Tabular Summary Reports[LINK]
Several predefined reports are available from the Output Table:Predefined object including the following.
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outside Air Summary
Object Count Summary
In addition, specifying “All Summary” will enable all the reports in this category (more than are shown here).
First and foremost, the Annual Building Utility Performance Summary gives a good overview of the energy use by category:
Report: AnnualBuildingUtilityPerformanceSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Values gathered over 8760.00 hours
Site and Source Energy
p1.5inp1.5inp1.5inp1.5in & Total Energy [GJ] & Energy Per Total Building Area [MJ/m2] & Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy & 180.73 & 194.92 & 194.92
Net Site Energy & 180.73 & 194.92 & 194.92
Total Source Energy & 1141.64 & 1231.28 & 1231.28
Net Source Energy & 1141.64 & 1231.28 & 1231.28
Source to Site Energy Conversion Factors
Electricity |
0.293 |
Natural Gas |
0.010 |
District Cooling |
0.098 |
District Heating |
0.033 |
Steam |
0.250 |
Gasoline |
1.050 |
Diesel |
1.050 |
Coal |
1.050 |
Fuel Oil #1 |
1.050 |
Fuel Oil #2 |
1.050 |
Propane |
1.050 |
Building Area
End Uses
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & & &
Total End Uses & 152.57 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Note: Natural gas appears to be the principal heating source based on energy usage.
End Uses By Subcategory
p0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75in & Subcategory & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & Boiler & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
& Boiler Parasitic & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & General & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & GeneralLights & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & General & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & General & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & General & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Normalized Metrics
Utility Use Per Conditioned Floor Area
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Utility Use Per Total Floor Area
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Electric Loads Satisfied
p2.9inp1.5inp1.59in & Electricity [GJ] & Percent Electricity [%]
Fuel-Fired Power Generation & 0.00 & 0.00
High Temperature Geothermal* & 0.00 & 0.00
Photovoltaic Power & 0.00 & 0.00
Wind Power* & 0.00 & 0.00
Net Decrease in On-Site Storage & 0.00 & 0.00
Total On-Site Electric Sources & 0.00 & 0.00
& &
Electricity Coming From Utility & 152.57 & 100.00
Surplus Electricity Going To Utility & 0.00 & 0.00
Net Electricity From Utility & 152.57 & 100.00
& &
Total On-Site and Utility Electric Sources & 152.57 & 100.00
Total Electricity End Uses & 152.57 & 100.00
On-Site Thermal Sources
Water-Side Heat Recovery |
0.00 |
|
Air to Air Heat Recovery for Cooling |
0.00 |
|
Air to Air Heat Recovery for Heating |
0.00 |
|
High-Temperature Geothermal* |
0.00 |
|
Solar Water Thermal |
0.00 |
|
Solar Air Thermal |
0.00 |
|
Total On-Site Thermal Sources |
0.00 |
|
Water Source Summary
p3.0inp1.5inp1.5in & Water [m3] & Percent Water [%]
Rainwater Collection & 0.00 & -
Condensate Collection & 0.00 & -
Groundwater Well & 0.00 & -
Total On Site Water Sources & 0.00 & -
- & - & -
Initial Storage & 0.00 & -
Final Storage & 0.00 & -
Change in Storage & 0.00 & -
- & - & -
Water Supplied by Utility & 0.00 & -
- & - & -
Total On Site, Change in Storage, and Utility Water Sources & 0.00 & -
Total Water End Uses & 0.00 & -
Comfort and Setpoint Not Met Summary
p4.5inp1.5in & Facility [Hours]
Time Set Point Not Met During Occupied Heating & 0.00
Time Set Point Not Met During Occupied Cooling & 213.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 & 72.50
Note 1: An asterisk (*) indicates that the feature is not yet implemented.
