The zone air mass flow conservation object, ZoneAirMassFlowConservation,
activates zone air mass flow balance calculations. This
feature is available only for controlled zones
(ZoneVAC:EquipmentConnections) which also have either a zone
mixing or infiltration object. The user may specify that zone
mixing, infiltration, or both can be overridden to balance the
zone air mass flows. The following rules apply:
If there are no zone mixing flows to adjacent zones,
then the zone air mass flow is balanced by setting the Zone
Mixing objects mass flow rate to zero.
If there are no zone exhaust fans defined and there are
no zone mixing objects specified, then a zone in an air loop
is always balanced.
Infiltration mass flow is included in the zone air mass
flow balance depending upon one of three options: none (all
infiltration is assumed to be self-balanced), all zones, or
only zones that serve as a source zone for zone mixing
objects.
The base infiltration mass flow rate (calculated based
on user inputs) may be controlled one of two ways for zone air
mass flow balance purposes: adjust the base infiltration up or
down as needed to balance the zone air mass flow, or assume
the base infiltration rate is self-balanced and add
infiltration if needed to balance the zone air mass
flow.
Optional user inputs can override the default return
air flow rate.
The zone air mass flow conservation equation always
includes: supply air flow rates, return air flow rates, and
zone exhaust fan flow rates. Zone
mixing and infiltration object flow rates may be included
depending upon the selected options. A particular zone can be
a source zone, receiving zone, or both depending on the number
of ZoneMixing
objects specified for that zone.
The return air flow rate is calculated one of several ways,
depending on whether ZoneAirMassFlowConservation
is active, if there is more than one return node, and if Zone
Return Air Node 1 Flow Rate Fraction Schedule Name or Zone
Return Air Node 1 Flow Rate Basis Node or NodeList
Name has been specified.
The total zone return flow calculation with no ZoneAirMassFlowConservation
is the sum of the zone inlets less the sum of the zone
exhausts adjusted for any balanced exhaust fan flow:
If ZoneAirMassFlowConservation
is active, then the total zone return air flow rate is \[{\dot m_{R}} = MAX\left( {0.0,\,{{\dot
m}_S} - [{{\dot m}_{EX,tot}} - {\dot m_{EXF,bal}}] + [{{\dot
m}_{XR}} - {{\dot m}_{XS}}]} \right)\]
The first return air node is treated differently to
maintain backward compatibility. If one or more Zone
Return Air Node 1 Flow Rate Basis Nodes are specified in the
ZoneHVAC:EquipmentConnections
object, then the mass flow rate for the first return air node
is:
If there are multiple return air nodes in the zone, then
each return air node is assumed to be paired with one supply
air inlet node. The initial flow rate at a given return air
node is based on the supply air inlet node for the same
airloop and the AirloopHVAC Design Return Air Flow Fraction of
Supply Air Flow:
Once the initial allocation to multiple return air nodes is
complete, the total return node flow is compared with the
expected total zone return air mass flow rate. If the sum of
the zone return node flows is greater than expected, then the
surplus return flow is:
Return nodes without an outdoor air inlet are not adjusted.
The remaining return node flow rates are reduced if necessary
to balance the zone air mass flow:
If the total (unbalanced) exhaust fan flow exceeds the
supply flow in a given zone, this exhaust flow can be made up
with outdoor air by any air loop serving the zone and the
return air in other zones on the same air loop(s) will be
reduced proportionally. First, the amount of excess exhaust
for all zones on a given air loop is totalled. If a zone with
excess exhuast is served by more than one air loop, the
exhaust is shared by each air loop in proportion to the
maximum available outdoor air for a given air loop.
Figure 1
illustrates the zone mass flow components for an air loop
system providing conditioned air to the two zones connected
with a zone mixing object. Since Zone
1 is a source zone only, infiltration object is defined for
zone 1 only. The zone mixing object air flow rate depends on
the user specified values and the zone air mass flow balance
requirements. When required the zone mixing object flow rate
is adjusted from the user specified value for balancing
purpose.
Illustration of zone air mass
flow balance components [fig:illustration-of-zone-air-mass-flow-balance]
An individual zone may be a source zone for multiple
receiving zones, and the same source zone may receive mixing
flows from multiple adjacent zones in an air loop. The source
and receiving mass flow rates of ZoneMixing
objects are calculated from user defined mixing flow rates at
the first HVAC iteration for each time step and adjusted in
subsequent iterations to balance the zone air mass flow. The
source zone mixing mass flow rate is calculated by tracking
the mass flow rates of ZoneMixing
objects connected to a zone and is given by:
Determine the zone return air mass flow rate as shown
above, then adjust the zone mixing mass flow rates based on
the current zone return air mass flow rate:
This updated receiving zone mixing air mass flow rate is
distributed to the mixing objects connected to the current
zone proportional to user specified design flow rate. A single
zone may be connected to more than one adjacent zone using
multiple ZoneMixing
objects. Thus, the mixing flow rate of each contributing
mixing objects defined in the current zone is updated as
follows:
There are three options for the treatement of infiltration
in the zone air mass balance: None, AddInfiltrationFlow, and
AdjustInfiltrationFlow. There are also two options to specify
which zones are included in the infiltration adjustments:
AllZones or MixingSourceZonesOnly.
