
REAL |
Porosity |
| Resistance |
REAL |
Resistance |
| Ronly |
INTEGER |
Flag that indicates the material
definition is of type Material:Regular-R |
| SpecHeat |
REAL |
Specific heat |
| ThermGradCoef |
REAL |
Thermal gradient
coefficient |
| Thickness |
REAL |
Thickness, in meters |
| VaporDiffus |
REAL |
Vapor diffusivity |
Please see the Materials object in the Group-Surface Construction
Elements section of the Input-Output Reference for more
information.
RoomAirModels Table[LINK]
An overview of the RoomAirModels SQL table is shown below.
Please see the Group-RoomAir Models section of the
Input-Output Reference for more information.
SQL RoomAirModels Table Contents
| Field Name |
Field Type |
Description |
| ZoneIndex |
INTEGER PRIMARY KEY |
Zone index |
| AirModelName |
TEXT |
Air model name |
| AirModelType |
INTEGER |
Air model index |
| TempCoupleScheme |
INTEGER |
Temperature coupling index |
| SimAirModel |
INTEGER |
Simulation air model index |
ComponentSizes Table[LINK]
An overview of the ComponentSizes SQL table is shown
below.
SQL ComponentSizes Table Contents
| Field Name |
Field Type |
Description |
| ComponentSizesIndex |
INTEGER PRIMARY KEY |
Component Sizes Index |
| CompType |
TEXT |
Component type |
| CompName |
TEXT |
Component name |
| Description |
TEXT |
Component description |
| Value |
REAL |
Sizing value |
| Units |
TEXT |
Sizing units |
Please see the Sizing object in the Group-Design Objects
section of the Input-Output Reference for more
information.
SystemSizes Table[LINK]
An overview of the SystemSizes SQL table is shown below.
Please see the System Sizing object in the Group-Design
Objects section of the Input-Output Reference for more
information.
SQL SystemSizes Table Contents
| Field Name |
Field Type |
Description |
| SystemSizesIndex |
INTEGER PRIMARY KEY |
System Sizes Index |
| SystemName |
TEXT |
System name |
| Description |
TEXT |
System description |
| Value |
REAL |
Sizing value |
| Units |
TEXT |
Sizing units |
ZoneSizes Table[LINK]
An overview of the ZoneSizes SQL table is shown below.
SQL ZoneSizes Table Contents
| Field Name |
Field Type |
Description |
| ZoneSizesIndex |
INTEGER PRIMARY KEY |
Zone Sizes Index |
| ZoneName |
TEXT |
Zone name |
| LoadType |
TEXT |
Load type |
| DesLoad |
REAL |
Design load |
| CalcDesFlow |
REAL |
Calculated design flow |
| UserDesFlow |
REAL |
User-specified design flow |
| DesDayName |
TEXT |
Design day name |
| PeakHrMin |
TEXT |
Time of the peak
temperature |
| PeakTemp |
REAL |
Peak temperature |
| PeakHumRat |
REAL |
Peak humidity ratio |
| CalcOutsideAirFlow |
REAL |
Calculated outside air flow
rate, in m3/s |
Please see the Zone
Sizing object in the Group-Design Objects section of the
Input-Output Reference for more information.
ZoneGroups Table[LINK]
An overview of the ZoneGroups SQL table is shown below.
SQL ZoneGroups Table Contents
| Field Name |
Field Type |
Description |
| ZoneGroupIndex |
INTEGER PRIMARY KEY |
Zone group index |
| ZoneGroupName |
TEXT |
Zone list name |
| ZoneListIndex |
INTEGER |
The ZoneListIndex links this
record to the respective zone list record (see ZoneLists table
below) |
| ZoneListMultiplier |
INTEGER |
Zone list multiplier |
Please see the Zone
Group object in the Group-Thermal Zone
Description/Geometry section of the Input-Output Reference for
more information.
ZoneLists Table[LINK]
An overview of the ZoneLists SQL table is shown below.
SQL ZoneLists Table Contents
| Field Name |
Field Type |
Description |
| ZoneListIndex |
INTEGER PRIMARY KEY |
Zone list index |
| Name |
TEXT |
Zone list name |
Please see the Zone
List object in the Group-Thermal Zone
Description/Geometry section of the Input-Output Reference for
more information.
ZoneInfoZoneLists Table[LINK]
An overview of the ZoneInfoZoneLists SQL table is shown
below.
