The heart of the heat balance method is the internal heat
balance involving the inside faces of the zone surfaces. This
heat balance is generally modeled with four coupled heat
transfer components: 1) conduction through the building
element, 2) convection to the air, 3) short wave radiation
absorption and reflectance and 4) longwave radiant
interchange. The incident short wave radiation is from the
solar radiation entering the zone through windows and
emittance from internal sources such as lights. The longwave
radiation interchange includes the absorption and emittance of
low temperature radiation sources, such as all other zone
surfaces, equipment, and people.
The heat balance on the inside face can be written as
follows:
Long-wave radiation exchange is balanced within an
enclosure which may be a single zone or a group of zones
connected by air boundaries (see Construction:AirBoundary)
using the GroupedZone radiant exchange method.
Throughout this section, "Zone" refers to either type of
enclosure.
There are two limiting cases for internal LW radiation
exchange that are easily modeled:
The zone air is completely transparent to LW
radiation.
The zone air completely absorbs LW radiation from the
surfaces within the zone.
The limiting case of completely absorbing air has been used
for load calculations and also in some energy analysis
calculations. This model is attractive because it can be
formulated simply using a combined radiation and convection
heat transfer coefficient from each surface to the zone air.
However, it oversimplifies the zone surface exchange problem,
and as a result, the heat balance formulation in EnergyPlus
treats air as completely transparent. This means that it does
not participate in the LW radiation exchange among the
surfaces in the zone. The model, which considers room air to
be completely transparent, is reasonable physically because of
the low water vapor concentrations and the short mean path
lengths. It also permits separating the radiant and
convective parts of the heat transfer at the surface, which is
an important attribute of the heat balance method.
EnergyPlus uses a grey interchange model for the longwave
radiation among zone surfaces. EnergyPlus offers two
algorithms for modeling long wave radiation: The “ScriptF”
method, and the “CarrollMRT” methods. Users can select between
these two algorithms using the “PerformancePrecisionTradeoffs”
object.
The “ScriptF” algorithm was developed by Hottel (Hottel and
Sarofim, Radiative Transfer, Chapter 3, McGraw Hill, 1967).
This procedure relies on a matrix of exchange coefficients
between pairs of surfaces that include all exchange paths
between the surfaces. In other words all reflections,
absorptions and re-emissions from other surfaces in the
enclosure are included in the exchange coefficient, which is
called ScriptF. The major assumptions are that all surface
radiation properties are grey and all radiation is diffuse.
Both assumptions are reasonable for building zone
interchange.
The ScriptF coefficients are developed by starting with
the traditional direct radiation view factors. In the case of
building rooms and zones, there are several complicating
factors in finding the direct view factors—the main one being
that the location of surfaces such as thermal mass
representing furniture and partitions are not known. The
other limitation is that the exact calculation of direct view
factors is computationally very intensive even if the
positions of all surfaces are known. Accordingly, EnergyPlus
uses a procedure to approximate the direct view factors. The
procedure has two steps:
1) Determine the total area of other surfaces “seen” by a
surface.
2) Approximate the direct view factor from surface 1 to
surface 2 as the ratio of the area of surface 2 to the total
area “seen” by surface 1.
The determination of the “seen” area has several
constraints:
No surface sees itself.
All surfaces see thermal mass surfaces.
No surface facing within 10 degrees of another surface
is seen by the other surface.
All surfaces see roofs, floors and ceilings (subject to
the preceding facing direction constraint).
Because the approximate view factors may not satisfy the
basic requirements of reciprocity (two surfaces should
exchange equal amounts of heat in each direction), and
completeness (every surface should have a direct view factor
sum of 1.0), EnergyPlus does a view factor fix operation
before they are used in the ScriptF determination. Normally
both of the requirements are satisfied, but in some special
situations they are not, and special rules are applied.
If a user includes less than four surfaces in a zone,
the enforcement of "completeness" is not strictly possible
because it is not possible to have a completed enclosure with
less than four surfaces. In this situation, reciprocity is
enforced initially and then view factors from each surface are
summed. When dealing with this few surfaces, the result of
using approximate view factors is that once reciprocity is
enforced that the largest surface in the zone will end up
having view factors that sum up to greater than unity. This is
not physically possible. So, to correct this and maintain
completeness for one surface, the entire view factor matrix is
divided by the largest summation of view factors for any
surface in the zone. By dividing the entire view factor matrix
by the same value, the reciprocity established by the standard
algorithm is maintained and completeness for one surface is
established. All of the other surfaces will not have view
factors that sum up to unity and thus will not satisfy
completeness. However, these other surfaces will not have view
factors that sum up to greater than unity thus avoiding a
physically impossible situation.
If the area of one surface in a zone is greater than
the sum of the areas of all other surfaces, reciprocity only
is enforced, but sometimes, for very large surfaces, that
enforcement becomes impossible, and the view factors are
modified so that only the large surface is seen by very small
surfaces.
Warning messages are produced for both of these cases, and
the results should be examined very carefully to ascertain
that they are reasonable. The suggested action for the
second case (the extra-large surface) is to divide the large
surface into several smaller surfaces; then the enclosure will
be treated as normal.
Once the ScriptF coefficients are determined, the longwave
radiant exchange is calculated for each surface using:
The Carroll method is an approximation of gray-body
long-wave radiation exchange within an enclosure that
simplifies the surface-to-surface radiation exchange by using
a single, mean radiant temperature node, \(Tr\), that acts as a
clearinghouse for the radiation heat exchange between
surfaces. Instead of solving a dense-matrix, linear algebra
problem, the mean radiant temperature can be calculated using
a single equation, and subsequently used to determine the net
long-wave radiation to/from each surface. Unlike the \(O(n^2)\) complexity of the
current dense-matrix solution, this approach has linear
complexity.
The mean radiant temperature is calculated using three
steps:
Calculation of the mean radiant temperature “view
factor”, \(Fi\). These view
factors represent each surface’s “view” to the mean radiant
temperature node as though all surfaces were part of a
spherical enclosure (i.e., they all have equal view of the
node regardless of their orientation to each other). \(Fi\) is calculated as:
Because of the circular reference in this equation, the
collection of all “view factors” must be solved iteratively,
but only once per simulation as surface areas do not change
throughout. This converges for realistic enclosures but won’t
necessarily converge for “enclosures” having only two or three
surfaces, particularly if there are large area
disparities.
Calculating the gray-body radiation resistance, \(F'i\). This calculation must
be computed every time surface emissivity changes. \(F'i\) is calculated as:
Once the mean radiant temperature is known, the net
radiation heat transfer for each surface can be calculated
as:
\[q=F'_i A_i
(T_r^4-T_i^4)\]
Carroll, J. A., 1980, “An ‘MRT Method’ of Computing Radiant
Energy Exchange in Rooms,” Proceedings of the Second Systems
Simulation and Economic Analysis Conference, San Diego,
CA.
Carroll, J. A., 1980a, “An MRT method of computing radiant
energy exchange in rooms,” Proceedings of the 2nd Systems
Simulation and Economic Analysis Conference, San Diego,
CA.
Carroll, J. A., 1981, “A Comparison of Radiant Interchange
Algorithms,” Proceedings of the 3rd Annual Systems Simulation
and Economics Analysis/Solar Heating and Cooling Operational
Results Conference, Reno. Solar Engineering, Proceedings of
the ASME Solar division.
Furniture in a zone has the effect of increasing the amount
of surface area that can participate in the radiation and
convection heat exchanges. It also adds participating thermal
mass to the zone. These two changes both affect the response
to temperature changes in the zone and also affect the heat
extraction characteristics.
The proper modeling of furniture is an area that needs
further research, but the heat balance formulation allows the
effect to be modeled in a realistic manner by including the
furniture surface area and thermal mass in the heat exchange
process.
The traditional model for this source is to define a
radiative/convective split for the heat introduced into a zone
from equipment. The radiative part is then distributed over
the surfaces within the zone in some prescribed manner. This,
of course, is not a completely realistic model, and it departs
from the heat balance principles. However, it is virtually
impossible to treat this source in any more detail since the
alternative would require knowledge of the placement and
surface temperatures of all equipment.
Transmitted solar radiation is also distributed over the
surfaces in the zone in a prescribed manner. It would be
possible to calculate the actual position of beam solar
radiation, but that would involve partial surface irradiation,
which is inconsistent with the rest of the zone model that
assumes uniform conditions over an entire surface. The
current procedures incorporate a set of prescribed
distributions. Since the heat balance approach can deal with
any distribution function, it is possible to change the
distribution function if it seems appropriate.
The convection flux is calculated using the heat transfer
coefficients as follows:
\[{q''_{conv}} =
{h_c}({T_s} - {T_a})\]
The inside convection coefficients (h\(_{c}\)) can be calculated
using one of many different models. Currently the
implementation uses coefficients based on correlations for
natural, mixed, and forced convection.
This contribution to the inside surface heat balance is the
wall conduction term, \({q''_{ki}}\) shown in
Equation [eq:InsideFaceHeatBalanceEquation].
This represents the heat transfer to the inside face of the
building element. Again, a CTF formulation is used to
determine this heat flux.
There are many different modeling options available in
EnergyPlus for inside convection coefficients, h\(_{c}\). There are four
different settings to direct how EnergyPlus managers select
h\(_{c}\) models
during a simulation. There are numerous individual model
equations for h\(_{c}\) in EnergyPlus to
cover different situations that arise from surface
orientations, room airflow conditions, and heat flow
direction. Additionally, in many cases multiple researchers
have developed competing models for the same situations that
differ and there is no way to declare one is better than
another. An overall default for the simulation is selected in
the “SurfaceConvectionAlgorithm:Inside”
object and can be overridden by selecting a different option
in a zone description. These models are explained in the
following sections. In addition to the correlation choices
described below, it is also possible to override the
convection coefficients on the inside of any surface by using
the “SurfaceProperty:ConvectionCoefficients”
object in the input file to set the convection coefficient
value on the inside of any surface. The values can be
specified directly or with schedules. Specific details are
given in the Input Output Reference document.
