AirTerminal:SingleDuct:Uncontrolled[LINK]
An internal variable called
“AirTerminal:SingleDuct:Uncontrolled Maximum Mass Flow Rate”
provides information about the design flow rate for direct air
terminals. The units are kg/s. This is the mass flow rate (for
dry air at standard conditions) at the volume flow rate
entered in the field Maximum Air Flow Rate (m\(^{3}\)/s) in the AirTerminal:SingleDuct:Uncontrolled
input object. This internal variable is useful for scaling the
flow rates assigned to the “Mass Flow Rate” control in the
“AirTerminal:SingleDuct:Uncontrolled” EMS actuator.
AirTerminal:SingleDuct:ConstantVolume:NoReheat[LINK]
An internal variable called
“AirTerminal:SingleDuct:ConstantVolume:NoReheat Maximum Mass
Flow Rate” provides information about the design flow rate for
single duct constant volume no reheat air terminals. The units
are kg/s. This is the mass flow rate (for dry air at standard
conditions) at the volume flow rate entered in the field
Maximum Air Flow Rate (m\(^{3}\)/s) in the
’AirTerminal:SingleDuct:ConstantVolume:NoReheat input object.
This internal variable is useful for scaling the flow rates
assigned to the “Mass Flow Rate” control in the
“AirTerminal:SingleDuct:ConstantVolume:NoReheat” EMS
actuator.
Fan Nominal Ratings[LINK]
Fan Maximum Mass Flow
Rate[LINK]
The input variable “Fan Maximum Mass Flow Rate” provides
information about the maximum flow rate for a fan. The units
are kg/s. This is the mass flow rate (for dry air at standard
conditions) associated with the volume flow rate entered into
the Maximum Air Flow Rate (m\(^{3}\)/s) in the various fan
input objects. This internal variable is useful for scaling
the flow rates assigned to the “Fan Air Mass Flow Rate”
control in the “Fan” EMS actuator.
Fan Nominal Pressure
Rise[LINK]
The input variable “Fan Nominal Pressure Rise” provides
information about the static pressure rise experienced by a
fan. The units are Pascals. This is the value entered into the
field called Pressure Rise in the various fan input objects.
This internal variable is useful for scaling the pressures
assigned to the “Fan Pressure Rise” control in the “Fan” EMS
actuator.
Fan Nominal Total
Efficiency[LINK]
The input variable “Fan Nominal Total Efficiency” provides
information about the nominal efficiency of each fan. The
value is dimensionless and expressed as a fraction. This is
the value entered into the field called Fan Efficiency in the
various fan input objects. This internal variable is useful
for scaling the value assigned to “Fan Total Efficiency”
control in the “Fan” EMS actuator.
Unitary HVAC Nominal
Ratings[LINK]
Unitary HVAC
Design Heating Capacity[LINK]
The internal variable called “Unitary HVAC Design Heating
Capacity” provides information about the nominal heating
capacity of unitary or furnace HVAC equipment. The units are
Watts. The source of these data will vary depending on the
type of heating coil. This internal variable is useful for
scaling the value assigned to “Sensible Load Request” control
in the “Unitary HVAC” EMS actuator.
Unitary HVAC
Design Cooling Capacity[LINK]
The internal variable called “Unitary HVAC Design Cooling
Capacity” provides information about the nominal cooling
capacity of unitary or furnace HVAC equipment. The units are
Watts. The source of these data will vary depending on the
type of cooling coil. This internal variable is useful for
scaling the value assigned to “Sensible Load Request” control
in the “Unitary HVAC” EMS actuator.
Outdoor Air Mixer
Nominal Ratings[LINK]
Outdoor
Air Controller Maximum Mass Flow Rate[LINK]
The internal variable called “Outdoor Air Controller
Maximum Mass Flow Rate” provides information about the maximum
outdoor air rate for each outdoor air system. The units are
kg/s. The sources of these data are inputs in the Controller:OutdoorAir
input object. This internal variable is useful for scaling the
value assigned to the “Air Mass Flow Rate” control in the
“Outdoor Air Controller” EMS actuator.
Outdoor
Air Controller Minimum Mass Flow Rate[LINK]
The internal variable called “Outdoor Air Controller
Minimum Mass Flow Rate” provides information about the minimum
outdoor air rate for each outdoor air system. The units are
kg/s. The sources of these data are inputs in the Controller:OutdoorAir
input object. This internal variable is useful for scaling the
value assigned to the “Air Mass Flow Rate” control in the
“Outdoor Air Controller” EMS actuator.
Pump Nominal Ratings[LINK]
The internal variable called “Pump Maximum Mass Flow Rate”
provides information about the size of the pump. The units are
kg/s. This is the mass flow rate associated with the volume
flow rate entered into the Rated Flow Rate (m\(^{3}\)/s) in the various pump
input objects. This internal variable is useful for scaling
the flow rates assigned to the “Pump Mass Flow Rate” control
in the “Pump” EMS actuator.
