The AirflowNetwork model provides the ability to simulate
the performance of an air distribution system, including
supply and return leaks, and calculate multizone airflows
driven by outdoor wind and forced air during HVAC system
operation. The pressure and airflow model described here was
developed based on AIRNET (Walton 1989). This detailed model
is used to simulate thermal conduction and air leakage losses
for constant volume air distribution systems (e.g., in
residential or light commercial buildings). The multizone
airflow calculations are performed at the HVAC system time
step which, among other benefits, allows for modeling hybrid
ventilation systems.
The input object AirflowNetwork:SimulationControl
provides access to the airflow network method, which consists
of a set of nodes connected by airflow components through
linkages. The objects AirflowNetwork:Multizone:Zone,
AirflowNetwork:Multizone:ExternalNode, and AirflowNetwork:Distribution:Node
represent airflow nodes. The objects
AirflowNetwork:Multizone:Surface and AirflowNetwork:Distribution:Linkage
represent airflow linkages. The other objects with a
relationship between pressure and airflow represent airflow
components.
The AirflowNetwork model consists of three sequential
steps:
Pressure and airflow calculations
Node temperature and humidity calculations
Sensible and latent load calculations
The pressure and airflow calculations determine pressure at
each node and airflow through each linkage given wind
pressures and forced airflows. Based on the airflow calculated
for each linkage, the model then calculates node temperatures
and humidity ratios given zone air temperatures and zone
humidity ratios. Using these node temperatures and humidity
ratios, the sensible and latent loads from duct system
conduction and leakage are summed for each zone. The sensible
and latent loads obtained in this step are then used in the
zone energy balance equations to predict HVAC system loads and
to calculate the final zone air temperatures, humidity ratios,
and pressures.
The present AirflowNetwork model may only be applied to a
single heating and cooling system that uses a single air
distribution system (a single AirLoopHVAC
object). The model excludes the impact of the air and duct
system thermal capacitance.
The EnergyPlus airflow network consists of a set of nodes
linked by airflow components. Therefore, it is a simplified
airflow model, compared to detailed models such as those used
in computational fluid dynamics (CFD) models. The node
variable is pressure and the linkage variable is airflow rate.
A brief description is presented below. A detailed description
of the airflow network model may be found in the work of
Walton (1989), Dols and Walton (2002), and Walton and Dols
(2003).
Newton’s method is used to solve for node air pressures and
it requires an initial set of values for the node pressures.
There are two initialization methods available. The first is
linear initialization and equivalent to Initialization flag =
0. These initial values may be obtained by including in each
airflow component a linear approximation relating airflow to
pressure drop:
\[\dot{m}_{i} =
C_{i}\rho\frac{\Delta P_i}{\mu}\]
where:
This initialization handles stack effects very well and
tends to establish the proper direction for the airflows. The
linear approximation is provided by the laminar regime.
The second initialization method assumes the initial
pressures are zero and uses Newton’s method directly.
Conservation of air mass flow rate at each linkage provides
the convergence criterion. When the sum of mass flow rates in
all the linkages approaches zero within the convergence
tolerance, the solution has converged. The solution is assumed
to have converged when the sum is less than the convergence
value, in order to reduce the number of iterations and obtain
sufficient accuracy. There are two convergence criteria used
in the AirflowNetwork model: Relative airflow convergence
tolerance and Absolute airflow convergence tolerance.
The relative airflow tolerance is equivalent to the ratio
of the absolute value of the sum of all network airflows to
the sum of the network airflow magnitudes. The absolute
airflow tolerance is the summation of the absolute value of
all network airflows. The solution has converged when both of
these convergence criteria have been met.
A linkage used in the AirflowNetwork model has two nodes,
inlet and outlet, and is linked by a component which has a
relationship between airflow and pressure. The pressure
difference across each component in a linkage is assumed to be
governed by Bernoulli’s equation:
By rearranging terms and adding wind pressure impacts, the
above equation may be rewritten in the format used by the
airflow network model:
\[\Delta P = {P_n} - {P_m} +
{P_S} + {P_W}\]
where:
The Input Output Reference provides the relationship
between airflow and pressure for the most of the components
(Ref.AirflowNetwork Model). The relationship between airflow
and pressure for the
AirflowNetwork:Multizone:Component:DetailedOpening,
AirflowNetwork:Multizone:Component:SimpleOpening, and
AirflowNetwork:Multizone:Component:HorizontalOpening objects
are provided in detail in this reference.
The general problem of
gravitational flow through a vertical opening
The schematic drawing of a possible air flow pattern
through a detailed vertical opening
(AirflowNetwork:Multizone:Component:DetailedOpening) is shown
in Figure.
The equations used below are extracted from the COMIS
Fundamentals manual (1990).
The air density is assumed to be a linear function of
height:
\[{\rho_i}(z) = {\rho_{0i}} +
{b_i}z\]
The pressure difference is assumed to be linear and
simulate the effect of turbulence:
\[\Delta P_t = P_{t0} + b_t
z\]
The reference pressures on each side are given at the
bottom of the opening. By assuming the Bernoulli hypothesis on
both sides, the pressure difference can be defined at any
level of z as:
The locations of the two possible neutral planes are given
by an equilibrium in pressure which leads to a zero velocity
point. By assuming the left terms in the equation above to be
zero, one may have:
This equation above can have two, one, or zero real
solutions. The zero solution represents a one-way flow
through the opening and may be expressed in the following
equation:
The discharge coefficient, opening width, opening height,
and start height factor are modulated based on opening
factors. A detailed description of opening factor calculations
may be found in the Input Output Reference (Ref.
AirflowNetwork:Multizone:Zone,
AirflowNetwork:Multizone:Surface, and
The above calculation procedure is used for a normal
rectangular window. For a horizontally pivoted rectangular
window, the calculation procedure is slightly different. A
schematic drawing of a horizontally-pivoted window is shown in
Figure.
Schematic drawing of a
horizontally-pivoted window
The opening angle α (0-90°) is linearly proportional to the
window opening factor (0-1.0). An opening factor of 1.0 is
equal to an opening angle of 90°. The heights in the pivoted
area are expressed as:
When z < h2 or z > h4, where z is the distance from
the bottom of the window, the integration procedure is the
same as the procedure for a normal rectangular window. When
h2<z<h4, the window width W in the above equations is
modified as:
It should be pointed out that the discharge coefficient is
modulated based on opening factors, while opening width,
opening height, and start height factor do not apply for a
horizontally-pivoted window. The actual window width and
height are used to calculate airflows for a
horizontally-pivoted window.
The schematic drawing of air flow patterns through a simple
vertical opening
(AirflowNetwork:Multizone:Component:SimpleOpening) is shown in
Figure.
The equations used below are available from Walton (1989).
Schematic of large opening and
associated three flow patterns
The air density for each node is assumed to be constant.
The hydrostatic equation is used to relate pressures at
various heights for each node:
\[Pn\left( y \right) = {P_{0n}}
- {\rho_n}gy\]
\[{P_m}(y) = {P_{0m}} -
{\rho_m}gy\]
where:
It is assumed that the velocity of the airflow as a
function of height is given by the orifice equation (Brown and
Solvason 1962):
When the neutral plane is within the opening (first pattern
in Figure),
two-way (bi-directional) flows occur. The total flow through a
large opening is the sum of both flows.
The opening width is modulated based on opening factors. A
detailed description of opening factor calculations may be
found in the Input Output Reference (Ref.
AirflowNetwork:Multizone:Zone,
AirflowNetwork:Multizone:Surface, and
AirflowNetwork:Multizone:Component:DetailedOpening).
The above two objects are used to simulate airflows across
large vertical openings. The simple opening component
(AirflowNetwork:Multizone:Component:SimpleOpening) assumes the
pressure difference across the opening is a function of height
varied from opening bottom to top, so that two-way flow may be
obtained if appropriate (Walton 1989). The Detailed Opening
component (AirflowNetwork:Multizone:Component:DetailedOpening)
assumes both the pressure difference across the opening and
air density are a function of height, so that three-way flow
may be obtained (COMIS 1990). If these opening models would be
used for horizontal openings, the pressure difference across
the opening and air density remain constant, so that only
one-way flow is possible using the detailed and simple opening
components which are meant for vertical or near-vertical
openings. In reality, there are two-way flows (air
recirculation) across a large horizontal opening caused by
buoyancy due to temperature and pressure difference and forced
flow driven by air pressure difference only. Therefore, a
horizontal opening component
(AirflowNetwork:Multizone:Component:HorizontalOpening) is
available to simulate airflows across large horizontal
openings with the possibility of two-way flow by combining
forced and buoyancy airflows together.
The model for horizontal openings consists of forced
airflow, buoyancy airflow, purge pressure and sloping plane.
The model is mainly from a NIST report presented by Cooper
(1989). The sloping plane (Bolmqvist and Sandberg 2004)
portion of the model was added to allow for staircase
simulations.
For simplicity, a two zone building (upper and lower zones)
connected by a large horizontal opening is used to describe
the model, as shown in Figure.
Forced and buoyancy airflows are described separately
below.
The air mass flow rate is determined by the pressure
difference across the opening. The relationship between
pressure and airflow is the same as AIRNET for a component
(see AirflowNetwork:Multizone:Component:SimpleOpening
description above). Since the height of the opening is
constant, the forced airflow is unidirectional. A positive
value for pressure difference indicates flow direction is from
the lower zone to the upper zone across the opening, while a
negative value represents flow in the opposite direction. The
following description addresses forced air mass flow rates and
partial derivatives for three possible scenarios of pressure
difference:
Buoyancy flow only occurs when the air density in the upper
zone is greater than the air density in the lower zone. The
flow is bi-directional and the amount of upper flow is equal
to the lower flow across the opening. The following discussion
assumes the air density in the upper zone is greater than the
air density in the lower zone. Otherwise, the buoyancy flow
rate is equal to zero. It is also assumed that the maximum
buoyancy flow occurs when the pressure difference across the
opening due to forced airflows is zero. The maximum buoyancy
flow may be expressed as a part of Cooper’s model:
When forced and buoyancy flows co-exist, it is possible to
have either unidirectional or bi-directional flows. For
example, when the upward force due to pressure difference is
greater than the buoyancy force (downward), unidirectional
flow occurs. Bi-directional flow only occurs when the upward
imposed force is less than the buoyancy force. The critical
pressure between unidirectional and bi-directional flows is
called the purge pressure (Tan and Jaluria 1992). The purge
pressure is a function of opening geometry and the buoyancy
force (ΔP/(gΔρD\(_{H}\))) and
may be expressed as (Cooper 1998):
As mentioned above, when the air pressure difference
between two zones is zero there is the maximum bi-directional
flow due to the buoyancy force. When the pressure difference
increases from 0 and is less than \(\Delta P_{Flood}\), there is some
bi-directional flow across the opening, but less than the
maximum flow. If the pressure difference keeps increasing and
exceeds \(\Delta P_{Flood}\),
there is no bi-directional flow. Cooper’s model assumes the
buoyancy flow varies linearly with pressure difference.
The total air flow across the opening is based on
superposition of the forced and buoyancy flows, and may be
expressed for three different pressure difference scenarios as
follows:
A Staircase is attached to the
horizontal opening.
When a staircase is introduced as shown in Figure,
the effective opening area will be used to replace A (opening
area) in the above equations. The effective area may be
estimated as (Bolmqvist and Sandberg 2004):
\[A_{eff} = A\sin \alpha (1 +
\cos \alpha )\]
where:
Note: the hydraulic diameter calculation is based on the
effective opening area, while the opening depth remains the
same.
Figure
demonstrates possible forced and buoyancy flow rates at
different ratios of pressure difference to purging pressure
across a horizontal opening when the upper zone air density is
greater than the lower zone air density. The pressure
difference is the lower zone pressure minus the upper zone
pressure. Otherwise, the buoyancy flow is zero. In addition,
when the absolute ratio is above 1, the buoyancy flow is also
zero. The following table provides a brief description for the
legend listed in Figure.
Legend Description
Legend
Description
Forced downward
Forced flow rate from upper to
lower at P -P < 0
Forced upward
Forced flow rate from lower to
upper at P -P > 0
Buoyancy upward
Total upward flow rate due to
buoyancy only at P -P < 0
Buoyancy downward
Total downward flow rate due to
buoyancy only at P -P > 0
Combined downward
Total downward flow at P -P <
0 (Forced downward + buoyancy upward)
Combined upward
Total upward flow at P -P > 0
(Forced upward + buoyancy downward)
\(C_p\) is a function of
location on the building envelope and wind direction. When
Wind Pressure Coefficient Type = “INPUT”, the \(C_p\) values are explicitly
defined in the input for AirflowNetwork:Multizone:Wind
Pressure Coefficient Values. When Wind Pressure Coefficient
Type = “AVERAGE-SURFACE CALCULATION” and the building shape is
rectangular, the program uses the following equations to
calculate wind pressure coefficient (\(C_p\)) values for different wind
directions. For a low rise building, the normalized surface
pressure coefficient may be written as (Swami and Chandra
1988):
For walls of a high rise building, a two-dimensional array
of surface-averaged wind pressure coefficients is generated
based on wind incident angle and side ratio. The wind pressure
coefficients are provided in 2001 ASHRAE Fundamentals
Handbook, p. 16.5, Fig. 7, “Surface Averaged Wall Pressure
Coefficients for Tall Buildings”. The original work was
performed by Atkins et al. (1979). The incident angle has an
increment of 30 degrees. The side ratio values are 0.25, 1.0,
and 4.0. For a given incident angle and building aspect ratio,
the program uses linear interpolation to calculate the
corresponding wind pressure coefficient \(C_{p,n}\).
For the roof of a high rise building, a two-dimensional
array of surface-averaged wind pressure coefficients is also
generated based on wind incident angle and side ratio. The
wind pressure coefficients are provided in 2001 ASHRAE
Fundamentals Handbook, p. 16.6, Fig. 9, “Surface Averaged Roof
Pressure Coefficients for Tall Buildings”. The original work
was performed by Holmes (1986). The incident angle has an
increment of 30 degrees. The side ratio values are 0.25, 1.0,
and 4.0. At a given wind incident angle and building aspect
ratio, the program uses linear interpolation to calculate the
corresponding wind pressure coefficient \(C_{p,n}\).
