Some of the data formats have inherent omissions (e.g. TMY
does not have location data, BLAST ASCII does not have
elevations). In order to overcome this limitation and to
provide further flexibility, a definitions file (extension
must be .def) is implemented. By naming this with the same
“file name” as your input file (in the same folder), the
weather converter will read the format and use that data, as
appropriate, in the file conversions. The .def file uses
Fortran “Namelist” input fields as shown in the example below.
For flexibility, you can also define a “presets.def” file
(such as when you have a list of files to process and the
format or some portion is all the same between the group of
files. The two def files (one named the same as the file name
for the raw data and one named presets.def) will both be
processed. Conflicts between the two will be shown in the
.audit file. The set of namelist groups is:
&location - Location data
&miscdata - Comments to be applied to “COMMENT2” in
the EPW file and “Source Data”
&wthdata - weather data specifications including
file type, custom formats
&datacontrol - user specified control over
“missing” data (Custom format only)
Note that the “Def” formats are entirely different
from the usual IDF formats of EnergyPlus. No commas separate
fields. No semicolon terminates the entry.
&location
City = 'Hong Kong'
StateProv = ' '
Country = 'CHN'
InLat = 22.75
InLong = 115
InTime = 8
InElev = 0
InWMO = 450040
/
&miscdata
Comments1 = 'This file was given to us by....'
SourceData = 'Original xyz data'
/
The “slash” (/) character terminating each block is very
important - omissions results in incorrect reading of
data.
Definitions File Details are shown in the following table.
You may leave out a field if you wish - the program will use
whatever default is applicable (or usable) from the data
format. All data formats accept this additional file. Only
Custom format currently uses the &datacontrol element. And
only Custom format input type uses the Data Elements, Format
and Conversion factors from the &wthdata element.
Note that strings in the “def” should be enclosed in single
quotes if there is more than one word in the string - if only
one word, quotes do not need to be used.
These fields are string variables. If Country is
not included, an attempt to use the State/Prov entry
may be used to determine country. Otherwise, these fields are
not validated and are used to create part of the “location”
header record in the EPW file. City can be up to 30 characters
in length; StateProv up to 15 characters; Country up to 10
characters (standard 3 character abbreviation preferred).
These fields are decimal equivalent for Latitude and
Longitude. The convention is North Latitude is positive; South
is negative. Likewise, East Longitude is positive; West
Longitude is negative. That is, if your latitude is N 30° 15’
(North 30 degrees, 15 minutes) then your input is +30.25.
This field is the decimal equivalent for the Time Zone
value. The convention is GMT +/-. That is, if your time zone
is “behind” GMT time by 6 hours, your input would be -6.
This field is the location elevation in meters. Range can
be from -300 to 6096. (These are the values from EnergyPlus -
there is no validation of these in the weather converter.)
This field is the WMO (World Meterological Organization)
number for the location. Though not validated per se, if found
in the “design conditions” auxiliary files, the Design Day
information can be generated.
When a list of files is being processed, one of the outputs
that results from the processing is a KML (Keyhole Markup
Language) file that can be used with Google Earth to pinpoint
the locations of the weather site. This field can be used to
set this URL for later output. The list file format also
includes a URL as its third (optional) parameter. If included,
this input would overwrite other URL designations.
You can always use this field and def file to “override”
the default input format type that depends on the extension of
your file (see Table [table:input-file-extensions-with-implied-data-types].
Input File Extensions with implied Data types). A complete set
of valid values for Input File types is shown in the following
table. Data Files are described more fully in the section
Source Weather Data Formats that occurs later in this
document.
This field can be used to specify multi-interval (per hour)
files. Without this field, the only formats that can have
multiple intervals per hour are the EPW and CSV file formats -
using the header record DataPeriods value for that field.
Fields
below only used in “Custom” format processing[LINK]
For custom files, you will need to indicate which data
elements are in which positions of the raw data file. The
fields must come from a standardized list of names see
following tables that include internal names (short and long -
as shown in Table 8) as well as the EnergyPlus CSV format
names (short and long - shown in Table 6)
plus some further elements that can be specified when the
standard data elements are not part of the raw data (as shown
in Table 7).