Unitary Systems[LINK]
Unitary
System Control Zone Mass Flow Fraction[LINK]
The internal variable called “Unitary System Control Zone
Mass Flow Fraction” is used to adjust the zone load such that
the total load met by the HVAC system, when distributed to the
conditioned zones, will meet the controlling zones load. The
controlling zone is the zone with the thermostat. See the
AirloopHVAC:UnitarySystem input field named “Controlling Zone
or Thermostat Location.”
Low Temperature
Radiant Hydronic[LINK]
Constant
Flow Low Temp Radiant Design Water Mass Flow Rate[LINK]
The internal variable called “Constant Flow Low Temp
Radiant Design Water Mass Flow Rate” provides information
about the design water flow rate for radiant systems defined
using a ZoneHVAC:LowTemperatureRadiant:ConstantFlow
input object. The units are m\(^{3}\)/s. This internal variable
is useful for scaling the flow rates assigned to the “Water
Mass Flow Rate” control in the “Constant Flow Low Temp
Radiant” EMS actuator.
Hydronic
Low Temp Radiant Design Water Mass Flow Rate for Heating[LINK]
The internal variable called “Hydronic Low Temp Radiant
Design Water Mass Flow Rate for Heating” provides information
about the heating design water flow rate for radiant systems
defined using a ZoneHVAC:LowTemperatureRadiant:VariableFlow
input object. The units are m\(^{3}\)/s. This internal variable
is useful for scaling the flow rates assigned to the “Water
Mass Flow Rate” control in the “Hydronic Low Temp Radiant” EMS
actuator.
Hydronic
Low Temp Radiant Design Water Mass Flow Rate for Cooling[LINK]
The internal variable called “Hydronic Low Temp Radiant
Design Water Mass Flow Rate for Heating” provides information
about the cooling design water flow rate for radiant systems
defined using a ZoneHVAC:LowTemperatureRadiant:VariableFlow
input object. The units are m\(^{3}\)/s. This internal variable
is useful for scaling the flow rates assigned to the “Water
Mass Flow Rate” control in the “Hydronic Low Temp Radiant” EMS
actuator.
Boiler Nominal Ratings[LINK]
Boiler Nominal Capacity[LINK]
The internal variable called “Boiler Nominal Capacity”
provides information about the nominal heating capacity of
boiler equipment. The units are Watts.
Chiller Nominal Ratings[LINK]
Chiller Nominal
Capacity[LINK]
The internal variable called “Chiller Nominal Capacity”
provides information about the nominal cooling capacity of
chiller equipment. The units are Watts.
HVAC Systems[LINK]
AirTerminal:SingleDuct:Uncontrolled[LINK]
An internal variable called “AirTerminal:SingleDuct:Uncontrolled Maximum Mass Flow Rate” provides information about the design flow rate for direct air terminals. The units are kg/s. This is the mass flow rate (for dry air at standard conditions) at the volume flow rate entered in the field Maximum Air Flow Rate (m\(^{3}\)/s) in the AirTerminal:SingleDuct:Uncontrolled input object. This internal variable is useful for scaling the flow rates assigned to the “Mass Flow Rate” control in the “AirTerminal:SingleDuct:Uncontrolled” EMS actuator.
AirTerminal:SingleDuct:ConstantVolume:NoReheat[LINK]
An internal variable called “AirTerminal:SingleDuct:ConstantVolume:NoReheat Maximum Mass Flow Rate” provides information about the design flow rate for single duct constant volume no reheat air terminals. The units are kg/s. This is the mass flow rate (for dry air at standard conditions) at the volume flow rate entered in the field Maximum Air Flow Rate (m\(^{3}\)/s) in the ’AirTerminal:SingleDuct:ConstantVolume:NoReheat input object. This internal variable is useful for scaling the flow rates assigned to the “Mass Flow Rate” control in the “AirTerminal:SingleDuct:ConstantVolume:NoReheat” EMS actuator.
Fan Nominal Ratings[LINK]
Fan Maximum Mass Flow Rate[LINK]
The input variable “Fan Maximum Mass Flow Rate” provides information about the maximum flow rate for a fan. The units are kg/s. This is the mass flow rate (for dry air at standard conditions) associated with the volume flow rate entered into the Maximum Air Flow Rate (m\(^{3}\)/s) in the various fan input objects. This internal variable is useful for scaling the flow rates assigned to the “Fan Air Mass Flow Rate” control in the “Fan” EMS actuator.
Fan Nominal Pressure Rise[LINK]
The input variable “Fan Nominal Pressure Rise” provides information about the static pressure rise experienced by a fan. The units are Pascals. This is the value entered into the field called Pressure Rise in the various fan input objects. This internal variable is useful for scaling the pressures assigned to the “Fan Pressure Rise” control in the “Fan” EMS actuator.
