Internal heat gains from lights, people, and equipment of
various types are often significant elements in the zone
thermal balance. EnergyPlus allows the user to specify heat
gains for several equipment types including people, lights,
gas/electric equipment, and several other types. The total
heat gain is comprised of convective, radiant and latent gains
in various proportions from these sources. Convective gains
are instantaneous additions of heat to the zone air. Radiant
gains are distributed on the surfaces of the zone, where they
are first absorbed and then released back into the room (with
some fraction conducted through the surface) according to the
surface heat balances. {See Surface Heat Balance Manager /
Processes in this document}. Latent gains must be handled by
ventilation or air conditioning equipment. Recommended heat
gains are given in the ASHRAE Handbook of Fundamentals. These
recommendations include the sensible (convective plus
radiative) and latent proportions. Sensible gains from
equipment are primarily radiant. The user can specify the
heat gains and proportions for any type of equipment.
Determining the gains from lights, people and baseboard heat
are slightly more complicated.
The input object Lights
provides a model for internal gains from lights. Radiant
gains from lights must be handled differently from other
radiant gains for reasons described here (long wavelength
description). The total radiant gains from lights must be
divided into visible and thermal portions. For example, the
total electric input to typical incandescent lights is
converted to 10% visible radiation, 80% thermal radiation, and
10% convective gain. In contrast, the electric input to
typical fluorescent lights is converted to 20% visible
radiation, 20% thermal radiation, and 60% convective gain (see
Carrier 1965). These percentage splits are under user control
with the Lights
input object.
When the value of Return Air Fraction is greater than 0 and
the return air flow rate is greater than 0, the portion of
light heat will be added to the return air node. The added
heat will make the node temperature rise. The temperature
difference is calculated in the CalcZoneLeavingConditions
funtion of the ZoneEquipmentManager module:
\(TempRetRise\) is the
temperature rise due to added light heat gain (C)
\(QRetAir\) is the added
heat gain from return air fraction (W)
\(MassFlowRA\) is the mass
flow rate at the return node (kg/s)
\(CpAir\) is the specific
heat (J/kg)
When both node names of return air and exhaust air are
entered in the Lights
object, the return heat is shared by both nodes. Both nodes
will have the same temperature due to added return heat:
\(TempRetRise\) is the
temperature rise due to added light heat gain (C)
\(QRetAir\) is the added
heat gain from return air fraction (W)
\(MassFlowRA\) is the mass
flow rate at the return node (kg/s)
\(MassFlowEx\) is the mass
flow rate at the exhaust node (kg/s)
\(CpAir\) is the specific
heat (J/kg)
Although a single Lights
object allows a return node and an exhaust node, it is
possible to have multiple Lights
objects with different return nodes and referrred to the same
exhaust node. Therefore, the exhaust node will share return
heat from different return nodes. The temperature rise at i-th
return node is given below:
The input object People
provides a model for internal gains from occupants. Heat is
generated in the human body by oxidation at a rate called the
metabolic rate (see Thermal Comfort discussion for more
details). This heat is dissipated from the body surface and
respiratory tract by a combination of radiation, convection,
and evaporation. The relative proportions of sensible
(radiation plus convection) and latent (evaporation) heat from
people is a complex function of the metabolic rate and the
environmental conditions. EnergyPlus uses a polynomial
function to divide the total metabolic heat gain into sensible
and latent portions. That function is based on a fit to data
[3] at average adjusted metabolic rates of 350, 400, 450, 500,
750, 850, 1000 and 1450 Btu/h each at temperatures of 70, 75,
78, 80, 82\(^{\circ}\)Fahrenheit. Sensible
gains of 0 at 96\(^{\circ}\)F
and sensible gains equal to the metabolic rate at 30\(^{\circ}\)F were assumed in order
to give reasonable values beyond the reported temperature
range.
