AirflowNetwork and
EarthTube[LINK]
When I use an Earthtube with an AirFlowNetwork, I get a
“Orphan Object” warning.
Currently, Earthtube and AirFlowNetworks do not work
together. If both objects co-exist, the AirflowNetwork mode
supersedes the Earthtube mode at two control choices. Since
this causes the Earthtube objects to not be used, the “orphan”
warning appears.
There are four control choices in the second field of the
AirflowNetwork Simulation object (spaces included for
readability)
MULTIZONE WITH DISTRIBUTION
MULTIZONE WITHOUT DISTRIBUTION
MULTIZONE WITH DISTRIBUTION ONLY DURING FAN
OPERATION
NO MULTIZONE OR DISTRIBUTION
When the first two choices are selected, the AirflowNetwork
model takes over airflow calculation. The earthtube objects
are not used in the airflow calculation, causing the “orphan”
warning. The example file,
AirflowNetwork_Multizone_SmallOffice.idf, uses the first
choice. When the second choice is used, the AirflowNetwork
model is only used during HVAC operation time. During system
off time, the earthtube model is used to calculate airflows.
Thus, no “orphan” warning will be given, but the earthtube may
be being used less than expected. The example file,
AirflowNetwork_Simple_House.idf, uses the third choice.
AirflowNetwork and EarthTube[LINK]
When I use an Earthtube with an AirFlowNetwork, I get a “Orphan Object” warning.
Currently, Earthtube and AirFlowNetworks do not work together. If both objects co-exist, the AirflowNetwork mode supersedes the Earthtube mode at two control choices. Since this causes the Earthtube objects to not be used, the “orphan” warning appears.
There are four control choices in the second field of the AirflowNetwork Simulation object (spaces included for readability)
MULTIZONE WITH DISTRIBUTION
MULTIZONE WITHOUT DISTRIBUTION
MULTIZONE WITH DISTRIBUTION ONLY DURING FAN OPERATION
NO MULTIZONE OR DISTRIBUTION
When the first two choices are selected, the AirflowNetwork model takes over airflow calculation. The earthtube objects are not used in the airflow calculation, causing the “orphan” warning. The example file, AirflowNetwork_Multizone_SmallOffice.idf, uses the first choice. When the second choice is used, the AirflowNetwork model is only used during HVAC operation time. During system off time, the earthtube model is used to calculate airflows. Thus, no “orphan” warning will be given, but the earthtube may be being used less than expected. The example file, AirflowNetwork_Simple_House.idf, uses the third choice.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.