Air wall,
Open air connection between zones[LINK]
Modeling the interactions between thermal zones which are
connected by a large opening requires special consideration.
EnergyPlus models only what is explicitly described in the
input file, so simply leaving a void (no surfaces) between two
zones will accomplish nothing - the two zones will not be
connected. A building surface or fenestration surface with Construction:AirBoundary
may be used connect the zones. Construction:AirBoundary
has options for modeling the interactions which occur across
the dividing line between two zones which are fully open to
each other:
- Convection or airflow
-
transfers both sensible heat and moisture. Some modelers
use ZoneMixing
(one-way flow) or ZoneCrossMixing
(two-way flow) to move air between the zones, but the user
must specify airflow rates and schedules for this flow. Other
modelers use AirFlowNetwork with large openings between the
zones as well as other openings and cracks in the exterior
envelope to provide the driving forces. ZoneMixing
flows can be linked to HVAC system operation using ZoneAirMassFlowConservation
or AirflowNetwork:Distribution:*. Construction:AirBoundary
has an option to automatically add a pair of ZoneMixing
objects.
- Solar gains and daylighting
-
gains in perimeter zones often project into a core zone
across an open air boundary. Normally, the only way to pass
solar and daylight from one zone to the next is through a
window or glass door described as a subsurface on an interzone
wall surface. Note that all solar is diffuse after passing
through an interior window. Construction:AirBoundary
provides the option to group adjacent zones into a common
enclosure for solar and daylighting distribution allowing both
direct and diffuse solar (and daylighting) to pass between the
adjacent zones. Construction:AirBoundary
also offers an option to automatically create a perfect
interior window instead of grouping the zones.
- Radiant (long-wave thermal) transfer
-
can be signifcant between exterior surfaces of a perimeter
zone and interior surfaces of a core zone with an open
boundary between them. Normally, there is no direct radiant
exchange between surfaces in different thermal zones. Construction:AirBoundary
provides the option to group adjacent zones into a common
enclosure for radiant exchange, allowing surfaces in different
zones to “see” each other. Construction:AirBoundary
also offers an option to automatically create an infrared
transparent surface (see Material:InfraredTransparent) instead
of grouping the zones.
- Visible and thermal radiant output
-
from internal gains will not normally cross zone
boundaries. Construction:AirBoundary
with the GroupedZones option for radiant exchange will
distribute these gains across all surfaces in the grouped
enclosure.
Air wall, Open air connection between zones[LINK]
Modeling the interactions between thermal zones which are connected by a large opening requires special consideration. EnergyPlus models only what is explicitly described in the input file, so simply leaving a void (no surfaces) between two zones will accomplish nothing - the two zones will not be connected. A building surface or fenestration surface with Construction:AirBoundary may be used connect the zones. Construction:AirBoundary has options for modeling the interactions which occur across the dividing line between two zones which are fully open to each other:
transfers both sensible heat and moisture. Some modelers use ZoneMixing (one-way flow) or ZoneCrossMixing (two-way flow) to move air between the zones, but the user must specify airflow rates and schedules for this flow. Other modelers use AirFlowNetwork with large openings between the zones as well as other openings and cracks in the exterior envelope to provide the driving forces. ZoneMixing flows can be linked to HVAC system operation using ZoneAirMassFlowConservation or AirflowNetwork:Distribution:*. Construction:AirBoundary has an option to automatically add a pair of ZoneMixing objects.
gains in perimeter zones often project into a core zone across an open air boundary. Normally, the only way to pass solar and daylight from one zone to the next is through a window or glass door described as a subsurface on an interzone wall surface. Note that all solar is diffuse after passing through an interior window. Construction:AirBoundary provides the option to group adjacent zones into a common enclosure for solar and daylighting distribution allowing both direct and diffuse solar (and daylighting) to pass between the adjacent zones. Construction:AirBoundary also offers an option to automatically create a perfect interior window instead of grouping the zones.
can be signifcant between exterior surfaces of a perimeter zone and interior surfaces of a core zone with an open boundary between them. Normally, there is no direct radiant exchange between surfaces in different thermal zones. Construction:AirBoundary provides the option to group adjacent zones into a common enclosure for radiant exchange, allowing surfaces in different zones to “see” each other. Construction:AirBoundary also offers an option to automatically create an infrared transparent surface (see Material:InfraredTransparent) instead of grouping the zones.
from internal gains will not normally cross zone boundaries. Construction:AirBoundary with the GroupedZones option for radiant exchange will distribute these gains across all surfaces in the grouped enclosure.