SQL ZoneLists Table Contents
| Field Name |
Field Type |
Description |
| ZoneListIndex |
INTEGER |
Zone list index |
| ZoneIndex |
INTEGER |
Zone index |
This is a join table to represent the many-to-many
relationship of zones and zone lists. ZoneListIndex and
ZoneIndex together are the Primary Key for this table.
Miscellaneous Tables[LINK]
Schedules Table[LINK]
An overview of the Schedules SQL table is shown below.
SQL Schedules Table Contents
| Field Name |
Field Type |
Description |
| ScheduleIndex |
INTEGER PRIMARY KEY |
Schedule index |
| ScheduleName |
TEXT |
Schedule name |
| ScheduleType |
TEXT |
Schedule Type |
| ScheduleMinimum |
REAL |
ScheduleMinimum |
| ScheduleMaximum |
REAL |
ScheduleMaximum |
Please see the Group-Schedules section of the Input-Output
Reference for more information.
Simulations Table[LINK]
An overview of the Simulations SQL table is shown below.
Currently there will only be one record in the table, because
the SQLite database is relevant to only one simulation. In the
future this might change if multiple simulations are
aggregated into a larger database.
SQL Simulations Table Contents
| Field Name |
Field Type |
Description |
| SimulationIndex |
INTEGER PRIMARY KEY |
Simulation index, currently
there will be only one record in this table. |
| EnergyPlusVersion |
TEXT |
The version of EnergyPlus that
was used to run the simulation. |
| TimeStamp |
TEXT |
A text string containing the
timestamp when the simulation was run. |
| NumTimestepsPerHour |
INTEGER |
The number of timesteps per hour
used for the simulation. See the Timestep object for more
information. |
| Completed |
BOOL |
True if the simulation completed
without crashing. |
| CompletedSuccessfully |
BOOL |
True if the simulation completed
without any severe or fatal errors. |
EnvironmentPeriods
Table[LINK]
An overview of the EnvironmentPeriods SQL table is shown
below.
SQL EnvironmentPeriods Table Contents
| Field Name |
Field Type |
Description |
| EnvironmentPeriodIndex |
INTEGER PRIMARY KEY |
Environment period index |
| SimulationIndex |
INTEGER |
A foreign key to a record in the
Simulations table. |
| EnvironmentName |
TEXT |
A text string identifying the
environment. |
| EnvironmentType |
INTEGER |
An enumeration of the
environment type. (1 = Design Day, 2 = Design Run Period, 3
= Weather Run Period) See the various SizingPeriod objects
and the RunPeriod object for details. |
TabularData Table[LINK]
An overview of the TabularData SQL table is shown below.
The TabularData table is only output when the
“SimpleAndTabular” choice is made in the Output:SQLite
object. The TabularData table contains all of the tabular
report information that is typically output to one of the
formats controlled by the OutputControl:Table:Style
object. This is a generic way of dumping all of the existing
tabular reports to the SQLite database. This table has many
references to the companion Strings table. The Strings table
simply associates strings to an integer value for space
efficiency of the database. Tabular data is easier to query
from the TabularDataWithStrings table, which is implemented as
a database view that joins this table with the Strings
table.
SQL TabularData Table Contents
| Field Name |
Field Type |
Description |
| TabularDataIndex |
INTEGER PRIMARY KEY |
Tabular Data Index |
| ReportNameIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the name of the report the
record belongs to. |
| ReportForStringIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the “For” text that is
associated with the record. An example is the Space Loads
report where the “For” text identifies which zone the record
pertains to. |
| TableNameIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the name of the table the
record belongs to. This is typically the text that
immediately precedes the tables in html format. |
| SimulationIndex |
INTEGER |
A foreign key to the Simulations
table. |
| RowNameIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the name of the row the record
belongs to. |
| ColumnNameIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the name of the column the
record belongs to. |
| UnitsIndex |
INTEGER |
A foreign key to an entry in the
Strings table, which indicates the units associated with the
record. |
| SimulationIndex |
INTEGER |
A foreign key to the Simulations
table. |
| RowId |
INTEGER |
The index of the row associated
with the record. Data in the first row of a tabular report
would have the Id 1. |
| ColumnId |
INTEGER |
The index of the column
associated with the record. Data in the first column of a
tabular report would have the Id 1. |
| Value |
REAL |
The value of the record. Most
data is numeric, thus the type for this column is REAL. The
SQLite engine will first try to store the value as a REAL,
however if this fails the value will be stored as text. |
Strings Table[LINK]
An overview of the Strings SQL table is shown below. The
Strings table is only output when the “SimpleAndTabular”
choice is made in the Output:SQLite
object. The Strings table simply associates strings with
integers to save space in the database.
