eplustbl.<ext>[LINK]
The eplustbl file contains the tabular output results that
are created when using the following objects:
The format and the extension for the file depends on the
setting of the ColumnSeparator field of the Output:Table:Style
object. The choices of HTML, tab, fixed, comma, and XML result
in eplustbl.htm, eplustbl.tab, eplustbl.txt, eplustbl.csv,
eplustbl.xml respectively. The HTML version of the report also
includes a table of contents that allows easier navigation
through the file.
By default the energy units reported in all of the eplustbl
files are in Joules (J) but the UnitConversion field of the
Output:Table:Style object allows for the values to be reported
in MJ, GJ or in kWh. In addition, the Output:Table:Style
object can specify for the tables to be in IP units for all
fields.
Output:Table:SummaryReports[LINK]
Several predefined reports are available from the Output:Table:SummaryReports
object including the following. (spaces are inserted in names
for readability; keys are included in the Input Data
Dictionary or by just removing the spaces):
Lists all following applicable tables with “Summary” in the
name.
Lists all following applicable tables with “Monthly” in the
name.
Lists all following applicable tables with both “Summary”
and “Monthly” in the name. This does not include the Zone
Component Load Summary report.
- All Summary and Sizing Period
Lists the All Summary tables as well as the Zone
Component Load report (currently the only Sizing Period
report). Please note that the Zone
Component Load report does increase the run time because it
repeats sizing periods.
- All Summary Monthly and Sizing Period
Lists the All Summary tables, the Monthly tables as well as
the Zone
Component Load report (currently the only Sizing Period
report). Please note that the Zone
Component Load report does increase the run time because it
repeats sizing periods.
Annual Building
Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Component Cost Economics Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
Zone
Component Load Summary
Zone
Cooling Summary Monthly
Zone
Heating Summary Monthly
Zone
Electric Summary Monthly
Space
Gains Monthly
Peak Space
Gains Monthly
Space
Gain Components At Cooling Peak Monthly
Energy Consumption Electricity Natural Gas
Monthly
Energy Consumption Electricity Generated Propane
Monthly
Energy Consumption Diesel FuelOil Monthly
Energy Consumption District Heating Cooling
Monthly
Energy Consumption Coal Gasoline Monthly
End Use Energy Consumption Electricity Monthly
End Use Energy Consumption NaturalGas Monthly
End Use Energy Consumption Diesel Monthly
End Use Energy Consumption FuelOil Monthly
End Use Energy Consumption Coal Monthly
End Use Energy Consumption Propane Monthly
End Use Energy Consumption Gasoline Monthly
Peak Energy End Use Electricity Part1 Monthly
Peak Energy End Use Electricity Part2 Monthly
Electric Components Of Peak Demand Monthly
Peak Energy End Use NaturalGas Monthly
Peak Energy End Use Diesel Monthly
Peak Energy End Use FuelOil Monthly
Peak Energy End Use Coal Monthly
Peak Energy End Use Propane Monthly
Peak Energy End Use Gasoline Monthly
Setpoints Not Met With Temperatures Monthly
Comfort Report Simple55 Monthly
Unglazed Transpired Solar Collector Summary
Monthly
Occupant Comfort Data Summary Monthly
Chiller Report Monthly
Tower Report Monthly
Boiler Report Monthly
DX Report Monthly
Window
Report Monthly
Window
Energy Report Monthly
Window
Zone
Summary Monthly
Window
Energy Zone
Summary Monthly
Average Outdoor Conditions Monthly
Outdoor Conditions Maximum DryBulb Monthly
Outdoor Conditions Minimum DryBulb Monthly
Outdoor Conditions Maximum WetBulb Monthly
Outdoor Conditions Maximum DewPoint Monthly
Outdoor Ground Conditions Monthly
WindowAC Report Monthly
Water Heater Report Monthly
Generator Report Monthly
Daylighting Report Monthly
Coil Report Monthly
PlantLoop
Demand Report Monthly
Fan Report Monthly
Pump Report Monthly
CondLoop Demand Report Monthly
Zone
Temperature Oscillation Report Monthly
AirLoop System Energy And Water Use Monthly
AirLoop System Component Loads Monthly
AirLoop System Component Energy Use Monthly
Mechanical Ventilation Loads Monthly
Each of these reports is made up of several sub-tables of
information. Examples of some of the tables are shown below.
To enable all of the reports the single All Summary may be
specified.
The Annual Building
Utility Performance Summary report provides an overview of
energy consumption in the building for different end uses. The
following is an example this report (some columns may be
truncated due to page size). The key used to obtain this
report is AnnualBuildingUtilityPerformanceSummary.
In the Comfort and Setpoint Not Met Summary
sub-table, facility hours represents the total number of hours
that any single zone did not meet the comfort or setpoint
criteria. It is not weighted by number of zones or number of
occupants.
The values in the End Uses sub-table are from
report meters. To determine which components are attached to
each end-use meter, consult the meter details output file
(*.mtd).
Report: Annual Building
Utility Performance Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Values gathered over 8760.00 hours
Site and Source Energy
| |
Total Energy (GJ) |
Energy Per Total Building Area
(MJ/m2) |
Energy Per Conditioned Building
Area (MJ/m2) |
| Total Site Energy |
194.80 |
210.09 |
210.09 |
| Net Site Energy |
194.80 |
210.09 |
210.09 |
| Total Source Energy |
532.25 |
574.04 |
574.04 |
| Net Source Energy |
532.25 |
574.04 |
574.04 |
Source to Site Energy Converstion Factors
| |
Source= > Site Conversion
Factor |
| Electricity |
3.167 |
| Natural Gas |
1.084 |
| District Cooling |
1.056 |
| District Heating |
3.613 |
| Steam |
0.300 |
| Gasoline |
1.050 |
| Diesel |
1.050 |
| Coal |
1.050 |
| Fuel Oil No 1 |
1.050 |
| Fuel Oil No 2 |
1050 |
| Propane |
1.050 |
Building
Area
| |
Area (m2) |
| Total Building Area |
927.20 |
| Net Conditioned Building
Area |
927.20 |
| Unconditioned Building Area |
0.00 |
End Uses
| |
Electricity (GJ) |
Natural Gas (GJ) |
Other Fuel (GJ) |
District Cooling (GJ) |
District Heating (GJ) |
Water (m3) |
| Heating |
0.00 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
18.18 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
7.03 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
|
| Total End Uses |
154.15 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
Note: Natural gas appears to be the principal heating
source based on energy usage.
End Uses By Subcategory
| |
Subcategory |
Electricity (GJ) |
Natural Gas (GJ) |
Other Fuel (GJ) |
District Cooling (GJ) |
District Heating (GJ) |
Water (m3) |
| Heating |
General |
0.00 |
40.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
General |
18.18 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
GeneralLights |
81.24 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
General |
47.70 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
General |
7.03 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Normalized Metrics
Utility Use Per Conditioned Floor Area
| |
Electricity Intensity
(MJ/m2) |
Natural Gas Intensity
(MJ/m2) |
Other Fuel Intensity
(MJ/m2) |
District Cooling Intensity
(MJ/m2) |
District Heating Intensity
(MJ/m2) |
Water Intensity (m3/m2) |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
27.19 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
166.25 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
Utility Use Per Total Floor Area
| |
Electricity Intensity
(MJ/m2) |
Natural Gas Intensity
(MJ/m2) |
Other Fuel Intensity
(MJ/m2) |
District Cooling Intensity
(MJ/m2) |
District Heating Intensity
(MJ/m2) |
Water Intensity (m3/m2) |
| Lighting |
87.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| HVAC |
27.19 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
| Other |
51.44 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
166.25 |
43.84 |
0.00 |
0.00 |
0.00 |
0.00 |
Electric Loads Satisfied
| |
Electricity (GJ) |
Percent Electricity (%) |
| Fuel-Fired Power Generation |
0.00 |
0.00 |
| High Temperature
Geothermal* |
0.00 |
0.00 |
| Photovoltaic Power |
0.00 |
0.00 |
| Wind Power* |
0.00 |
0.00 |
| Net Decrease in On-Site
Storage |
0.00 |
0.00 |
| Total On-Site Electric
Sources |
0.00 |
0.00 |
| |
|
|
| Electricity Coming From
Utility |
154.15 |
100.00 |
| Surplus Electricity Going To
Utility |
0.00 |
0.00 |
| Net Electricity From
Utility |
154.15 |
100.00 |
| |
|
|
| Total On-Site and Utility
Electric Sources |
154.15 |
100.00 |
| Total Electricity End Uses |
154.15 |
100.00 |
On-Site Thermal Sources
| |
Heat (GJ) |
Percent Heat (%) |
| Water-Side Heat Recovery |
0.00 |
|
| Air to Air Heat Recovery for
Cooling |
0.00 |
|
| Air to Air Heat Recovery for
Heating |
0.00 |
|
| High-Temperature
Geothermal* |
0.00 |
|
| Solar Water Thermal |
0.00 |
|
| Solar Air Thermal |
0.00 |
|
| Total On-Site Thermal
Sources |
0.00 |
|
Water Source Summary
| |
Water (m3) |
Percent Water (%) |
| Rainwater Collection |
0.00 |
- |
| Condensate Collection |
0.00 |
- |
| Groundwater Well |
0.00 |
- |
| Total On Site Water Sources |
0.00 |
- |
| - |
- |
- |
| Initial Storage |
0.00 |
- |
| Final Storage |
0.00 |
- |
| Change in Storage |
0.00 |
- |
| - |
- |
- |
| Water Supplied by Utility |
0.00 |
- |
| - |
- |
- |
| Total On Site, Change in
Storage, and Utility Water Sources |
0.00 |
- |
| Total Water End Uses |
0.00 |
- |
Comfort and Setpoint Not Met Summary
| |
Facility (Hours) |
| Time Set Point Not Met During
Occupied Heating |
0.00 |
| Time Set Point Not Met During
Occupied Cooling |
406.00 |
| Time Not Comfortable Based on
Simple ASHRAE 55-2004 |
1033.00 |
Note 1: An asterisk (*) indicates that the feature is not
yet implemented.
The Input Verification and Results Summary report provides
a summary of some of the most common input assumptions that
are not included in any of the other predefined reports.
Directly following is an example of the report. The key used
to obtain this report is
InputVerificationandResultsSummary.
Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
General
| |
Value |
| Program Version and Build |
EnergyPlus, Version 3.1 |
| Weather |
Chicago IL United States TMY2
94846 WMO#=725340 |
| Latitude (deg) |
41.78 |
| Longitude (deg) |
-87.8 |
| Elevation (m) |
190.00 |
| Time Zone |
-6.0 |
| North Axis Angle (deg) |
30.00 |
| Hours Simulated (hrs) |
8760.00 |
ENVELOPE
Window-Wall Ratio
| |
Total |
North (315 to 45 deg) |
East (45 to 135 deg) |
South (135 to 225 deg) |
West (225 to 315 deg) |
| Gross Wall Area (m2) |
274.20 |
91.50 |
45.60 |
91.50 |
45.60 |
| Window Opening Area (m2) |
61.65 |
20.85 |
9.12 |
22.56 |
9.12 |
| Window-Wall Ratio (%) |
22.48 |
22.79 |
20.00 |
24.66 |
20.00 |
Skylight-Roof Ratio
| |
Total |
| Gross Roof Area (m2) |
463.60 |
| Skylight Area (m2) |
0.00 |
| Skylight-Roof Ratio (%) |
0.00 |
PERFORMANCE
Zone
Summary
Note: In order to properly read the
summary rows of this table, the following rules apply:
If the Zone
Part of Total Floor Area is set to ‘No’, then it
will only be counted towards the "Not Part of Total"
row
Otherwise, it is added to the "Total" row. Then, if the
zone is also conditioned, it is added to the "Conditioned
Total" row; If unconditioned, it is added to the
"Unconditioned Total" row.
| Area |
[m2] Cond |
itioned (Y/N) Part |
of Total Floor Area (Y/N)
Volu |
me [m3] Mult |
i-pliers Abov |
e Ground Gross Wall Area [m2]
Unde |
rground Gross Wall Area [m2]
Wind |
ow Glass Area [m2] Open |
ing Area [m2] Ligh |
ting [W/m2] Peop |
le [m2 per person] Plug |
and Process [W/m2] |
| SPACE-1 |
200 |
Yes |
No |
400 |
1 |
20 |
0 |
0 |
0 |
4 |
300 |
4 |
| SPACE-2 |
100 |
No |
No |
200 |
1 |
50 |
0 |
0 |
0 |
1 |
100 |
1 |
| SPACE-3 |
1000 |
Yes |
Yes |
2000 |
1 |
180 |
0 |
40 |
5 |
20 |
10 |
10 |
| SPACE-4 |
500 |
No |
Yes |
1000 |
1 |
110 |
10 |
10 |
0 |
5 |
45 |
4 |
| Total |
1500 |
|
|
3000 |
|
290 |
10 |
50 |
5 |
15 |
13.5 |
8 |
| Conditioned Total |
1000 |
|
|
2000 |
|
180 |
0 |
40 |
5 |
20 |
10 |
10 |
| Unconditioned Total |
500 |
|
|
1000 |
|
110 |
10 |
10 |
0 |
5 |
45 |
4 |
| Not Part of Total |
300 |
|
|
600 |
|
70 |
0 |
0 |
0 |
3 |
180 |
3 |
Demand End Use
Components Summary[LINK]
The Demand End Use Components Summary report shows the
demand breakdown by component end use at the time that the
peak demand for each source of energy is set. The time of the
peak demand is shown in the first row. The contributions of
each end use at the time of the peak demand of the energy
source is shown in this report. The key used to obtain this
report is DemandEndUseComponentsSummary.
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
End Uses
| |
Electricity (W) |
Natural Gas (W) |
Propane (W) |
District Cooling (W) |
Steam (W) |
Water (m3/s) |
| Time of Peak |
02-JUL-14:00 |
31-DEC-07:15 |
- |
- |
- |
- |
| Heating |
0.00 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
12342.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
7500.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
4000.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
1498.36 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| |
|
|
|
|
|
|
| Total End Uses |
25340.97 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
End Uses By Subcategory
| |
Subcategory |
Electricity (W) |
Natural Gas (W) |
Propane (W) |
District Cooling (W) |
Steam (W) |
Water (m3/s) |
| Heating |
General |
0.00 |
81764.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Cooling |
General |
12342.62 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
GeneralLights |
7500.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
General |
4000.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
General |
1498.36 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Source
Energy End Use Components Summary[LINK]
The Source Energy End Use Components Summary report
produces a report that includes three tables. These tables
display source energy by fuel type that is calculated based on
site to source energy factors specified by the user in the EnvironmentalImpactFactors
and FuelFactors
objects. The last two tables display the source energy in
terms of area normalized metrics. Directly following is an
example of the three tables. The key used to obtain this
report is SourceEnergyEndUseComponentsSummary.
Report: Source Energy End Use Components
Summary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components
Summary
|
Source Electricity [GJ] |
Source Natural Gas [GJ] |
Source Other Fuel [GJ] |
Source District Cooling
[GJ] |
Source District Heating
[GJ] |
| Heating |
0.00 |
140.03 |
0.00 |
0.00 |
0.00 |
| Cooling |
167.65 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
569.39 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
325.49 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
55.72 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
7.57 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1125.82 140.03 0.00
0.00 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned
Floor Area
|
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1214.22 151.02 0.00
0.00 0.00
Source Energy End Use Components Per Total Floor
Area
|
Source Electricity [MJ/m2] |
Source Natural Gas [MJ/m2] |
Source Other Fuel [MJ/m2] |
Source District Cooling
[MJ/m2] |
Source District Heating
[MJ/m2] |
| Heating |
0.00 |
151.02 |
0.00 |
0.00 |
0.00 |
| Cooling |
180.82 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting |
614.09 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Equipment |
351.05 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Equipment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans |
60.10 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps |
8.16 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Humidification |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Recovery |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Water Systems |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Generators |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Total Source Energy End Use Components 1214.22 151.02 0.00
0.00 0.00
Equipment Summary[LINK]
The Equipment Summary report provides a summary of the HVAC
related equipment in the building. The central chiller example
shows the most common type of chillers, boilers and towers
used in EnergyPlus. The remaining subtables cover DX coils,
fans and water heating equipment. Not every type of HVAC
equipment is represented in this report. Directly following is
an example of the report. The key used to obtain this report
is EquipmentSummary.
Report: Equipment Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Central Plant
| |
Type |
Nominal Capacity (W) |
Nominal Efficiency (W/W) |
| None |
|
|
|
Cooling Coils
| |
Type |
Nominal Total Capacity (W) |
Nominal Sensible Capacity
(W) |
Nominal Latent Capacity (W) |
Nominal Sensible Heat Ratio |
Nominal Efficiency (W/W) |
| MAIN COOLING COIL 1 |
Coil:Cooling:DX:TwoSpeed |
37506.82 |
25504.64 |
12002.18 |
0.68 |
3.00 |
Heating Coils
| |
Type |
Nominal Total Capacity (W) |
Nominal Efficiency (W/W) |
| SPACE1-1 ZONE COIL |
Coil:Heating:Fuel |
17614.83 |
0.80 |
| SPACE2-1 ZONE COIL |
Coil:Heating:Fuel |
14619.82 |
0.80 |
| SPACE3-1 ZONE COIL |
Coil:Heating:Fuel |
16093.74 |
0.80 |
| SPACE4-1 ZONE COIL |
Coil:Heating:Fuel |
18942.35 |
0.80 |
| SPACE5-1 ZONE COIL |
Coil:Heating:Fuel |
19146.73 |
0.80 |
| MAIN HEATING COIL 1 |
Coil:Heating:Fuel |
19754.61 |
0.80 |
Fans
| |
Type |
Total Efficiency (W/W) |
Delta Pressure (pa) |
Max Flow Rate (m3/s) |
Rated Power (W) |
Motor Heat In Air Fraction |
End Use |
| SUPPLY FAN 1 |
Fan:VariableVolume |
0.70 |
600.00 |
2.27 |
1942.10 |
1.00 |
General |
Pumps
| |
Type |
Control |
Head (pa) |
Power (W) |
Motor Efficiency (W/W) |
| None |
|
|
|
|
|
Service Water Heating
| |
Type |
Storage Volume (m3) |
Input(W) |
Thermal Efficiency (W/W) |
Recovery Efficiency (W/W) |
Energy Factor |
| None |
|
|
|
|
|
|
Envelope Summary[LINK]
The Envelope Summary report provides a summary of the
elements of the envelope of the building. The first table
describes the exterior opaque elements and the second table
describes the fenestration elements. Reflectance is defined as
one minus the thermal absorptance. Directly following is an
example of the report. The key used to obtain this report is
EnvelopeSummary.
Report: Envelope Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Opaque Exterior
| |
Construction |
Reflectance |
U-Factor with Film (W/m2-K) |
U-Factor no Film (W/m2-K) |
Gross Area (m2) |
Azimuth (deg) |
Tilt (deg) |
Cardinal Direction |
| WALL-1PF |
WALL-1 |
0.22 |
0.384 |
0.41 |
18.30 |
210.00 |
90.00 |
S |
| WALL-1PR |
WALL-1 |
0.22 |
0.384 |
0.41 |
9.12 |
120.00 |
90.00 |
E |
| WALL-1PB |
WALL-1 |
0.22 |
0.384 |
0.41 |
18.30 |
30.00 |
90.00 |
N |
| WALL-1PL |
WALL-1 |
0.22 |
0.384 |
0.41 |
9.12 |
300.00 |
90.00 |
W |
| TOP-1 |
ROOF-1 |
0.35 |
0.268 |
0.28 |
463.60 |
210.00 |
0.00 |
|
| FRONT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
73.20 |
210.00 |
90.00 |
S |
| F1-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
99.16 |
30.00 |
180.00 |
|
| RIGHT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
36.48 |
120.00 |
90.00 |
E |
| F2-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
42.73 |
300.00 |
180.00 |
|
| BACK-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
73.20 |
30.00 |
90.00 |
N |
| F3-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
96.48 |
74.22 |
180.00 |
|
| LEFT-1 |
WALL-1 |
0.22 |
0.384 |
0.41 |
36.48 |
300.00 |
90.00 |
W |
| F4-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
42.73 |
120.00 |
180.00 |
|
| F5-1 |
FLOOR-SLAB-1 |
0.35 |
1.454 |
2.25 |
182.49 |
30.00 |
180.00 |
|
Fenestration
| |
Construction |
Area of One Opening (m2) |
Area of Openings (m2) |
U-Factor |
SHGC |
Visible Transmittance |
Shade Control |
Parent Surface |
Azimuth (deg) |
Cardinal Direction |
| WF-1 |
DBL CLR 3MM/13MM AIR |
16.56 |
16.56 |
2.72 |
0.763 |
0.812 |
No |
FRONT-1 |
210.00 |
S |
| DF-1 |
SGL GREY 3MM |
6.00 |
6.00 |
5.89 |
0.708 |
0.611 |
No |
FRONT-1 |
210.00 |
S |
| WR-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.72 |
0.763 |
0.812 |
No |
RIGHT-1 |
120.00 |
E |
| WB-1 |
DBL CLR 3MM/13MM AIR |
16.44 |
16.44 |
2.72 |
0.763 |
0.812 |
No |
BACK-1 |
30.00 |
N |
| DB-1 |
SGL GREY 3MM |
4.41 |
4.41 |
5.89 |
0.708 |
0.611 |
No |
BACK-1 |
30.00 |
N |
| WL-1 |
DBL CLR 3MM/13MM AIR |
9.12 |
9.12 |
2.72 |
0.763 |
0.812 |
No |
LEFT-1 |
300.00 |
W |
| Total or Average |
|
|
61.65 |
3.26 |
0.753 |
0.778 |
|
|
|
|
| North Total or Average |
|
|
20.85 |
3.39 |
0.751 |
0.769 |
|
|
|
|
| Non-North Total or Average |
|
|
40.80 |
3.19 |
0.755 |
0.782 |
|
|
|
|
Surface Shadowing
Summary[LINK]
The Surface Shadowing Summary report summarizes how the
surfaces may cast shadows on other surfaces. Directly
following is an example of the report. The key used to obtain
this report is SurfaceShadowingSummary.
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other
Surfaces
| |
Possible Shadow Casters |
| FRONT-1 |
MAIN SOUTH OVERHANG |Mir-MAIN
SOUTH OVERHANG | |
| SOUTH DOOR OVERHANG |
Mir-MAIN SOUTH OVERHANG
|WALL-1PF |FRONT-1 | |
| WALL-1PF |
Mir-MAIN SOUTH OVERHANG |SOUTH
DOOR OVERHANG |Mir-SOUTH DOOR OVERHANG | |
| MAIN SOUTH OVERHANG |
FRONT-1 | |
Subsurfaces (Windows and Doors) that may be Shadowed by
Surfaces
| |
Possible Shadow Casters |
| WF-1 |
FRONT-1 | |
| DF-1 |
FRONT-1 | |
| WR-1 |
RIGHT-1 | |
| WB-1 |
BACK-1 | |
| DB-1 |
BACK-1 | |
| WL-1 |
LEFT-1 | |
Shading Summary[LINK]
The Shading Summary report shows how much of each window is
sunlit at different times of the year and also includes a
summary of the window controls. Directly following is an
example of the report. The key used to obtain this report is
ShadingSummary.
Report: Shading Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Sunlit Fraction
| |
March 21 9am |
March 21 noon |
March 21 3pm |
June 21 9am |
June 21 noon |
June 21 3pm |
December 21 9am |
December 21 noon |
December 21 3pm |
| WF-1 |
0.00 |
0.00 |
0.43 |
0.00 |
0.00 |
0.00 |
0.30 |
0.52 |
0.86 |
| DF-1 |
0.73 |
0.26 |
0.62 |
0.00 |
0.00 |
0.28 |
0.90 |
0.69 |
0.92 |
| WR-1 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
| WB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| DB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| WL-1 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
Window
Control
| |
Name |
Type |
Shaded Construction |
Control |
Glare Control |
| none |
|
|
|
|
|
Lighting Summary[LINK]
The Lighting Summary report provides a description of the
interior and exterior lighting systems being simulated. It
also provides a summary of daylighting controls. The Interior
Lighting table has three columns that are explained below:
Scheduled Hours/Week [hr] - In the schedule shown, this
represents the average weekly sum of hourly values. It is
based on a full year even if the simulation is only performed
for part of the year. It is not affected by daylighting.