“Ignore” is used to skip a raw data field that is not
applicable to the weather converter formats. Note that
variables listed in the following table (in italics) are
allowed for flexibility - i.e. wetbulb temperature can be used
to determine relative humidity and/or dewpoint temperature.
The following three tables illustrate the names for data
elements.
Internal Data Element Names (directly applicable to
EPW)
Short Name
Long Name
Default EPW Units
Used by EnergyPlus
year
Year
-
n
month
Month
-
y
day
Day
-
y
hour
hour
-
y
minute
minute
-
n
datasource
datasource
-
n
drybulb
dry_bulb_temperature
C
y
dewpoint
dew_point_temperature
C
y
relhum
relative_humidity
%
y
atmos_pressure
atmospheric_pressure
Pa
y
exthorrad
extraterrestrial_horizontal_radiation
Wh/m2
n
extdirrad
extraterrestrial_direct_normal_radiation
Wh/m2
n
horirsky
horizontal_infrared_radiation_intensity_from_sky
Wh/m2
y
glohorrad
global_horizontal_radiation
Wh/m2
n
dirnorrad
direct_normal_radiation
Wh/m2
y
difhorrad
diffuse_horizontal_radiation
Wh/m2
y
glohorillum
global_horizontal_illuminance
lux
n
dirnorillum
direct_normal_illuminance
lux
n
difhorillum
diffuse_horizontal_illuminance
lux
n
zenlum
zenith_luminance
lux
n
winddir
wind_direction
degrees
y
windspd
wind_speed
m/2
y
totskycvr
total_sky_cover
tenths
n
opaqskycvr
opaque_sky_cover
tenths
n
visibility
visibility
km
n
ceiling_hgt
ceiling_height
m
n
presweathobs
present_weather_observation
-
y
presweathcodes
present_weather_codes
-
y
precip_wtr
precipitable_water
mm
n
aerosol_opt_depth
aerosol_optical_depth
thousandths
N
snowdepth
snow_depth
cm
Y
days_last_snow
days_since_last_snow
-
N
Albedo
albedo
-
N
liq_precip_depth
liquid_precip_depth
mm
Y
liq_precip_rate
liquid_precip_rate
Hour
N
The following table illustrates that the EnergyPlus CSV
header names can be used for data elements in DEF files, if
desired.
Often raw data files will not have the preceding elements
but similar elements that can be used to derive the values
used in the EPW files and in EnergyPlus. (For example, dew
point temperature and relative humidity are needed and can be
derived from dry builb temperature and a humidity indicating
element such as wet bulb temperature or humidity ratio). The
following table contains the data element names that can be
used in the Weather Converter program to derive other data
which will then be placed into the EPW data fields.
If you have direct horizontal radiation (and at least one
other solar element from global horizontal radiation or
diffuse horizontal radaition), this data element will be used
to derive the direct normal radiation.
If you wish, you can just put in the hour of the year for
each record. Note that if no date element is entered, then the
default is that the data is in hour of the year (including
possible number of records per hour).
Dates can be entered as month, day, and year. The units
field must be entered and should designate the format for the
date decoding. Date separator characters for this field are
entered in the DateSeparator item. Default date separator is
“/” and that is what is used in the table that shows the
allowable units:
There should be as many DataUnits entries as DataElement
entries. These are not generally used but may be used in the
future for automatic conversions. The exception to this is
“temperature” fields. Use “f” for Fahrenheit, “k” for Kelvin
temperatures. Note that the DataConversionFactor for this
field will be applied prior to conversion. (Many formats use
integer numbers to represent values that are in tenths, for
example.)
There should be as many DataConversionFactors entries as
DataElement entries. These factors are multiplicative factors
(i.e. the input value is multiplied by this factor) and can be
used to process input data into the values used in the EPW
weather files.
