The output of EnergyPlus performance curves (or tables) can
be modified as necessary to simulate hardware or controls that
cannot be accurately realized using a single performance
curve. This example describes a method for modifying the
capacity of a DX cooling coil via the DX coil objects Total
Cooling Capacity Function of Temperature performance curve
object.
A particular manufacturer controls the DX cooling coil such
that the capacity of the coil changes at 31°C outdoor air
dry-bulb temperature. The following EMS program logic will
calculate alternate inputs for cooling coil capacity and
over-write the existing performance curve results.
For this example, we will start with the equation for
cooling capacity of the DX coil object (ref.
Coil:Cooling:DX:SingleSpeed). From the engineering reference,
the equation used to calculate the cooling capacity is:
\[\text{TotCapTempModFac} = a +
b \left( T_{wb,i} \right) + c \left( T_{wb,i} \right) + d
\left( T_{c,i} \right) + e \left( T_{c,i} \right) + f \left(
T_{wb,i} \right)\left( T_{c,i} \right)\]
The first term (Twb,i) refers to the cooling coil inlet air
wet-bulb temperature and the second (Tc,i) refers to the
outdoor condenser inlet air dry-bulb temperature. Using the
EMS, a new total capacity as a function of temperature value
will be calculated and used during the simulation. The
Energyplus input objects for the cooling coil capacity curve,
the associated outdoor air mixer object, and the original
cooling capacity performance curve are shown here.
Coil:Cooling:DX:SingleSpeed,
Zone1PTHPDXCoolCoil, !- Name
CoolingCoilAvailSched, !- Availability Schedule Name
8750.0, !- Rated Total Cooling Capacity {W}
0.75, !- Rated Sensible Heat Ratio
3.0, !- Rated COP
0.5, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Zone1PTHPFanOutletNode, !- Air Inlet Node Name
Zone1PTHPDXCoolCoilOutletNode, !- Air Outlet Node Name
HPACCoolCapFT, !- Total Cooling Capacity f(Temperature) Curve Name
HPACCoolCapFFF, !- Total Cooling Capacity f(Flow Fraction) Curve Name
HPACEIRFT, !- Energy Input Ratio f(Temperature) Curve Name
HPACEIRFFF, !- Energy Input Ratio f(Flow Fraction) Curve Name
HPACPLFFPLR; !- Part Load Fraction Correlation Curve Name
OutdoorAir:Mixer,
Zone1PTHPOAMixer, !- Name
Zone1PTHPOAMixerOutletNode, !- Mixed Air Node Name
Zone1PTHPOAInNode, !- Outdoor Air Stream Node Name
Zone1PTHPExhNode, !- Relief Air Stream Node Name
Zone1PTHPAirInletNode; !- Return Air Stream Node Name
Curve:Biquadratic,
HPACCoolCapFT, !- Name
0.942587793, !- Coefficient1 Constant
0.009543347, !- Coefficient2 x
0.000683770, !- Coefficient3 x**2
-0.011042676, !- Coefficient4 y
0.000005249, !- Coefficient5 y**2
-0.000009720, !- Coefficient6 x*y
Note that the Total Cooling Capacity Function of
Temperature Curve Name is HPACCoolCapFT and the inlet air node
for this cooling coil is Zone1PTHPFanOutletNode. From the
mixer object, the outdoor air node name is Zone1PTHPOAInNode.
The existing cooling capacity performance curve name is
HPACCoolCapFT. These node or object names will be used in the
EMS program to point to the node or object as required.
The main input objects that implement this example for
over-riding a performance curve result are listed below. Note
that the node wet-bulb temperature at the inlet node of the
cooling coil is calculated both using the node wet-bulb
temperature and the psychrometric function to calculate a
wet-bulb temperature from dry-bulb temperature and humidity
ratio. The node wet-bulb temperature EMS sensor is left in
this example for the sole purpose of showing how to access
this node variable in a direct and indirect manner.