Beausoleil-Morrison (2000, 2002) developed a methodology
for dynamically managing the selection of h\(_{c}\) equations called
adaptive convection algorithm. The algorithm is used
to select among the available h\(_{c}\) equations for the one
that is most appropriate for a given surface at a given time.
As Beausoleil-Morrison notes, the adaptive convection
algorithm is intended to be expanded and altered to reflect
different classification schemes and/or new h\(_{c}\) equations. The
implementation in EnergyPlus has been modified from the
original in the following ways:
An input mechanism is provided (see the
SurfaceConvectionAlgorithm:Inside:AdapativeModelSelections
object) so that the user can customize the specific selections
of h\(_{c}\)
equations that are applied for different flow regimes and
surface orientations. The changes apply in a general way to
the entire model (but can be overridden by setting surface
properties).
To avoid requiring additional user input on the
position of ZoneHVAC-type equipment within a zone, there is no
distinction between zones that have convective zone heater
equipment located underneath the windows and those that have
convective heaters located away from the windows. This
applies to the air flow regime associated with convective zone
heaters. Using Beausoleil-Morrison’s terminology, regimes B1
and B2 are combined into just one B regime.
To avoid requiring additional user input on the
position of ZoneHVAC-type equipment within a zone, there is no
distinction between surfaces that are directly blown on the
fan and those that are away from the fan for the air flow
regime associated with mechanical circulation from a zone fan
(ZoneHVAC type equipment).
The correlation for horizontal free jet developed by
Fisher (1995) is not used. Ceiling diffuser models are used
for all mechanical circulation from central air system. This
decision was made for two reasons: (1) to avoid requiring
additional user input on the position of, and momentum
generated by, air terminal units, and (2) because Fisher
(1995) found that the Coanda effect is so significant that in
practice a free horizontal jet is difficult to maintain and
mechanical-driven room airflows generally attach to surfaces
and tend to match the flow regime of a ceiling diffuser much
more often than a free jet.
EnergyPlus supports arbitrary geometry so surfaces can
be tilted with respect to vertical or horizontal.
Beausoleil-Morrison’s adaptive convection algorithm was
originally structured to use h\(_{c}\) equations that have
no functional dependence on surface tilt angle. However,
tilted surfaces do perform differently than vertical or
horizontal surface when buoyancy forces are significant.
Therefore, the EnergyPlus implementation expands the structure
of the algorithm to include additional categories for tilted
surfaces. The h\(_{c}\) equations developed
by Walton (1983) are selected as the defaults for tilted
surfaces because they have a functional dependence on tilt
angle.
Fohanno and Polidari (2006) produced a new h\(_{c}\) equation for vertical
walls inside buildings with a simple buoyancy flow regime.
They used a theoretical approach based on integral formalism
and uniform heat flux (rather than uniform temperature) that
covers both laminar and turbulent flow situations. In
EnergyPlus, this model is selected as the default in place of
the model by Alamdari and Hammond (1983) for vertical
walls.
Karadag (2009) produced a new h\(_{c}\) equation for ceiling
surfaces that are actively chilled. He used computation fluid
dynamics and various sized rooms and temperature conditions.
In EnergyPlus, this model is selected as the default for
surfaces that have active, in-ceiling cooling (in place of the
model by Alamdari and Hammond (1983) for unstable
ceilings).
International Standard Organization (ISO) completed
Standard 15099-2003 which includes h\(_{c}\) equations for the
inside face of windows. EnergyPlus strives to adhere to
formal modeling Standards where possible. Therefore the
implementation includes a larger structure for the adaptive
algorithm that includes additional categories for windows in
all flow regimes and ISO 15099-2003 models are used as the
default for windows in natural convection flow regimes. The
ISO 15099 model applies to various tilt angles.
Goldstein and Novosalec (2010) produced new h\(_{c}\) equations for forced
air situations with ceiling slot diffusers along perimeters
with significant glazing fractions. They used experiments
with full-sized test room. These new equations are selected
as the default for windows, ceilings and floors when there is
an active central air system.
Interior mass surfaces are assigned the h\(_{c}\) equation that would
apply (stable or unstable) to a horizontal, upward facing
surface for each flow regime.
The algorithm switches between forced, mixed, and
natural flow regimes by calculating the Richardson number, Ri
= Gr/Re^2, for the zone. Large values of Ri indicate buoyancy
dominates, while small values indicate forced flows dominate.
To distinguish between opposing Zone
unit type equipment (with fans) are assumed to force air up
walls, and central air type equipment (with diffusers) are
assumed to force air down walls.
The adaptive convection algorithm implemented in EnergyPlus
for the inside face has a total of 45 different categories for
surfaces and 29 different options for h\(_{c}\) equation selections.
The following table summarizes the categories and the default
assignments for h\(_{c}\) equations. The
individual h\(_{c}\)
equations are documented below.
Inside Convection Categories and
Assignments
#
Zone Air Flow Regime
IB-M’s #
Surface orientation and heat
flow direction
Keywords for Applicable Model
Equation Sources
1
Vertical Walls
FohannoPolidoriVerticalWall*
AlamdariHammondVerticalWall
ASHRAEVerticalWall
2
Stable Horizontal
AlamdariHammondStableHorizontal*
WaltonStableHorizontalOrTilt
3
Simple Buoyancy
A3
Unstable Horizontal
AlamdariHammondUnstableHorizontal*
WaltonUnstableHorizontalOrTilt
4
Stable Tilted
WaltonStableHorizontalOrTilt*
5
Unstable Tilted
WaltonUnstableHorizontalOrTilt*
6
Windows
ISO15099Windows*
7
Vertical Walls
KhalifaEq3WallAwayFromHeat*
FohannoPolidoriVerticalWall
AlamdariHammondVerticalWall
ASHRAEVerticalWall
8
Stable Horizontal
AlamdariHammondStableHorizontal*
WaltonStableHorizontalOrTilt
9
In-floor Heating or In-ceiling
Cooling
A1
Unstable Horizontal
KhalifaEq4CeilingAwayFromHeat*
AlamdariHammondUnstableHorizontal
WaltonUnstableHorizontalOrTilt
10
Heated Floor
AwbiHattonHeatedFloor*
WaltonUnstableHorizontalOrTilt
AlamdariHammondUnstableHorizontal
11
Chilled Ceiling
KaradagChilledCeiling*
WaltonUnstableHorizontalOrTilt
12
Stable Tilted
WaltonStableHorizontalOrTilt*
13
Unstable Tilted
WaltonUnstableHorizontalOrTilt*
14
Windows
ISO15099Windows*
15
Vertical Walls (non-heated)
KhalifaEq6NonHeatedWalls*
FohannoPolidoriVerticalWall
ASHRAEVerticalWall
16
Heated Wall
AwbiHattonHeatedWall*
17
Wall Panel Heating
A2
Stable Horizontal
AlamdariHammondStableHorizontal*
WaltonStableHorizontalOrTilt
18
Unstable Horizontal
KhalifaEq7Ceiling*
AlamdariHammondUnstableHorizontal
WaltonUnstableHorizontalOrTilt
19
Stable Tilted
WaltonStableHorizontalOrTilt*
20
Unstable Tilted
WaltonUnstableHorizontalOrTilt*
21
Windows
ISO15099Windows*
22
Vertical Walls not near
heater
FohannoPolidoriVerticalWall*
KhalifaEq6NonHeatedWalls
KhalifaEq3WallAwayFromHeat
AlamdariHammondVerticalWall
ASHRAEVerticalWall
23
Vertical Walls near heater
KhalifaEq5WallNearHeat*
24
Convective Zone Heater
B
Stable Horizontal
AlamdariHammondStableHorizontal*
WaltonStableHorizontalOrTilt
25
Unstable Horizontal
KhalifaEq7Ceiling*
KhalifaEq4CeilingAwayFromHeat
WaltonUnstableHorizontalOrTilt
26
Stable Tilted
WaltonStableHorizontalOrTilt*
27
Unstable Tilted
WaltonUnstableHorizontalOrTilt*
28
Windows
ISO15099Windows*
29
Walls
GoldsteinNovoselacCeilingDiffuserWalls*
FisherPedersenCeilingDiffuserWalls
30
Ceiling
FisherPedersenCeilingDiffuserCeiling*
31
Mechanical Central Air
Diffuser
C
Floor
GoldsteinNovoselacCeilingDiffuserFloor*
FisherPedersenCeilingDiffuserFloor
32
Windows
GoldsteinNovoselacCeilingDiffuserWindow*
ISO15099Windows
33
Walls
KhalifaEq3WallAwayFromHeat
*
34
Stable Horizontal
AlamdariHammondStableHorizontal*
WaltonStableHorizontalOrTilt
35
Mechanical Zone Fan
Circulation
D
Unstable Horizontal
KhalifaEq4CeilingAwayFromHeat*
WaltonUnstableHorizontalOrTilt
36
Stable Tilted
WaltonStableHorizontalOrTilt*
37
Unstable Tilted
WaltonUnstableHorizontalOrTilt*
38
Windows
GoldsteinNovoselacCeilingDiffuserWindow*
ISO15099Windows
39
Assisting Flow Walls
BeausoleilMorrisonMixedAssistedWall*
40
Opposing Flow Walls
BeausoleilMorrisonMixedOpposingWall*
41
Stable Floor
BeausoleilMorrisonMixedStableFloor*
42
Mixed
E
Unstable Floor
BeausoleilMorrisonMixedUnstableFloor*
43
Stable Ceiling
BeausoleilMorrisonMixedStableCeiling*
44
Unstable Ceiling
BeausoleilMorrisonMixedUnstableCeiling*
45
Windows
GoldsteinNovoselacCeilingDiffuserWindow*
ISO15099Windows
*Indicates the default selection for h\(_{c}\) model equation.