There should be as many entries (though some can be blank)
as DataElement entries. The values entered will override the
default “missing” values (from the EPW data dictionary) and,
whereas the defaults may be interpreted as a > = missing
value (i.e. > = 999), these values will be exact (i.e. =
-999.)
A single character can be used to specify the decimal
“point” character. Default is the US Standard “.”. With use of
DelimiterChar and this field, one can essentially use the
fields to specify European Standard Excel export formats.
If you are entering the aforementiond “date” Data Element
and your date separator is a character other than slash (“/”),
then you need to enter a single character so the program can
interpret your date entries.
Most of the items in this element are particularly
applicable to custom format input files. Currently, they are
only used in custom files, but may be more generally
applicable in future releases.
This is an integer number of records to read (typically
8760 for a full year). You might use this if your input file
has some information after the data records.
These fields tell the converter program what to do with
“missing” data. Missing data can be found in two forms:
totally not included in the DataElements or a missing value
(as defined in the EPW format). Valid values for these fields
are:
DEFAULT - use the default processing that the weather
converter already uses - starts off with a specific value and
updates if data is found.
CONSTANT - use a constant value to replace all missing
data
RANDOM - use a random number to generate the missing
data
An additional value for MissingOpaqueSkyCoverAction is:
If you don’t want to see extra warnings when input values
are greater than max values (default or as specified in
previous fields), use NO as the keyword. Use YES to make sure
you see the warnings. Default is YES.
In the following examples, every attempt has been made to
make sure that these work with the Weather Converter program.
However, we cannot foresee all possible combinations.
Caveat emptor - user beware.
Here’s an example where the delimiter between fields is a
semi-colon (;) and the decimal symbol character is a comma (,)
- typical of some non-USA regional settings:
Figure 4. DEF file for with non-standard field delimiter
and decimal symbol
Here’s an example of a file used to “enhance” a DOE-2 FMT
file:
&location
City = 'Kelburn'
StateProv = 'Wellington'
Country = 'NZL'
InWMO = 934360
InLat = -42.3333
InLong = 174.8
InElev = 8
InTime = 1
/
&wthdata
NumInHour = 1
InputFileType = 'FMT'
/
&miscdata
Comments1 = 'Standard Data Files for Computer Thermal Simulation of Solar Low Energy Non-residential Buildings; ven der Werff, Amor, and Donn 1990'
Comments2 = 'Full Actual year of dataSource data is TRY format converted to DOE-2 format;'
/
Figure 5. DEF file for DOE-2 FMT file
Here’s an example of a fixed format used for custom file
processing. Note that random sky cover is used, to facilitate
calculating Horizontal IR from Sky that is used in EnergyPlus.
Also, random wind direction is used because the data set does
not contain wind direction.
&location
City = 'Torino-Caselle'
StateProv = ' '
Country = 'ITA'
InWMO = 160590
InLat = 45.18333
InLong = 7.65
InElev = 282
InTime = 1
/
&wthdata
NumInHour = 1
InputFileType = 'CUSTOM'
InFormat = '(I2, I2, I2, F7.2, F7.2, F5.1, F5.1, F5.1)'
DataElements = Month,Day,Hour,DirNorRad,DifHorRad,DryBulb,Wind\_Speed,Relative\_Humidity
DataUnits = ,,,'kJ/M2','kJ/M2','C','m/s','%'
DataConversionFactors = 1,1,1,.2777778,.2777778,1,1,1
/
&miscdata
Comments1 = 'Italian Climate Data Set Gianni de Giorgio'
Comments2 = 'Period of record 1951-1970'
SourceData = 'IGDG Data Set'
/
&datacontrol
MissingOpaqueSkyCoverAction = RANDOM
MissingWindDirAction = RANDOM
/
Figure 6. DEF file for formatted custom file.
An example of a free format custom file. Here, there were
several lines of text after the numeric data at the end of the
file - thus we used the number of records to read parameter
rather than hand editing each input file.
Suppose you have a file that is “almost” TMY2 format. You
can easily specify a Def file to treat it as a custom file
rather than a TMY2 file (which, by standards, will have the
data filled).