The wind surface pressure at the given incident angle can
be calculated by combining the above two equations:
Based on the relationship between airflow rate and pressure
drop for each component, a system of equations for all
components can be assembled together in an n x n square
matrix, where n is the number of nodes. Newton’s method is
used to iteratively solve for the air pressure at each node. A
new estimated vector for all node pressures, {P}, is computed
from the current estimated vector of node pressures, {P},
by:
\[{\left\{ P \right\}^*} =
\left\{ P \right\} - \left\{ C \right\}\]
where the correction vector, {C}, is computed by the matrix
relationship:
\[\left[ J \right]\left\{ C
\right\} = \left\{ B \right\}\]
{B} is a column vector with each component given by:
\[B_n = \sum_{i}
\dot{m}_i\]
where \(n\) is the node
number and \(i\) indicates
all flow paths connecting node \(n\) to other nodes, and [J] is
the square Jacobian matrix whose elements are given by:
The convergence tolerance is used to check the sum of the
mass flow rates by applying mass conservation. The convergence
acceleration equation shown below is used to correct the node
pressures to more rapidly obtain a solution. By assuming a
constant ratio of correction values from one iteration to the
next, the following method is applied:
\[{P_n}^* = P_n - C_n/(1 -
r)\]
where:
This method is similar to a Steffensen iteration (Conte and
de Boor 1972) which is used as a fixed-point iteration method
for individual nonlinear equations.
The iteration correction method presented in the above
equation gives a variable factor. When the solution is close
to convergence, the solution method converges quadratically.
By limiting cases where the value of r is less than some
value, such as -0.5, the solution will not interfere with the
rapid convergence. It has not been proven that the convergence
acceleration equation will always lead to convergence, but it
can be shown that it will not prevent convergence. Newton’s
method converges when the estimated solution values are within
some distance, called the radius of convergence, or the
correct solution. Applying the convergence acceleration
equation when -1 < r <0, will cause a smaller correction
than Newton’s method, which therefore, can not force the
iterations outside the radius of convergence. When r<-1,
the solution diverges in an oscillatory fashion. When r>1,
the solution also diverges, but in a nonoscillatory manner.
For 0<r<1, the solution is approached from one
direction. In all three cases, the convergence acceleration
equation applies as long as r is truly constant over several
iterations. However, for the last case, this involves a true
extrapolation of correction factor which is very sensitive to
the accuracy of r. This is most extreme for the case of r = 1,
which would cause an infinite correction.
A brief description of the air node temperature calculation
is given below. A detailed description can be found in the
work of Swami et al. (1992). The following equation is used to
calculate temperature distribution across a duct element at
the given airflow rate and inlet air temperature:
The outlet air temperature can be calculated using the
above equation at the given inlet air temperature. Since the
inlet temperature at one linkage is the outlet temperature for
the connected linkage, the outlet air temperatures at all
nodes are solved simultaneously. A square linear system
assembled by the AirflowNetwork model is expressed below:
\[\{ M\} [T] = [B]\]
where:
The zone air temperatures and primary air loop component
(fan and coils) outlet conditions are used as prescribed
conditions in the AirflowNetwork model. In addition, the
temperature difference across zone loop components (terminal
units) is held constant during the calculations. For example,
thermal zone temperatures calculated during the previous
system time step are used as prescribed temperatures when
calculating all other node temperatures. The zone air
temperature is assumed constant (prescribed) throughout the
AirflowNetwork iterative solution. The fan and coil outlet air
temperatures, and terminal unit temperature differences are
assumed constant within an AirflowNetwork iteration. The
sensible heat gains calculated during the AirflowNetwork
solution are then used to predict a new zone air
temperature.
The duct-surface user-defined view factors object defines
the view factor from the duct to the zone surfaces. Because
the view factors, duct surface area, and temperatures are
known, the heat gain to the duct can be directly calculated
and applied to the duct air heat balance to determine the
outlet temperature. The duct heat gain is then treated as a
direct heat loss from each participating surface. Once the
heat loss to the duct for each surface is calculated, the
surface temperatures are adjusted to maintain the surface
energy balance.
Radiation is treated as point loads heat source/sink on the
zone surfaces and the duct. These point loads will be added or
subtracted using the same implementation strategy as the
convective load for the ducts to the zone air. The radiative
rate of energy transfer between the duct (d) and a given
surface (s) for two grey surfaces can be written as shown
below.
A brief description of the air node humidity ratio
calculation is given below. A detailed description can found
in the work of Swami et al. (1992). The following equation is
used to calculate humidity ratio distribution across a duct
element at the given airflow rate and inlet air humidity
ratio:
The outlet air humidity ratio can be calculated using the
above equation at the given inlet air humidity ratio. Since
the inlet humidity ratio at one linkage is the outlet humidity
ratio for the connected linkage, the outlet air humidity ratio
at all nodes are solved simultaneously. A square linear system
assembled by the AirflowNetwork model is expressed below:
\[\{M_m\} [W] =
[B_m]\]
where:
The zone air humidity ratios and primary air loop component
(fan and coils) outlet conditions are used as prescribed
conditions in the AirflowNetwork model. For example, thermal
zone humidity ratios calculated during the previous system
time step are used as prescribed humidity ratios when
calculating all other node humidity ratios. The zone air
humidity ratio is assumed constant (prescribed) throughout the
AirflowNetwork iterative solution. The coil outlet air
humidity ratio is assumed constant within an AirflowNetwork
iteration. The latent heat gains calculated during the
AirflowNetwork solution are then used to predict a new zone
air humidity ratio.
The zone sensible and latent loads calculated in the
AirflowNetwork model consist of multizone, duct conduction and
leakage. In addition, the impact of infiltration and mixing is
accounted for in this calculation. The multizone load only
includes incoming airflows from outside (infiltration) and
other adjacent zones (mixing) with and without forced-air fan
operation. It is divided into two terms: variable and
constant. The constant term is the sum of the mass flow rate
multiplied by the specific heat for both infiltration and
mixing. The variable term includes the impact of zone and
outdoor air temperature. Each of these terms is used in the
zone energy balance equation. The sensible load items from the
multizone load calculations may be written as follows:
The air distribution system (ADS) loads due to duct
conduction and leakage depend on the air distribution system
component (e.g., duct) location. The air distribution system
sensible and latent loads are calculated for each zone as
follows:
Impacts
of Supply Air Constant Volume Fan Control on Load: Cycling
vs. Continuous[LINK]
The AirflowNetwork model currently allows two types of
constant volume fans: Fan:ConstantVolume
and Fan:OnOff.
The Fan:ConstantVolume
object has only one type of supply air fan operation mode:
continuous fan, cycling compressor
(ContinuousFanWithCyclingCompressor). However, the Fan:OnOff
has two types of supply air fan operation modes: cycling fan,
cycling compressor (CyclingFanAndCompressor) or continuous
fan, cycling compressor (ContinuousFanWithCyclingCompressor).
The CyclingFanAndCompressor operation mode is frequently
referred to as “AUTO fan”, where the compressor(s) and supply
air fan operate in unison to meet the zone heating or cooling
load, and cycle off together when the heating or cooling load
has been met. The ContinuousFanWithCyclingCompressor operation
mode is often referred to as “fan ON”, where the compressor(s)
cycle on and off to meet the zone heating or cooling load but
the supply air fan operates continuously regardless of
compressor operation. The supply air fan operation mode is
specified in an HVAC system object based on a given fan
operation mode schedule (e.g., AirLoopHVAC:UnitaryHeatCool
object).
The determination of the zone sensible and latent loads
caused by multizone airflows and forced air distribution
system operation is dependent on the supply air fan operation
mode (see Sensible and Latent Load Calculations section
above). The zone loads calculated by the AirflowNetwork model
are added to zone sensible and latent balances in the
ZonePredictorCorrector module to calculate zone air
temperatures and humidity ratios (see Integration of the
AirflowNetwork Model section below). For the case of
continuous fan/cycling compressor, the zone loads during
forced air distribution system operation are calculated with
the system design air mass flow rate without modification,
since the system air node conditions (temperature and
humidity) reflect the average values for the time step
considering the coil/fan on and off periods during the time
step.
For the case of cycling fan/cycling compressor, where the
forced air distribution system can operate for a portion of
the simulation time step, the airflows are determined based on
the air distribution system part-load ratio (ratio of the
average air mass flow rate for the time step divided by the
design air mass flow rate). The airflows for
the AirflowNetwork:Distribution:Linkage
objects are reported during the air distribution system on
cycle, since no airflow is assumed during the system off
cycle. The airflows for the
AirflowNetwork:Multizone:Surface objects are weighted by the
air distribution system part-load ratio. The zone
loads are the sum of energy losses during both the
air distribution system on and off cycle at each system time
step. The energy losses when the air distribution system is on
are calculated using the system “on” air flow rate multiplied
by the air distribution system run time fraction. The energy
losses when the air distribution system is off are obtained
from the multizone airflow calculations (without forced air
through the air distribution system) and these losses are
multiplied by (1.0 - system run time fraction), assuming no
airflows through the air distribution system when the fan is
off. The formulas used to calculate airflows and zone loads
are given below:
Airflow
Airflow = Airflow during ADS on cycle * ADS Part-load ratio
+ Airflow during ADS off cycle * (1.0 – ADS Part-load
ratio)
System run time fraction = Maximum run time fraction of
coils and fans in the air distribution system
Zone
energy losses = Zone
energy loss during ADS on cycle * System run time fraction +
Zone
energy loss during ADS off cycle * (1.0 - System run time
fraction)
The calculation of loads due to multizone airflow, without
forced air distribution system operation, is performed when
the HVAC system is first simulated during a simulation time
step (FirstHVACIteration = True). The calculation of loads due
to air distribution system operation is performed on
subsequent iterations within the same simulation time step
when the mass flow rate at the supply air fan inlet is greater
than 0.0 (and FirstHVACIteration = False).
Airflow
Calculation Procedure using A Supply Variable Air Volume
Fan[LINK]
The AirflowNetwork model currently also allows a variable
air volume fan type as Fan:VariableVolume.
The allowed terminal type is AirTerminal:SingleDuct:VAV:Reheat
only. Other types of terminals will be added later.
In general, the supply fan air flow rate in a VAV central
system is determined by a sum of terminal flow rates when the
AirflowNetwork model is not applied. When the AirflowNetwork
model is applied and the supply air fan flow rate is given,
each terminal flow is determined by pressure resistance of
each supply air pathway. It is possible that the delivered air
flow rate from the pressure resistance at each terminal may be
totally different from the desired flow rate determined by
terminal units. Therefore, it is not easy to meet both
requirements. The following compromised approach, including
possible supply and return leaks in an air distribution
system, is implemented.
Set up terminal airflows in the AirflowNetwork module
based on the SimVAV subroutine in the HVACSingleDuctSystem
module.
Require AirflowNetwork:Distribution:Component:LeakageRatio
objects to define supply leaks, so that the values of the
Effective Leakage Ratio field are used to decide the supply
fan flow rates. The base of the ratio will be actual supply
fan flow rate, instead of the maximum fan flow rate used in
the constant volume fan systems.
Assign the supply fan airflow rate based on the sum of
all terminal flow rates and all supply leak ratios until it
reaches the maximum fan flow rate
If the calculated supply fan flow rate is above the
maximum limit of the supply fan flow rate, and the supply leak
ratios remain the same, the supply fan flow rate is set to the
maximum limit, and the terminal flow rates are reduced
proportionally weighted by a ratio of the maximum supply fan
flow rate by input to the calculated supply fan flow rate.
Therefore, a sum of all terminal rates and all supply leak
rates is equal to the maximum supply fan rate.
The loads calculated by the AirflowNetwork model are
integrated into the EnergyPlus heat balance equation in a
similar manner as described elsewhere in this document in the
section “Basis for the Zone
and System Integration”. The mass flow rate summations and
sensible and latent loads described in the previous section
are included in the calculation of zone temperature and
humidity ratio.
The revised zone temperature update equation becomes:
Where MCPT\(_{airflow}\)
is the sum of mass flow rate multiplied by specific heat and
temperature for infiltration and mixing, Q\(_{ADS,z}\) is the added total
sensible load in the zone due to Air Distribution System
losses, and MCP\(_{airflow}\)
is the sum of mass flow rate multiplied by specific heat for
infiltration and mixing as calculated in the AirflowNetwork
model described above.
The revised coefficient (B) used in the zone humidity ratio
calculation is shown below:
Where MW\(_{airflow}\) is
the sum of mass flow rate multiplied by humidity ratio for
infiltration and mixing and Q\(_{ADS,m,z\\}\)is the added total
latent (moisture) load in the zone due to Air Distribution
System losses from the AirflowNetwork model described above.
This coefficient is used in the prediction of moisture as
described in the section “Moisture Predictor-Corrector” found
elsewhere in this document.
The available outputs from the AirflowNetwork model are
described in the EnergyPlus Input Output Reference manual.
Single
Sided Wind Pressure Coefficient Algorithm[LINK]
The approach in the single sided (SS) model is based on
correlating the flow rate into the room through one or more
openings with local flow conditions at the openings. These are
in one façade of a rectangular building of width WB, depth DB
and height HB. There is a vertical wind profile \(U(z)\) approaching the building,
which generates a local flow \(U_L\) parallel to the façade
(whose value depends on location, building geometry and wind
direction).
Consider first the 2-aperture case, where air flows in
through one opening of area \(A_\textup{in}\) and exits through
another of equal area. Let us denote the flow rate of ambient
air into the room by \(Q\),
and define a dimensionless flow rate \(Q'\) by \[Q'=Q/(A_\textup{in}
U_\textup{ref}),\] where \(U_\textup{ref}\) is a reference
velocity taken as the undisturbed wind speed \(U(z_\textup{ref})\) at a
reference height \(z_\textup{ref} =
10 \textup{m}\). There is a pressure difference \(\Delta p(t)\) between the two
opening locations, with time-averaged mean value \(\overline{\Delta p}\) and
standard deviation \(\sigma_{\Delta
p}\).
There are three principal mechanisms determining the flow
rate:
Mean pressure difference: a non-zero mean value for the
difference in pressure at the two opening locations, \(\overline{\Delta p}\), drives a
flow that scales as \(\overline{\Delta
p}^{1/2}\).
Unsteady pressure difference: turbulence drives a
fluctuating pressure difference between the two openings,
resulting in a net addition of air from the outside. This is
characterized by the standard deviation of the pressure
difference signal, \(\sigma_{\Delta
p}\) and the associated flow rate adds to that arising
from \(\overline{\Delta p}\).
It includes periodic Strouhal forcing (‘pumping’) at relevant
wind angles. Note that this contribution is non-zero even when
the mean pressure difference is zero.
Shear layer mechanism: when there is small or zero mean
pressure difference between the two opening locations, the
local flow parallel to the façade causes a mixing layer to
grow over the length of the opening resulting in the
incorporation of ambient air. This scales with \(U_L\).