The input verification summary gives a good overview of the facility being simulated:
Report: InputVerificationandResultsSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
General
p2.25inp3.74in & Value
Program Version and Build & EnergyPlus 4.0.0.017, 9/17/2009 5:30 PM
Weather & Climate Zone 6 CA USA WYEC2-C-00006 WMO#=722970
Latitude [deg] & 33.90
Longitude [deg] & -118.5
Elevation [m] & 30.00
Time Zone & -8.0
North Axis Angle [deg] & 30.00
Rotation for Appendix G [deg] & 0.00
Hours Simulated [hrs] & 8760.00
ENVELOPE
Window-Wall Ratio
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Total & North (315 to 45 deg) & East (45 to 135 deg) & South (135 to 225 deg) & West (225 to 315 deg)
Gross Wall Area [m2] & 274.20 & 91.50 & 45.60 & 91.50 & 45.60
Window Opening Area [m2] & 60.90 & 20.85 & 9.12 & 21.81 & 9.12
Window-Wall Ratio [%] & 22.21 & 22.79 & 20.00 & 23.84 & 20.00
Skylight-Roof Ratio
Gross Roof Area [m2] |
463.60 |
Skylight Area [m2] |
0.00 |
Skylight-Roof Ratio [%] |
0.00 |
PERFORMANCE
Zone Summary
p0.7inp0.4inp0.5inp0.5inp0.4inp0.5inp0.5inp0.5inp0.5inp0.5in & Area [m2] & Conditioned (Y/N) & Volume [m3] & Multipliers & Gross Wall Area [m2] & Window Glass Area [m2] & Lighting [W/m2] & People [m2] per person & Plug and Process [W/m2]
PLENUM-1 & 463.60 & Yes & 283.20 & 1.00 & 54.84 & 0.00 & 0.0000 & & 0.0000
SPACE1-1 & 99.16 & Yes & 239.25 & 1.00 & 73.20 & 21.81 & 15.9742 & 9.01 & 10.6495
SPACE2-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE3-1 & 96.48 & Yes & 239.25 & 1.00 & 73.20 & 20.85 & 16.4179 & 8.77 & 10.9453
SPACE4-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE5-1 & 182.49 & Yes & 447.68 & 1.00 & 0.00 & 0.00 & 16.2420 & 9.12 & 10.8280
Total & 927.20 & & 1416.00 & & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Conditioned Total & 927.20 & & 1416.00 & & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Unconditioned Total & 0.00 & & 0.00 & & 0.00 & 0.00 & & &
Source Energy End Use Components Summary[LINK]
The source energy end use components summary gives a good overview of the source energy consumption broken down by end uses for the facility being simulated:
Report: SourceEnergyEndUseComponentsSummary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components Summary
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [GJ] & Source Natural Gas [GJ] & Source Other Fuel [GJ] & Source District Cooling [GJ] & Source District Heating [GJ]
Heating & 0.00 & 140.03 & 0.00 & 0.00 & 0.00
Cooling & 167.65 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 569.39 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 325.49 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 55.72 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 7.57 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1125.82 & 140.03 & 0.00 & 0.00 & 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned Floor Area
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00
Source Energy End Use Components Per Total Floor Area
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00
Other Summary Reports[LINK]
The Climatic Data Summary, Envelope Summary and Equipment Summary reports might be quite important to some reporting or presentation.
Report: ClimaticDataSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
SizingPeriod:DesignDay
p1.2inp0.7inp0.7inp0.7inp0.7inp0.7inp0.7in & Maximum Dry Bulb [C] & Daily Temperature Range [C] & Humidity Value & Humidity Type & Wind Speed [m/s] & Wind Direction
LOS_ANGELES_CA_USA HEATING 99% CONDITIONS & 7.40 & 0.00 & 7.40 & 0 & 2.80 & 70.00
LOS_ANGELES_CA_USA COOLING 1% CONDITIONS DB= > MWB & 27.00 & 6.10 & 17.60 & 0 & 4.40 & 250.00
Weather Statistics File
p2.15inp3.84in & Value
Reference & CZ06RV2
Site:Location & Climate Zone 6 CA USA
Latitude & N 33° 54’
Longitude & W 118° 30’
Time Zone & GMT -8.0 Hours
Elevation & 30m above sea level
Standard Pressure at Elevation & 100965Pa
Data Source & WYEC2-C-00006
WMO Station & 722970
Design Conditions & Climate Design Data 2005 ASHRAE Handbook
Heating Design Temperature 99.6% (C) & 4.9
Heating Design Temperature 99% (C) & 6.2
Cooling Design Temperature 0.4% (C) & 33.1
Cooling Design Temperature 1% (C) & 30.9
Cooling Design Temperature 2% (C) & 29.2
Maximum Dry Bulb Temperature (C) & 31.7°
Maximum Dry Bulb Occurs on & Sep 24
Minimum Dry Bulb Temperature (C) & 3.5°
Minimum Dry Bulb Occurs on & Jan 8
Maximum Dew Point Temperature (C) & 20.9
Maximum Dew Point Occurs on & Jun 20
Minimum Dew Point Temperature (C) & -21.7
Minimum Dew Point Occurs on & Dec 27
Heating Degree-Days (base 10°C) & 2
Cooling Degree-Days (base 18°C) & 216
Köppen Classification & Csb
Köppen Description & Mediterranean climate (dry warm summer, mild winter, lat. 30-45°N)
Köppen Recommendation &