Finally, an example of using an EPW file as a custom file
with a DEF format. Note that the specially formatted CSV files
from EnergyPlus can be automatically read in and this format
is provided as an extra bonus.
In “normal” file processing, conversion from the input data
elements to the EPW data elements is automatic. In “custom”
file processing, there is limited flexibility in this regard.
For example, the user may use “wet bulb” temperature in their
inputs - this will allow the weather converter to calculate
appropriate values for dew point temperature (if it is
missing) and/or relative humidity. Again, limited
calculations/derivations are done - should one input wet bulb
temperature along with dew point temperature and relative
humidity. Likewise, if only values for global horizontal
radiation and diffuse horizontal radiation are given, the
program will calculate a value for direct normal radiation
using commonly recognized relationships between these
values.
Custom
File Processing - Solar Radiation Value Calculation[LINK]
EnergyPlus only uses the solar radiation data for Direct
Normal and Diffuse Horizontal radation in its calculations.
But many data sources have only Global Horizontal (sometimes
called Total) or none of the solar radiation elements. When
global radiation is available, then a different model (Perez
Model) is used to split the global into direct normal and
diffuse horizontal values.
With any two of the solar components, it is reasonable to
use the simple relationship of Global, Diffuse and Direct,
such as:
In custom weather file processing does the following:
If you have two of the solar radiation components, then
you can easily compute the third
If you have global horizontal then Perez model is used
for the direct/diffuse components split.
If you have no solar data, then Zhang-Huang model is
used to estimate global horizontal, and Perez model is used to
split that into direct and diffuse components.
However, many data sources may not have any solar radiation
components. A study was undertaken to find an appropriate
solar model to fill in missing solar data for weather files.
The goal was to determine one or more possible solar models to
use in the weather conversion/creation process. One model
seemed better overall with the usual given data from the
sources than others. The model, termed Zhang-Huang, has been
used in a variety of locations and data creations, including
the upcoming IWEC2 data. The model uses a simplistic approach
of recent drybulb temperatures, cloud-cover, global solar
constant and solar position. This model is only used when all
solar values are missing from the incoming data. Results, of
course, can vary depending on locations.
For example, in Brisbane AUS, comparing the solar creation
with the original IWEC data looks very good:
Solar radiation comparison -
IWEC vs Weather Solar Model (Brisbane AUS) [fig:solar-radiation-comparison-iwec-vs-weather]
Of course, there are other locations that don’t compare
quite as well:
Comparison of IWEC vs Weather
program Solar Model (Singapore) [fig:comparison-of-iwec-vs-weather-program-solar]
Definitions File & Custom File Processing[LINK]
Description of “Def” input file[LINK]
Some of the data formats have inherent omissions (e.g. TMY does not have location data, BLAST ASCII does not have elevations). In order to overcome this limitation and to provide further flexibility, a definitions file (extension must be .def) is implemented. By naming this with the same “file name” as your input file (in the same folder), the weather converter will read the format and use that data, as appropriate, in the file conversions. The .def file uses Fortran “Namelist” input fields as shown in the example below. For flexibility, you can also define a “presets.def” file (such as when you have a list of files to process and the format or some portion is all the same between the group of files. The two def files (one named the same as the file name for the raw data and one named presets.def) will both be processed. Conflicts between the two will be shown in the .audit file. The set of namelist groups is:
&location - Location data
&miscdata - Comments to be applied to “COMMENT2” in the EPW file and “Source Data”
&wthdata - weather data specifications including file type, custom formats
&datacontrol - user specified control over “missing” data (Custom format only)
Note that the “Def” formats are entirely different from the usual IDF formats of EnergyPlus. No commas separate fields. No semicolon terminates the entry.
The “slash” (/) character terminating each block is very important - omissions results in incorrect reading of data.
Definitions File Details are shown in the following table. You may leave out a field if you wish - the program will use whatever default is applicable (or usable) from the data format. All data formats accept this additional file. Only Custom format currently uses the &datacontrol element. And only Custom format input type uses the Data Elements, Format and Conversion factors from the &wthdata element.