Referring to the cooling capacity equation above, a new
equation must be developed to represent this same performance
aspect of the cooling coil. Since, in this example, the
cooling capacity changes at 31°C, one of the coefficients is
modified and used in the IF block to modify the cooling
capacity above and below this outdoor air temperature limit.
Note also that the coefficients used in the EMS program are
all positive values and the negative sign is accounted for the
CurveInput equation. Also, the value of C2 was changed to a
negative value to represent the change in performance at 31°C.
To calculate the new performance curve results, EMS sensors
are placed at the cooling coil air inlet node to capture air
dry-bulb temperature and humidity ratio, and at the outdoor
air mixer outdoor air node inlet to capture outdoor air
dry-bulb temperature and pressure. The curve input equation is
identical to the equation shown above except that 1) the
equation coefficients are all positive and any negative
coefficients are accounted for in the equation itself, and 2)
alternate coefficients (actually only C2a in this example) are
used for the second equation. The results of this example show
a marked difference in the cooling capacity above 31°C.
EnergyManagementSystem:ProgramCallingManager,
EMSBasedCurveManager, !- Name
AfterPredictorBeforeHVACManagers, !- EnergyPlus Model Calling Point
CurveOverwriteMGR; !- Program Name 1
EnergyManagementSystem:Program,
CurveOverwriteMGR,
SET TTmp = CoilInletDBT,
SET WTmp = CoilInletW,
SET PTmp = Pressure,
SET MyWB = @TwbFnTdbWPb TTmp WTmp PTmp,
SET IVOne = CoilInletWBT,
SET IVOne = MyWB,
SET IVTwo = OAT,
SET IVThree = IVOne*IVTwo,
SET C1 = 0.942567793,
SET C2 = 0.009543347,
SET C2a = 0.009543347, !- -0.009543347
SET C3 = 0.00068377,
SET C4 = 0.011042676, !- -0.011042676
SET C5 = 0.000005249,
SET C6 = 0.000009720, !- -0.000009720
IF OAT < 31.0,
SET CurveInput = C1 + (C2*IVOne) + (C3*IVOne*IVone) - (C4*IVTwo) + (C5*IVTwo*IVTwo) - (C6*IVThree),
ELSE,
SET CurveInput = C1 - (C2a*IVOne) + (C3*IVOne*IVone) - (C4*IVTwo) + (C5*IVTwo*IVTwo) - (C6*IVThree),
ENDIF,
SET CurveOverwrite = CurveInput;
EnergyManagementSystem:Actuator,
CurveOverwrite, !- Name
HPACCOOLCAPFT, !- Actuated Component Unique Name
Curve, !- Actuated Component Type
Curve Result; !- Actuated Component Control Type
EnergyManagementSystem:Sensor,
ActualCurve, !- Name
HPACCOOLCAPFT, !- Output:Variable or Output:Meter Index Key Name
Performance Curve Output Value; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
CoilInletWBT, !- Name
Zone1PTHPFanOutletNode, !- Output:Variable or Output:Meter Index Key Name
System Node Wetbulb Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Pressure, !- Name
Zone1PTHPOAInNode, !- Output:Variable or Output:Meter Index Key Name
System Node Pressure ; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
CoilInletDBT, !- Name
Zone1PTHPFanOutletNode, !- Output:Variable or Output:Meter Index Key Name
System Node Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
CoilInletW, !- Name
Zone1PTHPFanOutletNode, !- Output:Variable or Output:Meter Index Key Name
System Node Humidity Ratio; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
OAT, !- Name
Zone1PTHPOAInNode, !- Output:Variable or Output:Meter Index Key Name
System Node Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:OutputVariable,
ERLCurveValue, ! Name
ActualCurve, ! EMS Variable Name
Averaged, ! Type of Data in Variable
ZoneTimeStep ; ! Update Frequency
EnergyManagementSystem:OutputVariable,
NewCurveValue, ! Name
CurveInput, ! EMS Variable Name
Averaged, ! Type of Data in Variable
ZoneTimeStep ; ! Update Frequency
Output:EnergyManagementSystem,
Verbose, !- Actuator Availability Dictionary Reporting
Verbose, !- Internal Variable Availability Dictionary Reporting
Verbose; !- EMS Runtime Language Debug Output Level
Output:Variable,
*,
ERLCurveValue,
Hourly;
Output:Variable, HPACCOOLCAPFT,
Performance Curve Output Value,Hourly;
Output:Variable, HPACCOOLCAPFT,
Performance Curve Input Variable 1 Value,Hourly;
Output:Variable, HPACCOOLCAPFT,
Performance Curve Input Variable 2 Value,Hourly;
Output:Variable, Zone1PTHPFanOutletNode,
System Node Wetbulb Temperature, Hourly;
Results of Performance Curve
Override [fig:results-of-performance-curve-override]
Example 11. Performance Curve Result Override[LINK]
Problem Statement[LINK]
The output of EnergyPlus performance curves (or tables) can be modified as necessary to simulate hardware or controls that cannot be accurately realized using a single performance curve. This example describes a method for modifying the capacity of a DX cooling coil via the DX coil objects Total Cooling Capacity Function of Temperature performance curve object.