ASHRAE Climate Zone & 3C
ASHRAE Description & Warm-Marine
Report: EnvelopeSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Opaque Exterior
p0.66inp0.66inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6in & Construction & Reflectance & U-Factor with Film [W/m2-K] & U-Factor no Film [W/m2-K] & Gross Area [m2] & Azimuth [deg] & Tilt [deg] & Cardinal Direction
WALL-1PF & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 210.00 & 90.00 & S
WALL-1PR & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 120.00 & 90.00 & E
WALL-1PB & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 30.00 & 90.00 & N
WALL-1PL & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 300.00 & 90.00 & W
TOP-1 & ROOF-1 & 0.35 & 0.268 & 0.282 & 463.60 & 210.00 & 0.00 &
FRONT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 210.00 & 90.00 & S
F1-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 99.16 & 30.00 & 180.00 &
RIGHT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 120.00 & 90.00 & E
F2-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 300.00 & 180.00 &
BACK-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 30.00 & 90.00 & N
F3-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 96.48 & 74.22 & 180.00 &
LEFT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 300.00 & 90.00 & W
F4-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 120.00 & 180.00 &
F5-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 182.49 & 30.00 & 180.00 &
Fenestration
p0.6inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5in & Construction & Area of One Opening [m2] & Area of Openings [m2] & U-Factor [W/m2-K] & SHGC & Visible Transmittance & Shade Control & Parent Surface & Azimuth [deg] & Cardinal Direction
WF-1 & DBL CLR 3MM/13MM AIR & 16.56 & 16.56 & 2.720 & 0.764 & 0.812 & No & FRONT-1 & 210.00 & S
DF-1 & SGL GREY 3MM & 5.25 & 5.25 & 5.894 & 0.716 & 0.611 & No & FRONT-1 & 210.00 & S
WR-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & RIGHT-1 & 120.00 & E
WB-1 & DBL CLR 3MM/13MM AIR & 16.44 & 16.44 & 2.720 & 0.764 & 0.812 & No & BACK-1 & 30.00 & N
DB-1 & SGL GREY 3MM & 4.41 & 4.41 & 5.894 & 0.716 & 0.611 & No & BACK-1 & 30.00 & N
WL-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & LEFT-1 & 300.00 & W
Total or Average & & & 60.90 & 3.22 & 0.756 & 0.780 & & & &
North Total or Average & & & 20.85 & 3.39 & 0.754 & 0.769 & & & &
Non-North Total or Average & & & 40.05 & 3.14 & 0.757 & 0.785 & & & &
Report: ShadingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Sunlit Fraction
WF-1 |
0.00 |
0.00 |
0.26 |
0.00 |
0.00 |
0.00 |
0.00 |
0.30 |
0.74 |
DF-1 |
0.75 |
0.13 |
0.59 |
0.00 |
0.00 |
0.35 |
0.92 |
0.62 |
0.94 |
WR-1 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
1.00 |
1.00 |
0.00 |
WB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
DB-1 |
0.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
0.00 |
0.00 |
0.00 |
WL-1 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
0.00 |
0.00 |
1.00 |
Window Control
Report: LightingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Interior Lighting
Daylighting
Exterior Lighting
Exterior Lighting Total |
0.00 |
|
|
|
Report: EquipmentSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Central Plant
Cooling Coils
Heating Coils
Fans
Pumps
Service Water Heating
Tabular Summary Reports[LINK]
Several predefined reports are available from the Output Table:Predefined object including the following.
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Climatic Data Summary
Equipment Summary
Envelope Summary
Surface Shadowing Summary
Shading Summary
Lighting Summary
HVAC Sizing Summary
System Summary
Component Sizing Summary
Outside Air Summary
Object Count Summary
In addition, specifying “All Summary” will enable all the reports in this category (more than are shown here).
Annual Building Utility Performance Summary[LINK]
First and foremost, the Annual Building Utility Performance Summary gives a good overview of the energy use by category:
Report: AnnualBuildingUtilityPerformanceSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Values gathered over 8760.00 hours
Site and Source Energy
p1.5inp1.5inp1.5inp1.5in & Total Energy [GJ] & Energy Per Total Building Area [MJ/m2] & Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy & 180.73 & 194.92 & 194.92
Net Site Energy & 180.73 & 194.92 & 194.92
Total Source Energy & 1141.64 & 1231.28 & 1231.28
Net Source Energy & 1141.64 & 1231.28 & 1231.28
Source to Site Energy Conversion Factors
Building Area
End Uses
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & & &
Total End Uses & 152.57 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
Note: Natural gas appears to be the principal heating source based on energy usage.