Note that strings in the “def” should be enclosed in single quotes if there is more than one word in the string - if only one word, quotes do not need to be used.
Expected Formats for &location[LINK]
Fields: City, StateProv, Country[LINK]
These fields are string variables. If Country is not included, an attempt to use the State/Prov entry may be used to determine country. Otherwise, these fields are not validated and are used to create part of the “location” header record in the EPW file. City can be up to 30 characters in length; StateProv up to 15 characters; Country up to 10 characters (standard 3 character abbreviation preferred).
Fields: InLat, InLong[LINK]
These fields are decimal equivalent for Latitude and Longitude. The convention is North Latitude is positive; South is negative. Likewise, East Longitude is positive; West Longitude is negative. That is, if your latitude is N 30° 15’ (North 30 degrees, 15 minutes) then your input is +30.25.
Field: InTime[LINK]
This field is the decimal equivalent for the Time Zone value. The convention is GMT +/-. That is, if your time zone is “behind” GMT time by 6 hours, your input would be -6.
Field: InElev[LINK]
This field is the location elevation in meters. Range can be from -300 to 6096. (These are the values from EnergyPlus - there is no validation of these in the weather converter.)
Field: InWMO[LINK]
This field is the WMO (World Meterological Organization) number for the location. Though not validated per se, if found in the “design conditions” auxiliary files, the Design Day information can be generated.
Expected Formats for &miscdata[LINK]
Fields: Comments1, Comments2[LINK]
These are strings. After concatenation, they become part of the comment header lines in the EPW headers. Up to 150 characters each is allowed.
Field: SourceData[LINK]
This string is applied to the “Source Data” field in the Location Header. Up to 60 characters is allowed.
Field: OutputURL[LINK]
When a list of files is being processed, one of the outputs that results from the processing is a KML (Keyhole Markup Language) file that can be used with Google Earth to pinpoint the locations of the weather site. This field can be used to set this URL for later output. The list file format also includes a URL as its third (optional) parameter. If included, this input would overwrite other URL designations.
Expected Formats for &wthdata[LINK]
Field: InputFileType[LINK]
You can always use this field and def file to “override” the default input format type that depends on the extension of your file (see Table [table:input-file-extensions-with-implied-data-types]. Input File Extensions with implied Data types). A complete set of valid values for Input File types is shown in the following table. Data Files are described more fully in the section Source Weather Data Formats that occurs later in this document.
Field: NumInHour[LINK]
This field can be used to specify multi-interval (per hour) files. Without this field, the only formats that can have multiple intervals per hour are the EPW and CSV file formats - using the header record DataPeriods value for that field.
Fields below only used in “Custom” format processing[LINK]
Field: DataElements[LINK]
For custom files, you will need to indicate which data elements are in which positions of the raw data file. The fields must come from a standardized list of names see following tables that include internal names (short and long - as shown in Table 8) as well as the EnergyPlus CSV format names (short and long - shown in Table 6) plus some further elements that can be specified when the standard data elements are not part of the raw data (as shown in Table 7). “Ignore” is used to skip a raw data field that is not applicable to the weather converter formats. Note that variables listed in the following table (in italics) are allowed for flexibility - i.e. wetbulb temperature can be used to determine relative humidity and/or dewpoint temperature. The following three tables illustrate the names for data elements.
The following table illustrates that the EnergyPlus CSV header names can be used for data elements in DEF files, if desired.
Custom Files - Auxiliary Data[LINK]
Often raw data files will not have the preceding elements but similar elements that can be used to derive the values used in the EPW files and in EnergyPlus. (For example, dew point temperature and relative humidity are needed and can be derived from dry builb temperature and a humidity indicating element such as wet bulb temperature or humidity ratio). The following table contains the data element names that can be used in the Weather Converter program to derive other data which will then be placed into the EPW data fields.
Explanation of these data elements follows:
Wetbulb (Wet Bulb Temperature)[LINK]
If you have the wet bulb temperature, this data element can be used to derive the dew point temperature and relative humidity.