Our model therefore views the flow rate as comprising
contributions from each of these as appropriate, i.e. \[Q'=\left[a_p |\Delta c_p |+a_\sigma
\sigma_{\Delta c_p} \right]^{1/2}+a_s U_L'\] where
\(a_p\), \(a_\sigma\) and \(a_s\) are constants, the mean and
fluctuating pressure difference terms have been written as
pressure coefficients \[\Delta
c_p=\frac{\overline{\Delta p}}{\frac{1}{2} \rho
U_\textup{ref}^2},\]\[\sigma_{\Delta
c_p}=\frac{\sigma_{\Delta p}}{\frac{1}{2} \rho
U_\textup{ref}^2},\]\(\rho\) being the ambient air
density, and \[U_L'=\frac{U_L}{U_\textup{ref}}.\]
The pressure-difference mechanisms \(\ref{ss-mean-mech}\) and \(\ref{ss-unsteady-mech}\) are
dominant for the 2-opening case and \(\ref{ss-shear-mech}\) is
negligible, while, in contrast, in the case of a single
opening, shear is dominant. Hence we take \(a_s=0\) for 2-opening cases and
\(a_p = a_\sigma = 0\) for
one opening. Henceforth we focus on the 2-opening case,
although a procedure is given at the end of the section for
how to approximate a greater number by just two.
Figure shows
the geometry of this case in plan view. The two openings are a
distance \(s\) apart in a
façade of width WB whose normal has azimuthal angle \(\varphi_n\). The wind azimuthal
direction is \(\varphi_w\),
so that its direction relative to the façade is \[\theta=\varphi_w-\varphi_n.\] In
these definitions, \(\ang{0} \leq
\varphi_n, \varphi_w \leq \ang{360}\), while \(|\theta| \leq \ang{180}\). Note
that if \(\theta\) initially
falls outside the range indicated it should be replaced by
\(\operatorname{sgn}(\theta)
\left[|\theta| - \ang{360}\right]\).
According to the above discussion, the flow rate is modeled
as comprising two terms, arising, respectively, from the mean
and fluctuating components of the pressure difference between
the two aperture locations: \[\label{eqn:ss-flow-two-terms}
Q'=\left(a_p |\Delta c_p |+a_\sigma \sigma_{\Delta c_p}
\right)^{1/2}\]
Plan view of building with
2-opening façade.
There are two parts to deriving the detailed form of the
model:
Express the mean and fluctuating pressures in terms of
other physical quantities that are more readily accessible.
EnergyPlus does not have the information on variations in
pressure that is needed to compute \(\Delta c_p\) and \(\sigma_{\Delta c_p}\). Analysis
of wind tunnel pressure data (Linden et al., 2013) allows for
the derivation of simple expressions for these quantities in
terms of the wind direction and opening separation \(s\).
Find the coefficients \(a_p\) and \(a_\sigma\). This is achieved here
by analysis of ventilation rate data (Linden et al., 2013),
and using linear regression on the data.
Estimation
of pressure difference coefficients[LINK]
The analysis of pressure data carried out showed that the
contributions to the right-hand side of Equation \(\ref{eqn:ss-flow-two-terms}\) can
be written to first order as \[\Delta c_p=f(s',\theta)\]
and \[\sigma_{\Delta
c_p}=g(s',\theta)\] where the dimensionless
separation \(s' =
s/\textup{WB}\), \[f(s',\theta)=s'\cdot\Pi(\theta),\]
and \[g(s',\theta)=\Sigma_0+s'\cdot\Sigma(\theta).\]
That is, to a first approximation the pressure difference mean
and standard deviation vary linearly with opening separation,
each modulated by its own function of relative wind angle
\(\theta\).
The formulae for the components are as follows. \[\label{eqn:ss-first-formula}
\Pi(\theta) =
\begin{cases}
0.44\operatorname{sgn}(\theta)\sin(2.67|\theta|),&
|\theta| \leq \theta_0 \\
-0.69 \operatorname{sgn}(\theta)\sin(288-1.6|\theta|),&
\theta_0\leq|\theta|\leq\ang{180}.
\end{cases}\]\[\label{eqn:ss-second-formula}
\theta_0 = \ang{67.5}\]\[\label{eqn:ss-third-formula}
\Sigma(\theta) = 0.423 - 1.63\times 10^{-3}|\theta|\]\[\label{eqn:ss-last-formula}
\Sigma_0=0.24\]
Figures \(\ref{fig:ss-figure-2-upper}\) and
\(\ref{fig:ss-figure-2-lower}\)
show an example of \(\Delta
c_p\) and \(\sigma_{\Delta
c_p}\) generated by Equations \(\ref{eqn:ss-first-formula}\)
through \(\ref{eqn:ss-last-formula}\),
respectively, compared with the data.
Mean pressure difference, \(\Delta c_p\) predicted by
Equations \(\ref{eqn:ss-first-formula}\) and
\(\ref{eqn:ss-second-formula}\),
compared with experimental data. The façade containing the
openings is facing South and the separation is large (\(s' = 0.85\)).
Standard deviation of pressure
difference, \(\sigma_{\Delta
c_p}\), predicted by Equations \(\ref{eqn:ss-third-formula}\) and
\(\ref{eqn:ss-last-formula}\),
compared with experimental data. The façade containing the
openings is facing South and the separation is large (\(s' = 0.85\)).
This completes item \(\ref{ss-item-the-first}\) above,
i.e. the approximation of the two pressure coefficient terms
in Equation \(\ref{eqn:ss-flow-two-terms}\) in
terms of the dimensionless opening separation and the relative
wind angle. There remains item \(\ref{ss-item-the-second}\),
i.e. fitting the flow rate data to the formula-generated
pressure parameters to determine the constants \(a_p\) and \(a_\sigma\). When this was carried
out, the best fit was found to occur with \(a_p = 0.173\) and \(a_\sigma = 0.042\). Figure shows the
comparison between the flow rate prediction and the
experimental data.
Combining with the previous results we have \[\label{eqn:ss-combined-eqn}
\frac{Q}{A_\text{in} U_\text{ref}}=\left(0.01+\left[0.173
|\Pi(\theta)|+0.042
\Sigma(\theta)\right]s'\right)^{1/2}\]
The flow Q is defined to be positive when opening #1 is the
inlet and opening #2 is the outlet. Since \(\Delta p\) is defined as \(p_1-p_2\), this can occur when
\(\Delta c_p > 0\), which
in turn corresponds to certain relative wind angles,
i.e. \[\begin{gathered}
Q < 0\ \text{otherwise}\\
Q > 0\ \text{if}\ \ang{0} < \theta < \theta_0\
\text{or}\ \ang{-180} < \theta < -\theta_0
\end{gathered}\]
Note that the sense of \(Q\) is not necessarily
well-defined for all such angles, e.g. when the unsteady
contribution in Equation \(\ref{eqn:ss-flow-two-terms}\) is
significant: nevertheless, we retain this definition for all
angles.
Comparison of predicted flow
rates with experimental data. Each graph shows experimental
data (red diamonds) plotted against model prediction (gray
squares). Cases in the left-hand column, (a)-(c), are for
\(s'=0.75\), those in
right-hand column, (d)-(f), \(s'=0.32\). The three rows are
for 2-story isolated, 4-story isolated and 2-story with low
density surroundings, respectively.
Inversion
of flow rate to equivalent pressure difference[LINK]
Finally, we invert the flow rate to obtain the equivalent
pressure difference. The purpose of this procedure is to allow
incorporation of the model into the network airflow part of
EnergyPlus, which requires pressure coefficients to calculate
the flow rate: in this way the model will become essentially
transparent to the user. A nodal representation of the
2-aperture single-sided case is shown in Figure.
Pressure network for 2-opening
single-sided room.
Here, 0 is the ambient, 1 is at the upstream outer surface,
2 is at the downstream outer surface, and R is the room.
Let the openings have areas \(A_1\) and \(A_2\), not necessarily equal, and
a discharge coefficient \(C_d\), which is assumed equal,
and let \(Q\) be the flow
rate through the system. Then it can be shown that the
pressure difference between the two openings, \(\Delta p_{12}\), is related to
the flow rate by \[\label{eqn:ss-delta-p-1-2}
\frac{\Delta p_{12}}{\frac{1}{2}\rho V^2} =
\frac{1}{C_d^2}\left(\frac{Q/A_\text{eff}}{V}\right)^2\]
where the effective area \(A_\text{eff}\) is defined by
\[A_\text{eff}=\frac{A_1
A_2}{\left(A_1^2+A_2^2\right)^{1/2}}\] and \(V\) is a reference velocity. The
left-hand side of Equation \(\ref{eqn:ss-delta-p-1-2}\) is a
pressure coefficient, \(\Delta
c_{p,12}^{E+}\), say, and our task is to express this
in terms of the flow rate in Equation \(\ref{eqn:ss-combined-eqn}\) but
using the definition of a pressure coefficient appropriate to
EnergyPlus.
The first step is to re-write Equation \(\ref{eqn:ss-delta-p-1-2}\) as
follows: \[\Delta c_{p,12}^{E+} =
\frac{1}{C_d^2} \left(\frac{A_\text{in}}{A_\text{eff}}\right)^2
\left(\frac{U_\text{ref}}{V}\right)^2 Q'^2\] where
\(Q' =
Q/(A_\text{in}U_\text{ref})\) is the non-dimensional
flow rate of Equation \(\ref{eqn:ss-combined-eqn}\),
which is expressed in terms of \(Q\), the window area \(A_\text{in}\) and the wind speed
at 10 m height, \(U_\text{ref}\).
The factor \(\left(A_\text{in}/A_\text{eff}\right)^2
= 2\), since \(A_1 = A_2 =
A_\text{in}\), and therefore \(A_\text{eff} =
A_\text{in}/\sqrt{2}\). The factor \((U_\text{ref}/V)\) relating the
velocity scale used in the correlation with that used in the
EnergyPlus pressure coefficient may be simplified by noting
the following.
EnergyPlus assumes the surface pressure due to wind, \(p_w\), is derived from a pressure
coefficient \(C_p\) using the
local wind speed at window height, \(V_\text{ref}(z_win)\), i.e. \[p_w=\rho_a
\left[V_\text{ref}(z_\text{win}\right]^2 C_p/2\] Hence
the reference velocity \(V
= V_\text{ref}(z_\text{win})\).
EnergyPlus characterizes the vertical wind profile as a
power law in z, defined in terms of the local atmospheric
boundary layer depth \(\delta\) and a power law exponent
\(\alpha\). EnergyPlus also
uses an “interpolation” formula to derive the above local wind
speed from that measured at the meteorological site, \(U_\text{met}\), according to
\[V_\text{ref}(z)= U_\text{met}
\left(\frac{\delta_\text{met}}{z}\right)^{\alpha_\text{met}}
\left(\frac{z}{\delta}\right)^\alpha\] where the
subscript “met” denotes conditions at the meteorological site,
and the default values are \(z_\text{met} = 10\ \text{m}\),
\(\delta_\text{met} = 270\
\text{m}\) and \(\alpha_\text{met} = 0.14\). The
user can change the site parameters from their default
values.
The correlation in Equation \(\ref{eqn:ss-combined-eqn}\)
assumes the reference velocity is the wind speed at 10 m,
which will be taken as the local velocity at the building,
\(V_\text{ref}(10)\).
Combining these results, the pressure coefficient representing
the difference in pressure between the two openings is given
by \[\Delta c_{p,12}^{E+} =
\frac{1}{C_d^2} \left[
\frac{V_\text{ref}(10)}{V_\text{ref}(z_\text{win})} \right]^2
\left(0.02+\left[0.346 |\Pi(\theta)|+0.084
\Sigma(\theta)\right]{\cdot}s'\right)\] where the
velocity ratio \[\frac{V_\text{ref}(10)}{V_\text{ref}(z_\text{win})}
= \left(\frac{10}{z_\text{win}}\right)^\alpha\]
Thus, if we assign a pressure coefficient \(+0.5\Delta c_{p,12}^{E+}\) to
opening 1 and \(-0.5\Delta
c_{p,12}^{E+}\) to opening 2, then this will provide
the necessary pressure difference to give the flow in \(\ref{eqn:ss-combined-eqn}\) in a
network context.
Note: the pressure coefficient \(\Delta c_{p,12}^{E+}\) refers to
the difference in pressure between the two openings and is
defined in terms of the wind speed at window height. If this
is to be combined with a background pressure coefficient for
the façade it is important to ensure the two are defined using
the same reference velocity.
Local velocity as function of
wind angle for wind tunnel data analyzed. On the 2-story graph
‘WP85’ refers to Warren and Parkins (1985), whose measurement
location is most closely matched by the “Center”
curve.
Wind tunnel data, averaged over
all cases, plotted with curve to fit data.
The SS model was developed using wind tunnel pressure and
flow rate data acquired by CPP Wind Engineering & Air
Quality Consultants, who carried out two series of tests: (a)
Closed Box tests, with a sealed building, to obtain pressure
and velocity data and (b) Ventilation tests, with one or two
apertures open, to obtain flow rate data. See Linden et
al. (2013) for full details.
Each experimental configuration consisted of a cuboidal
building with or without a set of blocks representing nearby
buildings.
Building: either 2-story, with WB = 47.5 cm, DB = 19.3
cm, HB = 9.9 cm, or 4-story, with HB = 19.8 cm. The model has
a nominal scale of 1:70 (based on earlier tests).
Environment: building either isolated or at center of a
3 x 3 array of equal-sized blocks, which were of same aspect
ratio and either low (2-story height) or high (4-story
height), and with either narrow spacing (approximately 0.5WB
between blocks) or wide spacing (approximately WB), giving a
total of 5 different environments.
Approach flow: suburban boundary layer, approximately
10 m/s at 1 m height. The model was mounted on a turntable
allowing any desired wind direction to be used. Increments of
\(\ang{11.25}\) and \(\ang{22.5}\) were used for the
Closed Box and Ventilation runs, respectively.
Room and openings: the building envelope contained a
second-floor room of dimensions WRM = 45.9 cm, DRM = 17.7 cm
and HRM = 5.0 cm. A total of 15 opening positions were
available, distributed around the room. These were sealed for
the Closed Box tests but opened in various combinations for
the Ventilation runs.
Sensors: 56 pressure transducers, arranged around the
opening positions, including 32 at mid-opening height,
recorded static pressure, while hot film sensors at 6
different positions recorded flow speed near the surface. For
Ventilation runs the decay in concentration of a tracer was
measured at two locations inside the room.
The data used to develop the model consisted of 6
scenarios: 3 building/environment cases,
2-story isolated building
4-story isolated building
2-story building with low, widely-spaced
blocks
combined with 2 choices of opening position on the South
(long) façade, namely wide separation (\(s' = 0.75\)) and medium
separation (\(s' =
0.32\)).
The AirflowNetwork:OccupantVentilationControl
object enhances the AirflowNetwork model and provides more
practical and advanced controls for window opening and closing
operations, based on Marais & Teichmann (2014). This
control includes minimum open and closed time control, indoor
thermal comfort control, and opening and closing probability
controls.
It should be pointed that the open elapsed time and closed
elapsed time are not independent. In other words, when one of
the elapsed times value is greater than 0, then other elapsed
time value must be equal to 0. The model is either tracking a
window as open, in which case the open elapsed time grows, or
as closed, in which case the closed elapsed time grows.