Hours/Week > 1% [hr] – This represents the average hours
per week that are above 1% of the design value.
Full Load Hours/Week [hr] – This is based on consumption
and hours that the consumption occurred. It is dependent on
the run period used. When simulating only a portion of the
year, the value depends on which days of the year (the number
of weekdays versus weekend days, for example) are simulated.
It also indicates the impact of daylighting control. Directly
following is an example of the report. The key used to obtain
this report is LightingSummary.
Report: Lighting Summary
For: Entire Facility
Timestamp: 2012-09-05 12:10:52
Interior Lighting
|
Zone |
Lighting Power Density
[W/m2] |
Zone Area [m2] |
Total Power [W] |
End Use Subcategory |
Schedule Name |
Scheduled Hours/Week [hr] |
Hours/Week > 1% [hr] |
Full Load Hours/Week [hr] |
Return Air Fraction |
Conditioned (Y/N) |
Consumption [GJ] |
| SPACE1-1 LIGHTS 1 |
SPACE1-1 |
15.9742 |
99.16 |
1584.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
17.16 |
| SPACE2-1 LIGHTS 1 |
SPACE2-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
HALFPERCENT |
0.60 |
0.00 |
0.59 |
0.2000 |
Y |
0.08 |
| SPACE3-1 LIGHTS 1 |
SPACE3-1 |
16.4179 |
96.48 |
1584.00 |
GeneralLights |
ALWAYSON |
168.00 |
168.00 |
168.00 |
0.2000 |
Y |
49.95 |
| SPACE4-1 LIGHTS 1 |
SPACE4-1 |
16.0056 |
42.73 |
684.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
7.41 |
| SPACE5-1 LIGHTS 1 |
SPACE5-1 |
16.2420 |
182.49 |
2964.00 |
GeneralLights |
LIGHTS-1 |
57.70 |
168.00 |
57.70 |
0.2000 |
Y |
32.11 |
| Interior Lighting Total |
|
16.1777 |
463.60 |
7500.00 |
|
|
|
|
|
|
|
106.70 |
Daylighting
|
Zone |
Daylighting Type |
Control Type |
Fraction Controlled |
Lighting Installed in Zone
[W] |
Lighting Controlled [W] |
| None |
|
|
|
|
|
|
Exterior Lighting
|
Total Watts |
Astronomical Clock/Schedule |
Schedule Name |
Scheduled Hours/Week [hr] |
Hours/Week > 1% [hr] |
Full Load Hours/Week [hr] |
Consumption [GJ] |
| Exterior Lighting Total |
0.00 |
|
|
|
|
|
0.00 |
HVAC Sizing Summary[LINK]
The HVAC Sizing Summary report provides information on the
zone cooling and heating sizing and the peak load conditions
as well as information about the system air flow sizing. The
Design Load is the zone sensible load only and it does not
include any system effects or ventilation loads. The user
specified design load and airflow and the values calculated by
the program are shown in the report along with the time of the
peak load and the temperature and humidity ratio at the time
of the peak during the sizing periods. This information is
generated for both the Zone
Sensible Cooling and Zone
Sensible Heating tables.
Also included is the System Design Air Flow Rates which
includes the calculated cooling air flow rate, the user
specified air flow rate for cooling, the calculated heating
air flow rate, and the user specified air flow rate for
heating.
Note: values listed as “calculated” are the
unaltered result of the zone or system sizing calculations,
using the design sizing period weather and schedules specified
in the input. Values listed as “user specified” are either the
calculated values modified by global or zone sizing factors or
values specified with the flow/zone or
flow/system design air flow method.
The HVAC Sizing Summary also includes a coil summary report
table. This is a large data table that collects a variety of
results organized by each individual coil. It can be viewed in
html or csv format but it expected to be used from the sqlite
database. The table has 87 columns and a row for each coil in
the building model. The column titles are also called fields
here, as in fields to use with a database query.
Throughout this table the special value of -999.0 is
deliberately used to signal that no data are available to
report for that coil for that field or column. This could be
for a variety of reasons such as, no sizing calculations in
the model, did not run design day full simulations, particular
fields only applies to certain types of coils, certain
calculations are only performed for particular coils, etc. If
you find a -999.0 in a situation where you think the value
should be available, please report it. Another special value
of -99999.0 may be encountered which is used within EnergyPlus
to signal that numeric input fields were set to Autosize,
Autocalculate, or left blank and in some cases this value will
carry into the coil report table.
The encyclopedic documentation that follows is important
because in many cases, very similiar data are available from
up to three separate fields and one must be careful to
understand the subtle differences and be aware that there is
some repetition of the similar types of data in the fields.
This is mainly because coil performance changes with the
conditions under which it operates and so an important part of
this table is describing each coil under different sets of
operating conditions.
There are three broad groupings of data fields in the
table:
Meta data. The meta data fields include string names to
identify the coil, where it is being used, names and types of
IDF objects involved, what some of the various sizing method
input choices were set to, and information about the supply
fan and plant found to be associated with the coil. 40
fields.
Ideal loads sizing summary. The collection of fields
whose names end with “at Ideal Loads Peak” are all related to
the sizing calculations done by the ideal loads zone sizing
routines and the system sizing routines based on them. Many of
the values reported here come from Sizing:Zone
and/or Sizing:System
input. The operating conditions occuring during Ideal Loads
sizing calculations are unlikely to match the conditions used
in the definitions for coil input data. 36 fields.
Rating point summary. This is a collection of fields
with names that end in “at Rating Conditions.” The model input
data for many types of coils is based on defined set of
conditions variously referred to as the rating point,
reference, nominal, or design. The coil models are calculated
with conditions set to match the rating point and the inputs
and outputs from that are reported here. Many of the values
here are from the input documentation that defines the
conditions at the rating point. The coil capacities and
leaving conditions are the results from the running complete
coil model. Some coil models do not have a rating point as
part of the model definition, because the models are not
sensitive to operating conditions, and those coils will have
-999.0 in these fields. 11 fields.
The following is a comprehensive listing of each
column/field in the coil summary table with a brief definition
and/or summary.
Coil Type The input object class name in IDF
syntax. Text string.
Coil Location The broad type of HVAC this coil is
being used in. “AirLoop” means the coil is part of a central
air system, such as a main coil in a multizone air handler.
“Zone
Equipment” means that the coil is part of Zone
equipment like a PTAC, or in the zone terminal unit of an
airhandler like a VAV reheat coil. Text string.
HVAC Type This is more specifically what HVAC the
coil is used in. The values are the input object class name,
in IDF syntax, found to be associated with the coil. Text
string.
HVAC Name This is the unique user name input for
the HVAC Type. The strings will be converted to upper
case compared to what is in the actual input data file. Text
string.
Zone
Name(s) This is the zone, or list of zones, found to be
associated with this coil. The zone name is defined by the
user in the Zone
object. For multizone systems, the coils can have a list of
zone names with the individual names separated by a semicolon.
The zones listed here are those used to generate (aggregate
and volume-weighted average) values for the room conditions
and loads. Text string.
System Sizing Method Concurrence This field
applies to “AirLoop” coils. It describes if the central air
system sizing was done using “Coincident” or “Non-Coincident”
method. This refers to how the ideal loads sizing routines
process the time sequence of zone loads. The concurrent sum of
peaks, or coincident or "block", is often lower than the sum
of the individual peaks regardless of when they occur, or
non-conicident sum. This field is not applicable to “Zone
Equipment” coils and will show “N/A” here. This corresponds to
the input field called Type of Zone
Sum to Use in the Sizing:System
input object. Text string.
System Sizing Method Capacity This field applies
to “AirLoop” coils. It describes what was chosen for the
method of determining coil capacity during ideal loads sizing
routines. The values here will match the input key choices
available for the the Sizing:System
object’s input fields called Cooling Design Capacity
Method, for cooling coils, and Heating Design
Capacity Method, for heating coils. Values here of
“HeatingDesignCapacity” or “CoolingDesignCapacity” mean that
the coil was sized using the design loads calculated from the
zone ideal loads results. When sizing was scaled using floor
area the value here would be “CapacityPerFloorArea.” Values of
FractionOfAutosizedHeatingCapacity and
FractionOfAutosizeCoolingCapacity mean that the usual
design load based results were further scaled by a separate
user scaling factor. This field is not applicable to “Zone
Equipment” coils and will show “N/A” here. Text string.
System Sizing Method Air Flow This field applies
to “AirLoop” coils. It describes what was chosen for the
method of determining the system air flow rate during ideal
loads sizing routines. This field is not applicable to “Zone
Equipment” coils and will show “N/A” here. Text string.
Autosized Coil Capacity? This field describes if
the coil capacity was autosized or not. Values here will be
“Yes” or “No.” A “No” means that the size of the coil was set
at input, hard sized, and no capacity sizing calculations were
done for the coil. A “Yes” means that coil’s capacity was
autosized. Text string.
Autosized Coil Airflow? This field describes if
the coil’s airflow rate was autosized or not. Values here will
be “Yes” or “No.” A “No” means that the airflow rate used to
size the coil’s capacity was set at input, hard sized. This
means that the coil’s capacity was set for an airflow rate
that was not autosized. A “Yes” means that the airflow rate
for the coil came from sizing calculations. Text string.
Autosized Coil Water Flow? This field describes if
the coil’s water flow rate was autosized or not. Values here
will be “Yes” or “No.” A “No” means that the water flow rate
used to size the coil’s capacity was set at input, hard sized.
This means that the coil’s capacity was set for a water flow
rate that was not autosized. A “Yes” means that the water flow
rate for the coil came from sizing calculations. This field is
only applicable to water-to-air coils. Text string.
OA Pretreated prior to coil inlet? This field
describes if the coil’s sizing calculations are based on the
outdoor air being preconditioned, as with a separate coil, or
if the outdoor air is unconditioned. Values here will be “Yes”
or “No.” A “No” means that the outdoor air is not
preconditioned. A “Yes” means that the outdoor is
preconditioned. This field only really applies to central air
system coils. The outdoor air may be mixed with return air
before the coil, but that mixed air may be based on either
treated or untreated outdoor air, depending on Sizing:System
input. Text string.
Coil Final Gross Total Capacity [W] This field
describes the coil’s gross total capacity, in units of W. No
fan impact. This field will generally be the main value the
model uses for capacity as a result of the sizing
calculations. However if a coil was not autosized, the
capacity was hard sized on input, then this field will be
filled with the hard sized coil capacity (if that is a
parameter in the coil model). This field is very similiar to
the field called Coil Total Capacity at Rating Conditions with
the difference being that this one is the model input while
that other one is the result of running the full coil model at
the rating point conditions. Water heating coil models using
UA and design water flow rate performance input method do not
have a single design capacity in Watts and this field will
show as -99999.0 (and the coil is better characterized using
the field called Coil U-value Times Area Value). Real
number.
Coil Final Gross Sensible Capacity [W] Real
number. This field describes the coil’s gross sensible
capacity, if available, in units of W. No fan impact. This
field is generally the total capacity multiplied by the
sensible heat ratio if both are defined in the model. Real
number.
Coil Final Reference Air Volume Flow Rate [m3/s]
This field describes the coil’s rated/reference/nominal air
flow rate, in units of m3/s. This field will generally be the
model input (or autosize result) for the process air flow rate
through the coil at the rating point. Some coil models do not
have any rated/reference/nominal air flow rate as part of the
model description (d.g. electric and gas heating coils) and
these will have -999.0 in this field. Real number.
Coil Final Reference Plant Fluid Volume Flow Rate
[m3/s] This field describes the coil’s
rated/reference/nominal water flow rate, in units of m3/s.
This field will be the model input or autosize result for the
source water, or other plant fluid type, flow rate through the
coil at the design or rating point. Many coils have no water
source and these will have -999.0 in this field. Real
number.
Coil U-value Times Area Value [W/K] This field
describes the coil’s overall UA value, in units of W/K. This
is mainly for the Coil:Heating:Water
coil using the Performance Input method of
UFactorTimesAirAndDesignWaterFlowRate and is not avaliable for
other coils. This will be the result from the ideal loads
sizing calculations or the hard sized entry. Real number.
Terminal Unit Reheat Coil Multiplier This field
describes the coil sizing multiplier that might have affected
the calculated size of a coil used as a reheat coil in a zone
air terminal unit. This is a non-dimensional scaling factor.
Real number.
DX Coil Capacity Increase Ratio from Too Low
Flow/Capacity Ratio This field describes sizing
adjustments that can occur for DX coils when the combination
of capacity and air flow rate is outside of prescribed limits.
If the air flow to capacity ratio was too low this will ratio
will show how the capacity was increased to force the result
into the prescribed range. Real Number.
DX Coil Capacity Decrease Ratio from Too High
Flow/Capacity Ratio This field describes sizing
adjustments that can occur for DX coils when the combination
of capacity and air flow rate is outside of prescribed limits.
If the air flow to capacity ratio was too high this will ratio
will show how the capacity was decreased to force the result
into the prescribed range. Real Number.
Moist Air Heat Capacity [J/kg-K] This is the moist
air heat capacity, cp, that is applicable to coil
calculations. Real number.
Dry Air Heat Capacity [J/kg-K] This is the dry air
heat capacity, cp, that is applicable to coil calculations.
Real number.
Standard Air Density Adjusted for Elevation
[kg/m3] This is the dry air density, adjusted for
elevation above sea level, that is applicable to coil
calculations. Real number.
Supply Fan Name for Coil The program tries to
detect the supply fan associated with the coil. This field is
the user-defined name for that fan. Text string.
Supply Fan Type for Coil The program tries to
detect the supply fan associated with the coil. The values are
the input object class name, in IDF syntax, for the fan. Text
string.
Supply Fan Maximum Air Volume Flow Rate [m3/s]
This field is the design volume flow rate, in units of m3/s,
for the fan found to be associated with the coil. Real
number
Supply Fan Maximum Air Mass Flow Rate [kg/s] This
field is the design mass flow rate, in kg/s, for the fan found
to be associated with the coil. Real number
Plant Name for Coil If the coil is a water-to-air
or steam coil, then the program tries to detect the central
plant system serving the coil. This field is the user-defined
name for that plant system. This will be the name in the PlantLoop
and Sizing:Plant
objects. The next nine fields provides various results for
that the central plant loop system. If the coil is not a water
or steam coil, then this field will have “unknown” as the
value. Text string.
Plant Fluid Specific Heat Capacity [J/kg-K] This
is the specific heat of the fluid circulating through the
plant and serving the coil, in units of J/kg-K. This is
evaulated at the temperature used for sizing calculations. The
plant need not always be water, glycol mixtures and steam are
supported and this value will be adjusted accordingly. If the
coil is not served by a plant, then this field will have
-999.0 as the value. Real number.
Plant Fluid Density [kg/m3] This is the density of
the fluid circulating through the plant and serving the coil,
in units of kg/m3. This is evaulated at the temperature used
for sizing calculations. The plant need not always be water,
glycol mixtures are supported and this value will be adjusted
accordingly. If the coil is not served by a plant, then this
field will have -999.0 as the value. Real number.
Plant Maximum Fluid Mass Flow Rate [kg/s] This
field is the design flow rate for the (entire) central plant
system serving the coil, in units of kg/s. This value is the
final outcome from plant sizing calculations, or perhaps from
the hard-sized value entered in the PlantLoop
object for the maximum volume flow rate. If the coil is not
served by a plant, then this field will have -999.0 as the
value. Real number.
Plant Design Fluid Return Temperature [C] This is
the value, in degrees Celsius, used in sizing calculations for
the temperature of the fluid returning to the supply side of
the plant system. It is derived from values entered in the Sizing:Plant
object (except for steam which depends on subcooling input).
If the coil is not served by a plant, then this field will
have -999.0 as the value. Real number.
Plant Design Fluid Supply Temperature [C] This is
the value, in degrees Celsius, used in the sizing calculations
for the temperature of the fluid leaving the supply side of
the plant system and going into the coils. This is the value
entered in the Sizing:Plant
object in the input field called Design Loop Exit Temperature
(except for steam which is 100 C). If the coil is not served
by a plant, then this field will have -999.0 as the value.
Real number.
Plant Design Fluid Temperature Difference [Delta
C] This is the value, in degrees Celsius (difference),
used in the sizing calculations for the temperature difference
between the plant supply and return temperatures. This is the
value entered in the Sizing:Plant
object in the input field called Loop Design Temperature
Difference (except for steam it is the amount of subcooling in
the coil). If the coil is not served by a plant, then this
field will have -999.0 as the value. Real number.
Plant Design Capacity [W] This is the design
capacity of the central plant system, in Watts, that is the
result of the sizing calculations. For steam plants it is the
capacity of the steam boiler attached to the supply side of
the plant. If the coil is not served by a plant, then this
field will have -999.0 as the value. Real number.
Coil Capacity Percentage of Plant Design Capacity
[%] The coil being reported on here will be one among
many others that might be also be attached to the same plant.
This field compares this coil’s (design gross) total capacity
to the central plant’s design capacity, W/W, and gives a value
in percentage from 0.0 to 100.0. If the coil is not served by
a plant, then this field will have -999.0 as the value. Real
Number.
Coil Fluid Flow Rate Percentage of Plant Design Flow
Rate [%] The coil being reported on here will be one
among many others that might be also be attached to the same
plant. This field compares this coil’s design flow rate to the
central plant’s design flow rate, kg/s/kg/s, and gives a value
in percentage from 0.0 to 100.0. If the coil is not served by
a plant, then this field will have -999.0 as the value. Real
Number.
Design Day Name at Sensible Ideal Loads Peak This
field is the name of the design day selected to have the
sensible load peak for ideal loads sizing calculations. The
text here will be from the user-defined names entered in the
name field of the SizingPeriod:DesignDay
objects. If this is a cooling coil, the load peak will be for
sensible cooling loads and the name here will be from one of
the cooling design days. If this is a heating coil, the load
peak will be for sensible heating loads and the name from the
heating design days. Text String.
Date/Time at Sensible Ideal Loads Peak This field
provides the result for the date and time of day when the
sensible load peak was found to occur. The format is (M)M/(D)D
HH:MM:00, eg. 1/1 06:00:00 or 12/11 06:00:00. There is no
specific year associated with design days. Text String.
Design Day Name at Total Ideal Loads Peak The name
of the design day selected to have the total load peak for
ideal loads sizing calculations. The text here will be from
the user-defined names entered in the name field of the SizingPeriod:DesignDay
objects. If this is a cooling coil, the load peak will be for
total cooling loads and the name here will be from one of the
cooling design days. If this is a heating coil, this field
usually “unknown” because EnergyPlus does not use a total load
for heating sizing. Text String.
Date/Time at Total Ideal Loads Peak This field
provides the result for the date and time of day when the
total load peak was found to occur during ideal loads sizing.
The format is (M)M/(D)D HH:MM:00, eg. 1/1 06:00:00 or 12/11
06:00:00. There is no specific year associated with design
days. If the ideal loads sizing calculations never determine a
total load the value here will be “unknown.” Text String.
Design Day Name at Air Flow Ideal Loads Peak This
field is the name of the design day selected to have the air
flow peak for ideal loads sizing calculations. The text here
will be from the user-defined names entered in the name field
of the SizingPeriod:DesignDay
objects. If this is a cooling coil, the air flow peak might be
calculated separately and the name here will be from one of
the cooling design days. If this is a heating coil, the air
flow peak will be the same as the sensible load peak. Text
String.
Date/Time at Air Flow Ideal Loads Peak This field
provides the result for the date and time of day when the air
flow peak was found to occur. The format is (M)M/(D)D
HH:MM:00, eg. 1/1 06:00:00 or 12/11 06:00:00. There is no
specific year associated with design days. Text String.
Coil Total Capacity at Ideal Loads Peak [W] This
field is the coil’s gross total capacity, in Watts, resulting
from the ideal loads sizing calculations. This is the total,
sensible plus latent, capacity under the conditions used for
ideal loads sizing described in other “Ideal Loads Peak”
fields. This does not include the supply fan impacts. Real
Number.
Coil Sensible Capacity at Ideal Loads Peak [W]
This field is the coil’s gross sensible capacity, in Watts,
resulting from the ideal loads sizing calculations. This is
the sensible capacity under the conditiosn used for ideal
loads sizing described in the other “Ideal Loads Peak” fields.
This does not include the supply fan impacts. Real number.
Coil Off-Rating Capacity Modifier at Ideal Loads Peak [
] This field is the capacity modification factor for the
conditions during ideal loads sizing. The coil model may have
performance curves that alter the capacity as a function of
the conditions experienced by the coil. When the ideal loads
sizing conditions are different than the conditions that the
performance curves are normalized to, the rating point, the
coil is being sized at “Off-rating.” This value can be used to
convert the Coil Total Capacity at Ideal Loads Peak to what
the capacity should be at the rating point. The ideal loads
sizing is often not at the rating point because of a fraction
of outdoor air has been mixed into the entering air. Real
number.
Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s]
This field is the coil’s air mass flow rate, in kg/s,
resulting from, and/or used during, the ideal loads sizing
calculations. Real number.
Coil Air Volume Flow Rate at Ideal Loads Peak
[m3/s] This field is the coil’s air volume flow rate, in
m3/s, resulting from, and/or used during, the ideal loads
sizing calculations. Real number.
Coil Entering Air Drybulb at Ideal Loads Peak [C]
This field is the drybulb temperature, in degrees Celsius, of
the air entering the coil during ideal loads sizing
calculations. Real number.
Coil Entering Air Wetbulb at Ideal Loads Peak [C]
This field is the wetbulb temperature, in degrees Celsius, of
the air entering the coil during ideal loads sizing
calculations. Real number.
Coil Entering Air Humidity Ratio at Ideal Loads Peak
[kg-H2O/kg-DryAir] This field is the humidity ratio, in
kg-water/kg-dryAir, of the air entering the coil during ideal
loads sizing calculations. Real number.
Coil Entering Air Enthalpy at Ideal Loads Peak
[J/(kg-C)] This field is the enthalpy, in J/kg-C (base
0.0 at drybulb = 0.0C), of the air entering the coil during
ideal loads sizing calculations. Real number.
Coil Leaving Air Drybulb at Ideal Loads Peak [C]
This field is the drybulb temperature, in degrees Celsius, of
the air leaving the coil during the ideal loads sizing
calculations for the coil. Real number.
Coil Leaving Air Wetbulb at Ideal Loads Peak [C]
This field is the wetbulb temperature, in degrees Celsius, of
the air leaving the coil during ideal loads sizing
calculations. Real number.
Coil Leaving Air Humidity Ratio at Ideal Loads Peak
[C] This field is the humidity ratio, in
kg-water/kg-dryAir, of the air leaving the coil during ideal
loads sizing calculations. Real number.
Coil Leaving Air Enthalpy at Ideal Loads Peak
[J/(kg-C)] This field is the enthalpy, in J/kg-C (base
0.0 at drybulb = 0.0C), of the air leaving the coil during
ideal loads sizing calculations. Real number.
Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak
[kg/s] This field is the design or maximum water flow
rate, in kg/s, of the plant fluid serving the coil during
ideal loads sizing calculations. If the coil is not a water
coil then this field will have a value of -999.0. Real
number.
Coil Entering Plant Fluid Temperature at Ideal Loads
Peak [C] This field is the water temperature, in degrees
Celsius, of the plant fluid entering the coil during ideal
loads sizing calculations. If the coil is not a water coil
then this field will have a value of -999.0. Real number.
Coil Leaving Plant Fluid Temperature at Ideal Loads
Peak [C] This field is the water temperature, in degrees
Celsius, of the plant fluid leaving the coil during ideal
loads sizing calculations. If the coil is not a water coil
then this field will have a value of -999.0. Real number.
Coil Plant Fluid Temperature Difference at Ideal Loads
Peak [Delta C] This field is the water temperature
difference across the coil, in degrees Celsius (difference),
of the plant fluid passing through the coil during ideal loads
sizing calculations. If the coil is not a water coil then this
field will have a value of -999.0. Real number.
Supply Fan Air Heat Gain at Ideal Loads Peak [W]
This field is the fan load that was included in the ideal
loads sizing calculations. This may only be included in
calculations for central air system cooling coils. If the coil
was not sized with fan heat gain taken into account, then this
value will be 0.0 (even though there still is a fan with heat
during normal operation). Real number.
Coil and Fan Net Total Capacity at Ideal Loads Peak
[W] This field shows the net coil total capacity which is
the gross total capacity with the fan heat gain, if any was
calculated. Real number.