SQL Strings Table Contents
| Field Name |
Field Type |
Description |
| StringIndex |
INTEGER PRIMARY KEY |
The integer primary key that
uniquely identifies the string record. |
| StringTypeIndex |
INTEGER |
A foreign key to the StringTypes
table. |
| Value |
TEXT |
The record’s string value. |
StringTypes Table[LINK]
An overview of the StringTypes SQL table is shown below.
The StringTypes table is only output when the
“SimpleAndTabular” choice is made in the Output:SQLite
object.
SQL StringTypes Table Contents
| Field Name |
Field Type |
Description |
| StringTypeIndex |
INTEGER PRIMARY KEY |
The integer primary key. |
| Value |
TEXT |
The record’s string value.
Currently there are 6 possible values; ReportName,
ReportForString, TableName, RowName, ColumnName, and Units.
That is, entries in the Strings table are one of these
types. |
TabularDataWithStrings
Table[LINK]
An overview of the TabularDataWithStrings SQL table is
shown below. This table is implemented as a view of other
tables and is not actually a table in the database. This view
is similar to the TabularData table except text strings are
directly available in place of foreign keys to the Strings
table. The TabularDataWithStrings view is only created when
the “SimpleAndTabular” choice is made in the Output:SQLite
object.
An example of a SQL query to get a table out of the
AnnualBuildingUtilityPerformanceSummary report is the
following.
select * FROM TabularDataWithStrings WHERE
ReportName = `AnnualBuildingUtilityPerformanceSummary' and
TableName = `Site and Source Energy';
SQL TabularDataWithStrings Table Contents
| Field Name |
Field Type |
Description |
| TabularDataIndex |
INTEGER PRIMARY KEY |
The index of the record |
| Value |
REAL |
The value of the record |
| ReportName |
TEXT |
The name of the report the
record belongs to. |
| ReportForString |
TEXT |
The “For” string. |
| TableName |
TEXT |
The name of the table the record
belongs to. |
| RowName |
TEXT |
The name of the row associated
with the record. |
| ColumnName |
TEXT |
The name of the column
associated with the record. |
| Units |
TEXT |
The units associated with the
record. |
The Errors SQL table reports errors and warnings for the
simulation. The content of this table includes most of the
content of the error file. However, it does not contain purely
informational messages (e.g. not warnings or errors) and some
of the error summary statistics which may be readily computed.
Users should be aware that errors experienced while processing
input cause EnergyPlus to exit before the SQLite output
database has been initialized. This is because the Output:SQLite
object must be parsed from the input to request the database.
Therefore, failures in input processing are indicated by the
absence of a SQLite output file. The regular error or audit
files must be used to identify the erroneous input objects in
this case. Because each error or warning message is expected
to be unique these messages are stored directly in the Errors
table and not in the Strings table.
SQL Errors Table Contents
| Field Name |
Field Type |
Description |
| ErrorIndex |
INTEGER PRIMARY KEY |
The index of the error or
warning message. |
| SimulationIndex |
INTEGER FOREIGN KEY |
The simulation the error or
warning pertains to. |
| ErrorType |
INTEGER |
Type of error or warning
0=Warning, 1=Severe, 2=Fatal. |
| ErrorMessage |
TEXT |
The text of the error
message. |
| Count |
INTEGER |
Number of times that the error
was repeated. This will be 1 for normal warnings or errors, 0
for warning and error messages, and the number of times the
error or warning is repeated. |
How to Access the
SQLite Data[LINK]
The SQL database can be accessed in a number of ways,
including via the command line, through ODBC, or through as
SQLite’s API interface. SQLite uses the industry standard SQL
92 language.
One of the simplest ways to access the data in the SQL
database is by way of the SQL command line tool (i.e.,
sqlite3). A brief description of how to use sqlite3 for each
computing platform is given below.
Windows XP and Windows
Vista[LINK]
While Windows does not ship with sqlite3 installed, the
sqlite3 binary can be downloaded from the SQLite webpage
(www.sqlite.org/download.html). After downloading the
precompiled binary, install it in the EnergyPlus
directory.
Once the sqlite3 executable is installed, access the
program from the command line by typing “sqlite3” at the DOS
prompt.