A particular manufacturer controls the DX cooling coil such that the capacity of the coil changes at 31°C outdoor air dry-bulb temperature. The following EMS program logic will calculate alternate inputs for cooling coil capacity and over-write the existing performance curve results.
EMS Design Discussion[LINK]
For this example, we will start with the equation for cooling capacity of the DX coil object (ref. Coil:Cooling:DX:SingleSpeed). From the engineering reference, the equation used to calculate the cooling capacity is:
\[\text{TotCapTempModFac} = a + b \left( T_{wb,i} \right) + c \left( T_{wb,i} \right) + d \left( T_{c,i} \right) + e \left( T_{c,i} \right) + f \left( T_{wb,i} \right)\left( T_{c,i} \right)\]
The first term (Twb,i) refers to the cooling coil inlet air wet-bulb temperature and the second (Tc,i) refers to the outdoor condenser inlet air dry-bulb temperature. Using the EMS, a new total capacity as a function of temperature value will be calculated and used during the simulation. The Energyplus input objects for the cooling coil capacity curve, the associated outdoor air mixer object, and the original cooling capacity performance curve are shown here.
Note that the Total Cooling Capacity Function of Temperature Curve Name is HPACCoolCapFT and the inlet air node for this cooling coil is Zone1PTHPFanOutletNode. From the mixer object, the outdoor air node name is Zone1PTHPOAInNode. The existing cooling capacity performance curve name is HPACCoolCapFT. These node or object names will be used in the EMS program to point to the node or object as required.
EMS Input Objects[LINK]
The main input objects that implement this example for over-riding a performance curve result are listed below. Note that the node wet-bulb temperature at the inlet node of the cooling coil is calculated both using the node wet-bulb temperature and the psychrometric function to calculate a wet-bulb temperature from dry-bulb temperature and humidity ratio. The node wet-bulb temperature EMS sensor is left in this example for the sole purpose of showing how to access this node variable in a direct and indirect manner.
Referring to the cooling capacity equation above, a new equation must be developed to represent this same performance aspect of the cooling coil. Since, in this example, the cooling capacity changes at 31°C, one of the coefficients is modified and used in the IF block to modify the cooling capacity above and below this outdoor air temperature limit. Note also that the coefficients used in the EMS program are all positive values and the negative sign is accounted for the CurveInput equation. Also, the value of C2 was changed to a negative value to represent the change in performance at 31°C. To calculate the new performance curve results, EMS sensors are placed at the cooling coil air inlet node to capture air dry-bulb temperature and humidity ratio, and at the outdoor air mixer outdoor air node inlet to capture outdoor air dry-bulb temperature and pressure. The curve input equation is identical to the equation shown above except that 1) the equation coefficients are all positive and any negative coefficients are accounted for in the equation itself, and 2) alternate coefficients (actually only C2a in this example) are used for the second equation. The results of this example show a marked difference in the cooling capacity above 31°C.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.