The calculation procedures are presented in the following
steps:
Step 1: Open elapsed time check
The model checks the open elapsed time first. When the open
elapsed time is greater than 0 and less than the minimum
opening time, a window will remain open. Otherwise, the model
goes to Step 2.
Open elapsed time > minimum open time
Step 2: Closed elapsed time check
This step checks the closed elapsed time. When the closed
elapsed time is greater than 0 and less than the minimum
closed time, a window will remain closed. Otherwise, the model
goes to Step 3.
Closed elapsed time > minimum closed time
Step 3: Elapsed time only?
When either the open elapsed time or the closed elapsed
time is long enough (greater than the minimum time) and no
other checks are needed, the model returns to the other
ventilation control defined in the Ventilation Control Mode
field in AirflowNetwork:MultiZone:Zone
or AirflowNetwork:MultiZone:Surface.
If other checks are needed, the following steps will be
performed.
Step 4: Thermal comfort temperature calculation
The thermal comfort check requires the thermal comfort
temperature and the comfort band. The comfort temperature of
Tcomf is calculated as a function of the outdoor dry-bulb
temperature Tout. The comfort temperature calculation may be
based on two curves and a boundary temperature point.
After calculation of the comfort temperature and band, the
thermal comfort check will be performed using the zone air
operative temperature Tg. The check consists of upper and
lower boundary checks.
The upper boundary check checks window opening status and
uses the following logic:
\[T_g > \left(T_{comf} +
\theta\right)\]
If the above logic check is true, the opening probability
check will be performed. The detailed description is given in
the opening probability section.
If the above logic check is false, no action is needed.
If the opening probability check is true and upper boundary
check is satisfied, a window will be opened, regardless of
open/closed status at the previous time step. If the opening
probability check is false and upper boundary check is
satisfied, a window will remain at the status from the
previous time step.
The lower boundary check will follow the upper boundary
check to check the window closing status, using the following
logic.
\[T_g < \left(T_{comf} -
\theta\right)\]
If the above logic check is true, the closing probability
check will be performed. The detailed description is given in
the closing probability section.
If the above logic check is false, no action is needed.
If the closing probability check is true and lower boundary
check is satisfied, a window will be closed, regardless of
open/closed status at the previous time step. If the closing
probability check is false and lower boundary check is
satisfied, a window will remain at the status from the
previous time step.
The output variables from the model are open status,
opening probability status, and closing probability status.
The detailed description of opening status is given in the
Airflow Network Outputs section in the Input Output
Reference.
Note: The upper and lower boundary checks are not
independent. In other words, when one of boundary check is
satisfied, the other check will be dissatisfied.
Opening probability control provides an optional random
number check. The control logic of opening probability is
described in the following steps.
Step 1: Closed elapsed time check
This check requires that closed elapsed time is longer than
the minimum closing time.
Closed time > minimum closed time
If the time duration is not long enough, the output is
false so that a window remains closed.
If the time duration is long enough, an occupancy check is
performed.
Step 2: Occupancy check
If a zone is not occupied and the occupancy check is
requested, the output is false. If the zone is occupied, the
next step is to check the setpoints using zone air temperature
at the previous time step as a reference.
Step 3: Setpoint check
There are 5 temperature control types. The following types
are available:
No control: Bypass
Single heating setpoint: If Tzon > setpoint, go to
next step. Otherwise, return false.
Single cooling setpoint: If Tzon < setpoint, go to
next step. Otherwise, return false.
Single heating and cooling setpoint: no action by
returning false
Dual heating and setpoints: If heating setpoint <
Tzon < Cooling setpoint, go to next step. Otherwise, return
false.
Step 4: Select bypass or opening probability check
A choice is provided at this stage so that the opening
probability check may be performed or bypassed. If bypassed,
the output will be true to open a window. If performed,
probability will be determined from a schedule.
Step 5: Perform opening probability check
The opening probability (OP) value is determined from a
schedule.
OP = Schedule value or specific function
If the probability value is greater than a random number,
the output is true.
OP > random number (random number is between 0 and
1)
The control logic of closing probability is described as
follows.
Step 1: Open elapsed time check
This check requires that open elapsed time is longer than
the minimum opening time.
Open time > minimum open time
If the time duration is not long enough, the output is
false and the window remains open. Otherwise, Step 2 will be
performed.
Step 2: Select by-pass or closing probability check
A choice is provided at this step so that the closing
probability check may be performed or bypassed. If bypassed,
the output will be true to close a window. If performed, the
closing probability will be calculated. The closing
probability (CP) value is given from a schedule.
CP = Schedule value or specific function
If the closing probability check is performed and the
closing probability is greater than a random number, the
output is true.
CP > random number (random number is between 0 and
1)
Pressure control is achieved by varying either zone exhaust
fan flow rate in a controlled zone or relief air flow rate in
an AirLoop. It requires an AirLoop with an OA mixer to reach
the pressure setpoint by adjusting a relief air flow, or an OA
mixer and an exhaust fan in a controlled zone to reach the
pressure setpoint by adjusting an exhaust fan flow rate. The
calculation logic is shown below:
1. The AirflowNetwork model will run twice with zero and
maximum flow rates for either the controlled zone exhaust fan
or relief air flow rate. The controlled zone pressures are the
return values.
In general, the zero flow rate of either exhaust fan or
relief node will generate the maximum zone pressure, while the
maximum flow rate of either exhaust fan or relief node will
produce the minimum zone pressure.
2. If the setpoint pressure is between the maximum zone
pressure caused by zero exhaust fan or relief node flow rate
and the minimum zone pressure caused by maximum exhaust fan
flow rate or outdoor air flow rate, then the AirflowNetwork
model will use Regula Falsi to find a solution with calculated
zone exhaust fan flow rate or relief node flow rate.
Otherwise, the pressure setpoint will not be met.
3. If both maximum and minimum pressures are higher than
the setpoint, the maximum exhaust or outdoor flow rate will be
forced.
4. If both maximum and minimum pressures are lower than the
setpoint, then zero flow rate will be forced.
Atkins, R. E., J. A. Peterka, and J. E. Cermak. 1979.
“Averaged pressure coefficients for rectangular buildings,”
Wind Engineering, Proceedings of the Fifth International
Conference 7:369-80, Fort Collins, CO. Pergamon Press, NY.
Awbi, H. B. 2003. Ventilation of Buildings (2nd
Edition). Routledge.
Bolmqvist, C. and M. Sandberg, 2004, “Air Movements through
Horizontal Openings in Buildings – A Model Study,”
International Journal of Ventilation, Vol. 3, No. 1,
pp. 1-9.
COMIS Fundamentals. 1990. Edited by Helmut E. Feustel and
Alison Rayner-Hooson, LBL-28560, Lawrence Berkeley Laboratory,
Berkeley, California.
Conte, S. D. and C de Boor. 1972.Elementary Numerical
Analysis: an Algorithmic Approach, McGraw-Hill.
Cooper, L., 1989, “Calculation of the Flow Through a
Horizontal Ceiling/Floor Vent,” NISTIR 89-4052, National
Institute of Standards and Technology, Gaithersburg,
Maryland.
Dols, W. S. and G. N. Walton. 2002. “CONTAMW 2.0 User
Manual,” NISTIR 6921, National Institute of Standards and
Technology, Gaithersburg , Maryland.
Holmes, J. D. 1986. Wind Loads on low-rise buildings: The
structural and environmental effects of wind on buildings and
structures, Chapter 12, Faculty of Engineering, Monash
University, Melbourne, Australia.
Linden, P., D. Banks, N. Daish, M. Fountain, G. Gross, A.
Honnekeri, M. Pigman, R. Thomas, K. Adams, S. Brunswick, S.
Dutton, R. Gerard, P. Haves, M. Hovanec, P. Switenki, Y. Zhai,
E. Arens, G. Carrilho da Graça, W. Fisk, F. Gillan, M. Hill,
T. Lawton, G. Szakats, and H. Zhang. 2016. “Natural
Ventilation for Energy Savings in California Commercial
Buildings,” CEC-500-2016-039, California Energy
Commission.
Marais, J. M. and C. Teichmann, “Window Simulation Methods
Required for Manual Window
Ventilated Buildings,” Fifth German-Austrian IBPSA Conference,
September 22-24, 2014, RWTH Aachen University, Germany.
Swami, M. V. and S. Chandra. 1988. Correlations for
pressure distribution on buildings and calculation of
natural-ventilation airflow, ASHRAE Transactions 94(1988) (Pt
1), pp. 243-266.
Swami, M. V., L. Gu, and V. Vasanth. 1992. “Integration of
Radon and Energy Models for Building,” FSEC-CR-553-92, Florida
Solar Energy Center, Cocoa, Florida.
Tan, Q. and Y. Jaluria, 1992, “Flow through Horizontal
Vents as Related to Compartment Fire Environments,”
NIST-GCR-92-607, National Institute of Standards and
Technology, Gaithersburg, Maryland.
Walton, G. N. 1989. “AIRNET – A Computer Program for Building
Airflow Network Modeling,” NISTIR 89-4072, National Institute
of Standards and Technology, Gaithersburg, Maryland.
Walton, G. N. and W. S. Dols. 2003. “CONTAM 2.1
Supplemental User Guide and Program Documentation,” NISTIR
7049, National Institute of Standards and Technology,
Gaithersburg, Maryland.
Warren, P.R. and Parkins, L.M. (1985) Single-sided
ventilation through open windows. In Proceedings of the
ASHRAE/DOE/BTECC Conference on Thermal Performance of the
Exterior Envelopes of Buildings III, December 2-5, 1985,
Clearwater Beach, Florida, pp. 209-228.
AirflowNetwork Model[LINK]
Overview[LINK]
The AirflowNetwork model provides the ability to simulate the performance of an air distribution system, including supply and return leaks, and calculate multizone airflows driven by outdoor wind and forced air during HVAC system operation. The pressure and airflow model described here was developed based on AIRNET (Walton 1989). This detailed model is used to simulate thermal conduction and air leakage losses for constant volume air distribution systems (e.g., in residential or light commercial buildings). The multizone airflow calculations are performed at the HVAC system time step which, among other benefits, allows for modeling hybrid ventilation systems.
Model Description[LINK]
The input object AirflowNetwork:SimulationControl provides access to the airflow network method, which consists of a set of nodes connected by airflow components through linkages. The objects AirflowNetwork:Multizone:Zone, AirflowNetwork:Multizone:ExternalNode, and AirflowNetwork:Distribution:Node represent airflow nodes. The objects AirflowNetwork:Multizone:Surface and AirflowNetwork:Distribution:Linkage represent airflow linkages. The other objects with a relationship between pressure and airflow represent airflow components.
The AirflowNetwork model consists of three sequential steps:
Pressure and airflow calculations
Node temperature and humidity calculations
Sensible and latent load calculations
The pressure and airflow calculations determine pressure at each node and airflow through each linkage given wind pressures and forced airflows. Based on the airflow calculated for each linkage, the model then calculates node temperatures and humidity ratios given zone air temperatures and zone humidity ratios. Using these node temperatures and humidity ratios, the sensible and latent loads from duct system conduction and leakage are summed for each zone. The sensible and latent loads obtained in this step are then used in the zone energy balance equations to predict HVAC system loads and to calculate the final zone air temperatures, humidity ratios, and pressures.
The present AirflowNetwork model may only be applied to a single heating and cooling system that uses a single air distribution system (a single AirLoopHVAC object). The model excludes the impact of the air and duct system thermal capacitance.
Pressure and Airflow Calculations[LINK]
The EnergyPlus airflow network consists of a set of nodes linked by airflow components. Therefore, it is a simplified airflow model, compared to detailed models such as those used in computational fluid dynamics (CFD) models. The node variable is pressure and the linkage variable is airflow rate. A brief description is presented below. A detailed description of the airflow network model may be found in the work of Walton (1989), Dols and Walton (2002), and Walton and Dols (2003).
Initialization[LINK]
Newton’s method is used to solve for node air pressures and it requires an initial set of values for the node pressures. There are two initialization methods available. The first is linear initialization and equivalent to Initialization flag = 0. These initial values may be obtained by including in each airflow component a linear approximation relating airflow to pressure drop:
\[\dot{m}_{i} = C_{i}\rho\frac{\Delta P_i}{\mu}\]
where:
This initialization handles stack effects very well and tends to establish the proper direction for the airflows. The linear approximation is provided by the laminar regime.
The second initialization method assumes the initial pressures are zero and uses Newton’s method directly.
Convergence criteria[LINK]
Conservation of air mass flow rate at each linkage provides the convergence criterion. When the sum of mass flow rates in all the linkages approaches zero within the convergence tolerance, the solution has converged. The solution is assumed to have converged when the sum is less than the convergence value, in order to reduce the number of iterations and obtain sufficient accuracy. There are two convergence criteria used in the AirflowNetwork model: Relative airflow convergence tolerance and Absolute airflow convergence tolerance.
The relative airflow tolerance is equivalent to the ratio of the absolute value of the sum of all network airflows to the sum of the network airflow magnitudes. The absolute airflow tolerance is the summation of the absolute value of all network airflows. The solution has converged when both of these convergence criteria have been met.
Linkage models[LINK]
A linkage used in the AirflowNetwork model has two nodes, inlet and outlet, and is linked by a component which has a relationship between airflow and pressure. The pressure difference across each component in a linkage is assumed to be governed by Bernoulli’s equation:
\[\Delta P = \left( {P_n + \frac{{\rho V_n^2}}{2}} \right) - \left( {P_m + \frac{{\rho V_m^2}}{2}} \right) + \rho g\left( {z_n - z_m} \right)\]
where:
By rearranging terms and adding wind pressure impacts, the above equation may be rewritten in the format used by the airflow network model:
\[\Delta P = {P_n} - {P_m} + {P_S} + {P_W}\]
where:
The Input Output Reference provides the relationship between airflow and pressure for the most of the components (Ref.AirflowNetwork Model). The relationship between airflow and pressure for the AirflowNetwork:Multizone:Component:DetailedOpening, AirflowNetwork:Multizone:Component:SimpleOpening, and AirflowNetwork:Multizone:Component:HorizontalOpening objects are provided in detail in this reference.
The schematic drawing of a possible air flow pattern through a detailed vertical opening (AirflowNetwork:Multizone:Component:DetailedOpening) is shown in Figure. The equations used below are extracted from the COMIS Fundamentals manual (1990).