Average adjusted metabolic rate (Carrier 1965b) is the
metabolic rate to be applied to a mixed group of people with a
typical percent composition based on the following
factors:
Metabolic rate, adult female = Metabolic rate, adult
male X 0.85
Metabolic rate, children = Metabolic rate, adult male X
0.75
The original data was in I-P (Inch-Pound) units, but the
following correlation is in SI (Systems-International)
units.
\[\begin{array}{ll}
S &= 6.461927 + .946892 M + .0000255737 M^2 + 7.139322
T - .0627909 T M \\
&+ .0000589172 T M^2 - .198550 T^2 + .000940018 T^2
M - .00000149532 T^2 M^2
\end{array}\]
where:
\(M\) is the metabolic
rate (W)
\(T\) is the air
temperature (C)
\(S\) is the sensible gain
(W).
Latent Gain is simply the total gain (metabolic rate) –
sensible gain:
\[LatentGain = MetabolicRate -
SensibleGain\]
Sensible Heat Gain from People
Correlation
The function for sensible gain calculation is compared to
the original data points in the following figure. The radiant
fraction of the sensible gain is a user input on the People
object.
The input object ElectricEquipment:ITE:AirCooled
describes air-cooled electric information technology equipment
(ITE) which has variable power consumption as a function of
loading and temperature. The calculations are described
below.
PDesign is the design power input when fully loaded and
entering air temperature is at the user-specified design inlet
temperature (W)
PFanFracDesign is the design fan power input fraction
of total power input when fully loaded and entering air
temperature is at the user-specified design inlet
temperature
SchDesignLevel is the scheduled fraction of this
equipment which is powered up
SchCPULoading is the scheduled fraction of CPU
loading
TAirInDesign is the air inlet temperature at design
condition (\(^{\circ}\)C)
VAirDesign is the air volume flow rate at design
condition (m\(^3\)/s)
VAirfLoadTAir is the air volume flow rate modifier
function of TAirIn and SchCPULoading
PCPUfLoadTAir is the CPU power input modifier function
of TAirIn and SchCPULoading
PFanfFlowFrac is the fan power input modifier function
of air flow fraction
RecircFracDesign is the recirculation fraction at
design condition (\(^{\circ}\)C)
RecircfLoadTAir is the recirculation fraction modifier
function of TAirSupply and SchCPULoading
UPSEfficDesign is the design electric power supply
efficiency
UPSEfficfPLR is the electric power supply efficiency
function of part load ratio
UPSLossFracToZone is the fraction of electric power
supply losses to zone
The design power input is first split into portions for the
CPU (everything in the equipment except the cooling fans) and
the fan(s).
\[PCPUDesign = PDesign * (1 -
PFanFracDesign)\]
\[PFanDesign = PDesign *
PFanFracDesign\]
For each time step, the air inlet and outlet temperature is
calculated depending on the type of air flow calculation
method. Considering data centers are different from normal
well-mixed zones due to the uneven air distribution, two
methods are implemented to calculate the IT inlet temperature
and zone return air temperature,
FlowFromSystem and
FlowControlWithApproachTemperatures.
Specifically, the IT inlet temperature differs from AHU supply
air temperature, and the actual AHU return air temperature
differs from the regular return air temperature when the zone
is well mixed.
When using FlowFromSystem, the zone is
assumed to be well-mixed. The air inlet temperature is
calculated depending on the type of air node connection.
TAirIn:
If Air Node Connection Type = AdjustedSupply \[RecircFrac = RecircFracDesign *
RecircfLoadTAir(SchCPULoading TAirSupply)\]
The convective heat gain to the zone and the air outlet
temperature are then calculated. The user specified fration of
power supply losses are always added to the general zone heat
balace convective heat gain. For air node connection types
AdjustedSupply and ZoneAirNode, the CPU and fan power
consumption are also added to the zone convective heat gain.
