Variables are important to any programming language. All
Erl variables, except trend variables, are treated the same
way in Erl and can be used interchangeably with any
instruction.
The rules for selecting names of EMS variables are:
No spaces are allowed in user-defined variable
names.
Underscore (“_”) is the only special character allowed
in variable names.
Variable names are not case
sensitive.
Names of variables with global scope must be
unique.
Variables cannot be declared with the same name as a
built-in variable.
Variables can be alpha numeric strings but should NOT
start with a numeric.
The rules for using EMS variables are:
All numeric variables are treated as floating point
numbers. You use the underlying C++ language features to
handle these as double precision real numbers.
Variables need to be initialized before being used in
an expression. Beginning with version 8.6, EnergyPlus detects
when un-initialized variables are used and when they are it
issues a fatal warning. Warnings are sent to both the ERR file
and the EDD file. Before a variable can be used it must first
be given a value using SET statement, unless it is a Sensor,
Built-in, or Internal variable (see below).
You can use the SET statement to reassign sensor
variables and built-in variables.
Actuator variables use SET to perform control
actions.
EMS variables can have either local or global scope. Global
scope means that the variables can be used across Erl programs
and always refer to the same instance of a particular
variable. Global variables must have unique names. Local scope
means that variables can be used only within a given Erl
program.
Erl programs have eight types of variables:
Sensor. Each EnergyManagementSystem:Sensor
input object declares a user-defined variable and maps it to a
variable elsewhere in EnergyPlus (via output variables).
Variables so declared have global scope and are used to
get time-varying input data from elsewhere in the
EnergyPlus model.
Actuator. Each EnergyManagementSystem:Actuator
input object declares a user-defined Erl variable and maps it
to a variable elsewhere in EnergyPlus. Variables so declared
have global scope and are used to set control results
elsewhere in the EnergyPlus model.
Local. Local variables do not need to be explicitly
declared. These undeclared variables will be automatically
registered as EMS variables with local scope. This allows you
to create new variables “on the fly.” Local variables can be
used for temporary storage of intermediate results.
Global. EnergyManagementSystem:GlobalVariable
input objects are used to declare variables with a
user-defined name and global scope. Global variables can be
used to store intermediate results that span across Erl
programs. Because the Erl compiler does not support functions
or argument passing, global variables have an important role
in using subroutines. These variables are global only within
Erl and not with respect to code elsewhere in
EnergyPlus.
Built-in. The EMS system automatically declares a set
of built-in variables with predefined names. These variables
have global scope. The built-in variables are always created
and cannot be eliminated.
Internal. Each EnergyManagementSystem:InternalVariable
input object declares a user-defined Erl variable and maps it
to a variable elsewhere in EnergyPlus. Variables so declared
have global scope and are used to get static input
data from elsewhere in EnergyPlus.
Trend. Each EnergyManagementSystem:TrendVariable
input object declares a user-defined Erl trend variable and
maps it to a global Erl variable for logging. Trend variables
are used to store the history of Erl variables. Trend
variables differ from other Erl variables in that they can be
put to use only through the built-in trend functions (see Table).
Index. Each EnergyManagementSystem:CurveOrTableIndexVariable
and/or EnergyManagementSystem:ConstructionIndexVariable
declares a user defined Erl variable and maps it to a specific
item in the IDF of indicated type.
Built-in variables, internal variables, and sensor
variables are primarily used to get information about
the state of the simulation. However, because all variables
are treated alike, built-in variables and sensor variables can
also be overwritten by the SET instruction. (This applies
within the EMS only; the variables in the rest of EnergyPlus
program will not be overwritten.) This allows you to reassign
constants such as “on” and “off” as well as the values of the
other built-in variables and sensor variables. There is really
no problem with this, as long as you know what you are doing.
One possible application is to reset a sensor variable that
references the outdoor drybulb temperature so it contains the
temperature in degrees Fahrenheit instead of Celsius.
Regardless of reassignment, sensor variables and the dynamic
built-in variables (e.g., date and time) will be cleared and
updated with the latest values from EnergyPlus at the next
timestep. Resetting a sensor variable does not have a
retroactive effect on the report variable to which it is
mapped.
The actuator variable is the counterpart of the sensor
variable. Sensor variables are used to get the state
of building systems; actuator variables are used to
set the state of building systems. When used with
actuator variables, the SET instruction performs control
actions on the object to which it maps.