The air density is assumed to be a linear function of height:
\[{\rho_i}(z) = {\rho_{0i}} + {b_i}z\]
The pressure difference is assumed to be linear and simulate the effect of turbulence:
\[\Delta P_t = P_{t0} + b_t z\]
The reference pressures on each side are given at the bottom of the opening. By assuming the Bernoulli hypothesis on both sides, the pressure difference can be defined at any level of z as:
\[{P_1}(z) - {P_2}(z) = ({P_{01}} - {P_{02}}) - g\left[ {({\rho_{01}}z + {b_1}{z^2}/2) - ({\rho_{02}}z + {b_2}{z^2}/2)} \right] + ({P_{t0}} + {b_t}z)\]
The velocity at any level z is given by
\[v(z) = \sqrt {2\frac{{{P_1}(z) - {P_2}(z)}}{\rho }}\]
The locations of the two possible neutral planes are given by an equilibrium in pressure which leads to a zero velocity point. By assuming the left terms in the equation above to be zero, one may have:
\[g({b_1} - {b_2}){z^2}/2 + \left[ {g({\rho_{01}} - {\rho_{02}}) - {b_t}} \right]z + ( - {P_{01}} + {P_{02}} - {P_{t0}}) = 0\]
This equation above can have two, one, or zero real solutions. The zero solution represents a one-way flow through the opening and may be expressed in the following equation:
\[\dot m = {C_d}\theta \int\limits_{z = 0}^{z = H} {\rho \nu (z)Wdz}\]
The one real solution represents two-way (bi-directional) flow, which may be written in the following equations.
\[{\dot m_{0,z1}} = {C_d}\theta \int\limits_{z = 0}^{z = z1} {\rho \nu (z)Wdz}\]
\[{\dot m_{z1,H}} = {C_d}\theta \int\limits_{z = z1}^{z = H} {\rho \nu (z)Wdz}\]
The two real solutions represent three-way flow, which may be written in the following equations.
\[{\dot m_{z2,H}} = {C_d}\theta \int\limits_{z = z2}^{z = H} {\rho \nu (z)Wdz}\]
\[{\dot m_{z1,z2}} = {C_d}\theta \int\limits_{z = z1}^{z = z2} {\rho \nu (z)Wdz}\]
\[{\dot m_{z2,H}} = {C_d}\theta \int\limits_{z = z2}^{z = H} {\rho \nu (z)Wdz}\]
where:
The discharge coefficient, opening width, opening height, and start height factor are modulated based on opening factors. A detailed description of opening factor calculations may be found in the Input Output Reference (Ref. AirflowNetwork:Multizone:Zone, AirflowNetwork:Multizone:Surface, and
AirflowNetwork:Multizone:Component:DetailedOpening).
The above calculation procedure is used for a normal rectangular window. For a horizontally pivoted rectangular window, the calculation procedure is slightly different. A schematic drawing of a horizontally-pivoted window is shown in Figure.
The opening angle α (0-90°) is linearly proportional to the window opening factor (0-1.0). An opening factor of 1.0 is equal to an opening angle of 90°. The heights in the pivoted area are expressed as:
\[h2 = AxisHeight(1 - \cos (\alpha ))\]
\[h4 = AxisHeight + (WindowHeight - AxisHeight)\cos (\alpha )\]
When z < h2 or z > h4, where z is the distance from the bottom of the window, the integration procedure is the same as the procedure for a normal rectangular window. When h2<z<h4, the window width W in the above equations is modified as:
\[W_{pivot} = \sqrt{\frac{1}{{\frac{1}{{{W^2}}} + \frac{1}{{{{(2(AxisHeight - z)\tan (\alpha ))}^2}}}}}}\]
The mass flow rate in the pivoted area becomes:
\[{\dot m_{pivot}} = {C_d}\theta \int\limits_{z = h2}^{z = h4} {\rho \nu (z){W_{pivot}}dz}\]
It should be pointed out that the discharge coefficient is modulated based on opening factors, while opening width, opening height, and start height factor do not apply for a horizontally-pivoted window. The actual window width and height are used to calculate airflows for a horizontally-pivoted window.
The schematic drawing of air flow patterns through a simple vertical opening (AirflowNetwork:Multizone:Component:SimpleOpening) is shown in Figure. The equations used below are available from Walton (1989).
The air density for each node is assumed to be constant. The hydrostatic equation is used to relate pressures at various heights for each node:
\[Pn\left( y \right) = {P_{0n}} - {\rho_n}gy\]
\[{P_m}(y) = {P_{0m}} - {\rho_m}gy\]
where:
It is assumed that the velocity of the airflow as a function of height is given by the orifice equation (Brown and Solvason 1962):
\[v(y) = {C_d}\sqrt {2\frac{{{P_n}(y) - {P_m}(y)}}{\rho }}\]
where:
The neutral height, Y, where the velocity of the air is zero, may be calculated in the following equation:
\[Y = \frac{{{P_{on}} - {P_{0m}}}}{{g({\rho_n} - {\rho_m})}}\,\,\,\,\,\,\,\,or\,\,\,\,\,\,\,\frac{{{P_{om}} - {P_{0n}}}}{{g({\rho_m} - {\rho_n})}}\]
When the neutral plane is within the opening (first pattern in Figure), two-way (bi-directional) flows occur. The total flow through a large opening is the sum of both flows.
\[{\dot m_{0,Y}} = {C_d}\theta \int\limits_{y = 0}^{y = Y} {\rho \nu (y)Wdy}\]
\[{\dot m_{Y,H}} = {C_d}\theta \int\limits_{y = Y}^{y = H} {\rho \nu (y)Wdy}\]
When the neutral plane is below or above the large opening (second and third pattern in Figure), one-way flow occurs.
\[{\dot m_{}} = {C_d}\theta \int\limits_{y = 0}^{y = H} {\rho \nu (y)Wdy}\]
The opening width is modulated based on opening factors. A detailed description of opening factor calculations may be found in the Input Output Reference (Ref. AirflowNetwork:Multizone:Zone, AirflowNetwork:Multizone:Surface, and AirflowNetwork:Multizone:Component:DetailedOpening).
The above two objects are used to simulate airflows across large vertical openings. The simple opening component (AirflowNetwork:Multizone:Component:SimpleOpening) assumes the pressure difference across the opening is a function of height varied from opening bottom to top, so that two-way flow may be obtained if appropriate (Walton 1989). The Detailed Opening component (AirflowNetwork:Multizone:Component:DetailedOpening) assumes both the pressure difference across the opening and air density are a function of height, so that three-way flow may be obtained (COMIS 1990). If these opening models would be used for horizontal openings, the pressure difference across the opening and air density remain constant, so that only one-way flow is possible using the detailed and simple opening components which are meant for vertical or near-vertical openings. In reality, there are two-way flows (air recirculation) across a large horizontal opening caused by buoyancy due to temperature and pressure difference and forced flow driven by air pressure difference only. Therefore, a horizontal opening component (AirflowNetwork:Multizone:Component:HorizontalOpening) is available to simulate airflows across large horizontal openings with the possibility of two-way flow by combining forced and buoyancy airflows together.
The model for horizontal openings consists of forced airflow, buoyancy airflow, purge pressure and sloping plane. The model is mainly from a NIST report presented by Cooper (1989). The sloping plane (Bolmqvist and Sandberg 2004) portion of the model was added to allow for staircase simulations.
For simplicity, a two zone building (upper and lower zones) connected by a large horizontal opening is used to describe the model, as shown in Figure. Forced and buoyancy airflows are described separately below.
Forced airflows[LINK]
The air mass flow rate is determined by the pressure difference across the opening. The relationship between pressure and airflow is the same as AIRNET for a component (see AirflowNetwork:Multizone:Component:SimpleOpening description above). Since the height of the opening is constant, the forced airflow is unidirectional. A positive value for pressure difference indicates flow direction is from the lower zone to the upper zone across the opening, while a negative value represents flow in the opposite direction. The following description addresses forced air mass flow rates and partial derivatives for three possible scenarios of pressure difference:
Scenario 1 \[\begin{gathered} P_L = P_U \\ \dot{m}_U = \dot{m}_L = 0\end{gathered}\]
where:
Scenario 2 \[\begin{gathered} P_L > P_U \dot{m}_U = 0\end{gathered}\]
\[\dot{m}_L = \rho_L A C_d \left( {\frac{2\Delta P}{\rho_{ave}}} \right)^{0.5}\]
\[\frac{\partial \dot{m}_L}{\partial {P_L}} = \rho_L A C_d \left( \frac{1}{2\Delta P \rho_{ave}} \right)^{0.5}\]
where:
Scenario 3 \[\begin{gathered} P_L < P_U \dot{m}_L = 0\end{gathered}\]
\[\dot{m}_U = - {\rho_U}A{C_d}{\left( {\frac{{2\left| {\Delta P} \right|}}{{{\rho_{ave}}}}} \right)^{0.5}}\]
\[\frac{{\partial \dot{m}_U}}{{\partial {P_L}}} = {\rho_U}A{C_d}{\left( {\frac{1}{{2\left| {\Delta P} \right|{\rho_{ave}}}}} \right)^{0.5}}\]
where:
Buoyancy airflows[LINK]
Buoyancy flow only occurs when the air density in the upper zone is greater than the air density in the lower zone. The flow is bi-directional and the amount of upper flow is equal to the lower flow across the opening. The following discussion assumes the air density in the upper zone is greater than the air density in the lower zone. Otherwise, the buoyancy flow rate is equal to zero. It is also assumed that the maximum buoyancy flow occurs when the pressure difference across the opening due to forced airflows is zero. The maximum buoyancy flow may be expressed as a part of Cooper’s model:
\[\dot{m}_{buo,\max} = {\rho_{ave}}\cdot0.055{\left( {\frac{{g\left| {\Delta \rho } \right|D_{_H}^5}}{{{\rho_{ave}}}}} \right)^{0.5}}\]
where:
Combined airflows[LINK]
When forced and buoyancy flows co-exist, it is possible to have either unidirectional or bi-directional flows. For example, when the upward force due to pressure difference is greater than the buoyancy force (downward), unidirectional flow occurs. Bi-directional flow only occurs when the upward imposed force is less than the buoyancy force. The critical pressure between unidirectional and bi-directional flows is called the purge pressure (Tan and Jaluria 1992). The purge pressure is a function of opening geometry and the buoyancy force (ΔP/(gΔρD\(_{H}\))) and may be expressed as (Cooper 1998):
\[\Delta {P_{Flood}} = \left| {C_{Shape}^2\frac{{g\Delta \rho D_H^5}}{{2{A^2}}}} \right|\]
where:
\[C_{Shape} = \left\{ \begin{array}{l}0.754\;\;\;{\rm{for}}\;{\rm{a}}\;{\rm{circle}}\;{\rm{opening}}\\0.942(w/D)\;{\rm{for}}\;{\rm{a}}\;{\rm{rectangle}}\;{\rm{opening}}\end{array} \right\}\]
where:
As mentioned above, when the air pressure difference between two zones is zero there is the maximum bi-directional flow due to the buoyancy force. When the pressure difference increases from 0 and is less than \(\Delta P_{Flood}\), there is some bi-directional flow across the opening, but less than the maximum flow. If the pressure difference keeps increasing and exceeds \(\Delta P_{Flood}\), there is no bi-directional flow. Cooper’s model assumes the buoyancy flow varies linearly with pressure difference.
\[\dot{m}_{buo} = \left\{ \begin{array}{l}{\dot{m}_{buo,\max }}\cdot\left( {1 - \frac{{\left| {\Delta P} \right|}}{{\left| {\Delta {P_{Flood}}} \right|}}} \right)\;\,\,\mbox{If}\;\Delta \rho > 0\;\mbox{and}\;\frac{{\left| {\Delta P} \right|}}{{\left| {\Delta {P_{Flood}}} \right|}} < 1\\0\;\,\,\,\mbox{Otherwise}\end{array} \right\}\]
The total air flow across the opening is based on superposition of the forced and buoyancy flows, and may be expressed for three different pressure difference scenarios as follows:
a. \(P_L = P_U\)
\[\dot{m}_U = \dot{m}_{buo}\]
\[\dot{m}_L = \dot{m}_{buo}\]
\[\frac{\partial \dot{m}_L}{\partial P_L} = 0\]
b. \(P_L > P_U\)
\[\dot{m}_U = \dot{m}_{buo}\]
\[\dot{m}_L = \rho_L A C_d \left( \frac{2 \Delta P}{\rho_{ave}} \right)^{0.5} + \dot{m}_{buo}\]
\[\frac{\partial \dot{m}_L}{\partial P_L} = \rho_L A C_d \left( \frac{1}{2\Delta P \rho_{ave}} \right )^{0.5} - \frac{\dot{m}_{buo,max}}{|\Delta P_{Flood}|}\]
where:
c. \(P_L < P_U\)
\[\dot{m}_L = \dot{m}_{buo}\]
\[\dot{m}_U = - \rho_U A C_d \left( \frac{2\left| \Delta P \right|}{\rho_{ave}} \right)^{0.5} + \dot{m}_{buo}\]
\[\frac{\partial \dot{m}_U}{\partial P_L} = \rho_U A C_d \left( \frac{1}{2 \left| \Delta P \right| \rho_{ave}} \right)^{0.5} + \frac{\dot{m}_{buo,max}}{\left| \Delta P_{Flood} \right|}\]
Sloping Plane[LINK]
When a staircase is introduced as shown in Figure, the effective opening area will be used to replace A (opening area) in the above equations. The effective area may be estimated as (Bolmqvist and Sandberg 2004):
\[A_{eff} = A\sin \alpha (1 + \cos \alpha )\]
where:
Note: the hydraulic diameter calculation is based on the effective opening area, while the opening depth remains the same.
Figure demonstrates possible forced and buoyancy flow rates at different ratios of pressure difference to purging pressure across a horizontal opening when the upper zone air density is greater than the lower zone air density. The pressure difference is the lower zone pressure minus the upper zone pressure. Otherwise, the buoyancy flow is zero. In addition, when the absolute ratio is above 1, the buoyancy flow is also zero. The following table provides a brief description for the legend listed in Figure.
Wind pressure calculations[LINK]
The wind pressure is determined by Bernoulli’s equation, assuming no height change or pressure losses:
\[p_w = C_p \rho \frac{V_{ref}^2}{2}\]
where:
\(V_{ref}\) may be expressed as (Ref, Local Wind Speed Calculations)
\[V_{ref} = V_{met} \left( \frac{\delta_{met}}{z_{met}} \right)^{\alpha_{met}}\left( \frac{z}{\delta} \right)^\alpha\]
\(C_p\) is a function of location on the building envelope and wind direction. When Wind Pressure Coefficient Type = “INPUT”, the \(C_p\) values are explicitly defined in the input for AirflowNetwork:Multizone:Wind Pressure Coefficient Values. When Wind Pressure Coefficient Type = “AVERAGE-SURFACE CALCULATION” and the building shape is rectangular, the program uses the following equations to calculate wind pressure coefficient (\(C_p\)) values for different wind directions. For a low rise building, the normalized surface pressure coefficient may be written as (Swami and Chandra 1988):
\[C_{p,n} = 0.6 \cdot \ln \left[ \begin{array}{l}1.248 - 0.703\sin (\alpha /2) - 1.175{\sin ^2}(\alpha ) + 0.131{\sin ^3}(2\alpha G)\\ + \,0.769\cos (\alpha /2) + 0.07{G^2}{\sin ^2}(\alpha /2) + 0.717{\cos ^2}(\alpha /2)\end{array} \right]\]
where:
For walls of a high rise building, a two-dimensional array of surface-averaged wind pressure coefficients is generated based on wind incident angle and side ratio. The wind pressure coefficients are provided in 2001 ASHRAE Fundamentals Handbook, p. 16.5, Fig. 7, “Surface Averaged Wall Pressure Coefficients for Tall Buildings”. The original work was performed by Atkins et al. (1979). The incident angle has an increment of 30 degrees. The side ratio values are 0.25, 1.0, and 4.0. For a given incident angle and building aspect ratio, the program uses linear interpolation to calculate the corresponding wind pressure coefficient \(C_{p,n}\).