Fan Nominal Total Efficiency[LINK]
The input variable “Fan Nominal Total Efficiency” provides information about the nominal efficiency of each fan. The value is dimensionless and expressed as a fraction. This is the value entered into the field called Fan Efficiency in the various fan input objects. This internal variable is useful for scaling the value assigned to “Fan Total Efficiency” control in the “Fan” EMS actuator.
Unitary HVAC Nominal Ratings[LINK]
Unitary HVAC Design Heating Capacity[LINK]
The internal variable called “Unitary HVAC Design Heating Capacity” provides information about the nominal heating capacity of unitary or furnace HVAC equipment. The units are Watts. The source of these data will vary depending on the type of heating coil. This internal variable is useful for scaling the value assigned to “Sensible Load Request” control in the “Unitary HVAC” EMS actuator.
Unitary HVAC Design Cooling Capacity[LINK]
The internal variable called “Unitary HVAC Design Cooling Capacity” provides information about the nominal cooling capacity of unitary or furnace HVAC equipment. The units are Watts. The source of these data will vary depending on the type of cooling coil. This internal variable is useful for scaling the value assigned to “Sensible Load Request” control in the “Unitary HVAC” EMS actuator.
Outdoor Air Mixer Nominal Ratings[LINK]
Outdoor Air Controller Maximum Mass Flow Rate[LINK]
The internal variable called “Outdoor Air Controller Maximum Mass Flow Rate” provides information about the maximum outdoor air rate for each outdoor air system. The units are kg/s. The sources of these data are inputs in the Controller:OutdoorAir input object. This internal variable is useful for scaling the value assigned to the “Air Mass Flow Rate” control in the “Outdoor Air Controller” EMS actuator.
Outdoor Air Controller Minimum Mass Flow Rate[LINK]
The internal variable called “Outdoor Air Controller Minimum Mass Flow Rate” provides information about the minimum outdoor air rate for each outdoor air system. The units are kg/s. The sources of these data are inputs in the Controller:OutdoorAir input object. This internal variable is useful for scaling the value assigned to the “Air Mass Flow Rate” control in the “Outdoor Air Controller” EMS actuator.
Pump Nominal Ratings[LINK]
The internal variable called “Pump Maximum Mass Flow Rate” provides information about the size of the pump. The units are kg/s. This is the mass flow rate associated with the volume flow rate entered into the Rated Flow Rate (m\(^{3}\)/s) in the various pump input objects. This internal variable is useful for scaling the flow rates assigned to the “Pump Mass Flow Rate” control in the “Pump” EMS actuator.
Unitary Systems[LINK]
Unitary System Control Zone Mass Flow Fraction[LINK]
The internal variable called “Unitary System Control Zone Mass Flow Fraction” is used to adjust the zone load such that the total load met by the HVAC system, when distributed to the conditioned zones, will meet the controlling zones load. The controlling zone is the zone with the thermostat. See the AirloopHVAC:UnitarySystem input field named “Controlling Zone or Thermostat Location.”
Low Temperature Radiant Hydronic[LINK]
Constant Flow Low Temp Radiant Design Water Mass Flow Rate[LINK]
The internal variable called “Constant Flow Low Temp Radiant Design Water Mass Flow Rate” provides information about the design water flow rate for radiant systems defined using a ZoneHVAC:LowTemperatureRadiant:ConstantFlow input object. The units are m\(^{3}\)/s. This internal variable is useful for scaling the flow rates assigned to the “Water Mass Flow Rate” control in the “Constant Flow Low Temp Radiant” EMS actuator.
Hydronic Low Temp Radiant Design Water Mass Flow Rate for Heating[LINK]
The internal variable called “Hydronic Low Temp Radiant Design Water Mass Flow Rate for Heating” provides information about the heating design water flow rate for radiant systems defined using a ZoneHVAC:LowTemperatureRadiant:VariableFlow input object. The units are m\(^{3}\)/s. This internal variable is useful for scaling the flow rates assigned to the “Water Mass Flow Rate” control in the “Hydronic Low Temp Radiant” EMS actuator.
Hydronic Low Temp Radiant Design Water Mass Flow Rate for Cooling[LINK]
The internal variable called “Hydronic Low Temp Radiant Design Water Mass Flow Rate for Heating” provides information about the cooling design water flow rate for radiant systems defined using a ZoneHVAC:LowTemperatureRadiant:VariableFlow input object. The units are m\(^{3}\)/s. This internal variable is useful for scaling the flow rates assigned to the “Water Mass Flow Rate” control in the “Hydronic Low Temp Radiant” EMS actuator.
Boiler Nominal Ratings[LINK]
Boiler Nominal Capacity[LINK]
The internal variable called “Boiler Nominal Capacity” provides information about the nominal heating capacity of boiler equipment. The units are Watts.
Chiller Nominal Ratings[LINK]
Chiller Nominal Capacity[LINK]
The internal variable called “Chiller Nominal Capacity” provides information about the nominal cooling capacity of chiller equipment. The units are Watts.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.