The adaptive convection algorithm is based on classifying
surfaces by flow regime and orientation so that the correct
h\(_{c}\) equation
can be chosen at a particular point in time during the
simulation. The classification depends on user input with
some aspects processed only once at the beginning and others
during each timestep. There are also various parameters or
inputs to the h\(_{c}\) equations that need
static or dynamic processing.
For each surface, it and the zone it is attached to are
processed for the following static characteristics.
Characteristic height for convection is taken as the
zone height.
Surfaces listed as receiving heat from Zone
HVAC equipment with radiative models are considered “near” the
heater.
Zones are examined for low temperature radiant
systems. The surfaces that contain the active elements are
examined and the zone characterized to know if it has in-floor
heating, in-ceiling cooling, or in-wall heating.
A hydraulic diameter is calculated for horizontal
surfaces for the entire zone.
and calculating various parameters needed by h\(_{c}\) equations. Selecting
flow regime is done in the following manner. For each
surface, we examine the zone on the inside face for the
following:
HVAC system type
HVAC operating status
HVAC system ACH
During initial zone and system sizing calculations, HVAC
system characteristics are not known yet, so the flow regime
is selected assuming an uncontrolled zone. During simulations,
including HVAC sizing simulations, the HVAC system
characteristics are used.
Unstable refers to the direction of heat flow and the
associated buoyancy relative to the surfaces. Unstable is when
the natural tendency is to enhance flow in the sense that
rising warmer air, or falling cooler air, is free to move away
from the surface. This is usually bound at a minimum of .1 in
EnergyPlus. This is a component of the TARP overall algorithm
described below.
Stable refers to the direction of heat flow and the
associated buoyancy relative to the surfaces. Stable is when
the natural tendency is to retard flow in the sense that
rising warmer air, or falling cooler air, is driven against
the surface. This is usually bound at a minimum of .1 in
EnergyPlus. This is a component of the TARP overall algorithm
described below.
H is the characteristic height for the
surface. In EnergyPlus this is the zone’s ceiling height
(which could be larger than the height of an individual
surface when wall are subdivided into more than one
surface).
Khalifa (1989) conducted experiments with test chambers and
developed correlations for certain types of surfaces. One of
them, identified as “Equation 3” in original reference, is for
convectively heated zones and applies to the inside surfaces
of walls away from the heat source:
Khalifa (1989) conducted experiments with test chambers and
developed correlations for certain types of surfaces. One of
them, identified as “Equation 4” in original reference, is for
convectively heated zones and applies to the inside surfaces
of ceilings away from the heat source:
Khalifa (1989) conducted experiments with test chambers and
developed correlations for certain types of surfaces. One of
them, identified as “Equation 5” in original reference, is for
convectively heated zones and applies to the inside surfaces
of walls near the heat source:
Khalifa (1989) conducted experiments with test chambers and
developed correlations for certain types of surfaces. One of
them, identified as “Equation 6” in original reference, is for
heated zones and applies to the inside surfaces of walls that
are not heated:
Khalifa (1989) conducted experiments with test chambers and
developed correlations for certain types of surfaces. One of
them, identified as “Equation 7” in original reference, is for
heated zones and applies to the inside surfaces of
ceilings:
Awbi and Hatton (1999) conducted laboratory measurements
using environmental chambers and developed the following
correlation for floor surfaces that are being actively
heated.
\({D_h} =
\frac{{4A}}{P}\), hydraulic diameter of horizontal
surface, A is area (m\(^{2}\)) and P is the
perimeter (m) of the entire zone (all of the adjacent floor
surfaces if more than one in the zone).
\({D_h} =
\frac{{4A}}{P}\), hydraulic diameter of wall surface,
A is area (m\(^{2}\)) and P is the
perimeter (m) of the entire wall (all of the adjacent wall
surfaces if more than one along the wall).
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for walls where the flow driving
forces from mechanical forces are augmented by the driving
forces from buoyancy.
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for walls where the flow driving
forces from mechanical forces are opposed by the driving
forces from buoyancy.
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for floors where the flow driving
forces include both mechanical forces and thermally stable
buoyancy.
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for floors where the flow driving
forces include both mechanical forces and thermally unstable
buoyancy.
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for ceilings where the flow driving
forces include both mechanical forces and thermally Stable
buoyancy.
Beausoleil-Morrison (2000) used blending techniques to
combine correlations originally developed by Alamdari and
Hammond (1983) and Fisher and Pedersen (1997) to create the
following correlation is for ceilings where the flow driving
forces include both mechanical forces and thermally unstable
buoyancy.
ISO Standard 15099-2003 includes the equations for
h\(_{c}\) for
room-side of windows and surfaces with any tilt angle and heat
flow direction. The ISO 15099 correlation is for still room
air angle and is determined in terms of the Nusselt number,
\(Nu\) , where
\[{h_i} = Nu\left(
{\frac{\lambda }{H}} \right)\]
where,
\(\lambda\) is the
thermal conductivity of air, and
\(H\) is the height of
the window.
The Rayleigh number based on height, \(R{a_H}\) , is calculated
using:
There are four cases for the Nusselt correlation that vary
by the tilt angle in degrees, \(\gamma\) , and are based on
heating conditions. For cooling conditions (where \({T_{surf,i}} > {T_{air}}\) )
the tilt angle is complemented so that \(\gamma = 180 - \gamma\)
The material properties are evaluated at the mean film
temperature. Standard EnergyPlus psychrometric functions are
used for \(\rho\) and \({c_p}\) . Thermal conductivity
is calculated using:
This correlation depends on the surface temperature of the
room-side glazing surface and is therefore included inside the
window heat balance iteration loop.
Goldstein and Novoselac (2010) used laboratory chamber
measurements to develop convection correlations for perimeter
zones with highly glazed spaces served by overhead
slot-diffuser-based air systems. The following are for bare
windows in such spaces.
Goldstein and Novoselac (2010) used laboratory chamber
measurements to develop convection correlations for perimeter
zones with highly glazed spaces served by overhead
slot-diffuser-based air systems. The following are for
exterior walls in such spaces.
Goldstein and Novoselac (2010) used laboratory chamber
measurements to develop convection correlations for perimeter
zones with highly glazed spaces served by overhead
slot-diffuser-based air systems. The following is for floors
in such spaces.
The comprehensive natural convection model, accessed using
the keyword “TARP,” correlates the convective heat transfer
coefficient to the surface orientation and the difference
between the surface and zone air temperatures (where DT =
Surface Temperature - Air Temperature). The algorithm is
taken directly from Walton (1983). Walton derived his
algorithm from ASHRAE literature which can now be found for
example in the ASHRAE Handbook (HoF 2001), Table 5 on p. 3.12,
which gives equations for natural convection heat transfer
coefficients in the turbulent range for large, vertical plates
and for large, horizontal plates facing upward when heated (or
downward when cooled). A note in the text also gives an
approximation for large, horizontal plates facing downward
when heated (or upward when cooled) recommending that it
should be half of the facing upward value. Walton adds a
curve fit as a function of the cosine of the tilt angle to
provide intermediate values between vertical and horizontal.
The curve fit values at the extremes match the ASHRAE values
very well.
For no temperature difference OR a vertical surface the
following correlation is used:
The simple convection model uses constant coefficients for
different heat transfer configurations, using the same
criteria as the detailed model to determine reduced and
enhanced convection. The coefficients are also taken directly
from Walton (1983). Walton derived his coefficients from the
surface conductances for e = 0.90 found in the ASHRAE Handbook
(1985) in the table found on p. 23.2. The radiative heat
transfer component was estimated at 1.02 * 0.9 = 0.918
BTU/h-ft2-F and then subtracted off. Finally the coefficients
were converted to SI units to yield the values below.
For a vertical surface:
\[{\rm{h = 3}}{\rm{.076}}\]
For a horizontal surface with reduced convection:
\[{\rm{h = 0}}{\rm{.948}}\]
For a horizontal surface with enhanced convection:
The ceiling diffuser algorithm is based on empirical
correlations developed by Fisher and Pedersen (1997). The
correlation was reformulated to use the room outlet
temperature as the reference temperature. The correlations
are shown below.
For Floors:
\[h = 3.873 + 0.082 *
AC{H^{0.98}}\]
(93)
The correlation for floors is illustrated in Figure 2.
Ceiling Diffuser Correlation
for Floors [fig:ceiling-diffuser-correlation-for-floors]
For ceilings:
\[h = 2.234 + 4.099 *
AC{H^{0.503}}\]
The correlation for ceilings is illustrated in Figure 3.
Ceiling Diffuser Correlation
for Ceilings [fig:ceiling-diffuser-correlation-for-ceilings]
For Walls:
\[h = 1.208 + 1.012 *
AC{H^{0.604}}\]
The correlation for walls is illustrated in Figure 4.
Ceiling Diffuser Correlation
for Walls [fig:ceiling-diffuser-correlation-for-walls]
It should be noted that the conditions under which the
correlations were developed included ACH values down to around
3.0. However, extrapolation of the data down to ACH=1.0 is
reasonable and so within EnergyPlus, for ACH values of 1.0 or
greater, the ceiling diffuser correlations as shown above are
used. Below ACH values of 0.5, the natural convection
algorithm is used. Between ACH values of 0.5 and 1.0, there is
a linear interpolation between the two models to avoid any
discontinuities in the convection coefficient calculated.