For the roof of a high rise building, a two-dimensional array of surface-averaged wind pressure coefficients is also generated based on wind incident angle and side ratio. The wind pressure coefficients are provided in 2001 ASHRAE Fundamentals Handbook, p. 16.6, Fig. 9, “Surface Averaged Roof Pressure Coefficients for Tall Buildings”. The original work was performed by Holmes (1986). The incident angle has an increment of 30 degrees. The side ratio values are 0.25, 1.0, and 4.0. At a given wind incident angle and building aspect ratio, the program uses linear interpolation to calculate the corresponding wind pressure coefficient \(C_{p,n}\).
The wind surface pressure at the given incident angle can be calculated by combining the above two equations:
\[p_{w,n} = C_{p,n}\rho \frac{V_{ref}^2}{2}\]
Solution method[LINK]
Based on the relationship between airflow rate and pressure drop for each component, a system of equations for all components can be assembled together in an n x n square matrix, where n is the number of nodes. Newton’s method is used to iteratively solve for the air pressure at each node. A new estimated vector for all node pressures, {P}, is computed from the current estimated vector of node pressures, {P}, by:
\[{\left\{ P \right\}^*} = \left\{ P \right\} - \left\{ C \right\}\]
where the correction vector, {C}, is computed by the matrix relationship:
\[\left[ J \right]\left\{ C \right\} = \left\{ B \right\}\]
{B} is a column vector with each component given by:
\[B_n = \sum_{i} \dot{m}_i\]
where \(n\) is the node number and \(i\) indicates all flow paths connecting node \(n\) to other nodes, and [J] is the square Jacobian matrix whose elements are given by:
\[J_{n,m} = \sum_{i} \frac{\partial \dot{m}}{\partial P_m}\]
Convergence acceleration[LINK]
The convergence tolerance is used to check the sum of the mass flow rates by applying mass conservation. The convergence acceleration equation shown below is used to correct the node pressures to more rapidly obtain a solution. By assuming a constant ratio of correction values from one iteration to the next, the following method is applied:
\[{P_n}^* = P_n - C_n/(1 - r)\]
where:
This method is similar to a Steffensen iteration (Conte and de Boor 1972) which is used as a fixed-point iteration method for individual nonlinear equations.
The iteration correction method presented in the above equation gives a variable factor. When the solution is close to convergence, the solution method converges quadratically. By limiting cases where the value of r is less than some value, such as -0.5, the solution will not interfere with the rapid convergence. It has not been proven that the convergence acceleration equation will always lead to convergence, but it can be shown that it will not prevent convergence. Newton’s method converges when the estimated solution values are within some distance, called the radius of convergence, or the correct solution. Applying the convergence acceleration equation when -1 < r <0, will cause a smaller correction than Newton’s method, which therefore, can not force the iterations outside the radius of convergence. When r<-1, the solution diverges in an oscillatory fashion. When r>1, the solution also diverges, but in a nonoscillatory manner. For 0<r<1, the solution is approached from one direction. In all three cases, the convergence acceleration equation applies as long as r is truly constant over several iterations. However, for the last case, this involves a true extrapolation of correction factor which is very sensitive to the accuracy of r. This is most extreme for the case of r = 1, which would cause an infinite correction.
Node Temperature Calculations[LINK]
General[LINK]
A brief description of the air node temperature calculation is given below. A detailed description can be found in the work of Swami et al. (1992). The following equation is used to calculate temperature distribution across a duct element at the given airflow rate and inlet air temperature:
\[\dot{m} C_p \frac{dT}{dx} = UP(T_\infty - T)\]
where:
\[U = \frac{1}{{\frac{1}{{{h_i}}} + \frac{1}{{{h_o}}} + \sum {\frac{{{t_j}}}{{{k_j}}}} }}\]
The outlet air temperature at the end of the duct (x = L) is:
\[T_o = T_\infty + (T_i - T_\infty) \cdot \exp \left(- \frac{UA}{\dot{m} C_p} \right)\]
where:
The heat transfer by convection to ambient, \(Q\), is:
\[Q = \dot{m} {C_p}(T_\infty- T_i)\left[1 - \exp \left( - \frac{UA}{\dot{m} C_p} \right) \right]\]
The outlet air temperature can be calculated using the above equation at the given inlet air temperature. Since the inlet temperature at one linkage is the outlet temperature for the connected linkage, the outlet air temperatures at all nodes are solved simultaneously. A square linear system assembled by the AirflowNetwork model is expressed below:
\[\{ M\} [T] = [B]\]
where:
The zone air temperatures and primary air loop component (fan and coils) outlet conditions are used as prescribed conditions in the AirflowNetwork model. In addition, the temperature difference across zone loop components (terminal units) is held constant during the calculations. For example, thermal zone temperatures calculated during the previous system time step are used as prescribed temperatures when calculating all other node temperatures. The zone air temperature is assumed constant (prescribed) throughout the AirflowNetwork iterative solution. The fan and coil outlet air temperatures, and terminal unit temperature differences are assumed constant within an AirflowNetwork iteration. The sensible heat gains calculated during the AirflowNetwork solution are then used to predict a new zone air temperature.
Duct Radiation[LINK]
The duct-surface user-defined view factors object defines the view factor from the duct to the zone surfaces. Because the view factors, duct surface area, and temperatures are known, the heat gain to the duct can be directly calculated and applied to the duct air heat balance to determine the outlet temperature. The duct heat gain is then treated as a direct heat loss from each participating surface. Once the heat loss to the duct for each surface is calculated, the surface temperatures are adjusted to maintain the surface energy balance.
Radiation is treated as point loads heat source/sink on the zone surfaces and the duct. These point loads will be added or subtracted using the same implementation strategy as the convective load for the ducts to the zone air. The radiative rate of energy transfer between the duct (d) and a given surface (s) for two grey surfaces can be written as shown below.
\[\dot{Q}_{d\rightarrow s} = \frac{\sigma (T^4_d - T^4_s)}{\frac{1 - \epsilon_d}{f_e A_d \epsilon_d} + \frac{1}{f_e A_d F_{d\rightarrow s}}+\frac{1 - \epsilon_s}{A_s \epsilon_s}}\]
where:
Node Humidity Ratio Calculations[LINK]
A brief description of the air node humidity ratio calculation is given below. A detailed description can found in the work of Swami et al. (1992). The following equation is used to calculate humidity ratio distribution across a duct element at the given airflow rate and inlet air humidity ratio:
\[\dot{m} \frac{dW}{dx} = U_m P(W_\infty - W)\]
where:
\[U_m = \frac{1}{\frac{1}{h_{m,i}} + \frac{1}{h_{m,o}} + \sum {\frac{t_j}{D_j}} }\]
The outlet air humidity ratio at the end of the duct (x = L) is:
\[W_o = W_\infty + (W_i - W_\infty) \cdot \exp \left(- \frac{U_m A}{\dot{m}} \right)\]
where:
The moisture transfer by convection to ambient, Q\(_{m}\), is
\[Q_m = \dot{m} \cdot (W_\infty - W_i)\left[ 1 - \exp \left(- \frac{U_m A}{\dot{m}} \right) \right]\]
The outlet air humidity ratio can be calculated using the above equation at the given inlet air humidity ratio. Since the inlet humidity ratio at one linkage is the outlet humidity ratio for the connected linkage, the outlet air humidity ratio at all nodes are solved simultaneously. A square linear system assembled by the AirflowNetwork model is expressed below:
\[\{M_m\} [W] = [B_m]\]
where:
The zone air humidity ratios and primary air loop component (fan and coils) outlet conditions are used as prescribed conditions in the AirflowNetwork model. For example, thermal zone humidity ratios calculated during the previous system time step are used as prescribed humidity ratios when calculating all other node humidity ratios. The zone air humidity ratio is assumed constant (prescribed) throughout the AirflowNetwork iterative solution. The coil outlet air humidity ratio is assumed constant within an AirflowNetwork iteration. The latent heat gains calculated during the AirflowNetwork solution are then used to predict a new zone air humidity ratio.
Sensible and Latent Load Calculations[LINK]
The zone sensible and latent loads calculated in the AirflowNetwork model consist of multizone, duct conduction and leakage. In addition, the impact of infiltration and mixing is accounted for in this calculation. The multizone load only includes incoming airflows from outside (infiltration) and other adjacent zones (mixing) with and without forced-air fan operation. It is divided into two terms: variable and constant. The constant term is the sum of the mass flow rate multiplied by the specific heat for both infiltration and mixing. The variable term includes the impact of zone and outdoor air temperature. Each of these terms is used in the zone energy balance equation. The sensible load items from the multizone load calculations may be written as follows:
\[MCP_{airflow} = \dot{m}_{inf} {C_p} + \sum \left( {\dot{m}_{mix} C_p} \right)\]
\[MCPT_{airflow} = \dot{m}_{inf} C_p T_{amb} + \sum \left( \dot{m}_{mix} C_p T_{zone} \right)\]
where:
The latent load items from multizone load calculations may be written as follows:
\[M_{airflow} = \dot{m}_{inf} + \sum \dot{m}_{mix}\]
\[MW_{airflow} = \dot{m}_{inf} W_{amb} + \sum \dot{m}_{mix} W_{zone}\]
where:
The air distribution system (ADS) loads due to duct conduction and leakage depend on the air distribution system component (e.g., duct) location. The air distribution system sensible and latent loads are calculated for each zone as follows:
\[Q_{ADS,i} = \sum_{j} Q_{cond(i,j)} + \sum_{j} Q_{leak(i,j)}\]
\[Q_{ADS,m,i} = \sum_{j} Q_{cond,m(i,j)} + \sum_{j} Q_{leak,m(i,j)}\]
where:
Impacts of Supply Air Constant Volume Fan Control on Load: Cycling vs. Continuous[LINK]
The AirflowNetwork model currently allows two types of constant volume fans: Fan:ConstantVolume and Fan:OnOff. The Fan:ConstantVolume object has only one type of supply air fan operation mode: continuous fan, cycling compressor (ContinuousFanWithCyclingCompressor). However, the Fan:OnOff has two types of supply air fan operation modes: cycling fan, cycling compressor (CyclingFanAndCompressor) or continuous fan, cycling compressor (ContinuousFanWithCyclingCompressor). The CyclingFanAndCompressor operation mode is frequently referred to as “AUTO fan”, where the compressor(s) and supply air fan operate in unison to meet the zone heating or cooling load, and cycle off together when the heating or cooling load has been met. The ContinuousFanWithCyclingCompressor operation mode is often referred to as “fan ON”, where the compressor(s) cycle on and off to meet the zone heating or cooling load but the supply air fan operates continuously regardless of compressor operation. The supply air fan operation mode is specified in an HVAC system object based on a given fan operation mode schedule (e.g., AirLoopHVAC:UnitaryHeatCool object).
The determination of the zone sensible and latent loads caused by multizone airflows and forced air distribution system operation is dependent on the supply air fan operation mode (see Sensible and Latent Load Calculations section above). The zone loads calculated by the AirflowNetwork model are added to zone sensible and latent balances in the ZonePredictorCorrector module to calculate zone air temperatures and humidity ratios (see Integration of the AirflowNetwork Model section below). For the case of continuous fan/cycling compressor, the zone loads during forced air distribution system operation are calculated with the system design air mass flow rate without modification, since the system air node conditions (temperature and humidity) reflect the average values for the time step considering the coil/fan on and off periods during the time step.
For the case of cycling fan/cycling compressor, where the forced air distribution system can operate for a portion of the simulation time step, the airflows are determined based on the air distribution system part-load ratio (ratio of the average air mass flow rate for the time step divided by the design air mass flow rate). The airflows for the AirflowNetwork:Distribution:Linkage objects are reported during the air distribution system on cycle, since no airflow is assumed during the system off cycle. The airflows for the AirflowNetwork:Multizone:Surface objects are weighted by the air distribution system part-load ratio. The zone loads are the sum of energy losses during both the air distribution system on and off cycle at each system time step. The energy losses when the air distribution system is on are calculated using the system “on” air flow rate multiplied by the air distribution system run time fraction. The energy losses when the air distribution system is off are obtained from the multizone airflow calculations (without forced air through the air distribution system) and these losses are multiplied by (1.0 - system run time fraction), assuming no airflows through the air distribution system when the fan is off. The formulas used to calculate airflows and zone loads are given below:
Airflow
Airflow = Airflow during ADS on cycle * ADS Part-load ratio + Airflow during ADS off cycle * (1.0 – ADS Part-load ratio)
where:
Zone load
System run time fraction = Maximum run time fraction of coils and fans in the air distribution system
Zone energy losses = Zone energy loss during ADS on cycle * System run time fraction + Zone energy loss during ADS off cycle * (1.0 - System run time fraction)
The calculation of loads due to multizone airflow, without forced air distribution system operation, is performed when the HVAC system is first simulated during a simulation time step (FirstHVACIteration = True). The calculation of loads due to air distribution system operation is performed on subsequent iterations within the same simulation time step when the mass flow rate at the supply air fan inlet is greater than 0.0 (and FirstHVACIteration = False).
Airflow Calculation Procedure using A Supply Variable Air Volume Fan[LINK]
The AirflowNetwork model currently also allows a variable air volume fan type as Fan:VariableVolume. The allowed terminal type is AirTerminal:SingleDuct:VAV:Reheat only. Other types of terminals will be added later.
In general, the supply fan air flow rate in a VAV central system is determined by a sum of terminal flow rates when the AirflowNetwork model is not applied. When the AirflowNetwork model is applied and the supply air fan flow rate is given, each terminal flow is determined by pressure resistance of each supply air pathway. It is possible that the delivered air flow rate from the pressure resistance at each terminal may be totally different from the desired flow rate determined by terminal units. Therefore, it is not easy to meet both requirements. The following compromised approach, including possible supply and return leaks in an air distribution system, is implemented.
Set up terminal airflows in the AirflowNetwork module based on the SimVAV subroutine in the HVACSingleDuctSystem module.