Outdoor Air Drybulb at Ideal Loads Peak [C] This
field is the outdoor air drybulb temperature, in degrees
Celsius, used during the ideal loads sizing calculations. Real
number.
Outdoor Air Humidity Ratio at Ideal Loads Peak
[kg-H2O/kg-DryAir] This field is the outdoor air humidity
ratio, in kg of water per kg of dry air, used during the ideal
loads sizing calculations. Real number.
Outdoor Air Wetbulb at Ideal Loads Peak [C] This
field is the outdoor air wetbulb temperature, in degrees
Celsius, used during the ideal loads sizing calculations. Real
number.
Outdoor Air Volume Flow Rate at Ideal Loads Peak
[m3/s] This field is the outdoor air volume flow rate, in
m3/s, that occurred during the ideal loads sizing
calculations. Real number.
Outdoor Air Flow Percentage at Ideal Loads Peak
[%] This field is the percentage of outdoor air in the
air entering the coil that occurred during the ideal loads
sizing calculations. Real number.
System Return Air Drybulb at Ideal Loads Peak [C]
This field is the drybulb temperature, in degrees C, of air
returning into the HVAC system that occurred during the ideal
loads sizing calculations. Real number.
System Return Air Humidity Ratio at Ideal Loads Peak
[kg-H2O/kg-DryAir] This field is the humidity ratio, in
kg of water per kg of dry air, of air returning into the HVAC
system that occurred during the ideal loads sizing
calculations. Real number.
Zone
Air Drybulb at Ideal Loads Peak [C] This field is the
drybulb temperature, in degrees C, of the zone air that
occurred during the ideal loads sizing calculations. For
multizone system this is the supply-air-volume-flow-weighted
average. Real number.
Zone
Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir]
This field is the humidity ratio, in kg of water per kg of dry
air, of the zone air that occurred during the ideal loads
sizing calculations. For multizone system this is the
supply-air-volume-flow-weighted-weighted average. Real
number.
Zone
Air Relative Humidity at Ideal Loads Peak [%] This field
is the percent relative humidity of the zone air that occurred
during the ideal loads sizing calculations. For multizone
system this is the supply-air-volume-flow-weighted-weighted
average. Real number.
Zone
Sensible Heat Gain at Ideal Loads Peak [W] This field is
the zone sensible load, in Watts, found during ideal loads
sizing. For multizone system it is the sum of all the zones on
the air system. Real number.
Zone
Latent Heat Gain at Ideal Loads Peak [W] This field is
the zone latent load, in Watts, found during ideal loads
sizing. For multizone system it is the sum of all the zones on
the air system. Real number.
Coil Total Capacity at Rating Conditions [W] This
field is the gross total capacity of the coil when operated at
the rating point conditions, in units of Watts. This is the
result from calculating the full coil model under the
operating conditions specified for the rating point. Real
number.
Coil Sensible Capacity at Rating Conditions [W]
This field is the gross sensible capacity of the coil when
operated at the rating point conditions, in units of Watts.
This is the result from calculating the full coil model under
the operating conditions specified for the rating point. Real
number.
Coil Air Mass Flow Rate at Rating Conditions
[kg/s] This field is the air mass flow rate, in units of
kg/s, used when calculating the full coil model under the
operating conditions specified for the rating point. Real
number.
Coil Entering Air Drybulb at Rating Conditions [C]
This field is the coil air inlet drybulb temperature, in
degrees Celsius, used when calculating the full coil model
under the operating conditions specified for the rating point.
The value should match the definition of the rating point as
described in the coil model input documentation. For DX
cooling coils, this will be 26.6667C or 80F. Real number.
Coil Entering Air Wetbulb at Rating Conditions [C]
This field is the coil air inlet wetbulb temperature, in
degrees Celsius, used when calculating the full coil model
under the operating conditions specified for the rating point.
The value should match the definition of the rating point as
described in the coil model input documentation. For DX
cooling coils, this will be 19.444C or 67F. Real number
Coil Entering Air Humidity Ratio at Rating Conditions
[kg-H20/kg-DryAir] This field is the coil air inlet
humidity ratio, in kg-water/kg-dryAir, used when calculating
the full coil model under the operating conditions specified
for the rating point. Real number.
Coil Entering Air Enthalpy at Rating Conditions
[J/(kg-C)] This field is the coil air inlet enthalpy, in
J/kg-C with zero base at 0.0C, used when calculating the full
coil model under the operating conditins specified for the
rating point. Real number.
Coil Leaving Air Drybulb at Rating Conditions [C]
This field is the coil air outlet drybulb, in degrees Celsius,
from calculating the full coil model under the operating
conditions specified for the rating point. Real number.
Coil Leaving Air Wetbulb at Rating Conditions [C]
This field is the coil air outlet wetbulb, in degrees Celsius,
from calculating the full coil model under the operating
conditions specified for the rating point. Real number.
Coil Leaving Air Humidity Ratio at Rating Conditions
[kg-H20/kg-DryAir] This field is the coil air outlet
humidity ratio, in kg-water/kg-dryair, from calculating the
full coil model under the operating conditions specified for
the rating point. Real number.
Coil Leaving Air Enthalpy at Rating Conditions
[J/(kg-C)] This field is the coil air outlet enthalpy, in
J/kg-C with zero base at 0.0C, from calculating the full coil
model under the operating conditions specified for the rating
point. Real number. Directly following is an example of the
report.
The key used to obtain this report is
HVACSizingSummary.
Report: HVAC Sizing Summary
For: Entire Facility
** Timestamp: **2011-09-23 15:09:34
Zone
Sensible Cooling
|
Calculated Design Load [W] |
User Design Load [W] |
Calculated Design Air Flow
[m3/s] |
User Design Air Flow [m3/s] |
Design Day Name |
Date/Time Of Peak |
Temperature at Peak [C] |
Humidity Ratio at Peak
[kgWater/kgAir] |
| SPACE1-1 |
2647.33 |
2647.33 |
0.223 |
0.223 |
CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
7/21 15:45:00 |
31.02 |
0.01459 |
| SPACE2-1 |
2234.38 |
2234.38 |
0.188 |
0.188 |
CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
7/21 10:00:00 |
27.43 |
0.01459 |
| SPACE3-1 |
2506.34 |
2506.34 |
0.211 |
0.211 |
CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
7/21 15:00:00 |
31.50 |
0.01459 |
| SPACE4-1 |
2464.72 |
2464.72 |
0.207 |
0.207 |
CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
7/21 17:30:00 |
29.47 |
0.01459 |
| SPACE5-1 |
2628.69 |
2628.69 |
0.221 |
0.221 |
CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
7/21 15:00:00 |
31.50 |
0.01459 |
Zone
Sensible Heating
|
Calculated Design Load [W] |
User Design Load [W] |
Calculated Design Air Flow
[m3/s] |
User Design Air Flow [m3/s] |
Design Day Name |
Date/Time Of Peak |
Temperature at Peak [C] |
Humidity Ratio at Peak
[kgWater/kgAir] |
| SPACE1-1 |
3860.76 |
3860.76 |
0.117 |
0.117 |
CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
1/21 24:00:00 |
-17.30 |
0.00084 |
| SPACE2-1 |
1625.15 |
1625.15 |
0.049 |
0.049 |
CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
1/21 24:00:00 |
-17.30 |
0.00084 |
| SPACE3-1 |
3753.07 |
3753.07 |
0.113 |
0.113 |
CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
1/21 24:00:00 |
-17.30 |
0.00084 |
| SPACE4-1 |
1625.15 |
1625.15 |
0.049 |
0.049 |
CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
1/21 24:00:00 |
-17.30 |
0.00084 |
| SPACE5-1 |
2981.57 |
2981.57 |
0.090 |
0.103 |
CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
1/21 24:00:00 |
-17.30 |
0.00084 |
System Design Air Flow Rates
|
Calculated cooling [m3/s] |
User cooling [m3/s] |
Calculated heating [m3/s] |
User heating [m3/s] |
| VAV SYS 1 |
1.05 |
1.05 |
0.43 |
0.43 |
Plant Loop Coincident Design Fluid Flow Rate
Adjustments
|
Previous Design Volume Flow Rate
[m3/s] |
Algorithm Volume Flow Rate
[m3/s] |
Coincident Design Volume Flow
Rate [m3/s] |
Coincident Size Adjusted |
Peak Sizing Period Name |
Peak Day into Period |
Peak Hour Of Day |
Peak Step Start Minute |
| COOLSYS1 Sizing Pass 1 |
0.120672 |
0.141525 |
0.141525 |
Yes |
CHICAGO ANN CLG .4% CONDNS WB=
> MDB HVAC Sizing Pass 1 |
1 |
2 |
30 > |
| HEATSYS1 Sizing Pass 1 |
0.060598 |
0.049054 |
0.049054 |
Yes |
CHICAGO ANN HTG 99.6% CONDNS DB
HVAC Sizing Pass 1 |
1 |
7 |
20 > |
System Summary[LINK]
The System Summary report provides information about some
of the primary components in the system including the
economizer and demand controlled ventilation. In addition,
this report describes when the zone conditions are not
comfortable or when set points are not met.
In the Time Not Comfortable Based on Simple ASHRAE
55-2004 and Time Setpoint Not Met sub-tables, The
reported time represents the total number of hours that a
given zone did not meet the comfort or setpoint criteria. For
the Facility row, this is the total numbers of hours that one
or more zones were out of range. The values are not weighted
by number of zones or number of occupants.
Directly following is an example of the report. The key
used to obtain this report is SystemSummary.
Report: System Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Economizer
| |
High Limit Shutoff Control |
Minimum Outside Air (m3/s) |
Maximum Outside Air (m3/s) |
Return Air Temp Limit |
Return Air Enthalpy Limit |
Outside Air Temperature Limit
(C) |
Outside Air Enthalpy Limit
(C) |
| none |
|
|
|
|
|
|
|
Demand Controlled Ventilation using
VENTILATION:MECHANICAL
| |
Ventilation:Mechanical Name |
Outside Air Per
Person(m3/s-person) |
Outside Air Per Area
(m3/s-m2) |
| none |
|
|
|
Time Not Comfortable Based on Simple ASHRAE 55-2004
| |
Winter Clothes (hr) |
Summer Clothes (hr) |
Summer or Winter Clothes
(hr) |
| SPACE1-1 |
429.00 |
1913.75 |
79.25 |
| SPACE2-1 |
739.25 |
1719.75 |
22.50 |
| SPACE3-1 |
482.00 |
1885.50 |
85.50 |
| SPACE4-1 |
588.25 |
2039.75 |
59.50 |
| SPACE5-1 |
14.75 |
2535.75 |
14.75 |
| PLENUM-1 |
0.00 |
0.00 |
0.00 |
| Facility |
1041.75 |
2564.75 |
97.00 |
Time Setpoint Not Met
| |
During Heating (hr) |
During Cooling (hr) |
During Occupied Heating
(hr) |
During Occupied Cooling
(hr) |
| SPACE1-1 |
321.00 |
45.25 |
35.00 |
45.25 |
| SPACE2-1 |
104.25 |
44.00 |
0.25 |
10.75 |
| SPACE3-1 |
297.50 |
0.75 |
36.25 |
0.75 |
| SPACE4-1 |
77.75 |
27.00 |
0.25 |
0.00 |
| SPACE5-1 |
292.25 |
1.00 |
13.75 |
1.00 |
| PLENUM-1 |
0.00 |
0.00 |
0.00 |
0.00 |
| Facility |
333.50 |
117.00 |
37.25 |
56.75 |
Component Sizing
Summary[LINK]
The Component Sizing Summary report includes details on
many of the HVAC components in the simulation. For each of the
components, one or more parameters are shown. Directly
following is an example of the report. The key used to obtain
this report is ComponentSizingSummary.
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
SINGLE DUCT:VAV:REHEAT
| |
Maximum air flow rate
[m3/s] |
Max Reheat Water Flow
[m3/s] |
| SPACE1-1 VAV REHEAT |
0.226630 |
0.000059 |
| SPACE2-1 VAV REHEAT |
0.176548 |
0.000046 |
| SPACE3-1 VAV REHEAT |
0.209331 |
0.000054 |
| SPACE4-1 VAV REHEAT |
0.222526 |
0.000058 |
| SPACE5-1 VAV REHEAT |
0.221695 |
0.000057 |
COIL:Water:SimpleHeating
| |
Max Water Flow Rate of Coil
[m3/s] |
Design Coil Load [W] |
UA of the Coil [W/delK] |
| SPACE1-1 ZONE COIL |
0.000059 |
2698.50 |
66.13 |
| SPACE2-1 ZONE COIL |
0.000046 |
2102.17 |
51.51 |
| SPACE3-1 ZONE COIL |
0.000054 |
2492.52 |
61.08 |
| SPACE4-1 ZONE COIL |
0.000058 |
2649.63 |
64.93 |
| SPACE5-1 ZONE COIL |
0.000057 |
2639.74 |
64.69 |
| OA HEATING COIL 1 |
0.000148 |
6812.27 |
84.72 |
| MAIN HEATING COIL 1 |
0.000075 |
3458.59 |
55.80 |
BRANCH
| |
Maximum Branch Flow Rate
[m3/s] |
| VAV SYS 1 MAIN BRANCH |
1.06 |
AIR PRIMARY LOOP
| |
Primary air design volumetric
flow rate [m3/s] |
| VAV SYS 1 |
1.06 |
CONTROLLER:OUTSIDE AIR
| |
maximum outside air flow rate
[m3/s] |
minimum outside air flow rate
[m3/s] |
| OA CONTROLLER 1 |
1.06 |
0.264118 |
COIL:Water:Cooling
| |
Max Water Flow Rate of Coil
[m3/s] |
Max Air Flow Rate of Coil
[m3/s] |
Design Air Inlet Temperature
[C] |
Design Air Outlet Temperature
[C] |
Design Water Inlet Temperature
[C] |
Design Air Inlet Humidity
Ratio |
Design Air Outlet Humidity
Ratio |
| OA COOLING COIL 1 |
0.001145 |
0.264118 |
30.01 |
11.00 |
7.00 |
0.014595 |
0.008000 |
| MAIN COOLING COIL 1 |
0.000916 |
1.06 |
21.55 |
12.80 |
7.00 |
0.009333 |
0.008000 |
FAN:SIMPLE:VARIABLEVOLUME
| |
Max Flow Rate [m3/s] |
Min Flow Rate [m3/s] |
| SUPPLY FAN 1 |
1.06 |
0.353263 |
CONTROLLER:SIMPLE
| |
Max Actuated Flow [m3/s] |
| OA CC CONTROLLER 1 |
0.001145 |
| OA HC CONTROLLER 1 |
0.000148 |
| CENTRAL COOLING COIL CONTROLLER
1 |
0.000916 |
| CENTRAL HEATING COIL CONTROLLER
1 |
0.000075 |
PLANT LOOP
| |
Maximum Loop Volumetric Flow
Rate [m3/s] |
Volume of the plant loop
[m3] |
| HOT WATER LOOP |
0.000497 |
0.559158 |
| CHILLED WATER LOOP |
0.002061 |
2.32 |
BOILER:SIMPLE
| |
Nominal Capacity [W] |
Design Boiler Water Flow Rate
[m3/s] |
| CENTRAL BOILER |
22853.43 |
0.000497 |
CHILLER:ELECTRIC
| |
Nominal Capacity [W] |
Design Evaporator Volumetric
Water Flow Rate [m3/s] |
| CENTRAL CHILLER |
34468.25 |
0.002061 |
PUMP:VARIABLE SPEED
| |
Rated Volumetric Flow Rate
[m3/s] |
Rated Power Consumption [W] |
| HW CIRC PUMP |
0.000497 |
126.98 |
| CW CIRC PUMP |
0.002061 |
526.69 |
Outdoor Air Summary[LINK]
The Outdoor Air Summary provides information for each zone
on the average and minimum ventilation provided.
The reports described so far in this section are displayed
when specified in the Output:Table:SummaryReports
object. They are either on or off and are not customizable.
The next few types of tabular reports are customizable. You
can specify the report variables being used in each one.
Directly following is an example of the report. The key
used to obtain this report is OutdoorAirSummary.
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Average Outside Air During Occupied Hours
| |
Average Number of Occupants |
Nominal Number of Occupants |
Zone Volume (m3) |
Mechanical Ventilation
(ach) |
Infiltration (ach) |
Simple Ventilation (ach) |
| SPACE1-1 |
9.50 |
11.00 |
239.25 |
0.365 |
0.050 |
0.000 |
| SPACE2-1 |
4.32 |
5.00 |
103.31 |
0.630 |
0.051 |
0.000 |
| SPACE3-1 |
9.50 |
11.00 |
239.25 |
0.338 |
0.050 |
0.000 |
| SPACE4-1 |
4.32 |
5.00 |
103.31 |
0.708 |
0.051 |
0.000 |
| SPACE5-1 |
17.27 |
20.00 |
447.68 |
0.214 |
0.052 |
0.000 |
Minimum Outside Air During Occupied Hours
| |
Average Number of Occupants |
Nominal Number of Occupants |
Zone Volume (m3) |
Mechanical Ventilation
(ach) |
Infiltration (ach) |
Simple Ventilation (ach) |
| SPACE1-1 |
9.50 |
11.00 |
239.25 |
0.000 |
0.000 |
0.000 |
| SPACE2-1 |
4.32 |
5.00 |
103.31 |
0.000 |
0.000 |
0.000 |
| SPACE3-1 |
9.50 |
11.00 |
239.25 |
0.000 |
0.000 |
0.000 |
| SPACE4-1 |
4.32 |
5.00 |
103.31 |
0.000 |
0.000 |
0.000 |
| SPACE5-1 |
17.27 |
20.00 |
447.68 |
0.000 |
0.000 |
0.000 |
Outdoor Air Details[LINK]
The Outdoor Air Details report provides detailed
information on outdoor air flow for each zone and air loop.
This report may be specified in the Output:Table:SummaryReports
object with the key OutdoorAirDetails. It is also produced for
any AllSummary* key. Each subtable and column are described
below.
Mechanical
Ventilation Parameters by Zone[LINK]
- AirLoop Name
-
The name(s) of air loop(s) serving this zone,if any.
- Average Number of Occupants
-
Average number of occupants during occupied times
(occupants > 0) for the simulation period.
- Nominal Number of Occupants
-
Total number of people for all People
objects in this zone (ignoring schedules).
- Zone Volume
-
The zone volume in .
- Zone Area
-
The zone floor area in .
- Design Zone Outdoor Airflow - \(V_{oz}\)
-
The design outdoor air flow rate specified in the DesignSpecification:OutdoorAir
object for this zone in . This is the outdoor air flow rate
used for sizing without any schedule modifier.
- Minimum Dynamic Target Ventilation - \(V_{oz-dyn-min}\)
-
The minimum outdoor air flow rate specified in the DesignSpecification:OutdoorAir
object for this zone in . This is the outdoor air flow rate
for the minimum number of occupants without any schedule
modifier.
Total Outdoor Air by
Zone[LINK]
- Mechanical Ventilation
-
The total outdoor air delivered to this zone by mechanical
ventilation (HVAC systems) in (Output:Variable Zone
Mechanical Ventilation Standard Density Volume Flow Rate).
- Natural Ventilation
-
The total outdoor air delivered to this zone by natural
ventilation (ZoneVentilation:* or AirflowNetwork) in .
- Total Ventilation
-
The sum of Mechanical and Natural Ventilation in .
- Infiltration
-
The total outdoor air delivered to this zone by
infiltration (ZoneInfiltration:* or AirflowNetwork) in
(Output:Variable Zone
Infiltration Standard Density Volume Flow Rate).
- Total Ventilation and Infiltration
-
The sum of Mechanical and Natural Ventilation and
Infiltration in .
- Dynamic Target Ventilation - \(V_{oz-dyn}\)
-
The total dynamic outdoor air flow rate specified in the DesignSpecification:OutdoorAir
object for this zone in . This is the zone target ventilation
flow rate \(V_{oz-dyn}\) at
standard density at the current timestep including any
schedule modifier (Output:Variable Zone
Target Voz Ventilation Flow Rate).
- Time Below \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is more than
1% below the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Zone
Ventilation Below Target Voz Time).
- Time At \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is within 1%
of the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Zone
Ventilation At Target Voz Time).
- Time Above \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is more than
1% above the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Zone
Ventilation Above Target Voz Time).
- Time Above Zero When Unoccupied
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is greater
than zero when the zone is unoccupied (Output:Variable Zone
Ventilation When Unoccupied Time).
Average
Outdoor Air During Occupancy by Zone - Flow Rates[LINK]
This subtable is the same as Total Outdoor Air by Zone
except that it reports average flow rates in and status times
in hours for occupied periods only.
Total Outdoor Air by
AirLoop[LINK]
- Mechanical Ventilation
-
The total outdoor air delivered to the zones on this air
loop by only this air loop in (Output:Variable Air System
Mechanical Ventilation Flow Rate).
- Natural Ventilation
-
The total outdoor air delivered to the zones on this air
loop by natural ventilation (ZoneVentilation:* or
AirflowNetwork) in (Output:Variable Air System Natural
Ventilation Flow Rate). If any zone terminal unit has a DesignSpecification:AirTerminal:Sizing
object then the natural ventilation rate for that zone is
scaled by the Fraction of Minimum Outdoor Air Flow value.
- Total Ventilation
-
The sum of Mechanical and Natural Ventilation in .
- Sum Zone Dynamic Target Ventilation - \(V_{oz-dyn}\)
-
The total dynamic outdoor air flow rate specified in the DesignSpecification:OutdoorAir
object for the zones on this air loop in . This is the sum of
the zone target ventilation flow rates \(V_{oz-dyn}\) at standard density
at the current timestep including any schedule modifier
(Output:Variable Air System Target Voz Ventilation Flow Rate).
If any zone terminal unit has a DesignSpecification:AirTerminal:Sizing
object then the target ventilation rate for that zone is
scaled by the Fraction of Minimum Outdoor Air Flow value.
- Time Below \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is more than
1% below the Sum Zone
Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Air System Ventilation Below Target Voz
Time).
- Time At \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is within 1%
of the Sum Zone
Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Air System Ventilation At Target Voz
Time).
- Time Above \(V_{oz-dyn}\)
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is more than
1% above the Sum Zone
Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate
(Output:Variable Air System Ventilation Above Target Voz
Time).
- Time Above Zero When Unoccupied
-
The time in hours that the Total Ventilation rate
(mechanical ventilation plus natural ventilation) is greater
than zero when the all zones on this air loop are unoccupied
(Output:Variable Air System Ventilation When Unoccupied
Time).
Average
Outdoor Air During Occupancy by AirLoop[LINK]
This subtable is the same as Total Outdoor Air by AirLoop
except that it reports average flow rates in and status times
in hours when any zone on this air loop is occupied.
Outdoor
Air Controller Limiting Factors by AirLoop[LINK]
Times in hours that the outdoor air flow rate for this
airloop is set by one of the following limiting factors
(Output:Variable Air System Outdoor Air Limiting Factor).
- No Limiting Factor
-
None of the other limiting factors is active.
- Limits and Scheduled Limits
-
Fixed limits such as Controller:OutdoorAir
Minimum Outdoor Air Flow Rate, Maximum Outdoor Air Flow Rate,
Minimum Fraction of Outdoor Air Schedule Name, Maximum
Fraction of Outdoor Air Schedule Name.
- Economizer
-
Economizer is active and sets the flow greater than the
minimum outdoor air fraction.
- Exhaust Flow
-
Outdoor air flow rate equals the total zone exhaust flow
rate.
- Mixed Air Flow
-
Outdoor air flow rate is limited by the current mixed air
flow rate.
- High Humidity
-
Controller:OutdoorAir
High Humidity Control.
- Demand Controlled Ventilation
-
Controller:MechanicalVentilation
requested more than the minimum outdoor air fraction.
- Night Ventilation
-
AvailabilityManager:NightVentilation
is active.
- Demand Limiting
-
DemandManager:Ventilation
has reduced the outdoor air flow rate.
- Energy Management System
-
An EnergyManagementSystem:Actuator
has overridden the outdoor air flow rate.
Average
Outdoor Air for Limiting Factors During Occupancy[LINK]
This subtable is the same as Outdoor Air Controller
Limiting Factors by AirLoop except that it reports average
flow rates in at each limiting factor for occupied periods
only.