If a zone is excluded from infiltration adjustments, then
the base infiltration rate specified by the Infiltration:*
object(s) in the zone is assumed to be self-balanced, and
infiltration is not included in the mass flow calculations for
that zone.
If a zone is included in the infiltration adjustment, the
infiltration air mass flow rate required to balance the zone
is determined as follows:
This infiltration air mass flow rate calculated is either
added to the base infiltration air flow, which is calculated
from user inputs, or overrides the base infiltration air flow
depending on user choice. For AddInfiltrationFlow, the
zoneinfiltration flow rate is:
For AdjustInfiltrationFlow, the zone infiltration flow rate
is:
\[{\dot m_{Inf}} = {\dot
m_{Inf-required}}\]
where,
\({\dot m_{Inf}}\) = zone
infiltration mass flow rate, (kg/s)
\({\dot m_{Inf-base}}\) =
base zone infiltration mass flow rate calculated from
Infiltration:* objects, (kg/s)
\({\dot
m_{Inf-required}}\) = required zone infiltration mass
flow rate to balance the zone, (kg/s)
There is an additional constraint to the return air mass
flow rate calculation. The sum of the return air mass flow
rates of zones in air loop must satisfy the air loop return
air mass flow balance. The above four sets of equations are
iterated for each zone in an air loop until the convergence
criterion is satisfied or until the maximum iteration limit is
exceeded.
The mass conservation calculations are performed in routine
CalcZoneMassBalance in the ZoneEquipmentManager module. The
latest ZoneMixing
and Infiltration object flow rates are communicated back to
the zone air heat balance terms. This is done by re-simulating
the simple flow objects as zone equipment during each HVAC
iteration. This requires calling the routine CalcAirFlowSimple
in SimZoneEquipment routine as zone equipment. Both of these
routines are also in the ZoneEquipmentManager module.
The zone mass conservation calculation convergence
criterion is based on the absolute difference of the zone
mixing objects mass flow rates between successive iteration.
If the difference is above tolerance limits of 0.00001 then
the HVAC Air loop is simulated again.
Zone Air Mass Flow Conservation[LINK]
Overiew[LINK]
The zone air mass flow conservation object, ZoneAirMassFlowConservation, activates zone air mass flow balance calculations. This feature is available only for controlled zones (ZoneVAC:EquipmentConnections) which also have either a zone mixing or infiltration object. The user may specify that zone mixing, infiltration, or both can be overridden to balance the zone air mass flows. The following rules apply:
If there are no zone mixing flows to adjacent zones, then the zone air mass flow is balanced by setting the Zone Mixing objects mass flow rate to zero.
If there are no zone exhaust fans defined and there are no zone mixing objects specified, then a zone in an air loop is always balanced.
Infiltration mass flow is included in the zone air mass flow balance depending upon one of three options: none (all infiltration is assumed to be self-balanced), all zones, or only zones that serve as a source zone for zone mixing objects.
The base infiltration mass flow rate (calculated based on user inputs) may be controlled one of two ways for zone air mass flow balance purposes: adjust the base infiltration up or down as needed to balance the zone air mass flow, or assume the base infiltration rate is self-balanced and add infiltration if needed to balance the zone air mass flow.
Optional user inputs can override the default return air flow rate.
The zone air mass flow conservation equation always includes: supply air flow rates, return air flow rates, and zone exhaust fan flow rates. Zone mixing and infiltration object flow rates may be included depending upon the selected options. A particular zone can be a source zone, receiving zone, or both depending on the number of ZoneMixing objects specified for that zone.
Return Air Flow Rate Calculations[LINK]
The return air flow rate is calculated one of several ways, depending on whether ZoneAirMassFlowConservation is active, if there is more than one return node, and if Zone Return Air Node 1 Flow Rate Fraction Schedule Name or Zone Return Air Node 1 Flow Rate Basis Node or NodeList Name has been specified.