Require AirflowNetwork:Distribution:Component:LeakageRatio objects to define supply leaks, so that the values of the Effective Leakage Ratio field are used to decide the supply fan flow rates. The base of the ratio will be actual supply fan flow rate, instead of the maximum fan flow rate used in the constant volume fan systems.
Assign the supply fan airflow rate based on the sum of all terminal flow rates and all supply leak ratios until it reaches the maximum fan flow rate
\[\dot{m}_{fan} = \frac{\sum_i^n \dot{m}_{i,terminal}}{1 - \sum_j^k F_j}\]
where:
If the calculated supply fan flow rate is above the maximum limit of the supply fan flow rate, and the supply leak ratios remain the same, the supply fan flow rate is set to the maximum limit, and the terminal flow rates are reduced proportionally weighted by a ratio of the maximum supply fan flow rate by input to the calculated supply fan flow rate. Therefore, a sum of all terminal rates and all supply leak rates is equal to the maximum supply fan rate.
\[R = \frac{{{{\dot m}_{fan,max}}}}{{{{\dot m}_{fan,cal}}}}\]
\[{\dot m_{i,terminal,final}} = {\dot m_{i,terminal}}\cdot R\]
where:
Airflow Calculation Procedure using inputs of Intrazone nodes and linkages[LINK]
The inputs of both AirflowNetwork:IntraZone:Node and AirflowNetwork:IntraZone:Linkage objects are treated as normal model nodes and linkages. Therefore, the calculation procedures are the same as above.
Integration of the AirflowNetwork Model[LINK]
The loads calculated by the AirflowNetwork model are integrated into the EnergyPlus heat balance equation in a similar manner as described elsewhere in this document in the section “Basis for the Zone and System Integration”. The mass flow rate summations and sensible and latent loads described in the previous section are included in the calculation of zone temperature and humidity ratio.
The revised zone temperature update equation becomes:
\[T_z^t = \frac{\sum_{i=1}^{N_{sl}} \dot{Q}_i + \sum_{i-1}^{N_{surfaces}} h_i A_i T_{si} + MCPT_{airflow} + \dot{m}_{sys} C_p T_{supply} + QADS_z - \left( \frac{C_z}{\delta t} \right ) \left(-3 T_z^{t-\delta t} + \frac{3}{2} T_z^{t-2\delta t} -\frac{1}{3} T_z^{t-3\delta t} \right )}{\frac{11}{6} \frac{C_z}{\delta t} + \sum_{i=1}^{N_{surfaces}} h_i A + MCP_{airflow} + \dot{m}_{sys} C}\]
Where MCPT\(_{airflow}\) is the sum of mass flow rate multiplied by specific heat and temperature for infiltration and mixing, Q\(_{ADS,z}\) is the added total sensible load in the zone due to Air Distribution System losses, and MCP\(_{airflow}\) is the sum of mass flow rate multiplied by specific heat for infiltration and mixing as calculated in the AirflowNetwork model described above.
The revised coefficient (B) used in the zone humidity ratio calculation is shown below:
\[B = \sum kg_{mass,sched-loads} + MW_{airflow} + \dot{m}_{sys,in} W_{sys} + \sum_{i = 1}^{surf_s} A_i h_{mi} \rho_{air_z} W_{surf_{s_i}} + QADS_{m,z}\]
Where MW\(_{airflow}\) is the sum of mass flow rate multiplied by humidity ratio for infiltration and mixing and Q\(_{ADS,m,z\\}\)is the added total latent (moisture) load in the zone due to Air Distribution System losses from the AirflowNetwork model described above. This coefficient is used in the prediction of moisture as described in the section “Moisture Predictor-Corrector” found elsewhere in this document.
Model Output[LINK]
The available outputs from the AirflowNetwork model are described in the EnergyPlus Input Output Reference manual.
Single Sided Wind Pressure Coefficient Algorithm[LINK]
The approach in the single sided (SS) model is based on correlating the flow rate into the room through one or more openings with local flow conditions at the openings. These are in one façade of a rectangular building of width WB, depth DB and height HB. There is a vertical wind profile \(U(z)\) approaching the building, which generates a local flow \(U_L\) parallel to the façade (whose value depends on location, building geometry and wind direction).
Consider first the 2-aperture case, where air flows in through one opening of area \(A_\textup{in}\) and exits through another of equal area. Let us denote the flow rate of ambient air into the room by \(Q\), and define a dimensionless flow rate \(Q'\) by \[Q'=Q/(A_\textup{in} U_\textup{ref}),\] where \(U_\textup{ref}\) is a reference velocity taken as the undisturbed wind speed \(U(z_\textup{ref})\) at a reference height \(z_\textup{ref} = 10 \textup{m}\). There is a pressure difference \(\Delta p(t)\) between the two opening locations, with time-averaged mean value \(\overline{\Delta p}\) and standard deviation \(\sigma_{\Delta p}\).
There are three principal mechanisms determining the flow rate:
Mean pressure difference: a non-zero mean value for the difference in pressure at the two opening locations, \(\overline{\Delta p}\), drives a flow that scales as \(\overline{\Delta p}^{1/2}\).
Unsteady pressure difference: turbulence drives a fluctuating pressure difference between the two openings, resulting in a net addition of air from the outside. This is characterized by the standard deviation of the pressure difference signal, \(\sigma_{\Delta p}\) and the associated flow rate adds to that arising from \(\overline{\Delta p}\). It includes periodic Strouhal forcing (‘pumping’) at relevant wind angles. Note that this contribution is non-zero even when the mean pressure difference is zero.
Shear layer mechanism: when there is small or zero mean pressure difference between the two opening locations, the local flow parallel to the façade causes a mixing layer to grow over the length of the opening resulting in the incorporation of ambient air. This scales with \(U_L\).
Our model therefore views the flow rate as comprising contributions from each of these as appropriate, i.e. \[Q'=\left[a_p |\Delta c_p |+a_\sigma \sigma_{\Delta c_p} \right]^{1/2}+a_s U_L'\] where \(a_p\), \(a_\sigma\) and \(a_s\) are constants, the mean and fluctuating pressure difference terms have been written as pressure coefficients \[\Delta c_p=\frac{\overline{\Delta p}}{\frac{1}{2} \rho U_\textup{ref}^2},\] \[\sigma_{\Delta c_p}=\frac{\sigma_{\Delta p}}{\frac{1}{2} \rho U_\textup{ref}^2},\] \(\rho\) being the ambient air density, and \[U_L'=\frac{U_L}{U_\textup{ref}}.\]
The pressure-difference mechanisms \(\ref{ss-mean-mech}\) and \(\ref{ss-unsteady-mech}\) are dominant for the 2-opening case and \(\ref{ss-shear-mech}\) is negligible, while, in contrast, in the case of a single opening, shear is dominant. Hence we take \(a_s=0\) for 2-opening cases and \(a_p = a_\sigma = 0\) for one opening. Henceforth we focus on the 2-opening case, although a procedure is given at the end of the section for how to approximate a greater number by just two.
Figure shows the geometry of this case in plan view. The two openings are a distance \(s\) apart in a façade of width WB whose normal has azimuthal angle \(\varphi_n\). The wind azimuthal direction is \(\varphi_w\), so that its direction relative to the façade is \[\theta=\varphi_w-\varphi_n.\] In these definitions, \(\ang{0} \leq \varphi_n, \varphi_w \leq \ang{360}\), while \(|\theta| \leq \ang{180}\). Note that if \(\theta\) initially falls outside the range indicated it should be replaced by \(\operatorname{sgn}(\theta) \left[|\theta| - \ang{360}\right]\).
According to the above discussion, the flow rate is modeled as comprising two terms, arising, respectively, from the mean and fluctuating components of the pressure difference between the two aperture locations: \[\label{eqn:ss-flow-two-terms} Q'=\left(a_p |\Delta c_p |+a_\sigma \sigma_{\Delta c_p} \right)^{1/2}\]
There are two parts to deriving the detailed form of the model:
Express the mean and fluctuating pressures in terms of other physical quantities that are more readily accessible. EnergyPlus does not have the information on variations in pressure that is needed to compute \(\Delta c_p\) and \(\sigma_{\Delta c_p}\). Analysis of wind tunnel pressure data (Linden et al., 2013) allows for the derivation of simple expressions for these quantities in terms of the wind direction and opening separation \(s\).
Find the coefficients \(a_p\) and \(a_\sigma\). This is achieved here by analysis of ventilation rate data (Linden et al., 2013), and using linear regression on the data.
Estimation of pressure difference coefficients[LINK]
The analysis of pressure data carried out showed that the contributions to the right-hand side of Equation \(\ref{eqn:ss-flow-two-terms}\) can be written to first order as \[\Delta c_p=f(s',\theta)\] and \[\sigma_{\Delta c_p}=g(s',\theta)\] where the dimensionless separation \(s' = s/\textup{WB}\), \[f(s',\theta)=s'\cdot\Pi(\theta),\] and \[g(s',\theta)=\Sigma_0+s'\cdot\Sigma(\theta).\] That is, to a first approximation the pressure difference mean and standard deviation vary linearly with opening separation, each modulated by its own function of relative wind angle \(\theta\).
The formulae for the components are as follows. \[\label{eqn:ss-first-formula} \Pi(\theta) = \begin{cases} 0.44\operatorname{sgn}(\theta)\sin(2.67|\theta|),& |\theta| \leq \theta_0 \\ -0.69 \operatorname{sgn}(\theta)\sin(288-1.6|\theta|),& \theta_0\leq|\theta|\leq\ang{180}. \end{cases}\] \[\label{eqn:ss-second-formula} \theta_0 = \ang{67.5}\] \[\label{eqn:ss-third-formula} \Sigma(\theta) = 0.423 - 1.63\times 10^{-3}|\theta|\] \[\label{eqn:ss-last-formula} \Sigma_0=0.24\]
Figures \(\ref{fig:ss-figure-2-upper}\) and \(\ref{fig:ss-figure-2-lower}\) show an example of \(\Delta c_p\) and \(\sigma_{\Delta c_p}\) generated by Equations \(\ref{eqn:ss-first-formula}\) through \(\ref{eqn:ss-last-formula}\), respectively, compared with the data.
This completes item \(\ref{ss-item-the-first}\) above, i.e. the approximation of the two pressure coefficient terms in Equation \(\ref{eqn:ss-flow-two-terms}\) in terms of the dimensionless opening separation and the relative wind angle. There remains item \(\ref{ss-item-the-second}\), i.e. fitting the flow rate data to the formula-generated pressure parameters to determine the constants \(a_p\) and \(a_\sigma\). When this was carried out, the best fit was found to occur with \(a_p = 0.173\) and \(a_\sigma = 0.042\). Figure shows the comparison between the flow rate prediction and the experimental data.
Combining with the previous results we have \[\label{eqn:ss-combined-eqn} \frac{Q}{A_\text{in} U_\text{ref}}=\left(0.01+\left[0.173 |\Pi(\theta)|+0.042 \Sigma(\theta)\right]s'\right)^{1/2}\]
The flow Q is defined to be positive when opening #1 is the inlet and opening #2 is the outlet. Since \(\Delta p\) is defined as \(p_1-p_2\), this can occur when \(\Delta c_p > 0\), which in turn corresponds to certain relative wind angles, i.e. \[\begin{gathered} Q < 0\ \text{otherwise}\\ Q > 0\ \text{if}\ \ang{0} < \theta < \theta_0\ \text{or}\ \ang{-180} < \theta < -\theta_0 \end{gathered}\]
Note that the sense of \(Q\) is not necessarily well-defined for all such angles, e.g. when the unsteady contribution in Equation \(\ref{eqn:ss-flow-two-terms}\) is significant: nevertheless, we retain this definition for all angles.
Inversion of flow rate to equivalent pressure difference[LINK]
Finally, we invert the flow rate to obtain the equivalent pressure difference. The purpose of this procedure is to allow incorporation of the model into the network airflow part of EnergyPlus, which requires pressure coefficients to calculate the flow rate: in this way the model will become essentially transparent to the user. A nodal representation of the 2-aperture single-sided case is shown in Figure.
Here, 0 is the ambient, 1 is at the upstream outer surface, 2 is at the downstream outer surface, and R is the room.
Let the openings have areas \(A_1\) and \(A_2\), not necessarily equal, and a discharge coefficient \(C_d\), which is assumed equal, and let \(Q\) be the flow rate through the system. Then it can be shown that the pressure difference between the two openings, \(\Delta p_{12}\), is related to the flow rate by \[\label{eqn:ss-delta-p-1-2} \frac{\Delta p_{12}}{\frac{1}{2}\rho V^2} = \frac{1}{C_d^2}\left(\frac{Q/A_\text{eff}}{V}\right)^2\] where the effective area \(A_\text{eff}\) is defined by \[A_\text{eff}=\frac{A_1 A_2}{\left(A_1^2+A_2^2\right)^{1/2}}\] and \(V\) is a reference velocity. The left-hand side of Equation \(\ref{eqn:ss-delta-p-1-2}\) is a pressure coefficient, \(\Delta c_{p,12}^{E+}\), say, and our task is to express this in terms of the flow rate in Equation \(\ref{eqn:ss-combined-eqn}\) but using the definition of a pressure coefficient appropriate to EnergyPlus.
The first step is to re-write Equation \(\ref{eqn:ss-delta-p-1-2}\) as follows: \[\Delta c_{p,12}^{E+} = \frac{1}{C_d^2} \left(\frac{A_\text{in}}{A_\text{eff}}\right)^2 \left(\frac{U_\text{ref}}{V}\right)^2 Q'^2\] where \(Q' = Q/(A_\text{in}U_\text{ref})\) is the non-dimensional flow rate of Equation \(\ref{eqn:ss-combined-eqn}\), which is expressed in terms of \(Q\), the window area \(A_\text{in}\) and the wind speed at 10 m height, \(U_\text{ref}\).
The factor \(\left(A_\text{in}/A_\text{eff}\right)^2 = 2\), since \(A_1 = A_2 = A_\text{in}\), and therefore \(A_\text{eff} = A_\text{in}/\sqrt{2}\). The factor \((U_\text{ref}/V)\) relating the velocity scale used in the correlation with that used in the EnergyPlus pressure coefficient may be simplified by noting the following.
EnergyPlus assumes the surface pressure due to wind, \(p_w\), is derived from a pressure coefficient \(C_p\) using the local wind speed at window height, \(V_\text{ref}(z_win)\), i.e. \[p_w=\rho_a \left[V_\text{ref}(z_\text{win}\right]^2 C_p/2\] Hence the reference velocity \(V = V_\text{ref}(z_\text{win})\).