Climatic Data Summary[LINK]
The Climatic Data Summary provides some statistics from the
.STAT file concerning the selected weather. The Stat file must
be available (it is included with all the weather files on the
EnergyPlus website) for the report to be fully produced.
Directly following is an example of the report. The key used
to obtain this report is ClimaticDataSummary.
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2009-02-10 13:27:45
SizingPeriod:DesignDay
| |
Maximum Dry Bulb (C) |
Daily Temperature Range (C) |
Humidity Value |
Humidity Type |
Wind Speed (m/s) |
Wind Direction |
| CHICAGO_IL_USA ANNUAL HEATING
99% DESIGN CONDITIONS DB |
-17.30 |
0.00 |
-17.30 |
WETBULB |
4.90 |
270.00 |
| CHICAGO_IL_USA ANNUAL COOLING 1%
DESIGN CONDITIONS DB/MCWB |
31.50 |
10.70 |
23.00 |
WETBULB |
5.30 |
230.00 |
Weather Statistics File
| |
Value |
| Reference |
USA_Chicago-OHare_TMY2 |
| Site:Location |
Chicago IL USA |
| Latitude |
N 41° 58’ |
| Longitude |
W 87° 54’ |
| Time Zone |
GMT -6.0 Hours |
| Elevation |
190m above sea level |
| Standard Pressure at
Elevation |
99063Pa |
| Data Source |
Release Test |
| WMO Station |
725300 |
| Design Conditions |
Climate Design Data 2005 ASHRAE
Handbook |
| Heating Design Temperature 99.6%
(C) |
-20.6 |
| Heating Design Temperature 99%
(C) |
-17.3 |
| Cooling Design Temperature 0.4%
(C) |
33.2 |
| Cooling Design Temperature 1%
(C) |
31.5 |
| Cooling Design Temperature 2%
(C) |
29.9 |
| Maximum Dry Bulb Temperature
(C) |
35.6° |
| Maximum Dry Bulb Occurs on |
Jul 9 |
| Minimum Dry Bulb Temperature
(C) |
-22.8° |
| Minimum Dry Bulb Occurs on |
Jan 7 |
| Maximum Dew Point Temperature
(C) |
25.6 |
| Maximum Dew Point Occurs on |
Aug 4 |
| Minimum Dew Point Temperature
(C) |
-28.9 |
| Minimum Dew Point Occurs on |
Dec 31 |
| Heating Degree-Days (base
10°C) |
1745 |
| Cooling Degree-Days (base
18°C) |
464 |
| Köppen Classification |
Dfa |
| Köppen Description |
Humid continental (hot summer,
cold winter, no dry season, lat. 30-60°N) |
| Köppen Recommendation |
Unbearably humid periods in
summer, but passive cooling is possible |
| ASHRAE Climate Zone |
5A |
| ASHRAE Description |
Cool-Humid |
Object Count Summary[LINK]
The object count summary report provides the count on the
number of specific objects in the file. Directly following is
an example of the report. The key used to obtain this report
is ObjectCountSummary.
Report: Object Count Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Surfaces by Class
| |
Total |
Outdoors |
| Wall |
24 |
8 |
| Floor |
10 |
5 |
| Roof |
6 |
1 |
| Internal Mass |
0 |
0 |
| Building Detached Shading |
0 |
0 |
| Fixed Detached Shading |
0 |
0 |
| Window |
6 |
6 |
| Door |
0 |
0 |
| Glass Door |
0 |
0 |
| Shading |
4 |
4 |
| Overhang |
0 |
0 |
| Fin |
0 |
0 |
| Tubular Daylighting Device
Dome |
0 |
0 |
| Tubular Daylighting Device
Diffuser |
0 |
0 |
HVAC
| |
Count |
| HVAC Air Loops |
1 |
| Conditioned Zones |
6 |
| Unconditioned Zones |
0 |
| Supply Plenums |
0 |
| Return Plenums |
1 |
Component Cost
Economics Summary[LINK]
The Component Cost Economics Summary provides the
construction cost estimate summary for the project. The costs
are broken into eight catagories and the reference building
costs are provided as a comparison. A second table is also
produced that provides line item details with one line for
every line item object. Directly following is an example of
this report.
Report: Component Cost Economics Summary
For: Entire Facility
Timestamp: 2016-01-12 15:47:39
Construction
Cost Estimate Summary
|
Reference Bldg. |
Current Bldg. Model |
Difference |
| Line Item SubTotal ($) |
665082.04 |
719946.72 |
54864.68 |
| Misc. Costs ($) |
928979.09 |
928979.09 |
0 |
| Regional Adjustment ($) |
216792.31 |
224253.91 |
7461.6 |
| Design Fee ($) |
108651.21 |
149854.38 |
41203.17 |
| Contractor Fee ($) |
126759.74 |
131122.58 |
4362.84 |
| Contingency ($) |
181085.34 |
187317.97 |
6232.63 |
| Permits, Bonds, Insurance ($) |
0 |
0 |
0 |
| Commissioning ($) |
9054.27 |
18731.8 |
9677.53 |
| Cost Estimate Total ($) |
2236404 |
2360206.45 |
123802.44 |
| Cost Per Conditioned Building Area ($/m2) |
1203.69 |
1270.32 |
66.63 |
Cost Line Item Details
|
Line No. |
Item Name |
Quantity. |
Units |
$ per Qty. |
SubTotal $ |
| – |
1 |
EXTERIOR WALLS |
627.57 |
m2 |
168.64 |
105832.65 |
| – |
2 |
INTERIOR WALLS |
854.18 |
m2 |
31.16 |
26616.23 |
| – |
3 |
ROOF |
1857.96 |
m2 |
104.69 |
194509.64 |
| – |
4 |
GROUND FLR SLAB |
1857.96 |
m2 |
56.06 |
104157.14 |
| – |
5 |
ACOUSTICAL DROP CEILINGS |
1857.96 |
m2 |
23.79 |
44200.83 |
| – |
6 |
QUAD HIGH SHGC SUPERWINDOWS |
226.22 |
m2 |
687.84 |
155604.96 |
| – |
7 |
QUAD LOW SHGC SUPERWINDOWS |
42.68 |
m2 |
687.84 |
29359.55 |
| – |
8 |
CENTRAL CHILLER |
150.49 |
kW (tot cool cap.) |
340 |
51165.73 |
| – |
9 |
CONTINUOUS AIR BARRIER |
1 |
Ea. |
8500 |
8500 |
| Line Item SubTotal |
– |
– |
– |
– |
– |
719946.72 |
The LEED Summary report provides many of the simulation
results required for certification of Energy and Atmosphere
Credit 1 Optimized Energy Performance according to the LEED
Green Building
Rating SystemTM. The report can be produced by
specifying LEEDSummary in Output:Table:SummaryReports
which is also part of the AllSummary option. Directly
following is an example of this report.
Report: LEED Summary
For: Entire Facility
Timestamp: 2013-03-01 15:24:37
Sec1.1A-General Information
|
Data |
| Heating Degree Days |
1748 |
| Cooling Degree Days |
506 |
| Climate Zone |
5A |
| Weather File |
Chicago Ohare Intl Ap IL USA
TMY3 WMO#=725300 |
| HDD and CDD data source |
Weather File Stat |
| Total gross floor area [m2] |
927.20 |
| Principal Heating Source |
Natural Gas |
EAp2-1. Space
Usage Type
|
Space Area [m2] |
Regularly Occupied Area
[m2] |
Unconditioned Area [m2] |
Typical Hours/Week in Operation
[hr/wk] |
| SPACE1-1 |
99.16 |
99.16 |
0.00 |
55.06 |
| SPACE2-1 |
42.73 |
42.73 |
0.00 |
55.06 |
| SPACE3-1 |
96.48 |
96.48 |
0.00 |
55.06 |
| SPACE4-1 |
42.73 |
42.73 |
0.00 |
55.06 |
| SPACE5-1 |
182.49 |
182.49 |
0.00 |
55.06 |
| PLENUM-1 |
463.60 |
463.60 |
0.00 |
0.00 |
| Totals |
927.20 |
927.20 |
0.00 |
|
EAp2-2. Advisory Messages
|
Data |
| Number of hours heating loads not met |
0.00 |
| Number of hours cooling loads not met |
10.75 |
| Number of hours not met |
10.75 |
EAp2-3. Energy Type Summary
|
Utility Rate |
Virtual Rate [\$/unit
energy] |
Units of Energy |
Units of Demand |
| Electricity |
EXAMPLEA EXAMPLEI-SELL |
0.055 |
kWh |
kW |
| Natural Gas |
EXAMPLEA-GAS |
0.569 |
Therm |
Therm/Hr |
| Other |
|
|
|
|
EAp2-4/5. Performance Rating Method Compliance
|
Electric Energy Use [GJ] |
Electric Demand [W] |
Natural Gas Energy Use [GJ] |
Natural Gas Demand [W] |
Other Fuel Use [GJ] |
Other Fuel Demand [W] |
| Heating – Not Subdivided |
0.00 |
0.00 |
103.92 |
62499.99 |
0.00 |
0.00 |
| Cooling – Not Subdivided |
17.63 |
9523.66 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting – General |
81.24 |
7125.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Interior Lighting – Process |
81.24 |
7125.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Exterior Lighting – General |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Pumps – Not Subdivided |
1.54 |
319.57 |
0.00 |
0.00 |
0.00 |
0.00 |
| Heat Rejection – Not Subdivided |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans – Interior |
7.01 |
609.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Fans – Garage |
7.01 |
609.44 |
0.00 |
0.00 |
0.00 |
0.00 |
| Service Water Heating – Not Subdivided |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Receptacle Equipment - Not Subdivided |
47.70 |
4500.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Refrigeration Equipment – Not Subdivided |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
EAp2-6. Energy Use Summary
|
Process Subtotal [GJ] |
Total Energy Use [GJ] |
| Electricity |
47.70 |
155.12 |
| Natural Gas |
0.00 |
274.01 |
| Other |
0.00 |
0.00 |
| Total |
47.70 |
429.13 |
EAp2-7. Energy Cost Summary
|
Process Subtotal [\$] |
Total Energy Cost [\$] |
| Electricity |
552.55 |
1796.99 |
| Natural Gas |
0.00 |
1478.58 |
| Other |
0.00 |
0.00 |
| Total |
552.55 |
3275.57 |
Process energy cost based on ratio of process to total
energy.
L-1. Renewable Energy Source Summary
|
Rated Capacity [kW] |
Annual Energy Generated
[GJ] |
| Photovoltaic |
0.00 |
0.00 |
| Wind |
0.00 |
0.00 |
EAp2-17a. Energy Use Intensity - Electricity
|
Electricty [MJ/m2] |
| Interior Lighting |
87.62 |
| Space Heating |
0.00 |
| Space Cooling |
19.02 |
| Fans-Interior |
7.56 |
| Service Water Heating |
0.00 |
| Receptacle Equipment |
51.44 |
| Miscellaneous |
1.66 |
| Subtotal |
167.30 |
EAp2-17b. Energy Use Intensity - Natural Gas
|
Natural Gas [MJ/m2] |
| Space Heating |
112.08 |
| Service Water Heating |
0.00 |
| Miscellaneous |
183.45 |
| Subtotal |
295.53 |
EAp2-17c. Energy Use Intensity - Other
|
Other [MJ/m2] |
| Miscellaneous |
0.00 |
| Subtotal |
0.00 |
EAp2-18. End Use Percentage
|
Percent [%] |
| Interior Lighting |
18.93 |
| Space Heating |
24.22 |
| Space Cooling |
4.11 |
| Fans-Interior |
1.63 |
| Service Water Heating |
0.00 |
| Receptacle Equipment |
11.11 |
| Miscellaneous |
39.99 |
Schedules-Equivalent Full Load Hours (Schedule
Type=Fraction)
|
Equivalent Full Load Hours of
Operation Per Year [hr] |
Hours > 1% [hr] |
| OCCUPY-1 |
2532. |
3393. |
| LIGHTS-1 |
3009. |
8760. |
| EQUIP-1 |
2650. |
8760. |
| INFIL-SCH |
3624. |
3624. |
| SHADETRANSSCH |
0. |
0. |
| MIN OA SCHED |
3245. |
8760. |
| FANAVAILSCHED |
5678. |
5678. |
| COOLINGCOILAVAILSCHED |
1310. |
1310. |
| REHEATCOILAVAILSCHED |
5678. |
5678. |
Schedules-SetPoints (Schedule Type=Temperature)
|
First Object Used |
Month Assumed |
11am First Wednesday [C] |
Days with Same 11am Value |
11pm First Wednesday [C] |
Days with Same 11pm Value |
| HTG-SETP-SCH |
HEATING SETPOINT |
January |
21.10 |
365 |
12.80 |
365 |
| PLENUM-HTG-SETP-SCH |
PLENUM HEATING SETPOINT |
January |
12.80 |
365 |
12.80 |
365 |
| CLG-SETP-SCH3 |
COOLING SETPOINT |
July |
25.00 |
122 |
25.00 |
122 |
| PLENUM-CLG-SETP-SCH |
PLENUM COOLING SETPOINT |
July |
40.00 |
365 |
40.00 |
365 |
| CLG-SETP-SCH |
DUAL SETPOINT |
July |
23.90 |
365 |
40.00 |
365 |
Initialization Summary[LINK]
This report is not reproduced here since it is well
documented in the section in this document for the
eplusout.eio file.
Energy Meters[LINK]
This report provides the details on all the energy meters
generated by the simulation. Directly following is an example
of the report. The key used to obtain this report is
EnergyMeters.
Report: Energy Meters
For: Entire Facility
Timestamp: 2012-05-01 17:07:24
Annual and Peak Values - Electricity
|
Electricity Annual Value
[GJ] |
Electricity Minimum Value
[W] |
Timestamp of Minimum |
Electricity Maximum Value
[W] |
Timestamp of Maximum |
| Electricity:Facility |
156.68 |
475.00 |
01-APR-00:15 |
20165.58 |
17-JUL-15:00 |
| Electricity:Building |
128.94 |
475.00 |
01-JAN-00:15 |
12000.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE1-1 |
27.23 |
100.32 |
01-JAN-00:15 |
2534.40 |
01-JAN-10:15 |
| InteriorLights:Electricity |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE1-1 |
17.16 |
79.20 |
01-JAN-00:15 |
1584.00 |
01-JAN-10:15 |
| GeneralLights:InteriorLights:Electricity |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE2-1 |
11.76 |
43.32 |
01-JAN-00:15 |
1094.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE2-1 |
7.41 |
34.20 |
01-JAN-00:15 |
684.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE3-1 |
27.23 |
100.32 |
01-JAN-00:15 |
2534.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE3-1 |
17.16 |
79.20 |
01-JAN-00:15 |
1584.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE4-1 |
11.76 |
43.32 |
01-JAN-00:15 |
1094.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE4-1 |
7.41 |
34.20 |
01-JAN-00:15 |
684.00 |
01-JAN-10:15 |
| Electricity:Zone:SPACE5-1 |
50.96 |
187.72 |
01-JAN-00:15 |
4742.40 |
01-JAN-10:15 |
| InteriorLights:Electricity:Zone:SPACE5-1 |
32.11 |
148.20 |
01-JAN-00:15 |
2964.00 |
01-JAN-10:15 |
| InteriorEquipment:Electricity |
47.70 |
100.00 |
01-JAN-00:15 |
4500.00 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE1-1 |
10.07 |
21.12 |
01-JAN-00:15 |
950.40 |
01-JAN-09:15 |
| General:InteriorEquipment:Electricity |
47.70 |
100.00 |
01-JAN-00:15 |
4500.00 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE2-1 |
4.35 |
9.12 |
01-JAN-00:15 |
410.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE3-1 |
10.07 |
21.12 |
01-JAN-00:15 |
950.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE4-1 |
4.35 |
9.12 |
01-JAN-00:15 |
410.40 |
01-JAN-09:15 |
| InteriorEquipment:Electricity:Zone:SPACE5-1 |
18.85 |
39.52 |
01-JAN-00:15 |
1778.40 |
01-JAN-09:15 |
| ElectricityPurchased:Facility |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricityPurchased:Plant |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Cogeneration:ElectricityPurchased |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricitySurplusSold:Facility |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| ElectricitySurplusSold:Plant |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Cogeneration:ElectricitySurplusSold |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| ElectricityNet:Facility |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| ElectricityNet:Plant |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Cogeneration:ElectricityNet |
156.68 |
475.00 |
28-JUN-05:15 |
20165.58 |
17-JUL-15:00 |
| Electricity:HVAC |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| Fans:Electricity |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| General:Fans:Electricity |
8.87 |
0.00 |
01-APR-00:15 |
655.43 |
17-JUL-15:00 |
| Electricity:Plant |
18.88 |
0.00 |
01-JAN-00:15 |
8053.88 |
19-JUL-16:00 |
| Heating:Electricity |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Boiler Parasitic:Heating:Electricity |
0.00 |
0.00 |
01-JAN-00:15 |
0.00 |
01-JAN-00:15 |
| Cooling:Electricity |
16.44 |
0.00 |
01-JAN-00:15 |
7478.31 |
19-JUL-16:00 |
| Pumps:Electricity |
2.44 |
0.00 |
01-JAN-00:15 |
575.73 |
24-JUL-20:00 |
| MYGENERALLIGHTS |
81.24 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
| MYBUILDINGELECTRIC |
128.94 |
475.00 |
01-JAN-00:15 |
12000.00 |
01-JAN-10:15 |
| MYBUILDINGOTHER |
47.70 |
375.00 |
01-JAN-00:15 |
7500.00 |
01-JAN-10:15 |
Annual and Peak Values - Gas
|
Gas Annual Value [GJ] |
Gas Minimum Value [W] |
Timestamp of Minimum |
Gas Maximum Value [W] |
Timestamp of Maximum |
| Gas:Facility |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Gas:Plant |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Heating:Gas |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
| Boiler:Heating:Gas |
68.82 |
0.00 |
01-JAN-00:15 |
42092.68 |
01-FEB-06:15 |
Annual and Peak Values - Cooling
|
Cooling Annual Value [GJ] |
Cooling Minimum Value [W] |
Timestamp of Minimum |
Cooling Maximum Value [W] |
Timestamp of Maximum |
| PlantLoopCoolingDemand:Facility |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| PlantLoopCoolingDemand:HVAC |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| CoolingCoils:PlantLoopCoolingDemand |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
Annual and Peak Values - Water
|
Annual Value [m3] |
Minimum Value [m3/s] |
Timestamp of Minimum |
Maximum Value [m3/s] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other by Weight/Mass
|
Annual Value [kg] |
Minimum Value [kg/s] |
Timestamp of Minimum |
Maximum Value [kg/s] |
Timestamp of Maximum |
| Carbon Equivalent:Facility |
0.00 |
0.000 |
01-JAN-00:15 |
0.000 |
01-JAN-00:15 |
| CarbonEquivalentEmissions:Carbon Equivalent |
0.00 |
0.000 |
01-JAN-00:15 |
0.000 |
01-JAN-00:15 |
Annual and Peak Values - Other Volumetric
|
Annual Value [m3] |
Minimum Value [m3/s] |
Timestamp of Minimum |
Maximum Value [m3/s] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other Liquid/Gas
|
Annual Value [L] |
Minimum Value [L] |
Timestamp of Minimum |
Maximum Value [L] |
Timestamp of Maximum |
| None |
|
|
|
|
|
Annual and Peak Values - Other
|
Annual Value [GJ] |
Minimum Value [W] |
Timestamp of Minimum |
Maximum Value [W] |
Timestamp of Maximum |
| EnergyTransfer:Facility |
415.65 |
0.00 |
01-APR-00:15 |
102784.74 |
17-JUL-15:00 |
| EnergyTransfer:Building |
97.60 |
0.00 |
01-APR-00:15 |
21488.05 |
28-JAN-06:15 |
| EnergyTransfer:Zone:PLENUM-1 |
22.50 |
0.00 |
01-APR-00:15 |
4218.21 |
07-JAN-08:15 |
| Heating:EnergyTransfer |
42.23 |
0.00 |
19-MAR-15:30 |
21488.05 |
28-JAN-06:15 |
| Heating:EnergyTransfer:Zone:PLENUM-1 |
19.63 |
0.00 |
16-JAN-21:15 |
4218.21 |
07-JAN-08:15 |
| Cooling:EnergyTransfer |
55.38 |
0.00 |
01-JAN-06:15 |
13937.19 |
17-JUL-15:00 |
| Cooling:EnergyTransfer:Zone:PLENUM-1 |
2.87 |
0.00 |
01-JAN-00:15 |
2539.33 |
18-JUL-15:00 |
| EnergyTransfer:Zone:SPACE1-1 |
17.91 |
0.00 |
01-APR-00:15 |
4012.66 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE1-1 |
6.51 |
0.00 |
01-JAN-10:15 |
4012.66 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE1-1 |
11.40 |
0.00 |
01-JAN-00:15 |
3138.67 |
27-SEP-16:00 |
| EnergyTransfer:Zone:SPACE2-1 |
10.67 |
0.00 |
01-APR-00:15 |
3432.93 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE2-1 |
2.42 |
0.00 |
01-JAN-01:30 |
3432.93 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE2-1 |
8.25 |
0.00 |
01-JAN-00:15 |
2460.04 |
06-SEP-10:15 |
| EnergyTransfer:Zone:SPACE3-1 |
16.79 |
0.00 |
01-APR-00:15 |
3788.83 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE3-1 |
6.09 |
0.00 |
01-JAN-12:00 |
3788.83 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE3-1 |
10.70 |
0.00 |
01-JAN-00:15 |
2807.57 |
19-JUL-11:00 |
| EnergyTransfer:Zone:SPACE4-1 |
9.82 |
0.00 |
01-APR-00:15 |
3746.68 |
28-JAN-06:15 |
| Heating:EnergyTransfer:Zone:SPACE4-1 |
2.98 |
0.00 |
01-JAN-01:30 |
3746.68 |
28-JAN-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE4-1 |
6.85 |
0.00 |
01-JAN-00:15 |
2281.99 |
25-JUN-17:15 |
| EnergyTransfer:Zone:SPACE5-1 |
19.91 |
0.00 |
01-APR-00:15 |
4037.31 |
30-DEC-06:15 |
| Heating:EnergyTransfer:Zone:SPACE5-1 |
4.60 |
0.00 |
01-JAN-00:15 |
4037.31 |
30-DEC-06:15 |
| Cooling:EnergyTransfer:Zone:SPACE5-1 |
15.31 |
0.00 |
01-JAN-06:15 |
2611.53 |
17-JUL-15:00 |
| EnergyTransfer:HVAC |
117.82 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| HeatingCoils:EnergyTransfer |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| PlantLoopHeatingDemand:Facility |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| PlantLoopHeatingDemand:HVAC |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| HeatingCoils:PlantLoopHeatingDemand |
55.41 |
0.00 |
01-JAN-00:15 |
31769.77 |
07-JAN-06:15 |
| CoolingCoils:EnergyTransfer |
62.41 |
0.00 |
01-JAN-00:15 |
27050.46 |
17-JUL-15:00 |
| EnergyTransfer:Plant |
200.23 |
0.00 |
01-JAN-00:15 |
62116.41 |
19-JUL-16:00 |
| Boilers:EnergyTransfer |
55.06 |
0.00 |
01-JAN-00:15 |
33674.15 |
28-MAR-06:15 |
| Chillers:EnergyTransfer |
64.37 |
0.00 |
01-JAN-00:15 |
27319.05 |
19-JUL-16:00 |
| HeatRejection:EnergyTransfer |
80.81 |
0.00 |
01-JAN-00:15 |
34797.36 |
19-JUL-16:00 |
Sensible Heat Gain
Summary[LINK]
This report is more fully described in the Input Output
Reference but represents the major heat gain components for
each zone as well as the HVAC loads satisfied. Directly
following is an example of the report. The key used to obtain
this report is SensibleHeatGainSummary.