For air connection type RoomAirModel, the gains from the CPU
and fan power consumption are added to the outlet room air
model node.
\[QAir = PCPU +
PFan\]
\[QUPS = PUPS *
UPSLossFracToZone\]
QConv:
If Air Node Connection Type = AdjustedSupply OR
ZoneAirNode \[QConv = QAir +
QUPS\]
If Air Node Connection Type = RoomAirModel \[QConv = QUPS\]
If FlowControlWithApproachTemperatures is
chosen, Two indices are introduced to represent the deviation:
(1) Supply approach temperature (\(\delta T_{supply}\)) and (2)
Return approach temperature (\(\delta T_{return}\)). The two
temperature differences indicate to what degree the air flow
management of data centers affects the air distribution, and
how much they deviate from the regular well-mixed zone
scenario.
\[\delta
T_{supply}=T_{in}-T_{supply}\]
\[\delta
T_{return}=T_{return}-T_{out}\]
where:
\(T_{in}\) is the IT
equipment inlet temperature
\(T_{supply}\) is the AHU
supply air temperature
\(T_{return}\) is the
actual AHU return air temperature
\(T_{out}\) is the IT
equipment outlet temperature.
The two approach temperatures can be calculated by CFD
tools for typical IT load levels and air flow management of
data centers, or provided by measurement data or lookup
tables.
It should be noted that, when
FlowControlWithApproachTemperatures is
chosen,
The inputs of Air Inlet Connection Type, Design
Recirculation Fraction and Recirculation Function of Loading
and Supply Temperature Curve Name are ignored.
For multiple ITE objects defined for one zone, the same
calculation method should apply. The return air temperature of
this zone would be set as the weighted average return
temperature of all ITE objects in this zone.
Other return air heat gains from window or lights are
not allowed.
Apart from a single VAV terminal unit, other HVAC
systems do not apply this method in the ITE zone.
When FlowControlWithApproachTemperatures
method is applied, during sizing and simulation, as the zone
is assumed to be unevenly distributed, the supply air flow
rate of the AHU is calculated as:
where \(T_{return}\) is
the weighted return air temperature from all ITE objects in
the zone, and \(T_{supply}\)
is the designed supply air temperature to the ITE objects.
Another modified assumption for this case is, in zones with
ITE objects, to make sure the zone heat balance converge,
unlike the original thermostat setpoint control logic, the
well-mixed zone temperature is not controlled. The actual
controlled object is the supply air temperature. So when using
this method, the user input of zone cooling setpoint is
ignored and the unmet hour for cooling does not apply.
The input object ZoneBaseboard:OutdoorTemperatureControlled
provides a model for an outdoor temperature controlled
baseboard heater that adds energy to the zone according a
control profile as shown in the following figure. At TA = T2,
the baseboard heat gain is Q2. For TA > T2, there is no
heat gain. For TA < T1, a maximum amount of energy, Q1, is
added to the zone. There is proportional control between
those two temperatures:
Control of Outdoor Temperature
Controlled Baseboard Heat
These temperature and capacity fields can be autosized
based upon envelope, infiltration, and ventilation loads. To
autosize these fields, users may set a design zone heating
temperature that is assumed to be 20\(^{\circ}\)C if blank.
The capacity at low temperature is the maximum capacity of
the unit. It includes external envelope conduction load,
infiltration load, and ventilation load in a space where the
unit serves. The model first finds the lowest outdoor air
temperature throughout design days included in the simulation,
and determines the conduction load through external envelope
as:
It is useful to consider the distribution of short
wavelength (including visible) radiant energy separate from
long wavelength (thermal) radiant energy because many
materials have different optical properties at different
wavelengths. An extreme example is glass that is opaque to
the long wavelengths and transparent to the short. Properties
of materials vary across the entire spectrum of wavelengths.
In EnergyPlus, all radiant interactions are represented in
terms of only two wavelengths: “short” and “long”. Short
wavelength refers to the distribution given by a ~6000K black
body source such as the sun. Long wavelengths refer to
radiation from ~300K sources such as walls or people. There
is negligible overlap between these two distributions. Some
sources, such as lights, must be considered as emitting both
long and short wavelength radiation in proportions that
approximate their actual effects on room surfaces.
Long wavelength radiation from all internal sources, such
as people, lights and equipment, is combined and then
distributed over surfaces. (see Internal Long-Wave Radiation
Exchange).
