The basement routine is used to calculate the face
(surface) temperatures on the outside of the basement wall or
the floor slab. This is the plane between the outside
insulation and the basement wall. The insulation thermal
resistance can range from zero (no insulation) to any
reasonable value. The units are K/(W/m2). The
program will simulate two conditions: full insulation from
grade to the footing or half insulation that extends halfway
down from grade to footing. The temperature on this plane is
used with the OtherSideCoefficients object in EnergyPlus to
supply the outside face temperature of the walls or slab.
GHTfigx
Figure 22. Basement Configuration
The output from the program is a csv file, named
MonthlyResults.csv, as shown below.
GHTfigx
Figure 23. Output from Basement program
Column B gives the basement zone temperature. This can vary
month by month as will be explained later. Column C is the
monthly average wall outside face temperature, as shown in the
diagram above. Column D is the corresponding average monthly
average inside wall face temperature. Columns E and F contain
the same information for the basement floor slab. Columns G-J
contain the same information for the upper half and the lower
half of the basement walls.
Columns K through N contain the monthly average heat flux
for the floor, the walls, the upper half of the walls and the
lower half of the walls. The flux is reported in units of
W/m2.
The program also produces an output file named
EPObjects.TXT. This file contains the necessary idf objects to
make it easy to include the wall outside surface temperatures
in an EnergyPlus input file. Idf objects for all of the
temperatures in the output file shown above are included.
These objects are explained in detail in the section Using the
Interface Surface Temperature Results in EnergyPlus.
Using Ground Temperatures with Basements[LINK]
The basement routine is used to calculate the face (surface) temperatures on the outside of the basement wall or the floor slab. This is the plane between the outside insulation and the basement wall. The insulation thermal resistance can range from zero (no insulation) to any reasonable value. The units are K/(W/m2). The program will simulate two conditions: full insulation from grade to the footing or half insulation that extends halfway down from grade to footing. The temperature on this plane is used with the OtherSideCoefficients object in EnergyPlus to supply the outside face temperature of the walls or slab.
Figure 22. Basement Configuration
The output from the program is a csv file, named MonthlyResults.csv, as shown below.
Figure 23. Output from Basement program
Column B gives the basement zone temperature. This can vary month by month as will be explained later. Column C is the monthly average wall outside face temperature, as shown in the diagram above. Column D is the corresponding average monthly average inside wall face temperature. Columns E and F contain the same information for the basement floor slab. Columns G-J contain the same information for the upper half and the lower half of the basement walls.
Columns K through N contain the monthly average heat flux for the floor, the walls, the upper half of the walls and the lower half of the walls. The flux is reported in units of W/m2.
The program also produces an output file named EPObjects.TXT. This file contains the necessary idf objects to make it easy to include the wall outside surface temperatures in an EnergyPlus input file. Idf objects for all of the temperatures in the output file shown above are included. These objects are explained in detail in the section Using the Interface Surface Temperature Results in EnergyPlus.