End Uses By Subcategory
p0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75inp0.75in & Subcategory & Electricity [GJ] & Natural Gas [GJ] & Other Fuel [GJ] & District Cooling [GJ] & District Heating [GJ] & Water [m3]
Heating & Boiler & 0.00 & 28.16 & 0.00 & 0.00 & 0.00 & 0.00
& Boiler Parasitic & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Cooling & General & 16.56 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & GeneralLights & 81.24 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & General & 47.70 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & General & 6.59 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & General & 0.48 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & General & 0.00 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Normalized Metrics
Utility Use Per Conditioned Floor Area
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Utility Use Per Total Floor Area
p0.85inp0.85inp0.85inp0.85inp0.85inp0.85inp0.85in & Electricity Intensity [MJ/m2] & Natural Gas Intensity [MJ/m2] & Other Fuel Intensity [MJ/m2] & District Cooling Intensity [MJ/m2] & District Heating Intensity [MJ/m2] & Water Intensity [m3/m2]
Lighting & 87.62 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
HVAC & 25.49 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Other & 51.44 & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Total & 164.55 & 30.37 & 0.00 & 0.00 & 0.00 & 0.00
Electric Loads Satisfied
p2.9inp1.5inp1.59in & Electricity [GJ] & Percent Electricity [%]
Fuel-Fired Power Generation & 0.00 & 0.00
High Temperature Geothermal* & 0.00 & 0.00
Photovoltaic Power & 0.00 & 0.00
Wind Power* & 0.00 & 0.00
Net Decrease in On-Site Storage & 0.00 & 0.00
Total On-Site Electric Sources & 0.00 & 0.00
& &
Electricity Coming From Utility & 152.57 & 100.00
Surplus Electricity Going To Utility & 0.00 & 0.00
Net Electricity From Utility & 152.57 & 100.00
& &
Total On-Site and Utility Electric Sources & 152.57 & 100.00
Total Electricity End Uses & 152.57 & 100.00
On-Site Thermal Sources
Water Source Summary
p3.0inp1.5inp1.5in & Water [m3] & Percent Water [%]
Rainwater Collection & 0.00 & -
Condensate Collection & 0.00 & -
Groundwater Well & 0.00 & -
Total On Site Water Sources & 0.00 & -
- & - & -
Initial Storage & 0.00 & -
Final Storage & 0.00 & -
Change in Storage & 0.00 & -
- & - & -
Water Supplied by Utility & 0.00 & -
- & - & -
Total On Site, Change in Storage, and Utility Water Sources & 0.00 & -
Total Water End Uses & 0.00 & -
Comfort and Setpoint Not Met Summary
p4.5inp1.5in & Facility [Hours]
Time Set Point Not Met During Occupied Heating & 0.00
Time Set Point Not Met During Occupied Cooling & 213.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 & 72.50
Note 1: An asterisk (*) indicates that the feature is not yet implemented.