Some fraction of the beam solar radiation transmitted into
the zone is directly absorbed by the interior surfaces
according to the solar distribution algorithm (see Solar
Distribution) selected by the user. The beam radiation not
directly absorbed, plus the diffuse sky and ground-reflected
radiation, plus the short wavelength radiation from lights are
combined and distributed over the surfaces of the zone
according to:
If all surfaces in the room are opaque, the radiation is
distributed in proportion to the area*absorptance product of
each surface. For surfaces which are transparent,
\[{\rho_i} = 1 - {\alpha_i} -
{\tau_i}\]
That fraction of radiation represented by \({\tau_i}\) is lost from the
zone.
The transmittance and absorptance of transparent surfaces
(windows or glass doors) are calculated as in section Window
Calculation Module based on the optical properties of the
window material layers. The total absorptance of the window
is computed for the interior shading device, the inside
surface, and the outside surface for diffuse solar radiation
incident from outside the zone. Those absorptances are used
for short wavelength radiation incident from inside the zone.
In most cases, this should not cause significant error. When
movable insulation covers the window, the radiation that would
have been transmitted is absorbed at the outer surface of the
window (thermally equal to the inside surface of the
insulation).
Zone Internal Gains[LINK]
Sources and Types of Gains[LINK]
Internal heat gains from lights, people, and equipment of various types are often significant elements in the zone thermal balance. EnergyPlus allows the user to specify heat gains for several equipment types including people, lights, gas/electric equipment, and several other types. The total heat gain is comprised of convective, radiant and latent gains in various proportions from these sources. Convective gains are instantaneous additions of heat to the zone air. Radiant gains are distributed on the surfaces of the zone, where they are first absorbed and then released back into the room (with some fraction conducted through the surface) according to the surface heat balances. {See Surface Heat Balance Manager / Processes in this document}. Latent gains must be handled by ventilation or air conditioning equipment. Recommended heat gains are given in the ASHRAE Handbook of Fundamentals. These recommendations include the sensible (convective plus radiative) and latent proportions. Sensible gains from equipment are primarily radiant. The user can specify the heat gains and proportions for any type of equipment. Determining the gains from lights, people and baseboard heat are slightly more complicated.
Heat Gain from Lights[LINK]
The input object Lights provides a model for internal gains from lights. Radiant gains from lights must be handled differently from other radiant gains for reasons described here (long wavelength description). The total radiant gains from lights must be divided into visible and thermal portions. For example, the total electric input to typical incandescent lights is converted to 10% visible radiation, 80% thermal radiation, and 10% convective gain. In contrast, the electric input to typical fluorescent lights is converted to 20% visible radiation, 20% thermal radiation, and 60% convective gain (see Carrier 1965). These percentage splits are under user control with the Lights input object.
When the value of Return Air Fraction is greater than 0 and the return air flow rate is greater than 0, the portion of light heat will be added to the return air node. The added heat will make the node temperature rise. The temperature difference is calculated in the CalcZoneLeavingConditions funtion of the ZoneEquipmentManager module:
\[TempRetRise = \frac{QRetAir} {MassFlowRA * CpAir}\]
where:
\(TempRetRise\) is the temperature rise due to added light heat gain (C)
\(QRetAir\) is the added heat gain from return air fraction (W)
\(MassFlowRA\) is the mass flow rate at the return node (kg/s)
\(CpAir\) is the specific heat (J/kg)