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2011-09-09 08:02:03
Annual Building
Sensible Heat Gain Components
|
HVAC Input Sensible Air Heating
[GJ] |
HVAC Input Sensible Air Cooling
[GJ] |
HVAC Input Heated Surface
Heating [GJ] |
HVAC Input Cooled Surface
Cooling [GJ] |
People Sensible Heat Addition
[GJ] |
Lights Sensible Heat Addition
[GJ] |
Equipment Sensible Heat Addition
[GJ] |
Window Heat Addition [GJ] |
Interzone Air Transfer Heat
Addition [GJ] |
Infiltration Heat Addition
[GJ] |
Opaque Surface Conduction and
Other Heat Addition [GJ] |
Equipment Sensible Heat Removal
[GJ] |
Window Heat Removal [GJ] |
Interzone Air Transfer Heat
Removal [GJ] |
Infiltration Heat Removal
[GJ] |
Opaque Surface Conduction and
Other Heat Removal [GJ] |
| SPACE1-1 |
0.096 |
-0.070 |
0.000 |
0.000 |
0.035 |
0.131 |
0.065 |
0.220 |
0.000 |
0.000 |
0.001 |
0.000 |
-0.078 |
0.000 |
-0.004 |
-0.395 |
| SPACE2-1 |
0.051 |
-0.038 |
0.000 |
0.000 |
0.014 |
0.056 |
0.028 |
0.173 |
0.000 |
0.000 |
0.001 |
0.000 |
-0.029 |
0.000 |
-0.002 |
-0.253 |
| SPACE3-1 |
0.093 |
-0.030 |
0.000 |
0.000 |
0.034 |
0.131 |
0.065 |
0.157 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.082 |
0.000 |
-0.004 |
-0.363 |
| SPACE4-1 |
0.055 |
-0.015 |
0.000 |
0.000 |
0.015 |
0.056 |
0.028 |
0.105 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.032 |
0.000 |
-0.002 |
-0.211 |
| SPACE5-1 |
0.032 |
-0.072 |
0.000 |
0.000 |
0.073 |
0.244 |
0.121 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.007 |
-0.392 |
| PLENUM-1 |
0.118 |
-0.024 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.000 |
-0.094 |
| Total Facility |
0.445 |
-0.248 |
0.000 |
0.000 |
0.170 |
0.618 |
0.307 |
0.655 |
0.000 |
0.000 |
0.002 |
0.000 |
-0.221 |
0.000 |
-0.017 |
-1.709 |
Peak Cooling Sensible Heat Gain Components
|
Time of Peak |
HVAC Input Sensible Air Heating
[W] |
HVAC Input Sensible Air Cooling
[W] |
HVAC Input Heated Surface
Heating [W] |
HVAC Input Cooled Surface
Cooling [W] |
People Sensible Heat Addition
[W] |
Lights Sensible Heat Addition
[W] |
Equipment Sensible Heat Addition
[W] |
Window Heat Addition [W] |
Interzone Air Transfer Heat
Addition [W] |
Infiltration Heat Addition
[W] |
Opaque Surface Conduction and
Other Heat Addition [W] |
Equipment Sensible Heat Removal
[W] |
Window Heat Removal [W] |
Interzone Air Transfer Heat
Removal [W] |
Infiltration Heat Removal
[W] |
Opaque Surface Conduction and
Other Heat Removal [W] |
| SPACE1-1 |
14-JAN-15:00 |
0.00 |
-3502.16 |
0.00 |
0.00 |
724.60 |
1584.00 |
739.20 |
9347.85 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-8893.49 |
| SPACE2-1 |
14-JAN-10:07 |
0.00 |
-1738.94 |
0.00 |
0.00 |
345.99 |
684.00 |
410.40 |
4684.27 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-4385.71 |
| SPACE3-1 |
14-JAN-14:45 |
0.00 |
-1095.49 |
0.00 |
0.00 |
761.13 |
1584.00 |
844.80 |
356.87 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-2451.31 |
| SPACE4-1 |
14-JAN-16:00 |
0.00 |
-736.19 |
0.00 |
0.00 |
345.95 |
684.00 |
228.00 |
1157.98 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1679.74 |
| SPACE5-1 |
14-JAN-13:35 |
0.00 |
-2315.43 |
0.00 |
0.00 |
1135.19 |
2667.60 |
1778.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-3265.77 |
| PLENUM-1 |
07-JUL-19:46 |
0.00 |
-1579.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
1579.40 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total Facility |
14-JAN-15:00 |
0.00 |
-7822.86 |
0.00 |
0.00 |
3561.18 |
7500.00 |
3500.00 |
10470.76 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-17209.08 |
Peak Heating Sensible Heat Gain Components
|
Time of Peak |
HVAC Input Sensible Air Heating
[W] |
HVAC Input Sensible Air Cooling
[W] |
HVAC Input Heated Surface
Heating [W] |
HVAC Input Cooled Surface
Cooling [W] |
People Sensible Heat Addition
[W] |
Lights Sensible Heat Addition
[W] |
Equipment Sensible Heat Addition
[W] |
Window Heat Addition [W] |
Interzone Air Transfer Heat
Addition [W] |
Infiltration Heat Addition
[W] |
Opaque Surface Conduction and
Other Heat Addition [W] |
Equipment Sensible Heat Removal
[W] |
Window Heat Removal [W] |
Interzone Air Transfer Heat
Removal [W] |
Infiltration Heat Removal
[W] |
Opaque Surface Conduction and
Other Heat Removal [W] |
| SPACE1-1 |
14-JAN-07:00 |
10652.50 |
0.00 |
0.00 |
0.00 |
0.00 |
79.20 |
21.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1551.57 |
0.00 |
0.00 |
-9201.25 |
| SPACE2-1 |
14-JAN-07:00 |
7816.55 |
0.00 |
0.00 |
0.00 |
0.00 |
34.20 |
9.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-594.65 |
0.00 |
0.00 |
-7265.22 |
| SPACE3-1 |
14-JAN-07:00 |
11495.41 |
0.00 |
0.00 |
0.00 |
0.00 |
79.20 |
21.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-1539.09 |
0.00 |
0.00 |
-10056.64 |
| SPACE4-1 |
14-JAN-07:00 |
8837.62 |
0.00 |
0.00 |
0.00 |
0.00 |
34.20 |
9.12 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-604.20 |
0.00 |
0.00 |
-8276.74 |
| SPACE5-1 |
14-JAN-07:00 |
12359.25 |
0.00 |
0.00 |
0.00 |
0.00 |
148.20 |
39.52 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-12546.97 |
| PLENUM-1 |
14-JAN-07:18 |
5275.99 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-5275.99 |
| Total Facility |
14-JAN-07:15 |
55720.39 |
0.00 |
0.00 |
0.00 |
0.00 |
375.00 |
100.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
-4289.51 |
0.00 |
0.00 |
-51905.88 |
Standard 62.1 Summary[LINK]
This report is more fully described in the Input Output
Reference. The Standard 62.1 Summary produces a report that is
consistent with many of the outputs needed when doing
calculations consistent with ASHRAE Standard 62.1-2010.
The abbreviations used in the report are consistent with
the abbreviations used in Appendix A4 of the Standard.
Directly following is an example of the report. The key used
to obtain this report is Standard62.1Summary.
Note: The report is only generated when sizing
calculations are specified.: in SimulationControl,
“Do Zone
Sizing” or “Do System Sizing” must be set to “Yes”.
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2012-04-20 12:00:57
System Ventilation Requirements for Cooling
|
Sum of Zone Primary Air Flow -
Vpz-sum [m3/s] |
System Population - Ps |
Sum of Zone Population -
Pz-sum |
Occupant Diversity - D |
Uncorrected Outdoor Air Intake
Airflow - Vou [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Average Outdoor Air Fraction -
Xs |
System Ventilation Efficiency -
Ev |
Outdoor Air Intake Flow - Vot
[m3/s] |
Percent Outdoor Air - %OA |
| VAV SYS 1 |
1.05 |
52.00 |
52.00 |
1.00 |
0.26 |
1.05 |
0.252 |
1.000 |
0.27 |
0.26 |
System Ventilation Requirements for Heating
|
Sum of Zone Primary Air Flow -
Vpz-sum [m3/s] |
System Population - Ps |
Sum of Zone Population -
Pz-sum |
Occupant Diversity - D |
Uncorrected Outdoor Air Intake
Airflow - Vou [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Average Outdoor Air Fraction -
Xs |
System Ventilation Efficiency -
Ev |
Outdoor Air Intake Flow Vot
[m3/s] |
Percent Outdoor Air - %OA |
| VAV SYS 1 |
1.05 |
0.00 |
0.00 |
1.00 |
0.26 |
0.43 |
0.967 |
1.000 |
0.27 |
0.26 |
Zone
Ventilation Parameters
|
AirLoop Name |
People Outdoor Air Rate - Rp
[m3/s-person] |
Zone Population - Pz |
Area Outdoor Air Rate - Ra
[m3/s-m2] |
Zone Floor Area - Az [m2] |
Breathing Zone Outdoor Airflow -
Vbz [m3/s] |
Cooling Zone Air Distribution
Effectiveness - Ez-clg |
Cooling Zone Outdoor Airflow -
Voz-clg [m3/s] |
Heating Zone Air Distribution
Effectiveness - Ez-htg |
Heating Zone Outdoor Airflow -
Voz-htg [m3/s] |
| SPACE1-1 |
VAV SYS 1 |
0.002360 |
11.00 |
0.000305 |
99.16 |
0.0562 |
0.900 |
0.0624 |
|
|
| SPACE2-1 |
VAV SYS 1 |
0.002360 |
5.00 |
0.000305 |
42.73 |
0.0248 |
0.900 |
0.0276 |
|
|
| SPACE3-1 |
VAV SYS 1 |
0.002360 |
11.00 |
0.000305 |
96.48 |
0.0554 |
1.000 |
0.0554 |
|
|
| SPACE4-1 |
VAV SYS 1 |
0.002360 |
5.00 |
0.000305 |
42.73 |
0.0248 |
1.000 |
0.0248 |
|
|
| SPACE5-1 |
VAV SYS 1 |
0.002360 |
20.00 |
0.000305 |
182.49 |
0.1029 |
1.000 |
0.1029 |
|
|
System Ventilation Parameters
|
People Outdoor Air Rate - Rp
[m3/s-person] |
Sum of Zone Population -
Pz-sum |
Area Outdoor Air Rate - Ra
[m3/s-m2] |
Sum of Zone Floor Area - Az-sum
[m2] |
Breathing Zone Outdoor Airflow -
Vbz [m3/s] |
Cooling Zone Outdoor Airflow -
Voz-clg [m3/s] |
Heating Zone Outdoor Airflow -
Voz-htg [m3/s] |
| VAV SYS 1 |
0.002360 |
52.00 |
0.000305 |
463.60 |
0.2641 |
0.2731 |
0.0000 |
Zone
Ventilation Calculations for Cooling Design
|
AirLoop Name |
Box Type |
Zone Primary Airflow - Vpz
[m3/s] |
Zone Discharge Airflow - Vdz
[m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Cooling -
Voz-clg [m3/s] |
Primary Outdoor Air Fraction -
Zpz |
Primary Air Fraction - Ep |
Secondary Recirculation
Fraction- Er |
Supply Air Fraction- Fa |
Mixed Air Fraction - Fb |
Outdoor Air Fraction - Fc |
Zone Ventilation Efficiency -
Evz |
| SPACE1-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.22 |
0.22 |
0.08 |
0.0624 |
0.280 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.900 |
| SPACE2-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.19 |
0.19 |
0.03 |
0.0276 |
0.147 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
0.900 |
| SPACE3-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.21 |
0.21 |
0.07 |
0.0554 |
0.263 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
| SPACE4-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.21 |
0.21 |
0.03 |
0.0248 |
0.120 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
| SPACE5-1 |
VAV SYS 1 |
AIRTERMINAL:SINGLEDUCT:VAV:REHEAT |
0.22 |
0.22 |
0.14 |
0.1029 |
0.465 |
1.000 |
0.000 |
0.000 |
0.000 |
0.000 |
1.000 |
System Ventilation Calculations for Cooling Design
|
Sum of Zone Primary Airflow -
Vpz-sum [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Sum of Zone Discharge Airflow -
Vdz-sum [m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Cooling -
Voz-clg [m3/s] |
Zone Ventilation Efficiency -
Evz-min |
| VAV SYS 1 |
1.05 |
1.05 |
1.05 |
0.19 |
0.2731 |
1.000 |
Zone
Ventilation Calculations for Heating Design
|
AirLoop Name |
Box Type |
Zone Primary Airflow - Vpz
[m3/s] |
Zone Discharge Airflow - Vdz
[m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Heating -
Voz-htg [m3/s] |
Primary Outdoor Air Fraction -
Zpz |
Primary Air Fraction - Ep |
Secondary Recirculation
Fraction- Er |
Supply Air Fraction- Fa |
Mixed Air Fraction - Fb |
Outdoor Air Fraction - Fc |
Zone Ventilation Efficiency -
Evz |
| None |
|
|
|
|
|
|
|
|
|
|
|
|
|
System Ventilation Calculations for Heating Design
|
Sum of Zone Primary Airflow -
Vpz-sum [m3/s] |
System Primary Airflow - Vps
[m3/s] |
Sum of Zone Discharge Airflow -
Vdz-sum [m3/s] |
Minimum Zone Primary Airflow -
Vpz-min [m3/s] |
Zone Outdoor Airflow Heating -
Voz-htg [m3/s] |
Zone Ventilation Efficiency -
Evz-min |
| VAV SYS 1 |
1.05 |
1.05 |
1.05 |
0.18+309 |
0.0000 |
1.000 |
Component Loads Summary[LINK]
Three different Component Loads Summary reports can be
generated. The Zone
Component Loads Summary, the AirLoop Component Loads Summary
and the Facility Component Loads Summary. Each provides an
estimate of the heating and cooling peak loads for each zone
broken down into various components. This report may help
determine which components of the load have the largest impact
for the heating and cooling peak design conditions. When
specified, the Zone
Component Loads Summary report is created for each zone that
is conditioned. The Sensible-Delayed column of the summary is
only an estimate based on a procedure described in the
Engineering Reference documentation. An intermediate
calculation in this procedure is the decay curves that are
shown in the the EIO file when Output:Surfaces:List
is set to show DecayCurvesFromComponentLoadsSummary. The
difference between the peak design sensible load and the
estimated instant + delayed sensible load (as shown in the
Peak Conditions subtable) is an indication of how
consistent the overall total estimate may be to the computed
total peak loads for the zone. Engineering checks have been
added showing some ratios that may be useful in checking the
results. When the report is called the zone sizing
calculations are repeated twice so this may result in longer
simulation times. The key used to obtain these reports are
ZoneComponentLoadSummary, AirLoopComponentLoadSummary,
FacilityComponentLoadSummary.
Report: ZoneComponentLoadSummary
For: SPACE1-1
Timestamp: 2012-09-21 15:48:46
Estimated Cooling Peak Load Components
|
Sensible - Instant [W] |
Sensible - Delayed [W] |
Sensible - Return Air [W] |
Latent [W] |
Total [W] |
%Grand Total |
Related Area [m2] |
Total per Area [W/m2] |
| People |
536.56 |
258.31 |
|
523.12 |
1317.99 |
35.33 |
99.16 |
13.29 |
| Lights |
15.84 |
1335.72 |
316.80 |
|
1668.36 |
44.72 |
99.16 |
16.82 |
| Equipment |
535.92 |
316.37 |
|
0.00 |
852.29 |
22.84 |
99.16 |
8.60 |
| Refrigeration |
0.00 |
|
0.00 |
0.00 |
0.00 |
0.00 |
99.16 |
0.00 |
| Water Use Equipment |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
99.16 |
0.00 |
| HVAC Equipment Losses |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
|
|
| Power Generation Equipment |
0.00 |
0.00 |
|
|
0.00 |
0.00 |
|
|
| DOAS Direct to Zone |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
|
| Infiltration |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
73.20 |
0.00 |
| Zone Ventilation |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
|
| Interzone Mixing |
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
|
| Roof |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Interzone Ceiling |
|
467.30 |
|
|
467.30 |
12.53 |
99.16 |
4.71 |
| Other Roof |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Exterior Wall |
|
374.68 |
|
|
374.68 |
10.04 |
73.20 |
5.12 |
| Interzone Wall |
|
-645.5 |
|
|
-645.5 |
-17.3 |
80.56 |
-8.0 |
| Ground Contact Wall |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Other Wall |
|
0.00 |
|
|
0.00 |
0.00 |
73.20 |
0.00 |
| Exterior Floor |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Interzone Floor |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Ground Contact Floor |
|
-2177.1 |
|
|
-2177.1 |
-58.4 |
99.16 |
-22.0 |
| Other Floor |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Fenestration Conduction |
782.86 |
|
|
|
782.86 |
20.98 |
21.81 |
35.89 |
| Fenestration Solar |
|
1089.93 |
|
|
1089.93 |
29.21 |
21.81 |
49.97 |
| Opaque Door |
|
0.00 |
|
|
0.00 |
0.00 |
0.00 |
|
| Grand Total |
1871.18 |
1019.70 |
316.80 |
523.12 |
3730.80 |
|
|
|
Cooling Peak Conditions
|
Value |
| Time of Peak Load |
7/21 15:45:00 |
| Outside Dry Bulb Temperature [C] |
31.02 |
| Outside Wet Bulb Temperature [C] |
23.14 |
| Outside Humidity Ratio at Peak [kgWater/kgAir] |
0.01459 |
| Zone Dry Bulb Temperature [C] |
23.90 |
| Zone Relative Humidity [%] |
52.91 |
| Zone Humidity Ratio at Peak [kgWater/kgAir] |
0.00979 |
| Supply Air Temperature [C] |
14.00 |
| Mixed Air Temperature [C] |
|
| Main Fan Air Flow [m3/s] |
0.22 |
| Outside Air Flow [m3/s] |
0.06 |
| Peak Sensible Load with Sizing Factor [W] |
2647.21 |
| Difference Due to Sizing Factor [W] |
0.00 |
| Peak Sensible Load [W] |
2647.21 |
| Estimated Instant + Delayed Sensible Load [W] |
2890.88 |
| Difference Between Peak and Estimated Sensible Load
[W] |
-243.7 |
Engineering Checks for Cooling
|
Value |
| Outside Air (%) |
0.2524 |
| Airflow per Floor Area [m3/s-m2] |
0.0022 |
| Airflow per Total Capacity [m3/s-W] |
0.0001 |
| Floor Area per Total Capacity [m2/W] |
0.0375 |
| Total Capacity per Floor Area [W/m2] |
26.6963 |
| Number of People |
11.0 |
Estimated Heating Peak Load Components
|
Sensible - Instant [W] |
Sensible - Delayed [W] |
Sensible - Return Air [W] |
Latent [W] |
Total [W] |
%Grand Total |
Related Area [m2] |
Total per Area [W/m2] |
| People |
0.00 |
0.00 |
|
0.00 |
0.00 |
-0.00 |
99.16 |
0.00 |
| Lights |
0.79 |
87.93 |
15.84 |
|
104.57 |
-2.7 |
99.16 |
1.05 |
| Equipment |
147.84 |
95.40 |
|
0.00 |
243.24 |
-6.2 |
99.16 |
2.45 |
| Refrigeration |
0.00 |
|
0.00 |
0.00 |
0.00 |
-0.00 |
99.16 |
0.00 |
| Water Use Equipment |
0.00 |
|
|
0.00 |
0.00 |
-0.00 |
99.16 |
0.00 |
| HVAC Equipment Losses |
0.00 |
0.00 |
|
|
0.00 |
-0.00 |
|
|
| Power Generation Equipment |
0.00 |
0.00 |
|
|
0.00 |
-0.00 |
|
|
| DOAS Direct to Zone |
0.00 |
|
|
0.00 |
0.00 |
-0.00 |
|
|
| Infiltration |
-418.4 |
|
|
-76.3 |
-494.7 |
12.68 |
73.20 |
-6.8 |
| Zone Ventilation |
0.00 |
|
|
0.00 |
0.00 |
-0.00 |
|
|
| Interzone Mixing |
0.00 |
|
|
0.00 |
0.00 |
-0.00 |
|
|
| Roof |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Interzone Ceiling |
|
-937.7 |
|
|
-937.7 |
24.03 |
99.16 |
-9.5 |
| Other Roof |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Exterior Wall |
|
-735.5 |
|
|
-735.5 |
18.85 |
73.20 |
-10.0 |
| Interzone Wall |
|
82.11 |
|
|
82.11 |
-2.1 |
80.56 |
1.02 |
| Ground Contact Wall |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Other Wall |
|
0.00 |
|
|
0.00 |
-0.00 |
73.20 |
0.00 |
| Exterior Floor |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Interzone Floor |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Ground Contact Floor |
|
437.67 |
|
|
437.67 |
-11.2 |
99.16 |
4.41 |
| Other Floor |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Fenestration Conduction |
-2601.7 |
|
|
|
-2601.7 |
66.68 |
21.81 |
-119.3 |
| Fenestration Solar |
|
0.00 |
|
|
0.00 |
-0.00 |
21.81 |
0.00 |
| Opaque Door |
|
0.00 |
|
|
0.00 |
-0.00 |
0.00 |
|
| Grand Total |
-2871.5 |
-970.1 |
15.84 |
-76.3 |
-3902.1 |
|
|
|
Heating Peak Conditions
|
Value |
| Time of Peak Load |
1/21 24:00:00 |
| Outside Dry Bulb Temperature [C] |
-17.3 |
| Outside Wet Bulb Temperature [C] |
-17.3 |
| Outside Humidity Ratio at Peak [kgWater/kgAir] |
0.00084 |
| Zone Dry Bulb Temperature [C] |
22.20 |
| Zone Relative Humidity [%] |
22.83 |
| Zone Humidity Ratio at Peak [kgWater/kgAir] |
0.00377 |
| Supply Air Temperature [C] |
50.00 |
| Mixed Air Temperature [C] |
|
| Main Fan Air Flow [m3/s] |
0.12 |
| Outside Air Flow [m3/s] |
0.06 |
| Peak Sensible Load with Sizing Factor [W] |
-3860.8 |
| Difference Due to Sizing Factor [W] |
0.00 |
| Peak Sensible Load [W] |
-3860.8 |
| Estimated Instant + Delayed Sensible Load [W] |
-3841.6 |
| Difference Between Peak and Estimated Sensible Load
[W] |
-19.2 |
Engineering Checks for Heating
|
Value |
| Outside Air (%) |
0.4817 |
| Airflow per Floor Area [m3/s-m2] |
0.0012 |
| Airflow per Total Capacity [m3/s-W] |
-0.000 |
| Floor Area per Total Capacity [m2/W] |
-0.026 |
| Total Capacity per Floor Area [W/m2] |
-38.935 |
| Number of People |
11.0 |
Output:Table:TimeBins[LINK]
A TimeBins report shows a grid of the number of hours that
specific report variable spend in a range of values. The first
table is broken into two parts. The first part is monthly and
the second part is for each hour of the day. The columns show
the range of values. A second table is provided to show some
statistics on the report variable for the entire year
including the maximum and minimum. These statistics are
helpful in setting the field values for the interval in the
Output Table:TimeBins object. Due to this, it is often
necessary to run two simulations to fully utilize the TimeBins
report with the first run used to find the minimum and maximum
of the variable, these values are then used in the TimeBins
object and the second run a better table of binned results are
displayed.