The Trombe wall algorithm is used to model convection in a
“Trombe wall zone”, i.e. the air space between the storage
wall surface and the exterior glazing. (See the later
sections on Passive and Active Trombe Walls below for more
information about Trombe walls.) The algorithm is identical
to the convection model (based on ISO 15099) used in Window5
for convection between glazing layers in multi-pane window
systems. The use of the algorithm for modeling an unvented
Trombe wall has been validated against experimental data by
Ellis (2003).
This algorithm gives the convection coefficients for air in
a narrow vertical cavity that is sealed and not ventilated.
This applies both to the air gap in between panes of a window
or to the air gap between the Trombe wall glazing and the
inner surface (often a selective surface). These convection
coefficients are really the only difference between a normal
zone and a Trombe zone. The rest of the zone heat balance is
the same, e.g., transmitted solar, long-wave radiation between
surfaces, etc.
For a vertical cavity, the correlation from ISO 15099
is:
\[\begin{array}{lcl}
NU1 = 0.0673838 Ra^{\frac{1}{3}} & for & 5E4 <
Ra < 1E6 \\
NU1 = 0.028154 Ra^{0.4134} & for & 1E4 < Ra
< 5E4 \\
NU1 = 1 + 1.7596678E^{-10} Ra^{2.2984755} & for
& Ra \leq 1E4 \\
\end{array}\]
EnergyPlus also enables importing the pre-calculated
results of other heat transfer processes to be considered in
the inside heat balance calculation. An additional heat source
term defined as a surface property would enable the
consideration of these processes to be imported as schedules
in the interior surface heat balance calculation in
EnergyPlus.
The heat balance on the inside face can be written as
follows:
Alamdari, F. and G.P. Hammond. 1983. Improved data
correlations for buoyancy-driven convection in rooms. Building
Services Engineering Research & Technology. Vol. 4,
No. 3.
ASHRAE. 1985. 1985 ASHRAE Handbook – Fundamentals, Atlanta:
American Society of Heating, Refrigerating, and
Air-Conditioning Engineers, Inc.
ASHRAE. 2001. 2001 ASHRAE Handbook – Fundamentals, Atlanta:
American Society of Heating, Refrigerating, and
Air-Conditioning Engineers, Inc.
Awbi, H.B. and A. Hatton. 1999. Natural convection from
heated room surfaces. Energy and Buildings 30 (1999)
233-244.
Beausoleil-Morrison, I. 2000. The adaptive coupling of heat
and air flow modeling within dynamic whole-building
simulations. PhD. Thesis. University of Strathclyde, Glasgow,
UK.
Ellis, Peter G. 2003. Development and Validation of the
Unvented Trombe Wall Model in EnergyPlus. Master’s Thesis,
University of Illinois at Urbana-Champaign.
Fisher, D.E. and C.O. Pedersen. 1997. “Convective Heat
Transfer in Building
Energy and Thermal Load Calculations”, ASHRAE Transactions,
Vol. 103, Pt. 2.
Fohanno, S., and G. Polidori. 2006. Modelling of natural
convective heat transfer at an internal surface. Energy and
Buildings 38 (2006) 548 - 553
Goldstein, K. and A. Novoselac. 2010. Convective Heat
Transfer in Rooms With Ceiling Slot Diffusers (RP-1416).
HVAC&R Research Journal TBD
Karadag, R. 2009. New approach relevant to total heat
transfer coefficient including the effect of radiation and
convection at the ceiling in a cooled ceiling room. Applied
Thermal Engineering 29 (2009) 1561-1565
Khalifa AJN. 1989. Heat transfer processes in buildings.
Ph.D. Thesis, University of Wales College of Cardiff, Cardiff,
UK.
ISO. 2003. ISO 15099:2003. Thermal performance of windows,
doors, and shading devices – Detailed calculations.
International Organization for Standardization.
Walton, G. N. 1983. Thermal Analysis Research Program
Reference Manual. NBSSIR 83-2655. National Bureau of Standards
(now NIST). This is documentation for “TARP.”
Inside Heat Balance[LINK]
The heart of the heat balance method is the internal heat balance involving the inside faces of the zone surfaces. This heat balance is generally modeled with four coupled heat transfer components: 1) conduction through the building element, 2) convection to the air, 3) short wave radiation absorption and reflectance and 4) longwave radiant interchange. The incident short wave radiation is from the solar radiation entering the zone through windows and emittance from internal sources such as lights. The longwave radiation interchange includes the absorption and emittance of low temperature radiation sources, such as all other zone surfaces, equipment, and people.
The heat balance on the inside face can be written as follows:
\[{q''_{LWX}} + {q''_{SW}} + {q''_{LWS}} + {q''_{ki}} + {q''_{sol}} + {q''_{conv}} = 0 \label{eq:InsideFaceHeatBalanceEquation}\]
where:
\({q''_{LWX}}\) = Net longwave radiant exchange flux between surfaces in a zone or group of zones (enclosure).
\({q''_{SW}}\) = Net short wave radiation flux to surface from lights.
\({q''_{LWS}}\) = Longwave radiation flux from equipment in a zone or group of zones (enclosure).
\({q''_{ki}}\) = Conduction flux through the wall.
\({q''_{sol}}\) = Transmitted solar radiation flux absorbed at surface.
\({q''_{conv}}\) = Convective heat flux to zone air.
Each of these heat balance components is introduced briefly below.
Internal Long-Wave Radiation Exchange[LINK]
Long-wave radiation exchange is balanced within an enclosure which may be a single zone or a group of zones connected by air boundaries (see Construction:AirBoundary) using the GroupedZone radiant exchange method. Throughout this section, "Zone" refers to either type of enclosure.
LW Radiation Exchange Among Zone Surfaces[LINK]
There are two limiting cases for internal LW radiation exchange that are easily modeled:
The zone air is completely transparent to LW radiation.
The zone air completely absorbs LW radiation from the surfaces within the zone.
The limiting case of completely absorbing air has been used for load calculations and also in some energy analysis calculations. This model is attractive because it can be formulated simply using a combined radiation and convection heat transfer coefficient from each surface to the zone air. However, it oversimplifies the zone surface exchange problem, and as a result, the heat balance formulation in EnergyPlus treats air as completely transparent. This means that it does not participate in the LW radiation exchange among the surfaces in the zone. The model, which considers room air to be completely transparent, is reasonable physically because of the low water vapor concentrations and the short mean path lengths. It also permits separating the radiant and convective parts of the heat transfer at the surface, which is an important attribute of the heat balance method.
EnergyPlus uses a grey interchange model for the longwave radiation among zone surfaces. EnergyPlus offers two algorithms for modeling long wave radiation: The “ScriptF” method, and the “CarrollMRT” methods. Users can select between these two algorithms using the “PerformancePrecisionTradeoffs” object.
ScriptF[LINK]
The “ScriptF” algorithm was developed by Hottel (Hottel and Sarofim, Radiative Transfer, Chapter 3, McGraw Hill, 1967). This procedure relies on a matrix of exchange coefficients between pairs of surfaces that include all exchange paths between the surfaces. In other words all reflections, absorptions and re-emissions from other surfaces in the enclosure are included in the exchange coefficient, which is called ScriptF. The major assumptions are that all surface radiation properties are grey and all radiation is diffuse. Both assumptions are reasonable for building zone interchange.
The ScriptF coefficients are developed by starting with the traditional direct radiation view factors. In the case of building rooms and zones, there are several complicating factors in finding the direct view factors—the main one being that the location of surfaces such as thermal mass representing furniture and partitions are not known. The other limitation is that the exact calculation of direct view factors is computationally very intensive even if the positions of all surfaces are known. Accordingly, EnergyPlus uses a procedure to approximate the direct view factors. The procedure has two steps:
1) Determine the total area of other surfaces “seen” by a surface.
2) Approximate the direct view factor from surface 1 to surface 2 as the ratio of the area of surface 2 to the total area “seen” by surface 1.
The determination of the “seen” area has several constraints:
No surface sees itself.
All surfaces see thermal mass surfaces.
No surface facing within 10 degrees of another surface is seen by the other surface.
All surfaces see roofs, floors and ceilings (subject to the preceding facing direction constraint).
Because the approximate view factors may not satisfy the basic requirements of reciprocity (two surfaces should exchange equal amounts of heat in each direction), and completeness (every surface should have a direct view factor sum of 1.0), EnergyPlus does a view factor fix operation before they are used in the ScriptF determination. Normally both of the requirements are satisfied, but in some special situations they are not, and special rules are applied.
If a user includes less than four surfaces in a zone, the enforcement of "completeness" is not strictly possible because it is not possible to have a completed enclosure with less than four surfaces. In this situation, reciprocity is enforced initially and then view factors from each surface are summed. When dealing with this few surfaces, the result of using approximate view factors is that once reciprocity is enforced that the largest surface in the zone will end up having view factors that sum up to greater than unity. This is not physically possible. So, to correct this and maintain completeness for one surface, the entire view factor matrix is divided by the largest summation of view factors for any surface in the zone. By dividing the entire view factor matrix by the same value, the reciprocity established by the standard algorithm is maintained and completeness for one surface is established. All of the other surfaces will not have view factors that sum up to unity and thus will not satisfy completeness. However, these other surfaces will not have view factors that sum up to greater than unity thus avoiding a physically impossible situation.
If the area of one surface in a zone is greater than the sum of the areas of all other surfaces, reciprocity only is enforced, but sometimes, for very large surfaces, that enforcement becomes impossible, and the view factors are modified so that only the large surface is seen by very small surfaces.