The sqlite3 command line tool comes preinstalled on a
number of more recent Linux releases. To see if sqlite3 is
available (and which version is installed), type “sqlite3
–version” from the command line. If sqlite3 is not installed,
the sqlite3 binary, as well as source code, can be downloaded
from the SQLite webpage (http://www.sqlite.org/download.html) and
installed in the directory of your choice.
Macintosh OS X[LINK]
The sqlite3 program comes standard on MacOS X 10.5. From
the command line, type “sqlite3 –version” to see which version
of sqlite3 is installed. In order to access the database
created by EnergyPlus, version 3 or later is required.
Accessing
the Data from the Command Line[LINK]
Once it has been confirmed that SQLite3 is installed on
your machine, the SQL database can be accessed by typing:
sqlite3 <database name>
at the command line, where <database name > is the
name of the SQL database (e.g., sqlite3 eplusout.sql).
The sqlite.org website gives
examples of how sqlite3 can be used to access and output data
in various formats.
ODBC allows access to the SQL database from a variety of
programs, including Microsoft Excel, Microsoft Access, and
FileMaker. How to install and use ODBC drivers is outside the
scope of this document, and more information can be found at
the following websites:
Macintosh ODBC drivers:
http://www.actualtechnologies.com/
Windows and Linux ODBC information and drivers:
http://www.sqlite.org/cvstrac/wiki?p=SqliteOdbc
http://www.ch-werner.de/sqliteodbc/
Sqlite3 includes a rich C++ API (detailed on the SQLite
website www.sqlite.org/cintro.html),
and wrappers for the API interface are available in a variety
of programming languages, including Fortran, TCL, and Ruby
(see www.sqlite.org/cvstrac/wiki?p
= SqliteWrappers for more information).
eplusout.sql[LINK]
eplusout.sql is an optional output format for EnergyPlus. The eplusout.sql output file is a sqlite3 database file (see http://www.sqlite.org) and includes all of the data found in EnergyPlus’ eplustbl.* files, eplusout.eso and eplusout.mtr output files (i.e., EnergyPlus’ standard variable and meter output files) plus a number of reports that are found in the eplusout.eio output file.
A discussion of the individual data tables is presented below followed by a discussion about how to access data within the SQL file.
List of Available SQLite Tables[LINK]
This initial release of the SQL database output option includes a variety of data in the following tables:
ComponentSizes Table
ConstructionLayers Table
Constructions Table
Materials Table
NominalBaseboardHeaters Table
NominalElectricEquipment Table
NominalGasEquipment Table
NominalHotWaterEquipment Table
NominalInfiltration Table
NominalLighting Table
NominalOtherEquipment Table
NominalPeople Table
NominalSteamEquipment Table
NominalVentilation Table
ReportData Table
ReportDataDictionary Table
ReportExtendedData Table
RoomAirModels Table
Schedules Table
Surfaces Table
SystemSizes Table
Time Table
ZoneGroups Table
Zones Table
ZoneLists Table
ZoneSizes Table
ZoneInfoLists Table
Simulations Table
EnvironmentPeriods Table
TabularData Table
Strings Table
StringTypes Table
TabularDataWithStrings Table
Errors Table
A short discussion of contents of each of the above SQL tables is given in the sections that follow.
Report Data[LINK]
Data in the following four tables are also found in EnergyPlus’ standard output file (i.e., eplusout.eso – see that section for more information) or in EnergyPlus’ eplusout.mtr (i.e. meter) output file. As with the standard output file, the “Report Variable” and “Report Meter” commands control the data in these tables.
ReportDataDictionary Table[LINK]
The ReportDataDictionary table provides the equivalent of the dictionary portion of the ESO file (i.e., the first section of the .eso file) or eplusout.mtr. Please see the Report Variable section of the Input-Output Reference for more information. Like in the eplusout.mtr file (see the eplusout.mtr section), only data requested by “Report Meter” commands will set isMeter to 1 or True.
ReportData Table[LINK]
The ReportData table contains the report or meter variable data (e.g., the hourly, daily, and monthly report variable data). Please see the Report Variable section of the Input-Output Reference for more information.
ReportExtendedData Table[LINK]
The ReportExtendedData table contains additional data (e.g., monthly maximums and minimums) that is available for certain report or meter variables.
Time Table[LINK]
The Time table provides the time information for both the “report variable” and “report meter” variables (the ReportData table).
One time (EIO) File Data[LINK]
Data in the tables below can also be found in EnergyPlus input output file (i.e., in the eplusout.eio output file).