When both node names of return air and exhaust air are entered in the Lights object, the return heat is shared by both nodes. Both nodes will have the same temperature due to added return heat:
\[TempRetRise = \frac{QRetAir} {(MassFlowRA + MassFlowEx ) * CpAir}\]
where:
\(TempRetRise\) is the temperature rise due to added light heat gain (C)
\(QRetAir\) is the added heat gain from return air fraction (W)
\(MassFlowRA\) is the mass flow rate at the return node (kg/s)
\(MassFlowEx\) is the mass flow rate at the exhaust node (kg/s)
\(CpAir\) is the specific heat (J/kg)
Although a single Lights object allows a return node and an exhaust node, it is possible to have multiple Lights objects with different return nodes and referrred to the same exhaust node. Therefore, the exhaust node will share return heat from different return nodes. The temperature rise at i-th return node is given below:
\[TempRetRise_i = \frac{QRetAir_i} {(MassFlowRA_i + MassFlowEx ) * CpAir}\]
\(TempRetRise_i\) is the temperature rise at i-th return node due to added light heat gain (C)
\(QRetAir_i\) is the added heat gain from return air fraction at i-th return node (W)
\(MassFlowRA_i\) is the mass flow rate at i-th return node (kg/s)
\(MassFlowEx\) is the mass flow rate at the exhaust node (kg/s)
\(CpAir\) is the specific heat (J/kg)
The temperature arise at the exhaust node is a sum of all return node temperature rise:
\[TempRetRise = {\sum_{i=1} ^n}\frac{ QRetAir_i} {(MassFlowRA_i + MassFlowEx ) * CpAir}\]
where:
\(TempRetRise\) is the temperature rise at the exhaust node due to added light heat gain (C)
\(QRetAir_i\) is the added heat gain from return air fraction (W)
\(MassFlowRA_i\) is the mass flow rate at the return node (kg/s)
\(MassFlowEx\) is the mass flow rate at the exhaust node (kg/s)
\(CpAir\) is the specific heat (J/kg)
\(n\) is the number of Lights objects with the same exhaust node
Heat Gain from People[LINK]
The input object People provides a model for internal gains from occupants. Heat is generated in the human body by oxidation at a rate called the metabolic rate (see Thermal Comfort discussion for more details). This heat is dissipated from the body surface and respiratory tract by a combination of radiation, convection, and evaporation. The relative proportions of sensible (radiation plus convection) and latent (evaporation) heat from people is a complex function of the metabolic rate and the environmental conditions. EnergyPlus uses a polynomial function to divide the total metabolic heat gain into sensible and latent portions. That function is based on a fit to data [3] at average adjusted metabolic rates of 350, 400, 450, 500, 750, 850, 1000 and 1450 Btu/h each at temperatures of 70, 75, 78, 80, 82\(^{\circ}\)Fahrenheit. Sensible gains of 0 at 96\(^{\circ}\)F and sensible gains equal to the metabolic rate at 30\(^{\circ}\)F were assumed in order to give reasonable values beyond the reported temperature range.
Average adjusted metabolic rate (Carrier 1965b) is the metabolic rate to be applied to a mixed group of people with a typical percent composition based on the following factors:
Metabolic rate, adult female = Metabolic rate, adult male X 0.85
Metabolic rate, children = Metabolic rate, adult male X 0.75
The original data was in I-P (Inch-Pound) units, but the following correlation is in SI (Systems-International) units.
\[\begin{array}{ll} S &= 6.461927 + .946892 M + .0000255737 M^2 + 7.139322 T - .0627909 T M \\ &+ .0000589172 T M^2 - .198550 T^2 + .000940018 T^2 M - .00000149532 T^2 M^2 \end{array}\]
where:
\(M\) is the metabolic rate (W)
\(T\) is the air temperature (C)
\(S\) is the sensible gain (W).
Latent Gain is simply the total gain (metabolic rate) – sensible gain:
\[LatentGain = MetabolicRate - SensibleGain\]
The function for sensible gain calculation is compared to the original data points in the following figure. The radiant fraction of the sensible gain is a user input on the People object.
Heat Gain from IT Equipment[LINK]
The input object ElectricEquipment:ITE:AirCooled describes air-cooled electric information technology equipment (ITE) which has variable power consumption as a function of loading and temperature. The calculations are described below.