Base Zone Total Return Flow[LINK]
The total zone return flow calculation with no ZoneAirMassFlowConservation is the sum of the zone inlets less the sum of the zone exhausts adjusted for any balanced exhaust fan flow:
\[{\dot m_{R}} = MAX\left( {0.0,\,{{\dot m}_S} - [{{\dot m}_{EX,tot}} - {\dot m_{EXF,bal}}]} \right)\]
If ZoneAirMassFlowConservation is active, then the total zone return air flow rate is \[{\dot m_{R}} = MAX\left( {0.0,\,{{\dot m}_S} - [{{\dot m}_{EX,tot}} - {\dot m_{EXF,bal}}] + [{{\dot m}_{XR}} - {{\dot m}_{XS}}]} \right)\]
Zone Return Air Node 1[LINK]
The first return air node is treated differently to maintain backward compatibility. If one or more Zone Return Air Node 1 Flow Rate Basis Nodes are specified in the ZoneHVAC:EquipmentConnections object, then the mass flow rate for the first return air node is:
\[{\dot m_{R,1}} = ReturnFlowSchedule*\sum\nolimits_j {{{\dot m}_{BasisNode,j}}}\]
If there is only one return node and no Zone Return Air Node 1 Flow Rate Basis Nodes, then:
\[{\dot m_{R,1}} = ReturnFlowSchedule*{\dot m_{R}}\]
Allocation to Multiple Return Nodes[LINK]
If there are multiple return air nodes in the zone, then each return air node is assumed to be paired with one supply air inlet node. The initial flow rate at a given return air node is based on the supply air inlet node for the same airloop and the AirloopHVAC Design Return Air Flow Fraction of Supply Air Flow:
\[{\dot m_{R,i}} = {DesignReturnFrac_i} * {\dot m_{S,i}}\]
For any air loop without an outdoor air inlet:
\[{\dot m_{R,i}} = {\dot m_{R,i}}\]
Overall Return Air Balance[LINK]
Once the initial allocation to multiple return air nodes is complete, the total return node flow is compared with the expected total zone return air mass flow rate. If the sum of the zone return node flows is greater than expected, then the surplus return flow is:
\[{\dot m_{R,surplus}} = \sum\nolimits_i {{{\dot m}_{R,i}}} - {\dot m_{R}}\]
Return nodes without an outdoor air inlet are not adjusted. The remaining return node flow rates are reduced if necessary to balance the zone air mass flow:
\[{\dot m_{R,i,}} = {\dot m_{R,i}} * \left( 1 - \frac{\dot m_{R,surplus}} {\sum\nolimits_{i,withOA} {{{\dot m}_{R,i}}}} \right)\]
Allocation of Excess Exhaust Flow[LINK]
If the total (unbalanced) exhaust fan flow exceeds the supply flow in a given zone, this exhaust flow can be made up with outdoor air by any air loop serving the zone and the return air in other zones on the same air loop(s) will be reduced proportionally. First, the amount of excess exhaust for all zones on a given air loop is totalled. If a zone with excess exhuast is served by more than one air loop, the exhaust is shared by each air loop in proportion to the maximum available outdoor air for a given air loop.
\[{\dot m_{ExcessExh,i}} = {\sum\nolimits_{j} {\frac{\dot m_{ExcessExh,j} * \dot m_{MaxOA,i}} {\dot m_{TotOA,j}} }}\]
The adjusted total return flow for each air loop is calculated by subtracting the excess exhaust from the total return flow calculated earlier.
\[\dot{m}_{AdjReturn,i} = max\left( 0.0, \dot{m}_{OrigReturn,i} - \dot{m}_{ExcessExh,i} \right)\]
Finally, the return flow for each return node on the air loop is proportioned to the adjusted total return flow.
\[{\dot m_{R,i}} = {\dot m_{R,i}} * \frac{\dot m_{AdjReturn,i}} {\dot m_{OrigReturn,i}}\]
where,
\({\dot m_{R}}\) = total zone return air mass flow rate, (kg/s)
\({\dot m_{R,i}}\) = return air node i mass flow rate, (kg/s)
\({\dot m_{S}}\) = total zone supply air mass flow rate, (kg/s)
\({\dot m_{S,i}}\) = zone supply air node i mass flow rate, (kg/s)
\({\dot m_{Basis Node,j}}\) = return air flow basis node j mass flow rate, (kg/s)
\({\dot m_{EX,tot}}\) = total zone exhaust air mass flow rate from all zone exhaust air nodes, (kg/s)
\({\dot m_{EXF,bal}}\) = balanced zone exhaust fan air mass flow rate, (kg/s)
\({\dot m_{EXF,tot}}\) = total (balanced+unbalanced) zone exhaust fan air mass flow rate, (kg/s)
\({\dot m_{XR}}\) = zone mixing mass flow rate as a receiving zone, (kg/s)
\({\dot m_{XS}}\) = zone mixing mass flow rate as a source zone, (kg/s)
\(ReturnFlowSchedule\) = optional Zone Return Air Node 1 Flow Rate Fraction Schedule value
\({DesignReturnFrac_i}\) = air loop Design Return Air Flow Fraction of Supply Air Flow for air loop i
\(\dot m_{ExcessExh,j}\) = excess exhaust flow for zone j
\(\dot m_{ExcessExh,i}\) = total excess exhaust flow for air loop i
\(\dot m_{MaxOA,i}\) = current max available outdoor air flow for air loop i
\(\dot m_{TotOA,j}\) = total max available outdoor air flow for air loops serving zone j
\(\dot m_{OrigReturn,i}\) = total original return flow for air loop i
\(\dot m_{AdjReturn,i}\) = total adjusted return flow for air loop i
Zone Mixing Flow Rate Calculations[LINK]
Figure 1 illustrates the zone mass flow components for an air loop system providing conditioned air to the two zones connected with a zone mixing object. Since Zone 1 is a source zone only, infiltration object is defined for zone 1 only. The zone mixing object air flow rate depends on the user specified values and the zone air mass flow balance requirements. When required the zone mixing object flow rate is adjusted from the user specified value for balancing purpose.