Report: PURCHASEDCOOLING:FACILITY J per second
For: Meter
Timestamp: 2006-08-30 07:48:55
Values in table are in hours.
| |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
|
|
| Interval Start |
less than |
0. < = |
2000. < = |
4000. < = |
6000. < = |
8000. < = |
10000. < = |
12000. < = |
14000. < = |
16000. < = |
18000. < = |
equal to or more than |
Row |
| Interval End |
0. |
2000. > |
4000. > |
6000. > |
8000. > |
10000. > |
12000. > |
14000. > |
16000. > |
18000. > |
20000. > |
20000. |
Total |
| January |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| February |
0.00 |
672.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
672.00 |
| March |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| April |
0.00 |
524.17 |
40.67 |
40.33 |
45.67 |
45.50 |
19.67 |
4.00 |
0.00 |
0.00 |
0.00 |
0.00 |
720.00 |
| May |
0.00 |
480.33 |
44.50 |
55.50 |
41.00 |
53.50 |
38.17 |
20.67 |
10.33 |
0.00 |
0.00 |
0.00 |
744.00 |
| June |
0.00 |
393.50 |
31.83 |
55.33 |
19.83 |
53.00 |
65.83 |
62.83 |
24.00 |
13.83 |
0.00 |
0.00 |
720.00 |
| July |
0.00 |
372.67 |
30.83 |
40.83 |
45.67 |
53.83 |
42.83 |
48.33 |
45.33 |
47.83 |
15.83 |
0.00 |
744.00 |
| August |
0.00 |
373.50 |
24.50 |
37.17 |
44.50 |
64.50 |
56.67 |
50.67 |
52.33 |
35.00 |
5.17 |
0.00 |
744.00 |
| September |
0.00 |
406.33 |
52.00 |
42.50 |
14.83 |
54.50 |
64.67 |
54.50 |
27.17 |
3.50 |
0.00 |
0.00 |
720.00 |
| October |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| November |
0.00 |
720.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
720.00 |
| December |
0.00 |
744.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
744.00 |
| 12:01 to 1:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 1:01 to 2:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 2:01 to 3:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 3:01 to 4:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 4:01 to 5:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 5:01 to 6:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 6:01 to 7:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 7:01 to 8:00 am |
0.00 |
294.33 |
33.83 |
25.00 |
5.17 |
2.17 |
1.67 |
1.17 |
1.00 |
0.67 |
0.00 |
0.00 |
365.00 |
| 8:01 to 9:00 am |
0.00 |
238.00 |
14.17 |
16.50 |
17.00 |
40.33 |
29.67 |
9.33 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 9:01 to 10:00 am |
0.00 |
231.83 |
14.50 |
13.00 |
21.83 |
38.83 |
31.83 |
12.00 |
1.17 |
0.00 |
0.00 |
0.00 |
365.00 |
| 10:01 to 11:00 am |
0.00 |
226.33 |
14.00 |
12.50 |
17.50 |
36.50 |
31.33 |
22.17 |
4.67 |
0.00 |
0.00 |
0.00 |
365.00 |
| 11:01 to 12:00 pm |
0.00 |
221.33 |
12.17 |
13.00 |
14.50 |
30.67 |
33.50 |
27.83 |
11.00 |
1.00 |
0.00 |
0.00 |
365.00 |
| 12:01 to 1:00 pm |
0.00 |
211.00 |
18.00 |
14.00 |
14.00 |
29.17 |
32.33 |
25.67 |
17.67 |
3.17 |
0.00 |
0.00 |
365.00 |
| 1:01 to 2:00 pm |
0.00 |
208.00 |
15.00 |
15.33 |
11.00 |
22.17 |
27.83 |
27.50 |
26.83 |
10.83 |
0.50 |
0.00 |
365.00 |
| 2:01 to 3:00 pm |
0.00 |
205.33 |
11.83 |
18.17 |
11.00 |
17.50 |
23.17 |
29.50 |
26.17 |
18.17 |
4.17 |
0.00 |
365.00 |
| 3:01 to 4:00 pm |
0.00 |
203.00 |
9.50 |
17.67 |
14.00 |
16.17 |
20.67 |
30.17 |
22.00 |
24.83 |
7.00 |
0.00 |
365.00 |
| 4:01 to 5:00 pm |
0.00 |
201.17 |
10.83 |
18.83 |
13.67 |
16.33 |
19.50 |
29.67 |
22.83 |
25.17 |
7.00 |
0.00 |
365.00 |
| 5:01 to 6:00 pm |
0.00 |
200.00 |
13.50 |
21.33 |
14.83 |
22.17 |
22.67 |
26.00 |
25.83 |
16.33 |
2.33 |
0.00 |
365.00 |
| 6:01 to 7:00 pm |
0.00 |
227.33 |
29.17 |
43.17 |
28.33 |
27.50 |
9.50 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 7:01 to 8:00 pm |
0.00 |
235.83 |
27.83 |
43.17 |
28.67 |
25.33 |
4.17 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 8:01 to 9:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 9:01 to 10:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 10:01 to 11:00 pm |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| 11:01 to 12:00 am |
0.00 |
365.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
365.00 |
| Total |
0.00 |
6918.50 |
224.33 |
271.67 |
211.50 |
324.83 |
287.83 |
241.00 |
159.17 |
100.17 |
21.00 |
0.00 |
8760.00 |
Statistics
| |
Statistic |
| Minimum |
0.00 |
| Mean minus two standard
deviations |
-6496.35 |
| Mean |
1995.71 |
| Mean plus two standard
deviations |
10487.78 |
| Maximum |
19476.00 |
| Standard deviation |
4246.03 |
Output:Table:Monthly[LINK]
Monthly reports are not predefined. Instead each column is
defined when using the Output:Table:Monthly
object. In that object each column is defined by a variable
and how it should be aggregated. The StandardReports.idf file
is located in DataSets directory where EnergyPlus is installed
and contains a large number of examples of how to use Output:Table:Monthly
to get summaries of the performance of different components in
the building model. These examples include:
Zone
Cooling Summary
Zone
Heating Summary
Zone
Electric Summary
Space
Gains
Peak Space
Gains
Space
Gain Components at Cooling Peak
Energy Consumption - Electricity & Natural
Gas
Energy Consumption - Electricity Generated &
Propane
Energy Consumption - Diesel & Fuel Oil
Energy Consumption - Purchased Heating &
Cooling
Energy Consumption - Coal & Gasoline
End-Use Energy Consumption - Electricity
End-Use Energy Consumption - Natural Gas
End-Use Energy Consumption - Diesel
End-Use Energy Consumption - Fuel Oil
End-Use Energy Consumption - Coal
End-Use Energy Consumption - Propane
End-Use Energy Consumption - Gasoline
Peak Energy End-Use - Electricity Part 1
Peak Energy End-Use - Electricity Part 2
Electric Components of Peak Demand
Peak Energy End-Use - Natural Gas
Peak Energy End-Use - Diesel
Peak Energy End-Use - Fuel Oil
Peak Energy End-Use - Coal
Peak Energy End-Use - Propane
Peak Energy End-Use - Gasoline
Setpoints Not Met With Temperatures
Comfort Report - Simple 55
Unglazed Transpired Solar Collector Summary
Occupant Comfort Data Summary
Chiller Report
Tower Report
Boiler Report
DX Report
Window
Report
Window
Energy Report
Window
Zone
Summary
Average Outdoor Conditions
Outdoor Conditions Maximum Drybulb
Outdoor Conditions Minimum Drybulb
Outdoor Conditions Maximum Wetbulb
Outdoor Conditions Maximum Dewpoint
Outdoor Ground Conditions
Window
AC Report
Water Heater Report
Generator Report
Daylighting Report
Coil Report
Plant Loop Demand Report
Fan Report
Pump Report
Cond Loop Demand Report
Zone
Temperature Oscillation Report
Air Loop System Energy and Water Use
Air Loop System Component Loads
Air Loop System Component Energy Use
Mechanical Ventilation Loads
An example of the Zone
Cooling Summary monthly report is shown below.
Report: ZONE COOLING SUMMARY
For: SPACE2-1
Timestamp: 2006-08-29 07:21:57
| |
ZONE/SYS SENSIBLE COOLING ENERGY
[J] |
ZONE/SYS SENSIBLE COOLING RATE
{MAXIMUM}[W] |
ZONE/SYS SENSIBLE COOLING RATE
{TIMESTAMP} |
OUTDOOR DRY BULB {AT MAX/MIN}
[C] |
OUTDOOR WET BULB {AT MAX/MIN}
[C] |
ZONE TOTAL INTERNAL LATENT GAIN
[J] |
ZONE TOTAL INTERNAL LATENT GAIN
{MAXIMUM}[W] |
ZONE TOTAL INTERNAL LATENT GAIN
{TIMESTAMP} |
OUTDOOR DRY BULB {AT MAX/MIN}
[C] |
OUTDOOR WET BULB {AT MAX/MIN}
[C] |
| January |
281755456.00 |
1427.84 |
17-JAN-10:07 |
8.30 |
5.48 |
0.00 |
0.00 |
01-JAN-00:15 |
-4.32 |
-5.53 |
| February |
306879872.00 |
1440.59 |
28-FEB-10:46 |
11.27 |
6.67 |
0.00 |
0.00 |
01-FEB-00:15 |
-3.17 |
-4.91 |
| March |
419829728.00 |
1822.13 |
26-MAR-09:14 |
3.90 |
-0.20 |
0.00 |
0.00 |
01-MAR-00:15 |
-1.40 |
-2.84 |
| April |
752874688.00 |
1986.25 |
29-APR-10:22 |
21.10 |
11.44 |
0.00 |
0.00 |
01-APR-00:15 |
17.12 |
10.64 |
| May |
0.100670E+10 |
2163.18 |
22-MAY-09:45 |
25.17 |
15.42 |
0.00 |
0.00 |
01-MAY-00:15 |
3.75 |
1.60 |
| June |
0.100822E+10 |
2129.73 |
28-JUN-09:45 |
28.02 |
22.39 |
0.00 |
0.00 |
01-JUN-00:15 |
17.30 |
14.95 |
| July |
0.120671E+10 |
2312.36 |
08-JUL-09:00 |
31.70 |
23.35 |
0.00 |
0.00 |
01-JUL-00:15 |
15.60 |
12.95 |
| August |
0.109213E+10 |
2352.64 |
02-AUG-09:45 |
27.08 |
20.48 |
0.00 |
0.00 |
01-AUG-00:15 |
17.20 |
15.70 |
| September |
0.100619E+10 |
2453.23 |
06-SEP-10:15 |
28.35 |
20.53 |
0.00 |
0.00 |
01-SEP-00:15 |
16.75 |
15.45 |
| October |
771385600.00 |
2181.25 |
10-OCT-10:16 |
15.25 |
10.12 |
0.00 |
0.00 |
01-OCT-00:15 |
4.88 |
3.31 |
| November |
384831744.00 |
1566.35 |
11-NOV-10:45 |
14.00 |
8.89 |
0.00 |
0.00 |
01-NOV-00:15 |
14.65 |
11.75 |
| December |
246930448.00 |
1306.75 |
11-DEC-10:07 |
5.00 |
1.69 |
0.00 |
0.00 |
01-DEC-00:15 |
1.80 |
-0.11 |
| |
|
|
|
|
|
|
|
|
|
|
| Annual Sum or Average |
0.848444E+10 |
|
|
|
|
0.00 |
|
|
|
|
| Minimum of Months |
246930448.00 |
1306.75 |
|
3.90 |
-0.20 |
0.00 |
0.00 |
|
-4.32 |
-5.53 |
| Maximum of Months |
0.120671E+10 |
2453.23 |
|
31.70 |
23.35 |
0.00 |
0.00 |
|
17.30 |
15.70 |
UtilityCost:Tariff[LINK]
Two output reports – EconomicResultSummary and TariffReport
– are related to the use of UtilityCost:Tariff
for the calculation of annual utility costs. Since EnergyPlus
8.6, these reports are no longer generated and need to be
specifically requested. To get the reports individually use
EconomicResultSummary and TariffReport in
the Output:Table:SummaryReports
object. These are also available when using any of the
AllSummary options.
The first report is a summary across multiple tariffs and
is called the Economics Results Summary report and is shown
directly below. After that example is an example of the Tariff
report which is created for each of the UtilityCost:Tariff
Objects defined in the IDF file (some columns may be truncated
due to page size).
Report: Economics Results Summary Report
For: Entire Facility
Timestamp: 2006-08-29 07:21:57
Annual Cost
| |
Facility:Electric |
Facility:Gas |
Other |
Total |
| Cost ($) |
2269.11 |
612.08 |
0.00 |
2881.19 |
| Cost per Total Building Area
($/m2) |
2.45 |
0.66 |
0.00 |
3.11 |
| Cost per Net Conditioned
Building Area (\$/m2) |
2.45 |
0.66 |
0.00 |
3.11 |
Tariff Summary
| |
Selected |
Qualified |
Meter |
Group |
Annual Cost |
| EXAMPLE A |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2359.48 |
| EXAMPLE A-GAS |
Yes |
Yes |
GAS:FACILITY |
(none) |
612.08 |
| EXAMPLE A WITH VARIABLE MONTHLY
CHARGE |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2407.36 |
| EXAMPLE B |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
2668.34 |
| EXAMPLE C |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3017.45 |
| EXAMPLE D |
Yes |
Yes |
ELECTRICITY:FACILITY |
(none) |
2269.11 |
| EXAMPLE D WITH RATCHET |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3745.90 |
| EXAMPLE E |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3766.76 |
| EXAMPLE F |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3512.12 |
| EXAMPLE F MC |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3512.12 |
| EXAMPLE G |
No |
Yes |
ELECTRICITY:FACILITY |
(none) |
3866.91 |
The following is an example of the Tariff report which is
created for each of the UtilityCost:Tariff
objects defined in the file.
Report: Tariff Report
For: EXAMPLEA
Timestamp: 2006-08-29 07:21:57
| |
Parameter |
| Meter |
ELECTRICITY:FACILITY |
| Selected |
No |
| Group |
(none) |
| Qualified |
Yes |
| Disqualifier |
n/a |
| Computation |
automatic |
| Units |
kWh |
Categories
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| EnergyCharges |
181.84 |
159.97 |
170.98 |
178.85 |
207.28 |
207.97 |
249.10 |
234.09 |
202.57 |
191.20 |
169.19 |
176.34 |
2329.36 |
249.10 |
| DemandCharges |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ServiceCharges |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
2.51 |
30.12 |
2.51 |
| Basis |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
| Adjustment |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Surcharge |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Subtotal |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
| Taxes |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| Total |
184.35 |
162.48 |
173.49 |
181.36 |
209.79 |
210.48 |
251.61 |
236.60 |
205.08 |
193.71 |
171.70 |
178.85 |
2359.48 |
251.61 |
Charges
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
Category |
| FLAT ENERGY CHARGE |
181.84 |
159.97 |
170.98 |
178.85 |
207.28 |
207.97 |
249.10 |
234.09 |
202.57 |
191.20 |
169.19 |
176.34 |
2329.36 |
249.10 |
none |
Ratchets
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —
—– —– —– —– —– —– —– —– —– —– —– —– —– —–
Qualifies
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max —
—– —– —– —– —– —– —– —– —– —– —– —– —– —–
Native Variables
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| TotalEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| TotalDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| PeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ShoulderDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| OffPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| OffPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| MidPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| MidPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsOffPeak |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| OffPeakExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsMidPeak |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| MidPeakExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakExceedsShoulder |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderExceedsPeak |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsWinter |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsNotWinter |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsSpring |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotSpring |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsSummer |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotSummer |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| IsAutumn |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| IsNotAutumn |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
1.00 |
12.00 |
1.00 |
| PeakAndShoulderEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndShoulderDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| PeakAndMidPeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndMidPeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
| ShoulderAndOffPeakEnergy |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| ShoulderAndOffPeakDemand |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
| PeakAndOffPeakEnergy |
3285.70 |
2890.52 |
3089.52 |
3231.79 |
3745.42 |
3757.86 |
4501.09 |
4229.79 |
3660.28 |
3454.82 |
3057.13 |
3186.33 |
42090.24 |
4501.09 |
| PeakAndOffPeakDemand |
12.52 |
12.53 |
12.53 |
14.53 |
17.40 |
20.71 |
21.08 |
19.50 |
18.63 |
15.53 |
12.90 |
12.55 |
190.42 |
21.08 |
Other Variables
| |
Jan |
Feb |
Mar |
Apr |
May |
Jun |
Jul |
Aug |
Sep |
Oct |
Nov |
Dec |
Sum |
Max |
| NotIncluded |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
Computation - Automatic FLATENERGYCHARGE FROM TotalEnergy
EnergyCharges SUM FLATENERGYCHARGE Basis SUM EnergyCharges
DemandCharges ServiceCharges Subtotal SUM Basis Adjustment
Surcharge Total SUM Subtotal Taxes
Construction Cost
Estimate Summary[LINK]
The Construction
Cost Estimate Summary report shows the details of a simplified
cost estimate of the building along with a comparison with
reference building costs entered by the user. An example of
the Construction
Cost Estimate Summary report is shown below.
Construction
Cost Estimate Summary
| |
Reference Bldg. |
Current Bldg. Model |
Difference |
| Line Item SubTotal ($) |
665082.04 |
720964.07 |
55882.03 |
| Misc. Costs ($) |
928979.09 |
928979.09 |
0.00 |
| Regional Adjustment ($) |
216792.31 |
224392.27 |
7599.96 |
| Design Fee ($) |
108651.21 |
149946.83 |
41295.63 |
| Contractor Fee ($) |
126759.74 |
131203.48 |
4443.74 |
| Contigency ($) |
181085.34 |
187433.54 |
6348.20 |
| Permits, Bonds, Insurance
($) |
0.00 |
0.00 |
0.00 |
| Commissioning ($) |
9054.27 |
18743.35 |
9689.09 |
| Cost Estimate Total ($) |
2236404.00 |
2361662.65 |
125258.65 |
| Cost Per Conditioned Building
Area ($/m2) |
1203.69 |
1271.11 |
67.42 |
Cost Line Item Details
| |
Line No. |
Item Name |
Quantity. |
Units |
$ per Qty. |
SubTotal $ |
| – |
1 |
EXTERIOR WALLS |
627.57 |
m2 |
168.64 |
105832.65 |
| – |
2 |
INTERIOR WALLS |
854.18 |
m2 |
31.16 |
26616.23 |
| – |
3 |
ROOF |
1857.96 |
m2 |
104.69 |
194509.64 |
| – |
4 |
GROUND FLR SLAB |
1857.96 |
m2 |
56.06 |
104157.14 |
| – |
5 |
ACOUSTICAL DROP CEILINGS |
1857.96 |
m2 |
23.79 |
44200.83 |
| – |
6 |
QUAD HIGH SHGC SUPERWINDOWS |
226.22 |
m2 |
687.84 |
155604.96 |
| – |
7 |
QUAD LOW SHGC SUPERWINDOWS |
42.68 |
m2 |
687.84 |
29359.55 |
| – |
8 |
CENTRAL CHILLER |
153.48 |
kW (tot cool cap.) |
340.00 |
52183.09 |
| – |
9 |
CONTINUOUS AIR BARRIER |
1.00 |
Ea. |
8500.00 |
8500.00 |
| Line Item SubTotal |
– |
– |
– |
– |
– |
720964.07 |
XML Tabular Output[LINK]
The tables discussed in this section can also be output in
an XML format that may be easier for some other programs to
extract specific results. An excerpt of the XML file format is
shown below. This report presents the same output results as
the other tabular report formats but using XML tags.
<?xml version = “1.0”?>
<EnergyPlusTabularReports>
<BuildingName>NONE</BuildingName>
<EnvironmentName>Chicago Ohare Intl Ap IL USA TMY3
WMO# = 725300</EnvironmentName>
<WeatherFileLocationTitle>Chicago Ohare Intl Ap IL
USA TMY3 WMO# = 725300</WeatherFileLocationTitle>
<ProgramVersion>EnergyPlus, Version
8.0, YMD = 2013.02.18 15:50</ProgramVersion>
<SimulationTimestamp>
<Date>
2013-02-18
</Date>
<Time>
15:50:33
</Time>
</SimulationTimestamp>
<AnnualBuildingUtilityPerformanceSummary>
<for>Entire Facility</for>
<SiteAndSourceEnergy>
<name>TotalSiteEnergy</name>
<TotalEnergy units =
“kBtu”>200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units =
“kBtu/ft2”>143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units =
“kBtu/ft2”>143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSiteEnergy</name>
<TotalEnergy units =
“kBtu”>200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units =
“kBtu/ft2”>143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units =
“kBtu/ft2”>143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>TotalSourceEnergy</name>
<TotalEnergy units =
“kBtu”>442504.19</TotalEnergy>
<EnergyPerTotalBuildingArea units =
“kBtu/ft2”>316.04</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units =
“kBtu/ft2”>316.04</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSourceEnergy</name>
<TotalEnergy units =
“kBtu”>397810.98</TotalEnergy>
<EnergyPerTotalBuildingArea units =
“kBtu/ft2”>284.12</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units =
“kBtu/ft2”>284.12</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
An actual file will be much longer than this example
but follows this format.
eplustbl.<ext>[LINK]
The eplustbl file contains the tabular output results that are created when using the following objects:
Output:Table:SummaryReports
Output:Table:TimeBins
Output:Table:Monthly
UtilityCost:Tariff
ComponentCost:Line Item
The format and the extension for the file depends on the setting of the ColumnSeparator field of the Output:Table:Style object. The choices of HTML, tab, fixed, comma, and XML result in eplustbl.htm, eplustbl.tab, eplustbl.txt, eplustbl.csv, eplustbl.xml respectively. The HTML version of the report also includes a table of contents that allows easier navigation through the file.
By default the energy units reported in all of the eplustbl files are in Joules (J) but the UnitConversion field of the Output:Table:Style object allows for the values to be reported in MJ, GJ or in kWh. In addition, the Output:Table:Style object can specify for the tables to be in IP units for all fields.
Output:Table:SummaryReports[LINK]
Several predefined reports are available from the Output:Table:SummaryReports object including the following. (spaces are inserted in names for readability; keys are included in the Input Data Dictionary or by just removing the spaces):
Lists all following applicable tables with “Summary” in the name.
Lists all following applicable tables with “Monthly” in the name.
Lists all following applicable tables with both “Summary” and “Monthly” in the name. This does not include the Zone Component Load Summary report.
Lists the All Summary tables as well as the Zone Component Load report (currently the only Sizing Period report). Please note that the Zone Component Load report does increase the run time because it repeats sizing periods.
Lists the All Summary tables, the Monthly tables as well as the Zone Component Load report (currently the only Sizing Period report). Please note that the Zone Component Load report does increase the run time because it repeats sizing periods.
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Component Cost Economics Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
Zone Component Load Summary
Zone Cooling Summary Monthly
Zone Heating Summary Monthly
Zone Electric Summary Monthly
Space Gains Monthly
Peak Space Gains Monthly
Space Gain Components At Cooling Peak Monthly
Energy Consumption Electricity Natural Gas Monthly
Energy Consumption Electricity Generated Propane Monthly
Energy Consumption Diesel FuelOil Monthly
Energy Consumption District Heating Cooling Monthly
Energy Consumption Coal Gasoline Monthly
End Use Energy Consumption Electricity Monthly
End Use Energy Consumption NaturalGas Monthly
End Use Energy Consumption Diesel Monthly
End Use Energy Consumption FuelOil Monthly
End Use Energy Consumption Coal Monthly
End Use Energy Consumption Propane Monthly
End Use Energy Consumption Gasoline Monthly
Peak Energy End Use Electricity Part1 Monthly
Peak Energy End Use Electricity Part2 Monthly
Electric Components Of Peak Demand Monthly
Peak Energy End Use NaturalGas Monthly
Peak Energy End Use Diesel Monthly
Peak Energy End Use FuelOil Monthly
Peak Energy End Use Coal Monthly
Peak Energy End Use Propane Monthly
Peak Energy End Use Gasoline Monthly
Setpoints Not Met With Temperatures Monthly
Comfort Report Simple55 Monthly
Unglazed Transpired Solar Collector Summary Monthly
Occupant Comfort Data Summary Monthly
Chiller Report Monthly
Tower Report Monthly
Boiler Report Monthly
DX Report Monthly
Window Report Monthly
Window Energy Report Monthly
Window Zone Summary Monthly
Window Energy Zone Summary Monthly
Average Outdoor Conditions Monthly
Outdoor Conditions Maximum DryBulb Monthly
Outdoor Conditions Minimum DryBulb Monthly
Outdoor Conditions Maximum WetBulb Monthly
Outdoor Conditions Maximum DewPoint Monthly
Outdoor Ground Conditions Monthly
WindowAC Report Monthly
Water Heater Report Monthly
Generator Report Monthly
Daylighting Report Monthly
Coil Report Monthly
PlantLoop Demand Report Monthly
Fan Report Monthly
Pump Report Monthly
CondLoop Demand Report Monthly
Zone Temperature Oscillation Report Monthly
AirLoop System Energy And Water Use Monthly
AirLoop System Component Loads Monthly
AirLoop System Component Energy Use Monthly
Mechanical Ventilation Loads Monthly
Each of these reports is made up of several sub-tables of information. Examples of some of the tables are shown below. To enable all of the reports the single All Summary may be specified.
Annual Building Utility Performance Summary[LINK]
The Annual Building Utility Performance Summary report provides an overview of energy consumption in the building for different end uses. The following is an example this report (some columns may be truncated due to page size). The key used to obtain this report is AnnualBuildingUtilityPerformanceSummary.
In the Comfort and Setpoint Not Met Summary sub-table, facility hours represents the total number of hours that any single zone did not meet the comfort or setpoint criteria. It is not weighted by number of zones or number of occupants.