Variable Definitions – User Inputs:[LINK]
PDesign is the design power input when fully loaded and entering air temperature is at the user-specified design inlet temperature (W)
PFanFracDesign is the design fan power input fraction of total power input when fully loaded and entering air temperature is at the user-specified design inlet temperature
SchDesignLevel is the scheduled fraction of this equipment which is powered up
SchCPULoading is the scheduled fraction of CPU loading
TAirInDesign is the air inlet temperature at design condition (\(^{\circ}\)C)
VAirDesign is the air volume flow rate at design condition (m\(^3\)/s)
VAirfLoadTAir is the air volume flow rate modifier function of TAirIn and SchCPULoading
PCPUfLoadTAir is the CPU power input modifier function of TAirIn and SchCPULoading
PFanfFlowFrac is the fan power input modifier function of air flow fraction
RecircFracDesign is the recirculation fraction at design condition (\(^{\circ}\)C)
RecircfLoadTAir is the recirculation fraction modifier function of TAirSupply and SchCPULoading
UPSEfficDesign is the design electric power supply efficiency
UPSEfficfPLR is the electric power supply efficiency function of part load ratio
UPSLossFracToZone is the fraction of electric power supply losses to zone
Variable Definitions – Simulation Inputs:[LINK]
TAirIn is the air inlet temperature at current conditions (\(^{\circ}\)C)
TAirSupply is the supply air node temperature at current conditions (\(^{\circ}\)C)
TZone is the zone air temperature at current conditions (\(^{\circ}\)C)
TRoomAirNodeIn is the room air model inlet node air temperature at current conditions (\(^{\circ}\)C)
RhoAir is the air density (kg/m\(^3\))
CpAir is the air specific heat (J/kg-K)
Variable Definitions – Intermediate Calculations:[LINK]
PCPUDesign is the design CPU power input when fully loaded and entering air temperature is at the user-specified design inlet temperature (W)
PFanDesign is the design fan power input when fully loaded and entering air temperature is at the user-specified design inlet temperature (W)
UPSPLR is the electric power supply part load ratio (can be greater than 1.0)
Variable Definitions – Outputs:[LINK]
PCPU is the CPU power input (W)
PFan is the fan power input (W)
PUPS is the electric power supply net power input (W)
TAirOut is the air outlet temperature (\(^{\circ}\)C)
VAir is the air volume flow rate (m\(^3\)/s)
FlowFrac is the air volume flow rate fraction of design flow rate
RecircFrac is the recirculation fraction
QAir is the air cooling rate (W)
QUPS is the electric power supply heat loss rate to zone (W)
QConv is the convective heat gain rate to zone heat balance (W)
SHI is the supply heat index
SHIZone is the zone average supply heat index
Calculations[LINK]
The design power input is first split into portions for the CPU (everything in the equipment except the cooling fans) and the fan(s).
\[PCPUDesign = PDesign * (1 - PFanFracDesign)\]
\[PFanDesign = PDesign * PFanFracDesign\]
For each time step, the air inlet and outlet temperature is calculated depending on the type of air flow calculation method. Considering data centers are different from normal well-mixed zones due to the uneven air distribution, two methods are implemented to calculate the IT inlet temperature and zone return air temperature, FlowFromSystem and FlowControlWithApproachTemperatures. Specifically, the IT inlet temperature differs from AHU supply air temperature, and the actual AHU return air temperature differs from the regular return air temperature when the zone is well mixed.
When using FlowFromSystem, the zone is assumed to be well-mixed. The air inlet temperature is calculated depending on the type of air node connection.
TAirIn:
If Air Node Connection Type = AdjustedSupply \[RecircFrac = RecircFracDesign * RecircfLoadTAir(SchCPULoading TAirSupply)\]
\[TAirIn = TAirSupply * (1 – RecircFrac) +TAirZone * RecircFrac\]
If Air Node Connection Type = ZoneAirNode
\[TAirIn = TAirZone\]
If Air Node Connection Type = RoomAirModel \[TAirIn = TRoomAirNodeIn\]
Using the air inlet temperature, the CPU power consumption, air flow rate, fan power consumption, and power supply power consumption are calculated.
\[PCPU = PCPUDesign * SchDesignLevel * PfLoadTAir(SchCPULoading, TAirIn)\]
\[FlowFrac = VAirfLoadTAir(SchCPULoading, TAirIn)\]
\[VAir = VAirDesign * FlowFrac\]
\[PFan = PFanDesign * SchDesignLevel * PFanfFlowFrac(FlowFrac)\]
\[UPSPLR = (PCPU + PFan) / (PCPUDesign + PFanDesign)\]
\[PUPS = (PCPU + PFan) * (1 - UPSEfficDesign * UPSEfficfPLR (UPSPLR))\]
The convective heat gain to the zone and the air outlet temperature are then calculated. The user specified fration of power supply losses are always added to the general zone heat balace convective heat gain. For air node connection types AdjustedSupply and ZoneAirNode, the CPU and fan power consumption are also added to the zone convective heat gain. For air connection type RoomAirModel, the gains from the CPU and fan power consumption are added to the outlet room air model node.