Zones Table[LINK]
The Zones table provides a variety of information about the zones specified within EnergyPlus. One of its most common uses is to provide zone name and area information for the other tables within the SQL database (e.g., use the ZoneIndex to look up the ZoneName).
Please see the Zone object in the Group-Thermal Zone Description/Geometry section of the Input-Output Reference for more information.
NominalPeople Table[LINK]
An overview of the NominalPeople SQL table is shown below.
Please see the People object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalLighting Table[LINK]
An overview of the NominalLighting SQL table is shown below.
Please see the LIGHTS object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalElectricEquipment Table[LINK]
An overview of the NominalElectricEquipment SQL table is shown below.
Please see the Electric Equipment object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalGasEquipment Table[LINK]
An overview of the NominalGasEquipment SQL table is shown below.
Please see the Gas Equipment object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalSteamEquipment Table[LINK]
An overview of the NominalSteamEquipment SQL table is shown below.
Please see the Steam Equipment object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalHotWaterEquipment Table[LINK]
An overview of the NominalHotWaterEquipment SQL table is shown below.
Please see the Hot Water Equipment object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalOtherEquipment Table[LINK]
An overview of the NominalOtherEquipment SQL table is shown below.
Please see the Other Equipment object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalBaseboardHeaters Table[LINK]
An overview of the NominalBaseboardHeaters SQL table is shown below.
Please see the Baseboard Heat object in the Group-Internal Gains section of the Input-Output Reference for more information.
NominalInfiltration Table[LINK]
An overview of the NominalInfiltration SQL table is shown below.
Please see the Infiltration object in the Group-Airflow section of the Input-Output Reference for more information.
NominalVentilation Table[LINK]
An overview of the NominalVentilation SQL table is shown below.
Please see the Ventilation object in the Group-Airflow section of the Input-Output Reference for more information.
Surfaces Table[LINK]
An overview of the Surfaces SQL table is shown below.
Please see the Surface(s) object in the Group-Thermal Zone Description/Geometry section of the Input-Output Reference for more information.
Constructions Table[LINK]
An overview of the Constructions SQL table is shown below.
Please see the Construction object in the Group-Surface Construction Elements section of the Input-Output Reference for more information.
ConstructionLayers Table[LINK]
An overview of the ConstructionLayers SQL table is shown below.
Please see the Construction object in the Group-Surface Construction Elements section of the Input-Output Reference for more information.
Materials Table[LINK]
An overview of the Materials SQL table is shown below.
Please see the Materials object in the Group-Surface Construction Elements section of the Input-Output Reference for more information.
RoomAirModels Table[LINK]
An overview of the RoomAirModels SQL table is shown below. Please see the Group-RoomAir Models section of the Input-Output Reference for more information.
ComponentSizes Table[LINK]
An overview of the ComponentSizes SQL table is shown below.
Please see the Sizing object in the Group-Design Objects section of the Input-Output Reference for more information.
SystemSizes Table[LINK]
An overview of the SystemSizes SQL table is shown below. Please see the System Sizing object in the Group-Design Objects section of the Input-Output Reference for more information.
ZoneSizes Table[LINK]
An overview of the ZoneSizes SQL table is shown below.
Please see the Zone Sizing object in the Group-Design Objects section of the Input-Output Reference for more information.
ZoneGroups Table[LINK]
An overview of the ZoneGroups SQL table is shown below.
Please see the Zone Group object in the Group-Thermal Zone Description/Geometry section of the Input-Output Reference for more information.
ZoneLists Table[LINK]
An overview of the ZoneLists SQL table is shown below.
Please see the Zone List object in the Group-Thermal Zone Description/Geometry section of the Input-Output Reference for more information.
ZoneInfoZoneLists Table[LINK]
An overview of the ZoneInfoZoneLists SQL table is shown below.
This is a join table to represent the many-to-many relationship of zones and zone lists. ZoneListIndex and ZoneIndex together are the Primary Key for this table.
Miscellaneous Tables[LINK]
Schedules Table[LINK]
An overview of the Schedules SQL table is shown below.
Please see the Group-Schedules section of the Input-Output Reference for more information.
Simulations Table[LINK]
An overview of the Simulations SQL table is shown below. Currently there will only be one record in the table, because the SQLite database is relevant to only one simulation. In the future this might change if multiple simulations are aggregated into a larger database.
EnvironmentPeriods Table[LINK]
An overview of the EnvironmentPeriods SQL table is shown below.