Warning messages are produced for both of these cases, and the results should be examined very carefully to ascertain that they are reasonable. The suggested action for the second case (the extra-large surface) is to divide the large surface into several smaller surfaces; then the enclosure will be treated as normal.
Once the ScriptF coefficients are determined, the longwave radiant exchange is calculated for each surface using:
\[{q_{i,j}} = {A_i}{F_{i,j}}\left( {T_i^4 - T_j^4} \right)\]
where F\(_{i,j}\) is the ScriptF between surfaces i and j.
CarrollMRT[LINK]
The Carroll method is an approximation of gray-body long-wave radiation exchange within an enclosure that simplifies the surface-to-surface radiation exchange by using a single, mean radiant temperature node, \(Tr\), that acts as a clearinghouse for the radiation heat exchange between surfaces. Instead of solving a dense-matrix, linear algebra problem, the mean radiant temperature can be calculated using a single equation, and subsequently used to determine the net long-wave radiation to/from each surface. Unlike the \(O(n^2)\) complexity of the current dense-matrix solution, this approach has linear complexity.
The mean radiant temperature is calculated using three steps:
Calculation of the mean radiant temperature “view factor”, \(Fi\). These view factors represent each surface’s “view” to the mean radiant temperature node as though all surfaces were part of a spherical enclosure (i.e., they all have equal view of the node regardless of their orientation to each other). \(Fi\) is calculated as:
\[F_i=\frac{1}{1-\frac{A_i F_i}{\sum_1^n{A_j F_j} }}\]
Because of the circular reference in this equation, the collection of all “view factors” must be solved iteratively, but only once per simulation as surface areas do not change throughout. This converges for realistic enclosures but won’t necessarily converge for “enclosures” having only two or three surfaces, particularly if there are large area disparities.
Calculating the gray-body radiation resistance, \(F'i\). This calculation must be computed every time surface emissivity changes. \(F'i\) is calculated as:
\[F'_i=\frac{\sigma\varepsilon_i}{\frac{\varepsilon_i}{F_i} +1-\varepsilon_i}\]
Finally, the mean radiant temperature, \(Tr\), is:
\[T_r=\frac{\sum_1^nA_i F'_i T_i}{\sum_1^nA_i F'_i}\]
Once the mean radiant temperature is known, the net radiation heat transfer for each surface can be calculated as:
\[q=F'_i A_i (T_r^4-T_i^4)\]
Carroll, J. A., 1980, “An ‘MRT Method’ of Computing Radiant Energy Exchange in Rooms,” Proceedings of the Second Systems Simulation and Economic Analysis Conference, San Diego, CA.
Carroll, J. A., 1980a, “An MRT method of computing radiant energy exchange in rooms,” Proceedings of the 2nd Systems Simulation and Economic Analysis Conference, San Diego, CA.
Carroll, J. A., 1981, “A Comparison of Radiant Interchange Algorithms,” Proceedings of the 3rd Annual Systems Simulation and Economics Analysis/Solar Heating and Cooling Operational Results Conference, Reno. Solar Engineering, Proceedings of the ASME Solar division.
Thermal Mass and Furniture[LINK]
Furniture in a zone has the effect of increasing the amount of surface area that can participate in the radiation and convection heat exchanges. It also adds participating thermal mass to the zone. These two changes both affect the response to temperature changes in the zone and also affect the heat extraction characteristics.
The proper modeling of furniture is an area that needs further research, but the heat balance formulation allows the effect to be modeled in a realistic manner by including the furniture surface area and thermal mass in the heat exchange process.
LW Radiation From Internal Sources[LINK]
The traditional model for this source is to define a radiative/convective split for the heat introduced into a zone from equipment. The radiative part is then distributed over the surfaces within the zone in some prescribed manner. This, of course, is not a completely realistic model, and it departs from the heat balance principles. However, it is virtually impossible to treat this source in any more detail since the alternative would require knowledge of the placement and surface temperatures of all equipment.
Internal Short-Wave Radiation[LINK]
SW Radiation from Lights[LINK]
The short wavelength radiation from lights is distributed over the surfaces in the zone in some prescribed manner.
Transmitted Solar[LINK]
Transmitted solar radiation is also distributed over the surfaces in the zone in a prescribed manner. It would be possible to calculate the actual position of beam solar radiation, but that would involve partial surface irradiation, which is inconsistent with the rest of the zone model that assumes uniform conditions over an entire surface. The current procedures incorporate a set of prescribed distributions. Since the heat balance approach can deal with any distribution function, it is possible to change the distribution function if it seems appropriate.
Convection to Zone Air[LINK]
The convection flux is calculated using the heat transfer coefficients as follows:
\[{q''_{conv}} = {h_c}({T_s} - {T_a})\]
The inside convection coefficients (h\(_{c}\)) can be calculated using one of many different models. Currently the implementation uses coefficients based on correlations for natural, mixed, and forced convection.
Interior Conduction[LINK]
This contribution to the inside surface heat balance is the wall conduction term, \({q''_{ki}}\) shown in Equation [eq:InsideFaceHeatBalanceEquation]. This represents the heat transfer to the inside face of the building element. Again, a CTF formulation is used to determine this heat flux.
Interior Convection[LINK]
There are many different modeling options available in EnergyPlus for inside convection coefficients, h\(_{c}\). There are four different settings to direct how EnergyPlus managers select h\(_{c}\) models during a simulation. There are numerous individual model equations for h\(_{c}\) in EnergyPlus to cover different situations that arise from surface orientations, room airflow conditions, and heat flow direction. Additionally, in many cases multiple researchers have developed competing models for the same situations that differ and there is no way to declare one is better than another. An overall default for the simulation is selected in the “SurfaceConvectionAlgorithm:Inside” object and can be overridden by selecting a different option in a zone description. These models are explained in the following sections. In addition to the correlation choices described below, it is also possible to override the convection coefficients on the inside of any surface by using the “SurfaceProperty:ConvectionCoefficients” object in the input file to set the convection coefficient value on the inside of any surface. The values can be specified directly or with schedules. Specific details are given in the Input Output Reference document.
Adaptive Convection Algorithm[LINK]
Beausoleil-Morrison (2000, 2002) developed a methodology for dynamically managing the selection of h\(_{c}\) equations called adaptive convection algorithm. The algorithm is used to select among the available h\(_{c}\) equations for the one that is most appropriate for a given surface at a given time. As Beausoleil-Morrison notes, the adaptive convection algorithm is intended to be expanded and altered to reflect different classification schemes and/or new h\(_{c}\) equations. The implementation in EnergyPlus has been modified from the original in the following ways:
An input mechanism is provided (see the
SurfaceConvectionAlgorithm:Inside:AdapativeModelSelections object) so that the user can customize the specific selections of h\(_{c}\) equations that are applied for different flow regimes and surface orientations. The changes apply in a general way to the entire model (but can be overridden by setting surface properties).
To avoid requiring additional user input on the position of ZoneHVAC-type equipment within a zone, there is no distinction between zones that have convective zone heater equipment located underneath the windows and those that have convective heaters located away from the windows. This applies to the air flow regime associated with convective zone heaters. Using Beausoleil-Morrison’s terminology, regimes B1 and B2 are combined into just one B regime.
To avoid requiring additional user input on the position of ZoneHVAC-type equipment within a zone, there is no distinction between surfaces that are directly blown on the fan and those that are away from the fan for the air flow regime associated with mechanical circulation from a zone fan (ZoneHVAC type equipment).
The correlation for horizontal free jet developed by Fisher (1995) is not used. Ceiling diffuser models are used for all mechanical circulation from central air system. This decision was made for two reasons: (1) to avoid requiring additional user input on the position of, and momentum generated by, air terminal units, and (2) because Fisher (1995) found that the Coanda effect is so significant that in practice a free horizontal jet is difficult to maintain and mechanical-driven room airflows generally attach to surfaces and tend to match the flow regime of a ceiling diffuser much more often than a free jet.
EnergyPlus supports arbitrary geometry so surfaces can be tilted with respect to vertical or horizontal. Beausoleil-Morrison’s adaptive convection algorithm was originally structured to use h\(_{c}\) equations that have no functional dependence on surface tilt angle. However, tilted surfaces do perform differently than vertical or horizontal surface when buoyancy forces are significant. Therefore, the EnergyPlus implementation expands the structure of the algorithm to include additional categories for tilted surfaces. The h\(_{c}\) equations developed by Walton (1983) are selected as the defaults for tilted surfaces because they have a functional dependence on tilt angle.
Fohanno and Polidari (2006) produced a new h\(_{c}\) equation for vertical walls inside buildings with a simple buoyancy flow regime. They used a theoretical approach based on integral formalism and uniform heat flux (rather than uniform temperature) that covers both laminar and turbulent flow situations. In EnergyPlus, this model is selected as the default in place of the model by Alamdari and Hammond (1983) for vertical walls.
Karadag (2009) produced a new h\(_{c}\) equation for ceiling surfaces that are actively chilled. He used computation fluid dynamics and various sized rooms and temperature conditions. In EnergyPlus, this model is selected as the default for surfaces that have active, in-ceiling cooling (in place of the model by Alamdari and Hammond (1983) for unstable ceilings).
International Standard Organization (ISO) completed Standard 15099-2003 which includes h\(_{c}\) equations for the inside face of windows. EnergyPlus strives to adhere to formal modeling Standards where possible. Therefore the implementation includes a larger structure for the adaptive algorithm that includes additional categories for windows in all flow regimes and ISO 15099-2003 models are used as the default for windows in natural convection flow regimes. The ISO 15099 model applies to various tilt angles.
Goldstein and Novosalec (2010) produced new h\(_{c}\) equations for forced air situations with ceiling slot diffusers along perimeters with significant glazing fractions. They used experiments with full-sized test room. These new equations are selected as the default for windows, ceilings and floors when there is an active central air system.