Built-In Variables[LINK]
A set of built-in variables provides date, time, and
weather information that is not available via standard report
variables, as well as several handy constant variables such as
“true,” “false,” “on,” and “off.” Several variables provide
access to the time and date information during the course of a
simulation. The CurrentTime, Hour and Minute variables
represent the point in time at end of the timestep currently
being simulated. EnergyPlus primarily operates in standard
time and these clock values are not adjusted for daylight
savings time. The built-in variable DaylightSavings time is
available for use with the daylight savings time adjustment
feature (see RunPeriodControl:DaylightSavingTime). The
duration of simulation timesteps are available in the
variables ZoneTimeStep and SystemTimeStep. The status of
whether or not the simulation is currently during the initial
warmup days is available in the variable WarmupFlag.
Table
lists the built-in variables that are always available for use
in Erl programs.
Built-In Unique Variables for Erl
| Variable Name |
Value |
| Year |
1900–2100 |
| Month |
1–12 |
| DayOfMonth |
1–31 |
| DayOfWeek |
1–7 (1 = Sun, 2 = Mon, …) |
| DayOfYear |
1–365 |
| Holiday |
0 if not. 1.0, 2.0, etc., for
each type of holiday in model |
| DaylightSavings |
0 or 1, 0 if not daylight
savings time, 1 if daylight savings time |
| CurrentTime |
0.0-24.0, (fractional
hours) |
| Hour |
0–23 (whole hours only) |
| Minute |
1.0–60.0 (fractional
minutes) |
| True |
1.0 |
| False |
0.0 |
| On |
1.0 |
| Off |
0.0 |
| PI |
3.14159265358979 |
| SunIsUp |
0 (= no) or 1 (= yes) |
| IsRaining |
0 (= no) or 1 (= yes) |
| ZoneTimeStep |
Durating of the zone timestep in
hours |
| SystemTimeStep |
Current duration of the system
timestep in hours |
| CurrentEnvironment |
Integer index for the current
environment period (sizing periods and run periods accumulate
throughout the run) |
| Null |
Special structure that stops an
actuator from overriding control |
| ActualDateAndTime |
A simple sum of the values of
the date/time function. Could be used in random seeding. |
| ActualTime |
A simple sum of the values of
the time part of the date/time function. Could be used in
random seeding. |
| WarmupFlag |
0 (= not during warmup) or 1 (=
during warmup) |
Trend Variables[LINK]
Trend variables are used to log data over time. They hold
the history of Erl variables from previous zone timesteps. You
create trend variables with an EnergyManagementSystem:TrendVariable
input object, each of which declares a user-defined Erl trend
variable and maps it to a global Erl variable for logging.
Trend variables are also used to store the history of Erl
variables. The trend input includes the number of timesteps
that are to be logged. The logging of data is
first-in-first-out, meaning that the oldest data are pushed
out the back of the log to make room for the most recent data.
The zone timestep is used as the (constant) increment of time
between different elements in the log and this value, in
fractional hours, is available in the ZoneTimeStep built-in
variable.
Trend variables differ from other Erl variables in that
they can be used only through the built-in trend functions
(see Table).
Trend functions provide a number of ways to analyze trend data
and extract data from the log. There are functions to obtain
the maximum, minimum, average, and sum of logged data. There
is a function to obtain the rate of change in the data. All
the trend functions include an argument for a log index. This
index tells the function how far back in time to go when
evaluating.
Variables[LINK]
Variables are important to any programming language. All Erl variables, except trend variables, are treated the same way in Erl and can be used interchangeably with any instruction.
The rules for selecting names of EMS variables are:
No spaces are allowed in user-defined variable names.
Underscore (“_”) is the only special character allowed in variable names.
Variable names are not case sensitive.
Names of variables with global scope must be unique.
Variables cannot be declared with the same name as a built-in variable.
Variables can be alpha numeric strings but should NOT start with a numeric.
The rules for using EMS variables are:
All numeric variables are treated as floating point numbers. You use the underlying C++ language features to handle these as double precision real numbers.
Variables need to be initialized before being used in an expression. Beginning with version 8.6, EnergyPlus detects when un-initialized variables are used and when they are it issues a fatal warning. Warnings are sent to both the ERR file and the EDD file. Before a variable can be used it must first be given a value using SET statement, unless it is a Sensor, Built-in, or Internal variable (see below).
You can use the SET statement to reassign sensor variables and built-in variables.
Actuator variables use SET to perform control actions.
EMS variables can have either local or global scope. Global scope means that the variables can be used across Erl programs and always refer to the same instance of a particular variable. Global variables must have unique names. Local scope means that variables can be used only within a given Erl program.