The values in the End Uses sub-table are from report meters. To determine which components are attached to each end-use meter, consult the meter details output file (*.mtd).
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Values gathered over 8760.00 hours
Site and Source Energy
Source to Site Energy Converstion Factors
Building Area
End Uses
Note: Natural gas appears to be the principal heating source based on energy usage.
End Uses By Subcategory
Normalized Metrics
Utility Use Per Conditioned Floor Area
Utility Use Per Total Floor Area
Electric Loads Satisfied
On-Site Thermal Sources
Water Source Summary
Comfort and Setpoint Not Met Summary
Note 1: An asterisk (*) indicates that the feature is not yet implemented.
Input Verification and Results Summary[LINK]
The Input Verification and Results Summary report provides a summary of some of the most common input assumptions that are not included in any of the other predefined reports. Directly following is an example of the report. The key used to obtain this report is InputVerificationandResultsSummary.
Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
General
ENVELOPE
Window-Wall Ratio
Skylight-Roof Ratio
PERFORMANCE
Zone Summary
Note: In order to properly read the summary rows of this table, the following rules apply:
If the Zone
Part of Total Floor Areais set to ‘No’, then it will only be counted towards the "Not Part of Total" rowOtherwise, it is added to the "Total" row. Then, if the zone is also conditioned, it is added to the "Conditioned Total" row; If unconditioned, it is added to the "Unconditioned Total" row.
Demand End Use Components Summary[LINK]
The Demand End Use Components Summary report shows the demand breakdown by component end use at the time that the peak demand for each source of energy is set. The time of the peak demand is shown in the first row. The contributions of each end use at the time of the peak demand of the energy source is shown in this report. The key used to obtain this report is DemandEndUseComponentsSummary.
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
End Uses
End Uses By Subcategory
Source Energy End Use Components Summary[LINK]
The Source Energy End Use Components Summary report produces a report that includes three tables. These tables display source energy by fuel type that is calculated based on site to source energy factors specified by the user in the EnvironmentalImpactFactors and FuelFactors objects. The last two tables display the source energy in terms of area normalized metrics. Directly following is an example of the three tables. The key used to obtain this report is SourceEnergyEndUseComponentsSummary.
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components Summary
Total Source Energy End Use Components 1125.82 140.03 0.00 0.00 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned Floor Area
Total Source Energy End Use Components 1214.22 151.02 0.00 0.00 0.00
Source Energy End Use Components Per Total Floor Area
Total Source Energy End Use Components 1214.22 151.02 0.00 0.00 0.00
Equipment Summary[LINK]
The Equipment Summary report provides a summary of the HVAC related equipment in the building. The central chiller example shows the most common type of chillers, boilers and towers used in EnergyPlus. The remaining subtables cover DX coils, fans and water heating equipment. Not every type of HVAC equipment is represented in this report. Directly following is an example of the report. The key used to obtain this report is EquipmentSummary.
Report: Equipment Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Central Plant
Cooling Coils
Heating Coils
Fans
Pumps
Service Water Heating
Envelope Summary[LINK]
The Envelope Summary report provides a summary of the elements of the envelope of the building. The first table describes the exterior opaque elements and the second table describes the fenestration elements. Reflectance is defined as one minus the thermal absorptance. Directly following is an example of the report. The key used to obtain this report is EnvelopeSummary.
Report: Envelope Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Opaque Exterior
Fenestration
Surface Shadowing Summary[LINK]
The Surface Shadowing Summary report summarizes how the surfaces may cast shadows on other surfaces. Directly following is an example of the report. The key used to obtain this report is SurfaceShadowingSummary.
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces
Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces
Shading Summary[LINK]
The Shading Summary report shows how much of each window is sunlit at different times of the year and also includes a summary of the window controls. Directly following is an example of the report. The key used to obtain this report is ShadingSummary.
Report: Shading Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Sunlit Fraction
Window Control
Lighting Summary[LINK]
The Lighting Summary report provides a description of the interior and exterior lighting systems being simulated. It also provides a summary of daylighting controls. The Interior Lighting table has three columns that are explained below:
Scheduled Hours/Week [hr] - In the schedule shown, this represents the average weekly sum of hourly values. It is based on a full year even if the simulation is only performed for part of the year. It is not affected by daylighting.
Hours/Week > 1% [hr] – This represents the average hours per week that are above 1% of the design value.
Full Load Hours/Week [hr] – This is based on consumption and hours that the consumption occurred. It is dependent on the run period used. When simulating only a portion of the year, the value depends on which days of the year (the number of weekdays versus weekend days, for example) are simulated. It also indicates the impact of daylighting control. Directly following is an example of the report. The key used to obtain this report is LightingSummary.
Report: Lighting Summary
For: Entire Facility
Timestamp: 2012-09-05 12:10:52
Interior Lighting
Daylighting
Exterior Lighting
HVAC Sizing Summary[LINK]
The HVAC Sizing Summary report provides information on the zone cooling and heating sizing and the peak load conditions as well as information about the system air flow sizing. The Design Load is the zone sensible load only and it does not include any system effects or ventilation loads. The user specified design load and airflow and the values calculated by the program are shown in the report along with the time of the peak load and the temperature and humidity ratio at the time of the peak during the sizing periods. This information is generated for both the Zone Sensible Cooling and Zone Sensible Heating tables.
Also included is the System Design Air Flow Rates which includes the calculated cooling air flow rate, the user specified air flow rate for cooling, the calculated heating air flow rate, and the user specified air flow rate for heating.
Note: values listed as “calculated” are the unaltered result of the zone or system sizing calculations, using the design sizing period weather and schedules specified in the input. Values listed as “user specified” are either the calculated values modified by global or zone sizing factors or values specified with the flow/zone or flow/system design air flow method.
The HVAC Sizing Summary also includes a coil summary report table. This is a large data table that collects a variety of results organized by each individual coil. It can be viewed in html or csv format but it expected to be used from the sqlite database. The table has 87 columns and a row for each coil in the building model. The column titles are also called fields here, as in fields to use with a database query.
Throughout this table the special value of -999.0 is deliberately used to signal that no data are available to report for that coil for that field or column. This could be for a variety of reasons such as, no sizing calculations in the model, did not run design day full simulations, particular fields only applies to certain types of coils, certain calculations are only performed for particular coils, etc. If you find a -999.0 in a situation where you think the value should be available, please report it. Another special value of -99999.0 may be encountered which is used within EnergyPlus to signal that numeric input fields were set to Autosize, Autocalculate, or left blank and in some cases this value will carry into the coil report table.
The encyclopedic documentation that follows is important because in many cases, very similiar data are available from up to three separate fields and one must be careful to understand the subtle differences and be aware that there is some repetition of the similar types of data in the fields. This is mainly because coil performance changes with the conditions under which it operates and so an important part of this table is describing each coil under different sets of operating conditions.
There are three broad groupings of data fields in the table:
Meta data. The meta data fields include string names to identify the coil, where it is being used, names and types of IDF objects involved, what some of the various sizing method input choices were set to, and information about the supply fan and plant found to be associated with the coil. 40 fields.
Ideal loads sizing summary. The collection of fields whose names end with “at Ideal Loads Peak” are all related to the sizing calculations done by the ideal loads zone sizing routines and the system sizing routines based on them. Many of the values reported here come from Sizing:Zone and/or Sizing:System input. The operating conditions occuring during Ideal Loads sizing calculations are unlikely to match the conditions used in the definitions for coil input data. 36 fields.
Rating point summary. This is a collection of fields with names that end in “at Rating Conditions.” The model input data for many types of coils is based on defined set of conditions variously referred to as the rating point, reference, nominal, or design. The coil models are calculated with conditions set to match the rating point and the inputs and outputs from that are reported here. Many of the values here are from the input documentation that defines the conditions at the rating point. The coil capacities and leaving conditions are the results from the running complete coil model. Some coil models do not have a rating point as part of the model definition, because the models are not sensitive to operating conditions, and those coils will have -999.0 in these fields. 11 fields.
The following is a comprehensive listing of each column/field in the coil summary table with a brief definition and/or summary.
Coil Type The input object class name in IDF syntax. Text string.
Coil Location The broad type of HVAC this coil is being used in. “AirLoop” means the coil is part of a central air system, such as a main coil in a multizone air handler. “Zone Equipment” means that the coil is part of Zone equipment like a PTAC, or in the zone terminal unit of an airhandler like a VAV reheat coil. Text string.
HVAC Type This is more specifically what HVAC the coil is used in. The values are the input object class name, in IDF syntax, found to be associated with the coil. Text string.
HVAC Name This is the unique user name input for the HVAC Type. The strings will be converted to upper case compared to what is in the actual input data file. Text string.
Zone Name(s) This is the zone, or list of zones, found to be associated with this coil. The zone name is defined by the user in the Zone object. For multizone systems, the coils can have a list of zone names with the individual names separated by a semicolon. The zones listed here are those used to generate (aggregate and volume-weighted average) values for the room conditions and loads. Text string.
System Sizing Method Concurrence This field applies to “AirLoop” coils. It describes if the central air system sizing was done using “Coincident” or “Non-Coincident” method. This refers to how the ideal loads sizing routines process the time sequence of zone loads. The concurrent sum of peaks, or coincident or "block", is often lower than the sum of the individual peaks regardless of when they occur, or non-conicident sum. This field is not applicable to “Zone Equipment” coils and will show “N/A” here. This corresponds to the input field called Type of Zone Sum to Use in the Sizing:System input object. Text string.
System Sizing Method Capacity This field applies to “AirLoop” coils. It describes what was chosen for the method of determining coil capacity during ideal loads sizing routines. The values here will match the input key choices available for the the Sizing:System object’s input fields called Cooling Design Capacity Method, for cooling coils, and Heating Design Capacity Method, for heating coils. Values here of “HeatingDesignCapacity” or “CoolingDesignCapacity” mean that the coil was sized using the design loads calculated from the zone ideal loads results. When sizing was scaled using floor area the value here would be “CapacityPerFloorArea.” Values of FractionOfAutosizedHeatingCapacity and FractionOfAutosizeCoolingCapacity mean that the usual design load based results were further scaled by a separate user scaling factor. This field is not applicable to “Zone Equipment” coils and will show “N/A” here. Text string.
System Sizing Method Air Flow This field applies to “AirLoop” coils. It describes what was chosen for the method of determining the system air flow rate during ideal loads sizing routines. This field is not applicable to “Zone Equipment” coils and will show “N/A” here. Text string.
Autosized Coil Capacity? This field describes if the coil capacity was autosized or not. Values here will be “Yes” or “No.” A “No” means that the size of the coil was set at input, hard sized, and no capacity sizing calculations were done for the coil. A “Yes” means that coil’s capacity was autosized. Text string.
Autosized Coil Airflow? This field describes if the coil’s airflow rate was autosized or not. Values here will be “Yes” or “No.” A “No” means that the airflow rate used to size the coil’s capacity was set at input, hard sized. This means that the coil’s capacity was set for an airflow rate that was not autosized. A “Yes” means that the airflow rate for the coil came from sizing calculations. Text string.
Autosized Coil Water Flow? This field describes if the coil’s water flow rate was autosized or not. Values here will be “Yes” or “No.” A “No” means that the water flow rate used to size the coil’s capacity was set at input, hard sized. This means that the coil’s capacity was set for a water flow rate that was not autosized. A “Yes” means that the water flow rate for the coil came from sizing calculations. This field is only applicable to water-to-air coils. Text string.
OA Pretreated prior to coil inlet? This field describes if the coil’s sizing calculations are based on the outdoor air being preconditioned, as with a separate coil, or if the outdoor air is unconditioned. Values here will be “Yes” or “No.” A “No” means that the outdoor air is not preconditioned. A “Yes” means that the outdoor is preconditioned. This field only really applies to central air system coils. The outdoor air may be mixed with return air before the coil, but that mixed air may be based on either treated or untreated outdoor air, depending on Sizing:System input. Text string.
Coil Final Gross Total Capacity [W] This field describes the coil’s gross total capacity, in units of W. No fan impact. This field will generally be the main value the model uses for capacity as a result of the sizing calculations. However if a coil was not autosized, the capacity was hard sized on input, then this field will be filled with the hard sized coil capacity (if that is a parameter in the coil model). This field is very similiar to the field called Coil Total Capacity at Rating Conditions with the difference being that this one is the model input while that other one is the result of running the full coil model at the rating point conditions. Water heating coil models using UA and design water flow rate performance input method do not have a single design capacity in Watts and this field will show as -99999.0 (and the coil is better characterized using the field called Coil U-value Times Area Value). Real number.
Coil Final Gross Sensible Capacity [W] Real number. This field describes the coil’s gross sensible capacity, if available, in units of W. No fan impact. This field is generally the total capacity multiplied by the sensible heat ratio if both are defined in the model. Real number.
Coil Final Reference Air Volume Flow Rate [m3/s] This field describes the coil’s rated/reference/nominal air flow rate, in units of m3/s. This field will generally be the model input (or autosize result) for the process air flow rate through the coil at the rating point. Some coil models do not have any rated/reference/nominal air flow rate as part of the model description (d.g. electric and gas heating coils) and these will have -999.0 in this field. Real number.
Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] This field describes the coil’s rated/reference/nominal water flow rate, in units of m3/s. This field will be the model input or autosize result for the source water, or other plant fluid type, flow rate through the coil at the design or rating point. Many coils have no water source and these will have -999.0 in this field. Real number.
Coil U-value Times Area Value [W/K] This field describes the coil’s overall UA value, in units of W/K. This is mainly for the Coil:Heating:Water coil using the Performance Input method of UFactorTimesAirAndDesignWaterFlowRate and is not avaliable for other coils. This will be the result from the ideal loads sizing calculations or the hard sized entry. Real number.
Terminal Unit Reheat Coil Multiplier This field describes the coil sizing multiplier that might have affected the calculated size of a coil used as a reheat coil in a zone air terminal unit. This is a non-dimensional scaling factor. Real number.
DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio This field describes sizing adjustments that can occur for DX coils when the combination of capacity and air flow rate is outside of prescribed limits. If the air flow to capacity ratio was too low this will ratio will show how the capacity was increased to force the result into the prescribed range. Real Number.
DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio This field describes sizing adjustments that can occur for DX coils when the combination of capacity and air flow rate is outside of prescribed limits. If the air flow to capacity ratio was too high this will ratio will show how the capacity was decreased to force the result into the prescribed range. Real Number.
Moist Air Heat Capacity [J/kg-K] This is the moist air heat capacity, cp, that is applicable to coil calculations. Real number.
Dry Air Heat Capacity [J/kg-K] This is the dry air heat capacity, cp, that is applicable to coil calculations. Real number.
Standard Air Density Adjusted for Elevation [kg/m3] This is the dry air density, adjusted for elevation above sea level, that is applicable to coil calculations. Real number.
Supply Fan Name for Coil The program tries to detect the supply fan associated with the coil. This field is the user-defined name for that fan. Text string.
Supply Fan Type for Coil The program tries to detect the supply fan associated with the coil. The values are the input object class name, in IDF syntax, for the fan. Text string.
Supply Fan Maximum Air Volume Flow Rate [m3/s] This field is the design volume flow rate, in units of m3/s, for the fan found to be associated with the coil. Real number
Supply Fan Maximum Air Mass Flow Rate [kg/s] This field is the design mass flow rate, in kg/s, for the fan found to be associated with the coil. Real number
Plant Name for Coil If the coil is a water-to-air or steam coil, then the program tries to detect the central plant system serving the coil. This field is the user-defined name for that plant system. This will be the name in the PlantLoop and Sizing:Plant objects. The next nine fields provides various results for that the central plant loop system. If the coil is not a water or steam coil, then this field will have “unknown” as the value. Text string.
Plant Fluid Specific Heat Capacity [J/kg-K] This is the specific heat of the fluid circulating through the plant and serving the coil, in units of J/kg-K. This is evaulated at the temperature used for sizing calculations. The plant need not always be water, glycol mixtures and steam are supported and this value will be adjusted accordingly. If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Fluid Density [kg/m3] This is the density of the fluid circulating through the plant and serving the coil, in units of kg/m3. This is evaulated at the temperature used for sizing calculations. The plant need not always be water, glycol mixtures are supported and this value will be adjusted accordingly. If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Maximum Fluid Mass Flow Rate [kg/s] This field is the design flow rate for the (entire) central plant system serving the coil, in units of kg/s. This value is the final outcome from plant sizing calculations, or perhaps from the hard-sized value entered in the PlantLoop object for the maximum volume flow rate. If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Design Fluid Return Temperature [C] This is the value, in degrees Celsius, used in sizing calculations for the temperature of the fluid returning to the supply side of the plant system. It is derived from values entered in the Sizing:Plant object (except for steam which depends on subcooling input). If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Design Fluid Supply Temperature [C] This is the value, in degrees Celsius, used in the sizing calculations for the temperature of the fluid leaving the supply side of the plant system and going into the coils. This is the value entered in the Sizing:Plant object in the input field called Design Loop Exit Temperature (except for steam which is 100 C). If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Design Fluid Temperature Difference [Delta C] This is the value, in degrees Celsius (difference), used in the sizing calculations for the temperature difference between the plant supply and return temperatures. This is the value entered in the Sizing:Plant object in the input field called Loop Design Temperature Difference (except for steam it is the amount of subcooling in the coil). If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Plant Design Capacity [W] This is the design capacity of the central plant system, in Watts, that is the result of the sizing calculations. For steam plants it is the capacity of the steam boiler attached to the supply side of the plant. If the coil is not served by a plant, then this field will have -999.0 as the value. Real number.
Coil Capacity Percentage of Plant Design Capacity [%] The coil being reported on here will be one among many others that might be also be attached to the same plant. This field compares this coil’s (design gross) total capacity to the central plant’s design capacity, W/W, and gives a value in percentage from 0.0 to 100.0. If the coil is not served by a plant, then this field will have -999.0 as the value. Real Number.
Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] The coil being reported on here will be one among many others that might be also be attached to the same plant. This field compares this coil’s design flow rate to the central plant’s design flow rate, kg/s/kg/s, and gives a value in percentage from 0.0 to 100.0. If the coil is not served by a plant, then this field will have -999.0 as the value. Real Number.
Design Day Name at Sensible Ideal Loads Peak This field is the name of the design day selected to have the sensible load peak for ideal loads sizing calculations. The text here will be from the user-defined names entered in the name field of the SizingPeriod:DesignDay objects. If this is a cooling coil, the load peak will be for sensible cooling loads and the name here will be from one of the cooling design days. If this is a heating coil, the load peak will be for sensible heating loads and the name from the heating design days. Text String.
Date/Time at Sensible Ideal Loads Peak This field provides the result for the date and time of day when the sensible load peak was found to occur. The format is (M)M/(D)D HH:MM:00, eg. 1/1 06:00:00 or 12/11 06:00:00. There is no specific year associated with design days. Text String.
Design Day Name at Total Ideal Loads Peak The name of the design day selected to have the total load peak for ideal loads sizing calculations. The text here will be from the user-defined names entered in the name field of the SizingPeriod:DesignDay objects. If this is a cooling coil, the load peak will be for total cooling loads and the name here will be from one of the cooling design days. If this is a heating coil, this field usually “unknown” because EnergyPlus does not use a total load for heating sizing. Text String.
Date/Time at Total Ideal Loads Peak This field provides the result for the date and time of day when the total load peak was found to occur during ideal loads sizing. The format is (M)M/(D)D HH:MM:00, eg. 1/1 06:00:00 or 12/11 06:00:00. There is no specific year associated with design days. If the ideal loads sizing calculations never determine a total load the value here will be “unknown.” Text String.
Design Day Name at Air Flow Ideal Loads Peak This field is the name of the design day selected to have the air flow peak for ideal loads sizing calculations. The text here will be from the user-defined names entered in the name field of the SizingPeriod:DesignDay objects. If this is a cooling coil, the air flow peak might be calculated separately and the name here will be from one of the cooling design days. If this is a heating coil, the air flow peak will be the same as the sensible load peak. Text String.
Date/Time at Air Flow Ideal Loads Peak This field provides the result for the date and time of day when the air flow peak was found to occur. The format is (M)M/(D)D HH:MM:00, eg. 1/1 06:00:00 or 12/11 06:00:00. There is no specific year associated with design days. Text String.
Coil Total Capacity at Ideal Loads Peak [W] This field is the coil’s gross total capacity, in Watts, resulting from the ideal loads sizing calculations. This is the total, sensible plus latent, capacity under the conditions used for ideal loads sizing described in other “Ideal Loads Peak” fields. This does not include the supply fan impacts. Real Number.
Coil Sensible Capacity at Ideal Loads Peak [W] This field is the coil’s gross sensible capacity, in Watts, resulting from the ideal loads sizing calculations. This is the sensible capacity under the conditiosn used for ideal loads sizing described in the other “Ideal Loads Peak” fields. This does not include the supply fan impacts. Real number.
Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] This field is the capacity modification factor for the conditions during ideal loads sizing. The coil model may have performance curves that alter the capacity as a function of the conditions experienced by the coil. When the ideal loads sizing conditions are different than the conditions that the performance curves are normalized to, the rating point, the coil is being sized at “Off-rating.” This value can be used to convert the Coil Total Capacity at Ideal Loads Peak to what the capacity should be at the rating point. The ideal loads sizing is often not at the rating point because of a fraction of outdoor air has been mixed into the entering air. Real number.
Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] This field is the coil’s air mass flow rate, in kg/s, resulting from, and/or used during, the ideal loads sizing calculations. Real number.
Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] This field is the coil’s air volume flow rate, in m3/s, resulting from, and/or used during, the ideal loads sizing calculations. Real number.
Coil Entering Air Drybulb at Ideal Loads Peak [C] This field is the drybulb temperature, in degrees Celsius, of the air entering the coil during ideal loads sizing calculations. Real number.
Coil Entering Air Wetbulb at Ideal Loads Peak [C] This field is the wetbulb temperature, in degrees Celsius, of the air entering the coil during ideal loads sizing calculations. Real number.
Coil Entering Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] This field is the humidity ratio, in kg-water/kg-dryAir, of the air entering the coil during ideal loads sizing calculations. Real number.
Coil Entering Air Enthalpy at Ideal Loads Peak [J/(kg-C)] This field is the enthalpy, in J/kg-C (base 0.0 at drybulb = 0.0C), of the air entering the coil during ideal loads sizing calculations. Real number.
Coil Leaving Air Drybulb at Ideal Loads Peak [C] This field is the drybulb temperature, in degrees Celsius, of the air leaving the coil during the ideal loads sizing calculations for the coil. Real number.
Coil Leaving Air Wetbulb at Ideal Loads Peak [C] This field is the wetbulb temperature, in degrees Celsius, of the air leaving the coil during ideal loads sizing calculations. Real number.
Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] This field is the humidity ratio, in kg-water/kg-dryAir, of the air leaving the coil during ideal loads sizing calculations. Real number.
Coil Leaving Air Enthalpy at Ideal Loads Peak [J/(kg-C)] This field is the enthalpy, in J/kg-C (base 0.0 at drybulb = 0.0C), of the air leaving the coil during ideal loads sizing calculations. Real number.
Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] This field is the design or maximum water flow rate, in kg/s, of the plant fluid serving the coil during ideal loads sizing calculations. If the coil is not a water coil then this field will have a value of -999.0. Real number.
Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] This field is the water temperature, in degrees Celsius, of the plant fluid entering the coil during ideal loads sizing calculations. If the coil is not a water coil then this field will have a value of -999.0. Real number.
Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] This field is the water temperature, in degrees Celsius, of the plant fluid leaving the coil during ideal loads sizing calculations. If the coil is not a water coil then this field will have a value of -999.0. Real number.
Coil Plant Fluid Temperature Difference at Ideal Loads Peak [Delta C] This field is the water temperature difference across the coil, in degrees Celsius (difference), of the plant fluid passing through the coil during ideal loads sizing calculations. If the coil is not a water coil then this field will have a value of -999.0. Real number.
Supply Fan Air Heat Gain at Ideal Loads Peak [W] This field is the fan load that was included in the ideal loads sizing calculations. This may only be included in calculations for central air system cooling coils. If the coil was not sized with fan heat gain taken into account, then this value will be 0.0 (even though there still is a fan with heat during normal operation). Real number.
Coil and Fan Net Total Capacity at Ideal Loads Peak [W] This field shows the net coil total capacity which is the gross total capacity with the fan heat gain, if any was calculated. Real number.