Interior mass surfaces are assigned the h\(_{c}\) equation that would apply (stable or unstable) to a horizontal, upward facing surface for each flow regime.
The algorithm switches between forced, mixed, and natural flow regimes by calculating the Richardson number, Ri = Gr/Re^2, for the zone. Large values of Ri indicate buoyancy dominates, while small values indicate forced flows dominate. To distinguish between opposing Zone unit type equipment (with fans) are assumed to force air up walls, and central air type equipment (with diffusers) are assumed to force air down walls.
The adaptive convection algorithm implemented in EnergyPlus for the inside face has a total of 45 different categories for surfaces and 29 different options for h\(_{c}\) equation selections. The following table summarizes the categories and the default assignments for h\(_{c}\) equations. The individual h\(_{c}\) equations are documented below.
*Indicates the default selection for h\(_{c}\) model equation.
Inside Face Surface Classification[LINK]
The adaptive convection algorithm is based on classifying surfaces by flow regime and orientation so that the correct h\(_{c}\) equation can be chosen at a particular point in time during the simulation. The classification depends on user input with some aspects processed only once at the beginning and others during each timestep. There are also various parameters or inputs to the h\(_{c}\) equations that need static or dynamic processing.
For each surface, it and the zone it is attached to are processed for the following static characteristics.
Characteristic height for convection is taken as the zone height.
Surfaces listed as receiving heat from Zone HVAC equipment with radiative models are considered “near” the heater.
Zones are examined for low temperature radiant systems. The surfaces that contain the active elements are examined and the zone characterized to know if it has in-floor heating, in-ceiling cooling, or in-wall heating.
A hydraulic diameter is calculated for horizontal surfaces for the entire zone.
and calculating various parameters needed by h\(_{c}\) equations. Selecting flow regime is done in the following manner. For each surface, we examine the zone on the inside face for the following:
HVAC system type
HVAC operating status
HVAC system ACH
During initial zone and system sizing calculations, HVAC system characteristics are not known yet, so the flow regime is selected assuming an uncontrolled zone. During simulations, including HVAC sizing simulations, the HVAC system characteristics are used.
The surfaces are evaluated to determine:
Surface classification: Floor, wall, roof, window, types
Tilt angle
Convective stability (sign of ΔT)
The individual h\(_{c}\) model equations and their respective references are listed in next by the keyword used to identify them.
ASHRAE Vertical Wall[LINK]
Walton adopted the following equation for natural convection from ASHRAE .
\[h = 1.31{\left| {\Delta T} \right|^{\frac{1}{3}}}\]
This is usually bound at a minimum of .1 in EnergyPlus. This is a component of the TARP overall algorithm described below.
Walton Unstable Horizontal Or Tilt[LINK]
Walton (1983) developed the following equation by fitting curves from various sources.
\[h = \frac{{9.482{{\left| {\Delta T} \right|}^{\frac{1}{3}}}}}{{7.238 - \left| {\cos \Sigma } \right|}}\]
Unstable refers to the direction of heat flow and the associated buoyancy relative to the surfaces. Unstable is when the natural tendency is to enhance flow in the sense that rising warmer air, or falling cooler air, is free to move away from the surface. This is usually bound at a minimum of .1 in EnergyPlus. This is a component of the TARP overall algorithm described below.
Walton Stable Horizontal Or Tilt[LINK]
Walton (1983) developed the following equation by fitting curves from various sources.
\[h = \frac{{1.810{{\left| {\Delta T} \right|}^{\frac{1}{3}}}}}{{1.382 + \left| {\cos \Sigma } \right|}}\]
Stable refers to the direction of heat flow and the associated buoyancy relative to the surfaces. Stable is when the natural tendency is to retard flow in the sense that rising warmer air, or falling cooler air, is driven against the surface. This is usually bound at a minimum of .1 in EnergyPlus. This is a component of the TARP overall algorithm described below.
Fisher Pedersen Ceiling Diffuser Walls[LINK]
Fisher and Pedersen (1997) developed the following equation from laboratory chamber measurements.
\[h = 1.208 + 1.012 * AC{H^{0.604}}\]
This is a component of the CeilingDiffuser overall algorithm described below.
Fisher Pedersen Ceiling Diffuser Ceiling[LINK]
Fisher and Pedersen (1997) developed the following equation from laboratory chamber measurements.
\[h = 2.234 + 4.099 * AC{H^{0.503}}\]
This is a component of the CeilingDiffuser overall algorithm described below.
Fisher Pedersen Ceiling Diffuser Floor[LINK]
Fisher and Pedersen (1997) developed the following equation from laboratory chamber measurements.
\[h = 3.873 + 0.082 * AC{H^{0.98}}\]
This is a component of the CeilingDiffuser overall algorithm described below.
Alamdari Hammond Stable Horizontal[LINK]
Alamdari and Hammond (1983) developed the following correlation for horizontal surfaces in stable thermal situation.
\[h = 0.6{\left( {\frac{{\left| {\Delta T} \right|}}{{D_h^2}}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 5}}\right.}\!\lower0.7ex\hbox{5}}}}\]
where,
\({D_h} = \frac{{4A}}{P}\) , hydraulic diameter of horizontal surface, A is area (m\(^{2}\)) and P is the perimeter (m) of the entire zone.
Alamdari Hammond Unstable Horizontal[LINK]
Alamdari and Hammond (1983) developed the following correlation for horizontal surfaces in a buoyant thermal situation.
\[h = {\left\{ {{{\left[ {1.4{{\left( {\frac{{\left| {\Delta T} \right|}}{{{D_h}}}} \right)}^{^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}}}} \right]}^6} + {{\left[ {1.63{{\left| {\Delta T} \right|}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}} \right]}^6}} \right\}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 6}}\right.}\!\lower0.7ex\hbox{6}}}}\]
Alamdari Hammond Vertical Wall[LINK]
Alamdari and Hammond (1983) developed the following correlation for vertical surfaces.
\[h = {\left\{ {{{\left[ {1.5{{\left( {\frac{{\left| {\Delta T} \right|}}{H}} \right)}^{^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}}}} \right]}^6} + {{\left[ {1.23{{\left| {\Delta T} \right|}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}} \right]}^6}} \right\}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 6}}\right.}\!\lower0.7ex\hbox{6}}}}\]
where,
H is the characteristic height for the surface. In EnergyPlus this is the zone’s ceiling height (which could be larger than the height of an individual surface when wall are subdivided into more than one surface).
Khalifa Eq3 Wall Away From Heat[LINK]
Khalifa (1989) conducted experiments with test chambers and developed correlations for certain types of surfaces. One of them, identified as “Equation 3” in original reference, is for convectively heated zones and applies to the inside surfaces of walls away from the heat source:
\[h = 2.07{\left| {\Delta T} \right|^{0.23}}\]
Khalifa Eq4 Ceiling Away From Heat[LINK]
Khalifa (1989) conducted experiments with test chambers and developed correlations for certain types of surfaces. One of them, identified as “Equation 4” in original reference, is for convectively heated zones and applies to the inside surfaces of ceilings away from the heat source:
\[h = 2.72{\left| {\Delta T} \right|^{0.13}}\]
Khalifa Eq5 Wall Near Heat[LINK]
Khalifa (1989) conducted experiments with test chambers and developed correlations for certain types of surfaces. One of them, identified as “Equation 5” in original reference, is for convectively heated zones and applies to the inside surfaces of walls near the heat source:
\[h = 1.98{\left| {\Delta T} \right|^{0.32}}\]
Khalifa Eq6 Non Heated Walls[LINK]
Khalifa (1989) conducted experiments with test chambers and developed correlations for certain types of surfaces. One of them, identified as “Equation 6” in original reference, is for heated zones and applies to the inside surfaces of walls that are not heated:
\[h = 2.30{\left| {\Delta T} \right|^{0.24}}\]
Khalifa Eq7 Ceiling[LINK]
Khalifa (1989) conducted experiments with test chambers and developed correlations for certain types of surfaces. One of them, identified as “Equation 7” in original reference, is for heated zones and applies to the inside surfaces of ceilings:
\[h = 3.10{\left| {\Delta T} \right|^{0.17}}\]
Awbi Hatton Heated Floor[LINK]
Awbi and Hatton (1999) conducted laboratory measurements using environmental chambers and developed the following correlation for floor surfaces that are being actively heated.
\[h = \frac{{2.175{{\left| {\Delta T} \right|}^{0.308}}}}{{D_h^{0.076}}}\]
where,
\({D_h} = \frac{{4A}}{P}\), hydraulic diameter of horizontal surface, A is area (m\(^{2}\)) and P is the perimeter (m) of the entire zone (all of the adjacent floor surfaces if more than one in the zone).
Awbi Hatton Heated Wall[LINK]
Awbi and Hatton (1999) developed the following correlation for wall surfaces that are being actively heated.
\[h = \frac{{1.823{{\left| {\Delta T} \right|}^{0.293}}}}{{D_h^{0.076}}}\]
where,
\({D_h} = \frac{{4A}}{P}\), hydraulic diameter of wall surface, A is area (m\(^{2}\)) and P is the perimeter (m) of the entire wall (all of the adjacent wall surfaces if more than one along the wall).
Beausoleil Morrison Mixed Assisted Wall[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for walls where the flow driving forces from mechanical forces are augmented by the driving forces from buoyancy.
\[h = \left( \left\{ \left[1.5\left(\frac{\left|\Delta T\right|}{H}\right)^{1/4}\right]^6 + \left[1.23\left|\Delta T\right|^2\right]^{1/6} \right\}^{1/2} + \left\{ \left[\frac{T_{surf}-T_{SAT}}{\left|\Delta T\right|}\right] \left[-0.199+0.190\cdot ACH^{0.8}\right] \right\}^3 \right)^{1/3}\]
where,
T\(_{SAT}\) is the supply air temperature at the diffuser.