Input Verification Summary[LINK]
The input verification summary gives a good overview of the facility being simulated:
Report: InputVerificationandResultsSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
General
p2.25inp3.74in & Value
Program Version and Build & EnergyPlus 4.0.0.017, 9/17/2009 5:30 PM
Weather & Climate Zone 6 CA USA WYEC2-C-00006 WMO#=722970
Latitude [deg] & 33.90
Longitude [deg] & -118.5
Elevation [m] & 30.00
Time Zone & -8.0
North Axis Angle [deg] & 30.00
Rotation for Appendix G [deg] & 0.00
Hours Simulated [hrs] & 8760.00
ENVELOPE
Window-Wall Ratio
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Total & North (315 to 45 deg) & East (45 to 135 deg) & South (135 to 225 deg) & West (225 to 315 deg)
Gross Wall Area [m2] & 274.20 & 91.50 & 45.60 & 91.50 & 45.60
Window Opening Area [m2] & 60.90 & 20.85 & 9.12 & 21.81 & 9.12
Window-Wall Ratio [%] & 22.21 & 22.79 & 20.00 & 23.84 & 20.00
Skylight-Roof Ratio
PERFORMANCE
Zone Summary
p0.7inp0.4inp0.5inp0.5inp0.4inp0.5inp0.5inp0.5inp0.5inp0.5in & Area [m2] & Conditioned (Y/N) & Volume [m3] & Multipliers & Gross Wall Area [m2] & Window Glass Area [m2] & Lighting [W/m2] & People [m2] per person & Plug and Process [W/m2]
PLENUM-1 & 463.60 & Yes & 283.20 & 1.00 & 54.84 & 0.00 & 0.0000 & & 0.0000
SPACE1-1 & 99.16 & Yes & 239.25 & 1.00 & 73.20 & 21.81 & 15.9742 & 9.01 & 10.6495
SPACE2-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE3-1 & 96.48 & Yes & 239.25 & 1.00 & 73.20 & 20.85 & 16.4179 & 8.77 & 10.9453
SPACE4-1 & 42.73 & Yes & 103.31 & 1.00 & 36.48 & 9.12 & 16.0056 & 8.55 & 10.6704
SPACE5-1 & 182.49 & Yes & 447.68 & 1.00 & 0.00 & 0.00 & 16.2420 & 9.12 & 10.8280
Total & 927.20 & & 1416.00 & & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Conditioned Total & 927.20 & & 1416.00 & & 274.20 & 60.90 & 8.0889 & 17.83 & 5.3926
Unconditioned Total & 0.00 & & 0.00 & & 0.00 & 0.00 & & &
Source Energy End Use Components Summary[LINK]
The source energy end use components summary gives a good overview of the source energy consumption broken down by end uses for the facility being simulated:
Report: SourceEnergyEndUseComponentsSummary
For: Entire Facility
Timestamp: 2011-10-07 20:53:43
Values gathered over 8760.00 hours
Source Energy End Use Components Summary
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [GJ] & Source Natural Gas [GJ] & Source Other Fuel [GJ] & Source District Cooling [GJ] & Source District Heating [GJ]
Heating & 0.00 & 140.03 & 0.00 & 0.00 & 0.00
Cooling & 167.65 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 569.39 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 325.49 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 55.72 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 7.57 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1125.82 & 140.03 & 0.00 & 0.00 & 0.00
Normalized Metrics
Source Energy End Use Components Per Conditioned Floor Area
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00
Source Energy End Use Components Per Total Floor Area
p1.0inp1.0inp1.0inp1.0inp1.0inp1.0in & Source Electricity [MJ/m2] & Source Natural Gas [MJ/m2] & Source Other Fuel [MJ/m2] & Source District Cooling [MJ/m2] & Source District Heating [MJ/m2]
Heating & 0.00 & 151.02 & 0.00 & 0.00 & 0.00
Cooling & 180.82 & 0.00 & 0.00 & 0.00 & 0.00
Interior Lighting & 614.09 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Lighting & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Interior Equipment & 351.05 & 0.00 & 0.00 & 0.00 & 0.00
Exterior Equipment & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Fans & 60.10 & 0.00 & 0.00 & 0.00 & 0.00
Pumps & 8.16 & 0.00 & 0.00 & 0.00 & 0.00
Heat Rejection & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Humidification & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Heat Recovery & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Water Systems & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Refrigeration & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
Generators & 0.00 & 0.00 & 0.00 & 0.00 & 0.00
& & & & &
Total Source Energy End Use Components & 1214.22 & 151.02 & 0.00 & 0.00 & 0.00
Other Summary Reports[LINK]
The Climatic Data Summary, Envelope Summary and Equipment Summary reports might be quite important to some reporting or presentation.