An individual zone may be a source zone for multiple receiving zones, and the same source zone may receive mixing flows from multiple adjacent zones in an air loop. The source and receiving mass flow rates of ZoneMixing objects are calculated from user defined mixing flow rates at the first HVAC iteration for each time step and adjusted in subsequent iterations to balance the zone air mass flow. The source zone mixing mass flow rate is calculated by tracking the mass flow rates of ZoneMixing objects connected to a zone and is given by:
\[{\dot m_{XS}} = \sum\nolimits_j {{{\dot m}_{XS,j}}}\]
Determine the zone return air mass flow rate as shown above, then adjust the zone mixing mass flow rates based on the current zone return air mass flow rate:
\[{\dot m_{XR,\,new}} = {\dot m_R} + {\dot m_{EX}} + {\dot m_{XS}} - {\dot m_S}\]
This updated receiving zone mixing air mass flow rate is distributed to the mixing objects connected to the current zone proportional to user specified design flow rate. A single zone may be connected to more than one adjacent zone using multiple ZoneMixing objects. Thus, the mixing flow rate of each contributing mixing objects defined in the current zone is updated as follows:
\[{\dot m_{XR,\,new,j}} = \left( {{{\dot m}_{XR,jDesign}}/{{\dot m}_{XR,Design}}} \right) \cdot {\dot m_{XR,\,new}}\]
Infiltration Flow Rate Adjustments[LINK]
There are three options for the treatement of infiltration in the zone air mass balance: None, AddInfiltrationFlow, and AdjustInfiltrationFlow. There are also two options to specify which zones are included in the infiltration adjustments: AllZones or MixingSourceZonesOnly.
If a zone is excluded from infiltration adjustments, then the base infiltration rate specified by the Infiltration:* object(s) in the zone is assumed to be self-balanced, and infiltration is not included in the mass flow calculations for that zone.
If a zone is included in the infiltration adjustment, the infiltration air mass flow rate required to balance the zone is determined as follows:
\[{\dot m_{Inf-required}} = MAX\left( {0.0,\,{{\dot m}_{XS}} + {{\dot m}_{EX}} + {{\dot m}_{R}} - {{\dot m}_S}} \right)\]
This infiltration air mass flow rate calculated is either added to the base infiltration air flow, which is calculated from user inputs, or overrides the base infiltration air flow depending on user choice. For AddInfiltrationFlow, the zoneinfiltration flow rate is:
\[{\dot m_{Inf}} = {\dot m_{Inf-base}} + {\dot m_{Inf-required}}\]
For AdjustInfiltrationFlow, the zone infiltration flow rate is:
\[{\dot m_{Inf}} = {\dot m_{Inf-required}}\]
where,
\({\dot m_{Inf}}\) = zone infiltration mass flow rate, (kg/s)
\({\dot m_{Inf-base}}\) = base zone infiltration mass flow rate calculated from Infiltration:* objects, (kg/s)
\({\dot m_{Inf-required}}\) = required zone infiltration mass flow rate to balance the zone, (kg/s)
There is an additional constraint to the return air mass flow rate calculation. The sum of the return air mass flow rates of zones in air loop must satisfy the air loop return air mass flow balance. The above four sets of equations are iterated for each zone in an air loop until the convergence criterion is satisfied or until the maximum iteration limit is exceeded.
The mass conservation calculations are performed in routine CalcZoneMassBalance in the ZoneEquipmentManager module. The latest ZoneMixing and Infiltration object flow rates are communicated back to the zone air heat balance terms. This is done by re-simulating the simple flow objects as zone equipment during each HVAC iteration. This requires calling the routine CalcAirFlowSimple in SimZoneEquipment routine as zone equipment. Both of these routines are also in the ZoneEquipmentManager module.
The zone mass conservation calculation convergence criterion is based on the absolute difference of the zone mixing objects mass flow rates between successive iteration. If the difference is above tolerance limits of 0.00001 then the HVAC Air loop is simulated again.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.