HumRatio (Humidity Ratio)[LINK]
If you have the humidity ratio, this data element can be used to derive the dew point temperature and relative humidity.
Dirhorrad (Direct Horizontal Radiation)[LINK]
If you have direct horizontal radiation (and at least one other solar element from global horizontal radiation or diffuse horizontal radaition), this data element will be used to derive the direct normal radiation.
Interval[LINK]
If your “number of records per hour” is >1, then you can designate each interval of that hour with this field.
Hour_Of_Year[LINK]
If you wish, you can just put in the hour of the year for each record. Note that if no date element is entered, then the default is that the data is in hour of the year (including possible number of records per hour).
Time (or HH:MM)[LINK]
Time can be entered (rather than hour) and the units must be hh:mm; this is then decoded on each record to the appropriate hour.
Date[LINK]
Dates can be entered as month, day, and year. The units field must be entered and should designate the format for the date decoding. Date separator characters for this field are entered in the DateSeparator item. Default date separator is “/” and that is what is used in the table that shows the allowable units:
Field: DataUnits[LINK]
There should be as many DataUnits entries as DataElement entries. These are not generally used but may be used in the future for automatic conversions. The exception to this is “temperature” fields. Use “f” for Fahrenheit, “k” for Kelvin temperatures. Note that the DataConversionFactor for this field will be applied prior to conversion. (Many formats use integer numbers to represent values that are in tenths, for example.)
Field: DataConversionFactors[LINK]
There should be as many DataConversionFactors entries as DataElement entries. These factors are multiplicative factors (i.e. the input value is multiplied by this factor) and can be used to process input data into the values used in the EPW weather files.
Field: DataMissingValues[LINK]
There should be as many entries (though some can be blank) as DataElement entries. The values entered will override the default “missing” values (from the EPW data dictionary) and, whereas the defaults may be interpreted as a > = missing value (i.e. > = 999), these values will be exact (i.e. = -999.)
Field: InFormat[LINK]
The value in this field should be “delimited” if you are using a free format data file or specify a “Fortran style” format statement.
Field: DelimiterChar[LINK]
If you use a “delimited” format file, you need to specify a delimiter character. Only a single character may be specified.
Field: DecimalSymbolChar[LINK]
A single character can be used to specify the decimal “point” character. Default is the US Standard “.”. With use of DelimiterChar and this field, one can essentially use the fields to specify European Standard Excel export formats.
Field: DateSeparator[LINK]
If you are entering the aforementiond “date” Data Element and your date separator is a character other than slash (“/”), then you need to enter a single character so the program can interpret your date entries.
Expected Formats for &datacontrol[LINK]
Most of the items in this element are particularly applicable to custom format input files. Currently, they are only used in custom files, but may be more generally applicable in future releases.
Field: NumRecordsToSkip[LINK]
This is an integer number of records to skip during processing. You might use this if your input file has some information at the top of the file.
Field: MaxNumRecordsToRead[LINK]
This is an integer number of records to read (typically 8760 for a full year). You might use this if your input file has some information after the data records.
Fields: MissingDataAction, MissingWindDirAction, MissingOpaqueSkyCoverAction[LINK]
These fields tell the converter program what to do with “missing” data. Missing data can be found in two forms: totally not included in the DataElements or a missing value (as defined in the EPW format). Valid values for these fields are:
DEFAULT - use the default processing that the weather converter already uses - starts off with a specific value and updates if data is found.
CONSTANT - use a constant value to replace all missing data
RANDOM - use a random number to generate the missing data
An additional value for MissingOpaqueSkyCoverAction is:
Fields: MissingWindDirValue, MissingOpaqueSkyCoverValue[LINK]
The values specified in this field are used with the action fields previously mentioned.
Field: MaxWindSpeed[LINK]
The default maximum wind speed (40m/s) may not be enough for some locations - this allows the override capability.
Field: MaxDirectSolar, MaxDiffuseSolar, MaxIlluminanceValue[LINK]
Default maximum solar values may not be enough for some locations - this allows the override capability.