Erl programs have eight types of variables:
Sensor. Each EnergyManagementSystem:Sensor input object declares a user-defined variable and maps it to a variable elsewhere in EnergyPlus (via output variables). Variables so declared have global scope and are used to get time-varying input data from elsewhere in the EnergyPlus model.
Actuator. Each EnergyManagementSystem:Actuator input object declares a user-defined Erl variable and maps it to a variable elsewhere in EnergyPlus. Variables so declared have global scope and are used to set control results elsewhere in the EnergyPlus model.
Local. Local variables do not need to be explicitly declared. These undeclared variables will be automatically registered as EMS variables with local scope. This allows you to create new variables “on the fly.” Local variables can be used for temporary storage of intermediate results.
Global. EnergyManagementSystem:GlobalVariable input objects are used to declare variables with a user-defined name and global scope. Global variables can be used to store intermediate results that span across Erl programs. Because the Erl compiler does not support functions or argument passing, global variables have an important role in using subroutines. These variables are global only within Erl and not with respect to code elsewhere in EnergyPlus.
Built-in. The EMS system automatically declares a set of built-in variables with predefined names. These variables have global scope. The built-in variables are always created and cannot be eliminated.
Internal. Each EnergyManagementSystem:InternalVariable input object declares a user-defined Erl variable and maps it to a variable elsewhere in EnergyPlus. Variables so declared have global scope and are used to get static input data from elsewhere in EnergyPlus.
Trend. Each EnergyManagementSystem:TrendVariable input object declares a user-defined Erl trend variable and maps it to a global Erl variable for logging. Trend variables are used to store the history of Erl variables. Trend variables differ from other Erl variables in that they can be put to use only through the built-in trend functions (see Table).
Index. Each EnergyManagementSystem:CurveOrTableIndexVariable and/or EnergyManagementSystem:ConstructionIndexVariable declares a user defined Erl variable and maps it to a specific item in the IDF of indicated type.
Built-in variables, internal variables, and sensor variables are primarily used to get information about the state of the simulation. However, because all variables are treated alike, built-in variables and sensor variables can also be overwritten by the SET instruction. (This applies within the EMS only; the variables in the rest of EnergyPlus program will not be overwritten.) This allows you to reassign constants such as “on” and “off” as well as the values of the other built-in variables and sensor variables. There is really no problem with this, as long as you know what you are doing. One possible application is to reset a sensor variable that references the outdoor drybulb temperature so it contains the temperature in degrees Fahrenheit instead of Celsius. Regardless of reassignment, sensor variables and the dynamic built-in variables (e.g., date and time) will be cleared and updated with the latest values from EnergyPlus at the next timestep. Resetting a sensor variable does not have a retroactive effect on the report variable to which it is mapped.
The actuator variable is the counterpart of the sensor variable. Sensor variables are used to get the state of building systems; actuator variables are used to set the state of building systems. When used with actuator variables, the SET instruction performs control actions on the object to which it maps.
Built-In Variables[LINK]
A set of built-in variables provides date, time, and weather information that is not available via standard report variables, as well as several handy constant variables such as “true,” “false,” “on,” and “off.” Several variables provide access to the time and date information during the course of a simulation. The CurrentTime, Hour and Minute variables represent the point in time at end of the timestep currently being simulated. EnergyPlus primarily operates in standard time and these clock values are not adjusted for daylight savings time. The built-in variable DaylightSavings time is available for use with the daylight savings time adjustment feature (see RunPeriodControl:DaylightSavingTime). The duration of simulation timesteps are available in the variables ZoneTimeStep and SystemTimeStep. The status of whether or not the simulation is currently during the initial warmup days is available in the variable WarmupFlag.
Table lists the built-in variables that are always available for use in Erl programs.
Trend Variables[LINK]
Trend variables are used to log data over time. They hold the history of Erl variables from previous zone timesteps. You create trend variables with an EnergyManagementSystem:TrendVariable input object, each of which declares a user-defined Erl trend variable and maps it to a global Erl variable for logging.
Trend variables are also used to store the history of Erl variables. The trend input includes the number of timesteps that are to be logged. The logging of data is first-in-first-out, meaning that the oldest data are pushed out the back of the log to make room for the most recent data. The zone timestep is used as the (constant) increment of time between different elements in the log and this value, in fractional hours, is available in the ZoneTimeStep built-in variable.
Trend variables differ from other Erl variables in that they can be used only through the built-in trend functions (see Table). Trend functions provide a number of ways to analyze trend data and extract data from the log. There are functions to obtain the maximum, minimum, average, and sum of logged data. There is a function to obtain the rate of change in the data. All the trend functions include an argument for a log index. This index tells the function how far back in time to go when evaluating.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.