\[QAir = PCPU + PFan\]
\[QUPS = PUPS * UPSLossFracToZone\]
QConv:
If Air Node Connection Type = AdjustedSupply OR ZoneAirNode \[QConv = QAir + QUPS\]
If Air Node Connection Type = RoomAirModel \[QConv = QUPS\]
\[TAirOut = TAirIn + QAir / (VAir * RhoAir * CpAir)\]
The individual ITE supply heat index is calculated as shown below.
\[SHI = (TAirIn - TAirSupply) / (TAirOut - TAirSupply)\]
The zone average ITE supply heat index is weighted by the air flow rate of each ITE object.
\[SHIZone = \Sigma [VAir * (TAirIn - TAirSupply)] / \Sigma [VAir * (TAirOut - TAirSupply)]\]
If FlowControlWithApproachTemperatures is chosen, Two indices are introduced to represent the deviation: (1) Supply approach temperature (\(\delta T_{supply}\)) and (2) Return approach temperature (\(\delta T_{return}\)). The two temperature differences indicate to what degree the air flow management of data centers affects the air distribution, and how much they deviate from the regular well-mixed zone scenario.
\[\delta T_{supply}=T_{in}-T_{supply}\]
\[\delta T_{return}=T_{return}-T_{out}\]
where:
\(T_{in}\) is the IT equipment inlet temperature
\(T_{supply}\) is the AHU supply air temperature
\(T_{return}\) is the actual AHU return air temperature
\(T_{out}\) is the IT equipment outlet temperature.
The two approach temperatures can be calculated by CFD tools for typical IT load levels and air flow management of data centers, or provided by measurement data or lookup tables.
It should be noted that, when FlowControlWithApproachTemperatures is chosen,
The inputs of Air Inlet Connection Type, Design Recirculation Fraction and Recirculation Function of Loading and Supply Temperature Curve Name are ignored.
For multiple ITE objects defined for one zone, the same calculation method should apply. The return air temperature of this zone would be set as the weighted average return temperature of all ITE objects in this zone.
Other return air heat gains from window or lights are not allowed.
Apart from a single VAV terminal unit, other HVAC systems do not apply this method in the ITE zone.
When FlowControlWithApproachTemperatures method is applied, during sizing and simulation, as the zone is assumed to be unevenly distributed, the supply air flow rate of the AHU is calculated as:
\[{\dot m_{sys}} = {Q_{sys}}/({C_{p,air}} \cdot ({T_{return}} - {T_{supply}}))\]
where \(T_{return}\) is the weighted return air temperature from all ITE objects in the zone, and \(T_{supply}\) is the designed supply air temperature to the ITE objects.
Another modified assumption for this case is, in zones with ITE objects, to make sure the zone heat balance converge, unlike the original thermostat setpoint control logic, the well-mixed zone temperature is not controlled. The actual controlled object is the supply air temperature. So when using this method, the user input of zone cooling setpoint is ignored and the unmet hour for cooling does not apply.
Heat Gain from Baseboard Heat[LINK]
The input object ZoneBaseboard:OutdoorTemperatureControlled provides a model for an outdoor temperature controlled baseboard heater that adds energy to the zone according a control profile as shown in the following figure. At TA = T2, the baseboard heat gain is Q2. For TA > T2, there is no heat gain. For TA < T1, a maximum amount of energy, Q1, is added to the zone. There is proportional control between those two temperatures:
\[Q = Q2 - \frac{{(Q2 - Q1)\cdot (T2 - TA)}}{{(T2 - T1)}}\]
These temperature and capacity fields can be autosized based upon envelope, infiltration, and ventilation loads. To autosize these fields, users may set a design zone heating temperature that is assumed to be 20\(^{\circ}\)C if blank.