EnergyPlus characterizes the vertical wind profile as a power law in z, defined in terms of the local atmospheric boundary layer depth \(\delta\) and a power law exponent \(\alpha\). EnergyPlus also uses an “interpolation” formula to derive the above local wind speed from that measured at the meteorological site, \(U_\text{met}\), according to \[V_\text{ref}(z)= U_\text{met} \left(\frac{\delta_\text{met}}{z}\right)^{\alpha_\text{met}} \left(\frac{z}{\delta}\right)^\alpha\] where the subscript “met” denotes conditions at the meteorological site, and the default values are \(z_\text{met} = 10\ \text{m}\), \(\delta_\text{met} = 270\ \text{m}\) and \(\alpha_\text{met} = 0.14\). The user can change the site parameters from their default values.
The correlation in Equation \(\ref{eqn:ss-combined-eqn}\) assumes the reference velocity is the wind speed at 10 m, which will be taken as the local velocity at the building, \(V_\text{ref}(10)\). Combining these results, the pressure coefficient representing the difference in pressure between the two openings is given by \[\Delta c_{p,12}^{E+} = \frac{1}{C_d^2} \left[ \frac{V_\text{ref}(10)}{V_\text{ref}(z_\text{win})} \right]^2 \left(0.02+\left[0.346 |\Pi(\theta)|+0.084 \Sigma(\theta)\right]{\cdot}s'\right)\] where the velocity ratio \[\frac{V_\text{ref}(10)}{V_\text{ref}(z_\text{win})} = \left(\frac{10}{z_\text{win}}\right)^\alpha\]
Thus, if we assign a pressure coefficient \(+0.5\Delta c_{p,12}^{E+}\) to opening 1 and \(-0.5\Delta c_{p,12}^{E+}\) to opening 2, then this will provide the necessary pressure difference to give the flow in \(\ref{eqn:ss-combined-eqn}\) in a network context.
Note: the pressure coefficient \(\Delta c_{p,12}^{E+}\) refers to the difference in pressure between the two openings and is defined in terms of the wind speed at window height. If this is to be combined with a background pressure coefficient for the façade it is important to ensure the two are defined using the same reference velocity.
Testing/Validation/Data Source(s)[LINK]
The SS model was developed using wind tunnel pressure and flow rate data acquired by CPP Wind Engineering & Air Quality Consultants, who carried out two series of tests: (a) Closed Box tests, with a sealed building, to obtain pressure and velocity data and (b) Ventilation tests, with one or two apertures open, to obtain flow rate data. See Linden et al. (2013) for full details.
Each experimental configuration consisted of a cuboidal building with or without a set of blocks representing nearby buildings.
Building: either 2-story, with WB = 47.5 cm, DB = 19.3 cm, HB = 9.9 cm, or 4-story, with HB = 19.8 cm. The model has a nominal scale of 1:70 (based on earlier tests).
Environment: building either isolated or at center of a 3 x 3 array of equal-sized blocks, which were of same aspect ratio and either low (2-story height) or high (4-story height), and with either narrow spacing (approximately 0.5WB between blocks) or wide spacing (approximately WB), giving a total of 5 different environments.
Approach flow: suburban boundary layer, approximately 10 m/s at 1 m height. The model was mounted on a turntable allowing any desired wind direction to be used. Increments of \(\ang{11.25}\) and \(\ang{22.5}\) were used for the Closed Box and Ventilation runs, respectively.
Room and openings: the building envelope contained a second-floor room of dimensions WRM = 45.9 cm, DRM = 17.7 cm and HRM = 5.0 cm. A total of 15 opening positions were available, distributed around the room. These were sealed for the Closed Box tests but opened in various combinations for the Ventilation runs.
Sensors: 56 pressure transducers, arranged around the opening positions, including 32 at mid-opening height, recorded static pressure, while hot film sensors at 6 different positions recorded flow speed near the surface. For Ventilation runs the decay in concentration of a tracer was measured at two locations inside the room.
The data used to develop the model consisted of 6 scenarios: 3 building/environment cases,
2-story isolated building
4-story isolated building
2-story building with low, widely-spaced blocks
combined with 2 choices of opening position on the South (long) façade, namely wide separation (\(s' = 0.75\)) and medium separation (\(s' = 0.32\)).
Occupant Ventilation Control[LINK]
The AirflowNetwork:OccupantVentilationControl object enhances the AirflowNetwork model and provides more practical and advanced controls for window opening and closing operations, based on Marais & Teichmann (2014). This control includes minimum open and closed time control, indoor thermal comfort control, and opening and closing probability controls.
Procedures of occupant ventilation control[LINK]
It should be pointed that the open elapsed time and closed elapsed time are not independent. In other words, when one of the elapsed times value is greater than 0, then other elapsed time value must be equal to 0. The model is either tracking a window as open, in which case the open elapsed time grows, or as closed, in which case the closed elapsed time grows.
The calculation procedures are presented in the following steps:
Step 1: Open elapsed time check
The model checks the open elapsed time first. When the open elapsed time is greater than 0 and less than the minimum opening time, a window will remain open. Otherwise, the model goes to Step 2.
Step 2: Closed elapsed time check
This step checks the closed elapsed time. When the closed elapsed time is greater than 0 and less than the minimum closed time, a window will remain closed. Otherwise, the model goes to Step 3.
Step 3: Elapsed time only?
When either the open elapsed time or the closed elapsed time is long enough (greater than the minimum time) and no other checks are needed, the model returns to the other ventilation control defined in the Ventilation Control Mode field in AirflowNetwork:MultiZone:Zone or AirflowNetwork:MultiZone:Surface. If other checks are needed, the following steps will be performed.
Step 4: Thermal comfort temperature calculation
The thermal comfort check requires the thermal comfort temperature and the comfort band. The comfort temperature of Tcomf is calculated as a function of the outdoor dry-bulb temperature Tout. The comfort temperature calculation may be based on two curves and a boundary temperature point.
\[T_{comf} = \left\{ \begin{array}{ll} \rm{Low Temp Curve,} & \min T_{out} < x \leq \rm{Boundary Point} \\ \rm{High Temp Curve,} & \rm{Boundary Point} \leq x < \max T_{out} \end{array}\right.\]
Step 5: Thermal band calculation
The comfort band is calculated as a function of the design personal dissatisfaction PPD.
\[\theta = -0.0028 \left(100-\rm{PPD}\right)^2 + 0.3419 \left(100-\rm{PPD}\right) - 6.6275\]
This equation is valid for PPD 0% to 35%
Step 6: Upper boundary check of thermal comfort
After calculation of the comfort temperature and band, the thermal comfort check will be performed using the zone air operative temperature Tg. The check consists of upper and lower boundary checks.
The upper boundary check checks window opening status and uses the following logic:
\[T_g > \left(T_{comf} + \theta\right)\]
If the above logic check is true, the opening probability check will be performed. The detailed description is given in the opening probability section.
If the above logic check is false, no action is needed.
If the opening probability check is true and upper boundary check is satisfied, a window will be opened, regardless of open/closed status at the previous time step. If the opening probability check is false and upper boundary check is satisfied, a window will remain at the status from the previous time step.
\[T_g > \left(T_{comf} + \theta\right) \&\& \rm{OpeningProbability}\]
Step 7: Lower boundary check of thermal comfort
The lower boundary check will follow the upper boundary check to check the window closing status, using the following logic.
\[T_g < \left(T_{comf} - \theta\right)\]
If the above logic check is true, the closing probability check will be performed. The detailed description is given in the closing probability section.
If the above logic check is false, no action is needed.
If the closing probability check is true and lower boundary check is satisfied, a window will be closed, regardless of open/closed status at the previous time step. If the closing probability check is false and lower boundary check is satisfied, a window will remain at the status from the previous time step.
\[T_g < \left(T_{comf} - \theta\right) \&\& \rm{ClosingProbability}\]
The output variables from the model are open status, opening probability status, and closing probability status. The detailed description of opening status is given in the Airflow Network Outputs section in the Input Output Reference.
Note: The upper and lower boundary checks are not independent. In other words, when one of boundary check is satisfied, the other check will be dissatisfied.
Procedures of opening probability control[LINK]
Opening probability control provides an optional random number check. The control logic of opening probability is described in the following steps.
Step 1: Closed elapsed time check
This check requires that closed elapsed time is longer than the minimum closing time.
Closed time > minimum closed time
If the time duration is not long enough, the output is false so that a window remains closed.
If the time duration is long enough, an occupancy check is performed.
Step 2: Occupancy check
If a zone is not occupied and the occupancy check is requested, the output is false. If the zone is occupied, the next step is to check the setpoints using zone air temperature at the previous time step as a reference.
Step 3: Setpoint check
There are 5 temperature control types. The following types are available:
No control: Bypass
Single heating setpoint: If Tzon > setpoint, go to next step. Otherwise, return false.
Single cooling setpoint: If Tzon < setpoint, go to next step. Otherwise, return false.
Single heating and cooling setpoint: no action by returning false
Dual heating and setpoints: If heating setpoint < Tzon < Cooling setpoint, go to next step. Otherwise, return false.
Step 4: Select bypass or opening probability check
A choice is provided at this stage so that the opening probability check may be performed or bypassed. If bypassed, the output will be true to open a window. If performed, probability will be determined from a schedule.
Step 5: Perform opening probability check
The opening probability (OP) value is determined from a schedule.
OP = Schedule value or specific function
If the probability value is greater than a random number, the output is true.
OP > random number (random number is between 0 and 1)
Otherwise, the result will be false.
Procedures of closing probability control[LINK]
The control logic of closing probability is described as follows.
Step 1: Open elapsed time check
This check requires that open elapsed time is longer than the minimum opening time.
Open time > minimum open time
If the time duration is not long enough, the output is false and the window remains open. Otherwise, Step 2 will be performed.
Step 2: Select by-pass or closing probability check
A choice is provided at this step so that the closing probability check may be performed or bypassed. If bypassed, the output will be true to close a window. If performed, the closing probability will be calculated. The closing probability (CP) value is given from a schedule.
CP = Schedule value or specific function
If the closing probability check is performed and the closing probability is greater than a random number, the output is true.
CP > random number (random number is between 0 and 1)
Otherwise, the result will be false.
Pressure Control[LINK]
Pressure control is achieved by varying either zone exhaust fan flow rate in a controlled zone or relief air flow rate in an AirLoop. It requires an AirLoop with an OA mixer to reach the pressure setpoint by adjusting a relief air flow, or an OA mixer and an exhaust fan in a controlled zone to reach the pressure setpoint by adjusting an exhaust fan flow rate. The calculation logic is shown below:
1. The AirflowNetwork model will run twice with zero and maximum flow rates for either the controlled zone exhaust fan or relief air flow rate. The controlled zone pressures are the return values.
In general, the zero flow rate of either exhaust fan or relief node will generate the maximum zone pressure, while the maximum flow rate of either exhaust fan or relief node will produce the minimum zone pressure.
2. If the setpoint pressure is between the maximum zone pressure caused by zero exhaust fan or relief node flow rate and the minimum zone pressure caused by maximum exhaust fan flow rate or outdoor air flow rate, then the AirflowNetwork model will use Regula Falsi to find a solution with calculated zone exhaust fan flow rate or relief node flow rate. Otherwise, the pressure setpoint will not be met.
3. If both maximum and minimum pressures are higher than the setpoint, the maximum exhaust or outdoor flow rate will be forced.
4. If both maximum and minimum pressures are lower than the setpoint, then zero flow rate will be forced.
References[LINK]
Atkins, R. E., J. A. Peterka, and J. E. Cermak. 1979. “Averaged pressure coefficients for rectangular buildings,” Wind Engineering, Proceedings of the Fifth International Conference 7:369-80, Fort Collins, CO. Pergamon Press, NY.
Awbi, H. B. 2003. Ventilation of Buildings (2nd Edition). Routledge.
Bolmqvist, C. and M. Sandberg, 2004, “Air Movements through Horizontal Openings in Buildings – A Model Study,” International Journal of Ventilation, Vol. 3, No. 1, pp. 1-9.
COMIS Fundamentals. 1990. Edited by Helmut E. Feustel and Alison Rayner-Hooson, LBL-28560, Lawrence Berkeley Laboratory, Berkeley, California.
Conte, S. D. and C de Boor. 1972.Elementary Numerical Analysis: an Algorithmic Approach, McGraw-Hill.
Cooper, L., 1989, “Calculation of the Flow Through a Horizontal Ceiling/Floor Vent,” NISTIR 89-4052, National Institute of Standards and Technology, Gaithersburg, Maryland.
Dols, W. S. and G. N. Walton. 2002. “CONTAMW 2.0 User Manual,” NISTIR 6921, National Institute of Standards and Technology, Gaithersburg , Maryland.
Holmes, J. D. 1986. Wind Loads on low-rise buildings: The structural and environmental effects of wind on buildings and structures, Chapter 12, Faculty of Engineering, Monash University, Melbourne, Australia.
Linden, P., D. Banks, N. Daish, M. Fountain, G. Gross, A. Honnekeri, M. Pigman, R. Thomas, K. Adams, S. Brunswick, S. Dutton, R. Gerard, P. Haves, M. Hovanec, P. Switenki, Y. Zhai, E. Arens, G. Carrilho da Graça, W. Fisk, F. Gillan, M. Hill, T. Lawton, G. Szakats, and H. Zhang. 2016. “Natural Ventilation for Energy Savings in California Commercial Buildings,” CEC-500-2016-039, California Energy Commission.
Marais, J. M. and C. Teichmann, “Window Simulation Methods Required for Manual Window Ventilated Buildings,” Fifth German-Austrian IBPSA Conference, September 22-24, 2014, RWTH Aachen University, Germany.
Swami, M. V. and S. Chandra. 1988. Correlations for pressure distribution on buildings and calculation of natural-ventilation airflow, ASHRAE Transactions 94(1988) (Pt 1), pp. 243-266.
Swami, M. V., L. Gu, and V. Vasanth. 1992. “Integration of Radon and Energy Models for Building,” FSEC-CR-553-92, Florida Solar Energy Center, Cocoa, Florida.
Tan, Q. and Y. Jaluria, 1992, “Flow through Horizontal Vents as Related to Compartment Fire Environments,” NIST-GCR-92-607, National Institute of Standards and Technology, Gaithersburg, Maryland.
Walton, G. N. 1989. “AIRNET – A Computer Program for Building Airflow Network Modeling,” NISTIR 89-4072, National Institute of Standards and Technology, Gaithersburg, Maryland.
Walton, G. N. and W. S. Dols. 2003. “CONTAM 2.1 Supplemental User Guide and Program Documentation,” NISTIR 7049, National Institute of Standards and Technology, Gaithersburg, Maryland.
Warren, P.R. and Parkins, L.M. (1985) Single-sided ventilation through open windows. In Proceedings of the ASHRAE/DOE/BTECC Conference on Thermal Performance of the Exterior Envelopes of Buildings III, December 2-5, 1985, Clearwater Beach, Florida, pp. 209-228.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.