Here the reference temperature is the zone air temperature rather than the diffuser supply air temperature.
Beausoleil Morrison Mixed Opposing Wall[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for walls where the flow driving forces from mechanical forces are opposed by the driving forces from buoyancy.
\[h = \max \left\{ \begin{array}{l} \left(\left\{\left[1.5\left(\frac{\left|\Delta T\right|}{H}\right)^{1/4}\right]^6+\left[1.23\left|\Delta T\right|^2\right]^{1/6}\right\}^{1/2}-\left\{\left[\frac{T_{surf}-T_{SAT}}{\left|\Delta T\right|}\right]\cdot\left[-0.199+0.190\cdot ACH^{0.8}\right]\right\}^3\right)^{1/3} \\ 0.8\cdot \left\{\left[1.5\left(\frac{\left|\Delta T\right|}{H}\right)^{1/4}\right]^6+\left[1.23\left|\Delta T\right|^2\right]\right\}^{1/6} \\ 0.8\cdot \left\{\left[\frac{T_{surf}-T_{SAT}}{\left|\Delta T\right|}\right]\cdot\left[-0.199+0.190\cdot ACH^{0.8}\right]\right\} \end{array} \right.\]
Beausoleil Morrison Mixed Stable Floor[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for floors where the flow driving forces include both mechanical forces and thermally stable buoyancy.
\[h = {\left( {{{\left\{ {0.6 \cdot {{\left( {\frac{{\left| {\Delta T} \right|}}{{{D_H}}}} \right)}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 5}}\right.}\!\lower0.7ex\hbox{5}}}}} \right\}}^3} + {{\left\{ {\left[ {\frac{{{T_{surf}} - {T_{SAT}}}}{{\left| {\Delta T} \right|}}} \right]\cdot\left[ {0.159 + 0.116AC{H^{0.8}}} \right]} \right\}}^3}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}\]
Beausoleil Morrison Mixed Unstable Floor[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for floors where the flow driving forces include both mechanical forces and thermally unstable buoyancy.
\[h = {\left( {{{\left\{ {{{\left[ {1.4{{\left( {\frac{{\left| {\Delta T} \right|}}{{{D_h}}}} \right)}^{^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}}}} \right]}^6} + {{\left[ {1.63{{\left| {\Delta T} \right|}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}} \right]}^6}} \right\}}^{{\raise0.7ex\hbox{3} \!\mathord{\left/ {\vphantom {3 6}}\right.}\!\lower0.7ex\hbox{6}}}} + {{\left\{ {\left[ {\frac{{{T_{surf}} - {T_{SAT}}}}{{\left| {\Delta T} \right|}}} \right]\cdot\left[ {0.159 + 0.116AC{H^{0.8}}} \right]} \right\}}^3}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}\]
Beausoleil Morrison Mixed Stable Ceiling[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for ceilings where the flow driving forces include both mechanical forces and thermally Stable buoyancy.
\[h = {\left( {{{\left\{ {0.6 \cdot {{\left( {\frac{{\left| {\Delta T} \right|}}{{{D_H}}}} \right)}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 5}}\right.}\!\lower0.7ex\hbox{5}}}}} \right\}}^3} + {{\left\{ {\left[ {\frac{{{T_{surf}} - {T_{SAT}}}}{{\left| {\Delta T} \right|}}} \right]\cdot\left[ { - 0.166 + 0.484AC{H^{0.8}}} \right]} \right\}}^3}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}}\]
Beausoleil Morrison Mixed Unstable Ceiling[LINK]
Beausoleil-Morrison (2000) used blending techniques to combine correlations originally developed by Alamdari and Hammond (1983) and Fisher and Pedersen (1997) to create the following correlation is for ceilings where the flow driving forces include both mechanical forces and thermally unstable buoyancy.
\[h = \left( \left( \left[ 1.4 \left( \frac{ \left| \Delta T \right| }{ D_h } \right)^{1/4} \right]^6 + \left[ 1.63 \left|\Delta T\right|^{1/3} \right]^6 \right)^{3/6} + \left( \left[ \frac{ T_{surf}-T_{SAT} }{ \left|\Delta T\right| } \right] \cdot \left[ -0.166 + 0.484 \cdot ACH^{0.8} \right] \right)^3 \right)^{1/3}\]
Fohanno Polidori Vertical Wall[LINK]
Fohanno and Polidori (2006) developed the following equation for h\(_{c}\) for vertical walls under simple buoyancy flow conditions.
\[h = \left\{ \begin{array}{l}1.332{\left( {\frac{{\left| {\Delta T} \right|}}{H}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}}\quad ,\quad Ra_H^* \le 6.3 \times {10^9}\\1.235{e^{\left( {0.0467H} \right)}}{\left| {\Delta T} \right|^{0.316}}\quad ,\quad Ra_H^* > 6.3 \times {10^9}\end{array} \right.\]
where,
\[Ra_H^* = \frac{{g{\beta_f}{{q''}_c}{H^4}}}{{{k_f}\nu_f^2}}{\Pr_f}\]
Karadag Chilled Ceiling[LINK]
Karadag (2009) used numerical methods to develop the following equation for h\(_{c}\) for chilled-ceiling surfaces.
\[h = 3.1{\left| {\Delta T} \right|^{0.22}}\]
ISO 15099 Windows[LINK]
ISO Standard 15099-2003 includes the equations for h\(_{c}\) for room-side of windows and surfaces with any tilt angle and heat flow direction. The ISO 15099 correlation is for still room air angle and is determined in terms of the Nusselt number, \(Nu\) , where
\[{h_i} = Nu\left( {\frac{\lambda }{H}} \right)\]
where,
\(\lambda\) is the thermal conductivity of air, and
\(H\) is the height of the window.
The Rayleigh number based on height, \(R{a_H}\) , is calculated using:
\[R{a_H} = \frac{{{\rho ^2}{H^3}g\,{c_p}\left| {{T_{surf,i}} - {T_{air}}} \right|}}{{{T_{m,f}}\mu \lambda }}\]
where,
\(\rho\) is the density of air
\(g\) is the acceleration due to gravity,
\({c_p}\) is the specific heat of air,
\(\mu\) is the dynamic viscosity of air, and
\({T_{m,f}}\) is the mean film temperature in Kelvin given by,
\[{T_{m,f}} = {T_{air}} + \frac{1}{4}\left( {{T_{surf,i}} - {T_{air}}} \right)\]
There are four cases for the Nusselt correlation that vary by the tilt angle in degrees, \(\gamma\) , and are based on heating conditions. For cooling conditions (where \({T_{surf,i}} > {T_{air}}\) ) the tilt angle is complemented so that \(\gamma = 180 - \gamma\)
Case A. \({0^o } \leq \gamma < 15^o\)
\[Nu = 0.13Ra_H^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}\]
Case B. \(15^o \leq \gamma \leq 90^o\)
\[R{a_{cv}} = 2.5 \times {10^5}{\left( {\frac{{{e^{0.72\gamma }}}}{{\sin \lambda }}} \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 5}}\right.}\!\lower0.7ex\hbox{5}}}}\]
\[Nu = 0.56{\left( {R{a_H}\sin \gamma } \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}};\;for\;R{a_H} \le R{a_{CV}}\]
\[Nu = 0.13\left( {Ra_H^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}} - Ra_{CV}^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 3}}\right.}\!\lower0.7ex\hbox{3}}}} \right) + 0.56{\left( {R{a_{CV}}\sin \gamma } \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}};\;R{a_H} > R{a_{CV}}\]
Case C. \(90^o < \gamma \leq 179^o\)
\[Nu = 0.56{\left( {R{a_H}\sin \gamma } \right)^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 4}}\right.}\!\lower0.7ex\hbox{4}}}};\;{10^5} \le R{a_H}\sin \gamma < {10^{11}}\]
Case D. \(179^o < \gamma \leq 180^o\)
\[Nu = 0.58Ra_H^{{\raise0.7ex\hbox{1} \!\mathord{\left/ {\vphantom {1 5}}\right.}\!\lower0.7ex\hbox{5}}};\;R{a_H} \le {10^{11}}\]
The material properties are evaluated at the mean film temperature. Standard EnergyPlus psychrometric functions are used for \(\rho\) and \({c_p}\) . Thermal conductivity is calculated using:
\(\lambda = 2.873 \times {10^{ - 3}} + 7.76 \times {10^{ - 8}}{T_{m,f}}\) .
Kinematic viscosity is calculated using:
\(\mu = 3.723 \times {10^{ - 6}} + 4.94 \times {10^{ - 8}}{T_{m,f}}\) .
This correlation depends on the surface temperature of the room-side glazing surface and is therefore included inside the window heat balance iteration loop.
Goldstein Novoselac Ceiling Diffuser Window[LINK]
Goldstein and Novoselac (2010) used laboratory chamber measurements to develop convection correlations for perimeter zones with highly glazed spaces served by overhead slot-diffuser-based air systems. The following are for bare windows in such spaces.
For WWR<50% with window in upper part of wall:
\[h = 0.117{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
For WWR<50% with window in lower part of wall
\[h = 0.093{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
For WWR > 50%
\[h = 0.103{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
Where,
WWR is the window to wall ratio.
L is the length of exterior wall with glazing in the zone.
\(\dot V\) is the air system flow rate in m\(^{3}\)/s.
Goldstein Novoselac Ceiling Diffuser Walls[LINK]
Goldstein and Novoselac (2010) used laboratory chamber measurements to develop convection correlations for perimeter zones with highly glazed spaces served by overhead slot-diffuser-based air systems. The following are for exterior walls in such spaces.