Outdoor Air Drybulb at Ideal Loads Peak [C] This field is the outdoor air drybulb temperature, in degrees Celsius, used during the ideal loads sizing calculations. Real number.
Outdoor Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] This field is the outdoor air humidity ratio, in kg of water per kg of dry air, used during the ideal loads sizing calculations. Real number.
Outdoor Air Wetbulb at Ideal Loads Peak [C] This field is the outdoor air wetbulb temperature, in degrees Celsius, used during the ideal loads sizing calculations. Real number.
Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] This field is the outdoor air volume flow rate, in m3/s, that occurred during the ideal loads sizing calculations. Real number.
Outdoor Air Flow Percentage at Ideal Loads Peak [%] This field is the percentage of outdoor air in the air entering the coil that occurred during the ideal loads sizing calculations. Real number.
System Return Air Drybulb at Ideal Loads Peak [C] This field is the drybulb temperature, in degrees C, of air returning into the HVAC system that occurred during the ideal loads sizing calculations. Real number.
System Return Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] This field is the humidity ratio, in kg of water per kg of dry air, of air returning into the HVAC system that occurred during the ideal loads sizing calculations. Real number.
Zone Air Drybulb at Ideal Loads Peak [C] This field is the drybulb temperature, in degrees C, of the zone air that occurred during the ideal loads sizing calculations. For multizone system this is the supply-air-volume-flow-weighted average. Real number.
Zone Air Humidity Ratio at Ideal Loads Peak [kg-H2O/kg-DryAir] This field is the humidity ratio, in kg of water per kg of dry air, of the zone air that occurred during the ideal loads sizing calculations. For multizone system this is the supply-air-volume-flow-weighted-weighted average. Real number.
Zone Air Relative Humidity at Ideal Loads Peak [%] This field is the percent relative humidity of the zone air that occurred during the ideal loads sizing calculations. For multizone system this is the supply-air-volume-flow-weighted-weighted average. Real number.
Zone Sensible Heat Gain at Ideal Loads Peak [W] This field is the zone sensible load, in Watts, found during ideal loads sizing. For multizone system it is the sum of all the zones on the air system. Real number.
Zone Latent Heat Gain at Ideal Loads Peak [W] This field is the zone latent load, in Watts, found during ideal loads sizing. For multizone system it is the sum of all the zones on the air system. Real number.
Coil Total Capacity at Rating Conditions [W] This field is the gross total capacity of the coil when operated at the rating point conditions, in units of Watts. This is the result from calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Sensible Capacity at Rating Conditions [W] This field is the gross sensible capacity of the coil when operated at the rating point conditions, in units of Watts. This is the result from calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Air Mass Flow Rate at Rating Conditions [kg/s] This field is the air mass flow rate, in units of kg/s, used when calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Entering Air Drybulb at Rating Conditions [C] This field is the coil air inlet drybulb temperature, in degrees Celsius, used when calculating the full coil model under the operating conditions specified for the rating point. The value should match the definition of the rating point as described in the coil model input documentation. For DX cooling coils, this will be 26.6667C or 80F. Real number.
Coil Entering Air Wetbulb at Rating Conditions [C] This field is the coil air inlet wetbulb temperature, in degrees Celsius, used when calculating the full coil model under the operating conditions specified for the rating point. The value should match the definition of the rating point as described in the coil model input documentation. For DX cooling coils, this will be 19.444C or 67F. Real number
Coil Entering Air Humidity Ratio at Rating Conditions [kg-H20/kg-DryAir] This field is the coil air inlet humidity ratio, in kg-water/kg-dryAir, used when calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Entering Air Enthalpy at Rating Conditions [J/(kg-C)] This field is the coil air inlet enthalpy, in J/kg-C with zero base at 0.0C, used when calculating the full coil model under the operating conditins specified for the rating point. Real number.
Coil Leaving Air Drybulb at Rating Conditions [C] This field is the coil air outlet drybulb, in degrees Celsius, from calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Leaving Air Wetbulb at Rating Conditions [C] This field is the coil air outlet wetbulb, in degrees Celsius, from calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Leaving Air Humidity Ratio at Rating Conditions [kg-H20/kg-DryAir] This field is the coil air outlet humidity ratio, in kg-water/kg-dryair, from calculating the full coil model under the operating conditions specified for the rating point. Real number.
Coil Leaving Air Enthalpy at Rating Conditions [J/(kg-C)] This field is the coil air outlet enthalpy, in J/kg-C with zero base at 0.0C, from calculating the full coil model under the operating conditions specified for the rating point. Real number. Directly following is an example of the report.
The key used to obtain this report is HVACSizingSummary.
Report: HVAC Sizing Summary
For: Entire Facility
** Timestamp: **2011-09-23 15:09:34
Zone Sensible Cooling
Zone Sensible Heating
System Design Air Flow Rates
Plant Loop Coincident Design Fluid Flow Rate Adjustments
System Summary[LINK]
The System Summary report provides information about some of the primary components in the system including the economizer and demand controlled ventilation. In addition, this report describes when the zone conditions are not comfortable or when set points are not met.
In the Time Not Comfortable Based on Simple ASHRAE 55-2004 and Time Setpoint Not Met sub-tables, The reported time represents the total number of hours that a given zone did not meet the comfort or setpoint criteria. For the Facility row, this is the total numbers of hours that one or more zones were out of range. The values are not weighted by number of zones or number of occupants.
Directly following is an example of the report. The key used to obtain this report is SystemSummary.
Report: System Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Economizer
Demand Controlled Ventilation using VENTILATION:MECHANICAL
Time Not Comfortable Based on Simple ASHRAE 55-2004
Time Setpoint Not Met
Component Sizing Summary[LINK]
The Component Sizing Summary report includes details on many of the HVAC components in the simulation. For each of the components, one or more parameters are shown. Directly following is an example of the report. The key used to obtain this report is ComponentSizingSummary.
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
SINGLE DUCT:VAV:REHEAT
COIL:Water:SimpleHeating
BRANCH
AIR PRIMARY LOOP
CONTROLLER:OUTSIDE AIR
COIL:Water:Cooling
FAN:SIMPLE:VARIABLEVOLUME
CONTROLLER:SIMPLE
PLANT LOOP
BOILER:SIMPLE
CHILLER:ELECTRIC
PUMP:VARIABLE SPEED
Outdoor Air Summary[LINK]
The Outdoor Air Summary provides information for each zone on the average and minimum ventilation provided.
The reports described so far in this section are displayed when specified in the Output:Table:SummaryReports object. They are either on or off and are not customizable. The next few types of tabular reports are customizable. You can specify the report variables being used in each one.
Directly following is an example of the report. The key used to obtain this report is OutdoorAirSummary.
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2007-10-17 08:54:27
Average Outside Air During Occupied Hours
Minimum Outside Air During Occupied Hours
Outdoor Air Details[LINK]
The Outdoor Air Details report provides detailed information on outdoor air flow for each zone and air loop. This report may be specified in the Output:Table:SummaryReports object with the key OutdoorAirDetails. It is also produced for any AllSummary* key. Each subtable and column are described below.
Mechanical Ventilation Parameters by Zone[LINK]
The name(s) of air loop(s) serving this zone,if any.
Average number of occupants during occupied times (occupants > 0) for the simulation period.
Total number of people for all People objects in this zone (ignoring schedules).
The zone volume in .
The zone floor area in .
The design outdoor air flow rate specified in the DesignSpecification:OutdoorAir object for this zone in . This is the outdoor air flow rate used for sizing without any schedule modifier.
The minimum outdoor air flow rate specified in the DesignSpecification:OutdoorAir object for this zone in . This is the outdoor air flow rate for the minimum number of occupants without any schedule modifier.
Total Outdoor Air by Zone[LINK]
The total outdoor air delivered to this zone by mechanical ventilation (HVAC systems) in (Output:Variable Zone Mechanical Ventilation Standard Density Volume Flow Rate).
The total outdoor air delivered to this zone by natural ventilation (ZoneVentilation:* or AirflowNetwork) in .
The sum of Mechanical and Natural Ventilation in .
The total outdoor air delivered to this zone by infiltration (ZoneInfiltration:* or AirflowNetwork) in (Output:Variable Zone Infiltration Standard Density Volume Flow Rate).
The sum of Mechanical and Natural Ventilation and Infiltration in .
The total dynamic outdoor air flow rate specified in the DesignSpecification:OutdoorAir object for this zone in . This is the zone target ventilation flow rate \(V_{oz-dyn}\) at standard density at the current timestep including any schedule modifier (Output:Variable Zone Target Voz Ventilation Flow Rate).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is more than 1% below the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Zone Ventilation Below Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is within 1% of the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Zone Ventilation At Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is more than 1% above the Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Zone Ventilation Above Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is greater than zero when the zone is unoccupied (Output:Variable Zone Ventilation When Unoccupied Time).
Average Outdoor Air During Occupancy by Zone - Flow Rates[LINK]
This subtable is the same as Total Outdoor Air by Zone except that it reports average flow rates in and status times in hours for occupied periods only.
Total Outdoor Air by AirLoop[LINK]
The total outdoor air delivered to the zones on this air loop by only this air loop in (Output:Variable Air System Mechanical Ventilation Flow Rate).
The total outdoor air delivered to the zones on this air loop by natural ventilation (ZoneVentilation:* or AirflowNetwork) in (Output:Variable Air System Natural Ventilation Flow Rate). If any zone terminal unit has a DesignSpecification:AirTerminal:Sizing object then the natural ventilation rate for that zone is scaled by the Fraction of Minimum Outdoor Air Flow value.
The sum of Mechanical and Natural Ventilation in .
The total dynamic outdoor air flow rate specified in the DesignSpecification:OutdoorAir object for the zones on this air loop in . This is the sum of the zone target ventilation flow rates \(V_{oz-dyn}\) at standard density at the current timestep including any schedule modifier (Output:Variable Air System Target Voz Ventilation Flow Rate). If any zone terminal unit has a DesignSpecification:AirTerminal:Sizing object then the target ventilation rate for that zone is scaled by the Fraction of Minimum Outdoor Air Flow value.
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is more than 1% below the Sum Zone Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Air System Ventilation Below Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is within 1% of the Sum Zone Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Air System Ventilation At Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is more than 1% above the Sum Zone Dynamic Target Ventilation - \(V_{oz-dyn}\) flow rate (Output:Variable Air System Ventilation Above Target Voz Time).
The time in hours that the Total Ventilation rate (mechanical ventilation plus natural ventilation) is greater than zero when the all zones on this air loop are unoccupied (Output:Variable Air System Ventilation When Unoccupied Time).
Average Outdoor Air During Occupancy by AirLoop[LINK]
This subtable is the same as Total Outdoor Air by AirLoop except that it reports average flow rates in and status times in hours when any zone on this air loop is occupied.
Outdoor Air Controller Limiting Factors by AirLoop[LINK]
Times in hours that the outdoor air flow rate for this airloop is set by one of the following limiting factors (Output:Variable Air System Outdoor Air Limiting Factor).
None of the other limiting factors is active.
Fixed limits such as Controller:OutdoorAir Minimum Outdoor Air Flow Rate, Maximum Outdoor Air Flow Rate, Minimum Fraction of Outdoor Air Schedule Name, Maximum Fraction of Outdoor Air Schedule Name.
Economizer is active and sets the flow greater than the minimum outdoor air fraction.
Outdoor air flow rate equals the total zone exhaust flow rate.
Outdoor air flow rate is limited by the current mixed air flow rate.
Controller:OutdoorAir High Humidity Control.
Controller:MechanicalVentilation requested more than the minimum outdoor air fraction.
AvailabilityManager:NightVentilation is active.
DemandManager:Ventilation has reduced the outdoor air flow rate.
An EnergyManagementSystem:Actuator has overridden the outdoor air flow rate.
Average Outdoor Air for Limiting Factors During Occupancy[LINK]
This subtable is the same as Outdoor Air Controller Limiting Factors by AirLoop except that it reports average flow rates in at each limiting factor for occupied periods only.
Climatic Data Summary[LINK]
The Climatic Data Summary provides some statistics from the .STAT file concerning the selected weather. The Stat file must be available (it is included with all the weather files on the EnergyPlus website) for the report to be fully produced. Directly following is an example of the report. The key used to obtain this report is ClimaticDataSummary.
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2009-02-10 13:27:45
SizingPeriod:DesignDay
Weather Statistics File
Object Count Summary[LINK]
The object count summary report provides the count on the number of specific objects in the file. Directly following is an example of the report. The key used to obtain this report is ObjectCountSummary.
Report: Object Count Summary
For: Entire Facility
Timestamp: 2009-02-10 12:39:35
Surfaces by Class
HVAC
Component Cost Economics Summary[LINK]
The Component Cost Economics Summary provides the construction cost estimate summary for the project. The costs are broken into eight catagories and the reference building costs are provided as a comparison. A second table is also produced that provides line item details with one line for every line item object. Directly following is an example of this report.
Report: Component Cost Economics Summary
For: Entire Facility
Timestamp: 2016-01-12 15:47:39
Construction Cost Estimate Summary
Cost Line Item Details
LEED Summary[LINK]
The LEED Summary report provides many of the simulation results required for certification of Energy and Atmosphere Credit 1 Optimized Energy Performance according to the LEED Green Building Rating SystemTM. The report can be produced by specifying LEEDSummary in Output:Table:SummaryReports which is also part of the AllSummary option. Directly following is an example of this report.
Report: LEED Summary
For: Entire Facility
Timestamp: 2013-03-01 15:24:37
Sec1.1A-General Information
EAp2-1. Space Usage Type
EAp2-2. Advisory Messages
EAp2-3. Energy Type Summary
EAp2-4/5. Performance Rating Method Compliance
EAp2-6. Energy Use Summary
EAp2-7. Energy Cost Summary
Process energy cost based on ratio of process to total energy.
L-1. Renewable Energy Source Summary
EAp2-17a. Energy Use Intensity - Electricity
EAp2-17b. Energy Use Intensity - Natural Gas
EAp2-17c. Energy Use Intensity - Other
EAp2-18. End Use Percentage
Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)
Schedules-SetPoints (Schedule Type=Temperature)
Initialization Summary[LINK]
This report is not reproduced here since it is well documented in the section in this document for the eplusout.eio file.
Energy Meters[LINK]
This report provides the details on all the energy meters generated by the simulation. Directly following is an example of the report. The key used to obtain this report is EnergyMeters.
Report: Energy Meters
For: Entire Facility
Timestamp: 2012-05-01 17:07:24
Annual and Peak Values - Electricity
Annual and Peak Values - Gas
Annual and Peak Values - Cooling
Annual and Peak Values - Water
Annual and Peak Values - Other by Weight/Mass
Annual and Peak Values - Other Volumetric
Annual and Peak Values - Other Liquid/Gas
Annual and Peak Values - Other
Sensible Heat Gain Summary[LINK]
This report is more fully described in the Input Output Reference but represents the major heat gain components for each zone as well as the HVAC loads satisfied. Directly following is an example of the report. The key used to obtain this report is SensibleHeatGainSummary.
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2011-09-09 08:02:03
Annual Building Sensible Heat Gain Components
Peak Cooling Sensible Heat Gain Components
Peak Heating Sensible Heat Gain Components
Standard 62.1 Summary[LINK]
This report is more fully described in the Input Output Reference. The Standard 62.1 Summary produces a report that is consistent with many of the outputs needed when doing calculations consistent with ASHRAE Standard 62.1-2010.
The abbreviations used in the report are consistent with the abbreviations used in Appendix A4 of the Standard. Directly following is an example of the report. The key used to obtain this report is Standard62.1Summary.
Note: The report is only generated when sizing calculations are specified.: in SimulationControl, “Do Zone Sizing” or “Do System Sizing” must be set to “Yes”.
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2012-04-20 12:00:57
System Ventilation Requirements for Cooling
System Ventilation Requirements for Heating
Zone Ventilation Parameters
System Ventilation Parameters
Zone Ventilation Calculations for Cooling Design
System Ventilation Calculations for Cooling Design
Zone Ventilation Calculations for Heating Design
System Ventilation Calculations for Heating Design
Component Loads Summary[LINK]
Three different Component Loads Summary reports can be generated. The Zone Component Loads Summary, the AirLoop Component Loads Summary and the Facility Component Loads Summary. Each provides an estimate of the heating and cooling peak loads for each zone broken down into various components. This report may help determine which components of the load have the largest impact for the heating and cooling peak design conditions. When specified, the Zone Component Loads Summary report is created for each zone that is conditioned. The Sensible-Delayed column of the summary is only an estimate based on a procedure described in the Engineering Reference documentation. An intermediate calculation in this procedure is the decay curves that are shown in the the EIO file when Output:Surfaces:List is set to show DecayCurvesFromComponentLoadsSummary. The difference between the peak design sensible load and the estimated instant + delayed sensible load (as shown in the Peak Conditions subtable) is an indication of how consistent the overall total estimate may be to the computed total peak loads for the zone. Engineering checks have been added showing some ratios that may be useful in checking the results. When the report is called the zone sizing calculations are repeated twice so this may result in longer simulation times. The key used to obtain these reports are ZoneComponentLoadSummary, AirLoopComponentLoadSummary, FacilityComponentLoadSummary.
Report: ZoneComponentLoadSummary
For: SPACE1-1
Timestamp: 2012-09-21 15:48:46
Estimated Cooling Peak Load Components
Cooling Peak Conditions
Engineering Checks for Cooling
Estimated Heating Peak Load Components
Heating Peak Conditions
Engineering Checks for Heating
Output:Table:TimeBins[LINK]
A TimeBins report shows a grid of the number of hours that specific report variable spend in a range of values. The first table is broken into two parts. The first part is monthly and the second part is for each hour of the day. The columns show the range of values. A second table is provided to show some statistics on the report variable for the entire year including the maximum and minimum. These statistics are helpful in setting the field values for the interval in the Output Table:TimeBins object. Due to this, it is often necessary to run two simulations to fully utilize the TimeBins report with the first run used to find the minimum and maximum of the variable, these values are then used in the TimeBins object and the second run a better table of binned results are displayed.
Report: PURCHASEDCOOLING:FACILITY J per second
For: Meter
Timestamp: 2006-08-30 07:48:55
Values in table are in hours.
Statistics
Output:Table:Monthly[LINK]
Monthly reports are not predefined. Instead each column is defined when using the Output:Table:Monthly object. In that object each column is defined by a variable and how it should be aggregated. The StandardReports.idf file is located in DataSets directory where EnergyPlus is installed and contains a large number of examples of how to use Output:Table:Monthly to get summaries of the performance of different components in the building model. These examples include:
Zone Cooling Summary
Zone Heating Summary
Zone Electric Summary
Space Gains
Peak Space Gains
Space Gain Components at Cooling Peak
Energy Consumption - Electricity & Natural Gas
Energy Consumption - Electricity Generated & Propane
Energy Consumption - Diesel & Fuel Oil
Energy Consumption - Purchased Heating & Cooling
Energy Consumption - Coal & Gasoline
End-Use Energy Consumption - Electricity
End-Use Energy Consumption - Natural Gas
End-Use Energy Consumption - Diesel
End-Use Energy Consumption - Fuel Oil
End-Use Energy Consumption - Coal
End-Use Energy Consumption - Propane
End-Use Energy Consumption - Gasoline
Peak Energy End-Use - Electricity Part 1
Peak Energy End-Use - Electricity Part 2
Electric Components of Peak Demand
Peak Energy End-Use - Natural Gas
Peak Energy End-Use - Diesel
Peak Energy End-Use - Fuel Oil
Peak Energy End-Use - Coal
Peak Energy End-Use - Propane
Peak Energy End-Use - Gasoline
Setpoints Not Met With Temperatures
Comfort Report - Simple 55
Unglazed Transpired Solar Collector Summary
Occupant Comfort Data Summary
Chiller Report
Tower Report
Boiler Report
DX Report
Window Report
Window Energy Report
Window Zone Summary
Average Outdoor Conditions
Outdoor Conditions Maximum Drybulb
Outdoor Conditions Minimum Drybulb
Outdoor Conditions Maximum Wetbulb
Outdoor Conditions Maximum Dewpoint
Outdoor Ground Conditions
Window AC Report
Water Heater Report
Generator Report
Daylighting Report
Coil Report
Plant Loop Demand Report
Fan Report
Pump Report
Cond Loop Demand Report
Zone Temperature Oscillation Report
Air Loop System Energy and Water Use
Air Loop System Component Loads
Air Loop System Component Energy Use
Mechanical Ventilation Loads
An example of the Zone Cooling Summary monthly report is shown below.
Report: ZONE COOLING SUMMARY
For: SPACE2-1
Timestamp: 2006-08-29 07:21:57
UtilityCost:Tariff[LINK]
Two output reports – EconomicResultSummary and TariffReport – are related to the use of UtilityCost:Tariff for the calculation of annual utility costs. Since EnergyPlus 8.6, these reports are no longer generated and need to be specifically requested. To get the reports individually use EconomicResultSummary and TariffReport in the Output:Table:SummaryReports object. These are also available when using any of the AllSummary options.
The first report is a summary across multiple tariffs and is called the Economics Results Summary report and is shown directly below. After that example is an example of the Tariff report which is created for each of the UtilityCost:Tariff Objects defined in the IDF file (some columns may be truncated due to page size).
Report: Economics Results Summary Report
For: Entire Facility
Timestamp: 2006-08-29 07:21:57
Annual Cost
Tariff Summary
The following is an example of the Tariff report which is created for each of the UtilityCost:Tariff objects defined in the file.
Report: Tariff Report
For: EXAMPLEA
Timestamp: 2006-08-29 07:21:57
Categories
Charges
Ratchets
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max — —– —– —– —– —– —– —– —– —– —– —– —– —– —–
Qualifies
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max — —– —– —– —– —– —– —– —– —– —– —– —– —– —–
Native Variables
Other Variables
Computation - Automatic FLATENERGYCHARGE FROM TotalEnergy EnergyCharges SUM FLATENERGYCHARGE Basis SUM EnergyCharges DemandCharges ServiceCharges Subtotal SUM Basis Adjustment Surcharge Total SUM Subtotal Taxes
Construction Cost Estimate Summary[LINK]
The Construction Cost Estimate Summary report shows the details of a simplified cost estimate of the building along with a comparison with reference building costs entered by the user. An example of the Construction Cost Estimate Summary report is shown below.
Construction Cost Estimate Summary
Cost Line Item Details
XML Tabular Output[LINK]
The tables discussed in this section can also be output in an XML format that may be easier for some other programs to extract specific results. An excerpt of the XML file format is shown below. This report presents the same output results as the other tabular report formats but using XML tags.
<?xml version = “1.0”?>
<EnergyPlusTabularReports>
<BuildingName>NONE</BuildingName>
<EnvironmentName>Chicago Ohare Intl Ap IL USA TMY3 WMO# = 725300</EnvironmentName>
<WeatherFileLocationTitle>Chicago Ohare Intl Ap IL USA TMY3 WMO# = 725300</WeatherFileLocationTitle>
<ProgramVersion>EnergyPlus, Version 8.0, YMD = 2013.02.18 15:50</ProgramVersion>
<SimulationTimestamp>
<Date>
2013-02-18
</Date>
<Time>
15:50:33
</Time>
</SimulationTimestamp>
<AnnualBuildingUtilityPerformanceSummary>
<for>Entire Facility</for>
<SiteAndSourceEnergy>
<name>TotalSiteEnergy</name>
<TotalEnergy units = “kBtu”>200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units = “kBtu/ft2”>143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units = “kBtu/ft2”>143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSiteEnergy</name>
<TotalEnergy units = “kBtu”>200671.97</TotalEnergy>
<EnergyPerTotalBuildingArea units = “kBtu/ft2”>143.32</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units = “kBtu/ft2”>143.32</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>TotalSourceEnergy</name>
<TotalEnergy units = “kBtu”>442504.19</TotalEnergy>
<EnergyPerTotalBuildingArea units = “kBtu/ft2”>316.04</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units = “kBtu/ft2”>316.04</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
<SiteAndSourceEnergy>
<name>NetSourceEnergy</name>
<TotalEnergy units = “kBtu”>397810.98</TotalEnergy>
<EnergyPerTotalBuildingArea units = “kBtu/ft2”>284.12</EnergyPerTotalBuildingArea>
<EnergyPerConditionedBuildingArea units = “kBtu/ft2”>284.12</EnergyPerConditionedBuildingArea>
</SiteAndSourceEnergy>
An actual file will be much longer than this example but follows this format.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.