TabularData Table[LINK]
An overview of the TabularData SQL table is shown below. The TabularData table is only output when the “SimpleAndTabular” choice is made in the Output:SQLite object. The TabularData table contains all of the tabular report information that is typically output to one of the formats controlled by the OutputControl:Table:Style object. This is a generic way of dumping all of the existing tabular reports to the SQLite database. This table has many references to the companion Strings table. The Strings table simply associates strings to an integer value for space efficiency of the database. Tabular data is easier to query from the TabularDataWithStrings table, which is implemented as a database view that joins this table with the Strings table.
Strings Table[LINK]
An overview of the Strings SQL table is shown below. The Strings table is only output when the “SimpleAndTabular” choice is made in the Output:SQLite object. The Strings table simply associates strings with integers to save space in the database.
StringTypes Table[LINK]
An overview of the StringTypes SQL table is shown below. The StringTypes table is only output when the “SimpleAndTabular” choice is made in the Output:SQLite object.
TabularDataWithStrings Table[LINK]
An overview of the TabularDataWithStrings SQL table is shown below. This table is implemented as a view of other tables and is not actually a table in the database. This view is similar to the TabularData table except text strings are directly available in place of foreign keys to the Strings table. The TabularDataWithStrings view is only created when the “SimpleAndTabular” choice is made in the Output:SQLite object.
An example of a SQL query to get a table out of the AnnualBuildingUtilityPerformanceSummary report is the following.
Errors Table[LINK]
The Errors SQL table reports errors and warnings for the simulation. The content of this table includes most of the content of the error file. However, it does not contain purely informational messages (e.g. not warnings or errors) and some of the error summary statistics which may be readily computed. Users should be aware that errors experienced while processing input cause EnergyPlus to exit before the SQLite output database has been initialized. This is because the Output:SQLite object must be parsed from the input to request the database. Therefore, failures in input processing are indicated by the absence of a SQLite output file. The regular error or audit files must be used to identify the erroneous input objects in this case. Because each error or warning message is expected to be unique these messages are stored directly in the Errors table and not in the Strings table.
How to Access the SQLite Data[LINK]
The SQL database can be accessed in a number of ways, including via the command line, through ODBC, or through as SQLite’s API interface. SQLite uses the industry standard SQL 92 language.
Command Line[LINK]
One of the simplest ways to access the data in the SQL database is by way of the SQL command line tool (i.e., sqlite3). A brief description of how to use sqlite3 for each computing platform is given below.
Windows XP and Windows Vista[LINK]
While Windows does not ship with sqlite3 installed, the sqlite3 binary can be downloaded from the SQLite webpage (www.sqlite.org/download.html). After downloading the precompiled binary, install it in the EnergyPlus directory.
Once the sqlite3 executable is installed, access the program from the command line by typing “sqlite3” at the DOS prompt.
Linux[LINK]
The sqlite3 command line tool comes preinstalled on a number of more recent Linux releases. To see if sqlite3 is available (and which version is installed), type “sqlite3 –version” from the command line. If sqlite3 is not installed, the sqlite3 binary, as well as source code, can be downloaded from the SQLite webpage (http://www.sqlite.org/download.html) and installed in the directory of your choice.
Macintosh OS X[LINK]
The sqlite3 program comes standard on MacOS X 10.5. From the command line, type “sqlite3 –version” to see which version of sqlite3 is installed. In order to access the database created by EnergyPlus, version 3 or later is required.
Accessing the Data from the Command Line[LINK]
Once it has been confirmed that SQLite3 is installed on your machine, the SQL database can be accessed by typing:
at the command line, where <database name > is the name of the SQL database (e.g., sqlite3 eplusout.sql).
The sqlite.org website gives examples of how sqlite3 can be used to access and output data in various formats.
ODBC[LINK]
ODBC allows access to the SQL database from a variety of programs, including Microsoft Excel, Microsoft Access, and FileMaker. How to install and use ODBC drivers is outside the scope of this document, and more information can be found at the following websites:
Macintosh ODBC drivers:
http://www.actualtechnologies.com/
Windows and Linux ODBC information and drivers:
http://www.sqlite.org/cvstrac/wiki?p=SqliteOdbc
http://www.ch-werner.de/sqliteodbc/
API[LINK]
Sqlite3 includes a rich C++ API (detailed on the SQLite website www.sqlite.org/cintro.html), and wrappers for the API interface are available in a variety of programming languages, including Fortran, TCL, and Ruby (see www.sqlite.org/cvstrac/wiki?p = SqliteWrappers for more information).