For walls located below a window
\[h = 0.063{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
For walls located above a window
\[h = 0.093{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
Goldstein Novoselac Ceiling Diffuser Floor[LINK]
Goldstein and Novoselac (2010) used laboratory chamber measurements to develop convection correlations for perimeter zones with highly glazed spaces served by overhead slot-diffuser-based air systems. The following is for floors in such spaces.
\[h = 0.048{\left( {\frac{{\dot V}}{L}} \right)^{0.8}}\]
Separate from the above model structure, there are also other comprehensive algorithm structures which are described below.
TARP Algorithm[LINK]
The comprehensive natural convection model, accessed using the keyword “TARP,” correlates the convective heat transfer coefficient to the surface orientation and the difference between the surface and zone air temperatures (where DT = Surface Temperature - Air Temperature). The algorithm is taken directly from Walton (1983). Walton derived his algorithm from ASHRAE literature which can now be found for example in the ASHRAE Handbook (HoF 2001), Table 5 on p. 3.12, which gives equations for natural convection heat transfer coefficients in the turbulent range for large, vertical plates and for large, horizontal plates facing upward when heated (or downward when cooled). A note in the text also gives an approximation for large, horizontal plates facing downward when heated (or upward when cooled) recommending that it should be half of the facing upward value. Walton adds a curve fit as a function of the cosine of the tilt angle to provide intermediate values between vertical and horizontal. The curve fit values at the extremes match the ASHRAE values very well.
For no temperature difference OR a vertical surface the following correlation is used:
\(h = 1.31{\left| {\Delta T} \right|^{\frac{1}{3}}}\) (90)
For (\(\Delta\)T < 0.0 AND an upward facing surface) OR (\(\Delta\)T > 0.0 AND an downward facing surface) an enhanced convection correlation is used:
\(h = \frac{{9.482{{\left| {\Delta T} \right|}^{\frac{1}{3}}}}}{{7.238 - \left| {\cos \Sigma } \right|}}\) (91)
where \(\Sigma\) is the surface tilt angle.
For (\(\Delta\)T > 0.0 AND an upward facing surface) OR (\(\Delta\)T < 0.0 AND an downward facing surface) a reduced convection correlation is used:
\(h = \frac{{1.810{{\left| {\Delta T} \right|}^{\frac{1}{3}}}}}{{1.382 + \left| {\cos \Sigma } \right|}}\) (92)
where \(\Sigma\) is the surface tilt angle.
Simple Natural Convection Algorithm[LINK]
The simple convection model uses constant coefficients for different heat transfer configurations, using the same criteria as the detailed model to determine reduced and enhanced convection. The coefficients are also taken directly from Walton (1983). Walton derived his coefficients from the surface conductances for e = 0.90 found in the ASHRAE Handbook (1985) in the table found on p. 23.2. The radiative heat transfer component was estimated at 1.02 * 0.9 = 0.918 BTU/h-ft2-F and then subtracted off. Finally the coefficients were converted to SI units to yield the values below.
For a vertical surface:
\[{\rm{h = 3}}{\rm{.076}}\]
For a horizontal surface with reduced convection:
\[{\rm{h = 0}}{\rm{.948}}\]
For a horizontal surface with enhanced convection:
\[{\rm{h = 4}}{\rm{.040}}\]
For a tilted surface with reduced convection:
\[{\rm{h = 2}}{\rm{.281}}\]
For a tilted surface with enhanced convection:
\[{\rm{h = 3}}{\rm{.870}}\]
Ceiling Diffuser Algorithm[LINK]
The ceiling diffuser algorithm is based on empirical correlations developed by Fisher and Pedersen (1997). The correlation was reformulated to use the room outlet temperature as the reference temperature. The correlations are shown below.
For Floors:
\[h = 3.873 + 0.082 * AC{H^{0.98}}\] (93)
The correlation for floors is illustrated in Figure 2.
For ceilings:
\[h = 2.234 + 4.099 * AC{H^{0.503}}\]
The correlation for ceilings is illustrated in Figure 3.
For Walls:
\[h = 1.208 + 1.012 * AC{H^{0.604}}\]
The correlation for walls is illustrated in Figure 4.
It should be noted that the conditions under which the correlations were developed included ACH values down to around 3.0. However, extrapolation of the data down to ACH=1.0 is reasonable and so within EnergyPlus, for ACH values of 1.0 or greater, the ceiling diffuser correlations as shown above are used. Below ACH values of 0.5, the natural convection algorithm is used. Between ACH values of 0.5 and 1.0, there is a linear interpolation between the two models to avoid any discontinuities in the convection coefficient calculated.
Trombe Wall Algorithm[LINK]
The Trombe wall algorithm is used to model convection in a “Trombe wall zone”, i.e. the air space between the storage wall surface and the exterior glazing. (See the later sections on Passive and Active Trombe Walls below for more information about Trombe walls.) The algorithm is identical to the convection model (based on ISO 15099) used in Window5 for convection between glazing layers in multi-pane window systems. The use of the algorithm for modeling an unvented Trombe wall has been validated against experimental data by Ellis (2003).
This algorithm gives the convection coefficients for air in a narrow vertical cavity that is sealed and not ventilated. This applies both to the air gap in between panes of a window or to the air gap between the Trombe wall glazing and the inner surface (often a selective surface). These convection coefficients are really the only difference between a normal zone and a Trombe zone. The rest of the zone heat balance is the same, e.g., transmitted solar, long-wave radiation between surfaces, etc.
For a vertical cavity, the correlation from ISO 15099 is:
\[\begin{array}{lcl} NU1 = 0.0673838 Ra^{\frac{1}{3}} & for & 5E4 < Ra < 1E6 \\ NU1 = 0.028154 Ra^{0.4134} & for & 1E4 < Ra < 5E4 \\ NU1 = 1 + 1.7596678E^{-10} Ra^{2.2984755} & for & Ra \leq 1E4 \\ \end{array}\]
\[{\rm{NU2}} = 0.242{\left( {{\raise0.7ex\hbox{{{\rm{Ra}}}} \!\mathord{\left/ {\vphantom {{{\rm{Ra}}} {\rm{A}}}}\right.}\!\lower0.7ex\hbox{{\rm{A}}}}} \right)^{0.272}}\]
\[{\rm{NU = MAX(NU1,NU2)}}\]
where
Nu = Nusselt number
Ra = Rayleigh number
A = aspect ratio of cavity
This is then used in EnergyPlus as follows:
Net convection coefficient from glazing to wall is:
\[{h_{net}} = {\rm{k}}\left( {{\raise0.7ex\hbox{{{\rm{NU}}}} \!\mathord{\left/ {\vphantom {{{\rm{NU}}} {\rm{L}}}}\right.}\!\lower0.7ex\hbox{{\rm{L}}}}} \right)\]
where
k = conductivity of air
L = air gap thickness
Convection coefficient applied to each wall separately and actually used in the zone heat balance is:
\[{h_c} = 2{h_{net}}\]
Additional Heat Balance Source[LINK]
EnergyPlus also enables importing the pre-calculated results of other heat transfer processes to be considered in the inside heat balance calculation. An additional heat source term defined as a surface property would enable the consideration of these processes to be imported as schedules in the interior surface heat balance calculation in EnergyPlus.
The heat balance on the inside face can be written as follows:
\[{q''_{LWX}} + {q''_{SW}} + {q''_{LWS}} + {q''_{ki}} + {q''_{sol}} + {q''_{conv}} + {q''_{add}} = 0\]
where: \(q''_{add}\) = Pre-calculated results of the heat flux to the inside face from other heat transfer processes.
References[LINK]
Alamdari, F. and G.P. Hammond. 1983. Improved data correlations for buoyancy-driven convection in rooms. Building Services Engineering Research & Technology. Vol. 4, No. 3.
ASHRAE. 1985. 1985 ASHRAE Handbook – Fundamentals, Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
ASHRAE. 2001. 2001 ASHRAE Handbook – Fundamentals, Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
Awbi, H.B. and A. Hatton. 1999. Natural convection from heated room surfaces. Energy and Buildings 30 (1999) 233-244.
Beausoleil-Morrison, I. 2000. The adaptive coupling of heat and air flow modeling within dynamic whole-building simulations. PhD. Thesis. University of Strathclyde, Glasgow, UK.
Ellis, Peter G. 2003. Development and Validation of the Unvented Trombe Wall Model in EnergyPlus. Master’s Thesis, University of Illinois at Urbana-Champaign.
Fisher, D.E. and C.O. Pedersen. 1997. “Convective Heat Transfer in Building Energy and Thermal Load Calculations”, ASHRAE Transactions, Vol. 103, Pt. 2.
Fohanno, S., and G. Polidori. 2006. Modelling of natural convective heat transfer at an internal surface. Energy and Buildings 38 (2006) 548 - 553
Goldstein, K. and A. Novoselac. 2010. Convective Heat Transfer in Rooms With Ceiling Slot Diffusers (RP-1416). HVAC&R Research Journal TBD
Karadag, R. 2009. New approach relevant to total heat transfer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling room. Applied Thermal Engineering 29 (2009) 1561-1565
Khalifa AJN. 1989. Heat transfer processes in buildings. Ph.D. Thesis, University of Wales College of Cardiff, Cardiff, UK.
ISO. 2003. ISO 15099:2003. Thermal performance of windows, doors, and shading devices – Detailed calculations. International Organization for Standardization.
Walton, G. N. 1983. Thermal Analysis Research Program Reference Manual. NBSSIR 83-2655. National Bureau of Standards (now NIST). This is documentation for “TARP.”
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.