Report: ClimaticDataSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
SizingPeriod:DesignDay
p1.2inp0.7inp0.7inp0.7inp0.7inp0.7inp0.7in & Maximum Dry Bulb [C] & Daily Temperature Range [C] & Humidity Value & Humidity Type & Wind Speed [m/s] & Wind Direction
LOS_ANGELES_CA_USA HEATING 99% CONDITIONS & 7.40 & 0.00 & 7.40 & 0 & 2.80 & 70.00
LOS_ANGELES_CA_USA COOLING 1% CONDITIONS DB= > MWB & 27.00 & 6.10 & 17.60 & 0 & 4.40 & 250.00
Weather Statistics File
p2.15inp3.84in & Value
Reference & CZ06RV2
Site:Location & Climate Zone 6 CA USA
Latitude & N 33° 54’
Longitude & W 118° 30’
Time Zone & GMT -8.0 Hours
Elevation & 30m above sea level
Standard Pressure at Elevation & 100965Pa
Data Source & WYEC2-C-00006
WMO Station & 722970
Design Conditions & Climate Design Data 2005 ASHRAE Handbook
Heating Design Temperature 99.6% (C) & 4.9
Heating Design Temperature 99% (C) & 6.2
Cooling Design Temperature 0.4% (C) & 33.1
Cooling Design Temperature 1% (C) & 30.9
Cooling Design Temperature 2% (C) & 29.2
Maximum Dry Bulb Temperature (C) & 31.7°
Maximum Dry Bulb Occurs on & Sep 24
Minimum Dry Bulb Temperature (C) & 3.5°
Minimum Dry Bulb Occurs on & Jan 8
Maximum Dew Point Temperature (C) & 20.9
Maximum Dew Point Occurs on & Jun 20
Minimum Dew Point Temperature (C) & -21.7
Minimum Dew Point Occurs on & Dec 27
Heating Degree-Days (base 10°C) & 2
Cooling Degree-Days (base 18°C) & 216
Köppen Classification & Csb
Köppen Description & Mediterranean climate (dry warm summer, mild winter, lat. 30-45°N)
Köppen Recommendation &
ASHRAE Climate Zone & 3C
ASHRAE Description & Warm-Marine
Report: EnvelopeSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Opaque Exterior
p0.66inp0.66inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6inp0.6in & Construction & Reflectance & U-Factor with Film [W/m2-K] & U-Factor no Film [W/m2-K] & Gross Area [m2] & Azimuth [deg] & Tilt [deg] & Cardinal Direction
WALL-1PF & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 210.00 & 90.00 & S
WALL-1PR & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 120.00 & 90.00 & E
WALL-1PB & WALL-1 & 0.22 & 0.384 & 0.408 & 18.30 & 30.00 & 90.00 & N
WALL-1PL & WALL-1 & 0.22 & 0.384 & 0.408 & 9.12 & 300.00 & 90.00 & W
TOP-1 & ROOF-1 & 0.35 & 0.268 & 0.282 & 463.60 & 210.00 & 0.00 &
FRONT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 210.00 & 90.00 & S
F1-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 99.16 & 30.00 & 180.00 &
RIGHT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 120.00 & 90.00 & E
F2-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 300.00 & 180.00 &
BACK-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 73.20 & 30.00 & 90.00 & N
F3-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 96.48 & 74.22 & 180.00 &
LEFT-1 & WALL-1 & 0.22 & 0.384 & 0.408 & 36.48 & 300.00 & 90.00 & W
F4-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 42.73 & 120.00 & 180.00 &
F5-1 & FLOOR-SLAB-1 & 0.35 & 3.119 & 12.894 & 182.49 & 30.00 & 180.00 &
Fenestration
p0.6inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5inp0.5in & Construction & Area of One Opening [m2] & Area of Openings [m2] & U-Factor [W/m2-K] & SHGC & Visible Transmittance & Shade Control & Parent Surface & Azimuth [deg] & Cardinal Direction
WF-1 & DBL CLR 3MM/13MM AIR & 16.56 & 16.56 & 2.720 & 0.764 & 0.812 & No & FRONT-1 & 210.00 & S
DF-1 & SGL GREY 3MM & 5.25 & 5.25 & 5.894 & 0.716 & 0.611 & No & FRONT-1 & 210.00 & S
WR-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & RIGHT-1 & 120.00 & E
WB-1 & DBL CLR 3MM/13MM AIR & 16.44 & 16.44 & 2.720 & 0.764 & 0.812 & No & BACK-1 & 30.00 & N
DB-1 & SGL GREY 3MM & 4.41 & 4.41 & 5.894 & 0.716 & 0.611 & No & BACK-1 & 30.00 & N
WL-1 & DBL CLR 3MM/13MM AIR & 9.12 & 9.12 & 2.720 & 0.764 & 0.812 & No & LEFT-1 & 300.00 & W
Total or Average & & & 60.90 & 3.22 & 0.756 & 0.780 & & & &
North Total or Average & & & 20.85 & 3.39 & 0.754 & 0.769 & & & &
Non-North Total or Average & & & 40.05 & 3.14 & 0.757 & 0.785 & & & &
Report: ShadingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Sunlit Fraction
Window Control
Report: LightingSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Interior Lighting
Daylighting
Exterior Lighting
Report: EquipmentSummary
For: Entire Facility
Timestamp: 2009-09-17 17:30:22
Central Plant
Cooling Coils
Heating Coils
Fans
Pumps
Service Water Heating
Documentation content copyright © 1996-2021 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.