Field: GenerateSolarRadiationWarnings, GenerateIlluminanceWarnings[LINK]
If you don’t want to see extra warnings when input values are greater than max values (default or as specified in previous fields), use NO as the keyword. Use YES to make sure you see the warnings. Default is YES.
Def File Examples[LINK]
In the following examples, every attempt has been made to make sure that these work with the Weather Converter program. However, we cannot foresee all possible combinations. Caveat emptor - user beware.
Here’s an example where the delimiter between fields is a semi-colon (;) and the decimal symbol character is a comma (,) - typical of some non-USA regional settings:
Figure 4. DEF file for with non-standard field delimiter and decimal symbol
Here’s an example of a file used to “enhance” a DOE-2 FMT file:
Figure 5. DEF file for DOE-2 FMT file
Here’s an example of a fixed format used for custom file processing. Note that random sky cover is used, to facilitate calculating Horizontal IR from Sky that is used in EnergyPlus. Also, random wind direction is used because the data set does not contain wind direction.
Figure 6. DEF file for formatted custom file.
An example of a free format custom file. Here, there were several lines of text after the numeric data at the end of the file - thus we used the number of records to read parameter rather than hand editing each input file.
Figure 7. DEF File for delimited custom file.
Suppose you have a file that is “almost” TMY2 format. You can easily specify a Def file to treat it as a custom file rather than a TMY2 file (which, by standards, will have the data filled).
Figure 8. DEF File for almost TMY2 files.
Finally, an example of using an EPW file as a custom file with a DEF format. Note that the specially formatted CSV files from EnergyPlus can be automatically read in and this format is provided as an extra bonus.
Figure 9. DEF File for EPW files.
Custom File Processing[LINK]
In “normal” file processing, conversion from the input data elements to the EPW data elements is automatic. In “custom” file processing, there is limited flexibility in this regard. For example, the user may use “wet bulb” temperature in their inputs - this will allow the weather converter to calculate appropriate values for dew point temperature (if it is missing) and/or relative humidity. Again, limited calculations/derivations are done - should one input wet bulb temperature along with dew point temperature and relative humidity. Likewise, if only values for global horizontal radiation and diffuse horizontal radiation are given, the program will calculate a value for direct normal radiation using commonly recognized relationships between these values.
Custom File Processing - Solar Radiation Value Calculation[LINK]
EnergyPlus only uses the solar radiation data for Direct Normal and Diffuse Horizontal radation in its calculations. But many data sources have only Global Horizontal (sometimes called Total) or none of the solar radiation elements. When global radiation is available, then a different model (Perez Model) is used to split the global into direct normal and diffuse horizontal values.
With any two of the solar components, it is reasonable to use the simple relationship of Global, Diffuse and Direct, such as:
\[Global_{horizontalradiation} = Direct_{horizontalradiation}+Diffuse_{horizontalradiation}\]
Using known solar position (calculated internally by the Weather converter from latitude, longitude, date and hour), one has:
\[Direct_{normalradiation} = \frac{Direct_{horizontalradiation}}{\sin(Solar_{height}}\]
In custom weather file processing does the following:
If you have two of the solar radiation components, then you can easily compute the third
If you have global horizontal then Perez model is used for the direct/diffuse components split.
If you have no solar data, then Zhang-Huang model is used to estimate global horizontal, and Perez model is used to split that into direct and diffuse components.
However, many data sources may not have any solar radiation components. A study was undertaken to find an appropriate solar model to fill in missing solar data for weather files. The goal was to determine one or more possible solar models to use in the weather conversion/creation process. One model seemed better overall with the usual given data from the sources than others. The model, termed Zhang-Huang, has been used in a variety of locations and data creations, including the upcoming IWEC2 data. The model uses a simplistic approach of recent drybulb temperatures, cloud-cover, global solar constant and solar position. This model is only used when all solar values are missing from the incoming data. Results, of course, can vary depending on locations.
For example, in Brisbane AUS, comparing the solar creation with the original IWEC data looks very good:
Of course, there are other locations that don’t compare quite as well:
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.