The capacity at low temperature is the maximum capacity of the unit. It includes external envelope conduction load, infiltration load, and ventilation load in a space where the unit serves. The model first finds the lowest outdoor air temperature throughout design days included in the simulation, and determines the conduction load through external envelope as:
\[{q_{Cond}} = UA\left( {{T_{Htg}} - {T_L}} \right)\]
where:
q\(_{Cond}\) is the conduction load through external envelope (W)
U is the heat transfer coefficient of external wall (W/m\(^{2}\)K)
A is the area of external wall (m\(^{2}\))
T\(_{Htg}\) is the baseboard zone heating setpoint temperature (\(^{\circ}\)C)
T\(_{L}\) is the low temperature, (\(^{\circ}\)C).
The capacity at the low temperature that is the maximum capacity of the unit is thus expressed as:
\[Ca{p_{{T_L}}} = {q_{Cond}} + {q_I} + {q_V}\]
where:
\(Ca{p_{{T_L}}}\) is the capacity at low temperature (W)
q\(_{I}\) is the design infiltration sensible load (W)
q\(_{V}\) is the design ventilation sensible load (W).
The capacity at the high temperature is then prorated against the reference low and high temperatures as:
\[Ca{p_{{T_H}}} = Ca{p_{{T_L}}}\frac{{\left( {{T_{Htg}} - {T_H}} \right)}}{{\left( {{T_{Htg}} - {T_L}} \right)}}\]
where:
\(Ca{p_{{T_H}}}\) is capacity at high temperature (W)
T\(_{H}\) is high temperature (\(^{\circ}\)C).
Distribution of Radiant Gains[LINK]
It is useful to consider the distribution of short wavelength (including visible) radiant energy separate from long wavelength (thermal) radiant energy because many materials have different optical properties at different wavelengths. An extreme example is glass that is opaque to the long wavelengths and transparent to the short. Properties of materials vary across the entire spectrum of wavelengths. In EnergyPlus, all radiant interactions are represented in terms of only two wavelengths: “short” and “long”. Short wavelength refers to the distribution given by a ~6000K black body source such as the sun. Long wavelengths refer to radiation from ~300K sources such as walls or people. There is negligible overlap between these two distributions. Some sources, such as lights, must be considered as emitting both long and short wavelength radiation in proportions that approximate their actual effects on room surfaces.
Long wavelength radiation from all internal sources, such as people, lights and equipment, is combined and then distributed over surfaces. (see Internal Long-Wave Radiation Exchange).
Some fraction of the beam solar radiation transmitted into the zone is directly absorbed by the interior surfaces according to the solar distribution algorithm (see Solar Distribution) selected by the user. The beam radiation not directly absorbed, plus the diffuse sky and ground-reflected radiation, plus the short wavelength radiation from lights are combined and distributed over the surfaces of the zone according to:
\[QS{I_i} = Q{S_n}\cdot {\alpha_i}/\sum\limits_{i = 1}^{NS} {{S_i}\cdot (1 - {\rho_i})}\]
If all surfaces in the room are opaque, the radiation is distributed in proportion to the area*absorptance product of each surface. For surfaces which are transparent,
\[{\rho_i} = 1 - {\alpha_i} - {\tau_i}\]
That fraction of radiation represented by \({\tau_i}\) is lost from the zone.
The transmittance and absorptance of transparent surfaces (windows or glass doors) are calculated as in section Window Calculation Module based on the optical properties of the window material layers. The total absorptance of the window is computed for the interior shading device, the inside surface, and the outside surface for diffuse solar radiation incident from outside the zone. Those absorptances are used for short wavelength radiation incident from inside the zone. In most cases, this should not cause significant error. When movable insulation covers the window, the radiation that would have been transmitted is absorbed at the outer surface of the window (thermally equal to the inside surface of the insulation).
References[LINK]
ASHRAE. 2001. Handbook of Fundamentals, pp 29.8-29.13, Atlanta: ASHRAE.
Carrier Air Conditioning Company. 1965a. Handbook of Air Conditioning System Design, pp 1-99 to 1-100. New York: McGraw Hill.
Carrier Air Conditioning Company. 1965b. Handbook of Air Conditioning System Design, pp 1-100, Table # 48. New York: McGraw Hill.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.