The integration of a sophisticated building thermal
analysis tool with thermal comfort models allows one to
perform an energy analysis on a zone and simultaneously
determine if the environmental control strategy will be
sufficient for the occupants to be thermally comfortable. This
section is intended to provide background on thermal comfort,
present an overview of state of the art thermal comfort
models, and present the mathematical models that have been
incorporated into EnergyPlus.
Thermal comfort modeling in EnergyPlus is controlled
primarily by the People
input object. This includes input for selecting the type of
thermal comfort model that is desired by the user as well as
parameters that serve as inputs to the thermal comfort models.
These parameters include the activity level, the work
efficiency, the air velocity and the clothing insulation level
for people within the space. All four of these parameters can
be scheduled. More information on the People
input object can be found in the EnergyPlus Input/Output
Reference. More information on how each of these parameters is
used and the specific modeling equations for the thermal
comfort models can be found below.
Throughout the last few decades, researchers have been
exploring the thermal, physiological and psychological
response of people in their environment in order to develop
mathematical models to predict these responses. Researchers
have empirically determined building occupants’ thermal
responses to the combined thermal effect of the personal,
environmental and physiological variables that influence the
condition of thermal comfort.
There are two personal variables that influence the
condition of thermal comfort: the thermal resistance of the
clothing (I\(_{cl}\)), and
the metabolic rate (H/A\(_{Du}\)).
The thermal resistance of the clothing (I\(_{cl}\)) is measured in units of
“clo.” The 1985 ASHRAE Handbook of Fundamentals (ASHRAE 1985)
suggests multiplying the summation of the individual clothing
items clo value by a factor of 0.82 to determine the overall
clo value for clothing ensembles.
The metabolic rate (H/A\(_{Du}\)) is a measure of the
internal heat production rate of an occupant (H) in W/hr per
unit of “Dubois” body surface area (A\(_{Du}\)) in units of m\(^{2}\). The DuBois body surface
area is given by:
Using this equation, an area of 1.8 m\(^{2}\) represents the surface
area of an average person of weight 70 kg and height 1.73 m
(Fanger 1967). In EnergyPlus, this average person area of 1.8
m\(^{2}\) is used for the
body surface area all thermal comfort models. The metabolic
rate is measured in mets, where 1 met = 58.2 W/m\(^{2}\).
The environmental variables that influence the conditions
of thermal comfort include:
Air Temperature (T\(_{a}\)),
Mean Radiant Temperature (T\(_{r}\)),
Relative air velocity (v),
Water vapor pressure in ambient air (P\(_{a}\)).
The Air Temperature (T\(_{a}\)), a direct environmental
index, is the dry-bulb temperature of the environment. It is
calculated using either the mean air temperature for the zone
in question or the air temperature calculated by some of the
more detailed zone air models available in EnergyPlus. The
Mean Radiant Temperature (T\(_{r}\)) is a rationally derived
environmental index defined as the uniform black-body
temperature that would result in the same radiant energy
exchange as in the actual environment. This value can be
calculated in several ways as outlined in the Mean Radiant
Temperature Calculation section later in this document. The
Relative air velocity (v) a direct environmental index is a
measure of the air motion obtainable via a hot wire or vane
anemometers. The Water vapor pressure in ambient air (P\(_{a}\)) is a direct environmental
index.
The physiological variables that influence the conditions
of thermal comfort include:
Skin Temperature (T\(_{sk}\)),
Core or Internal Temperature (T\(_{cr}\)),
Sweat Rate,
Skin Wettedness (w),
Thermal Conductance (K) between the core and
skin.
where the Skin Temperature (T\(_{sk}\)), the Core Temperature
(T\(_{cr}\)) and the Sweat
Rate are physiological indices. The Skin Wettedness (w) is a
rationally derived physiological index defined as the ratio of
the actual sweating rate to the maximum rate of sweating that
would occur if the skin were completely wet.
One more consideration is important in dealing with thermal
comfort - the effect of asymmetrical heating or cooling. This
could occur when there is a draft or when there is a radiant
flux incident on a person (which is what is of primary
interest to us here). Fanger (1967) noted that the human
regulatory system is quite tolerant of asymmetrical radiant
flux. A reasonable upper limit on the difference in mean
radiant temperature (T\(_{r}\)) from one direction to the
opposing direction is 15\(^{\circ}\)C. (ASHRAE 1984). This
limit is lower if there is a high air velocity in the
zone.
General Nomenclature list for Thermal Comfort
Models
Mathematical variable
Description
Units
Range
Source Code Variable
A\(_{Du}\)
Dubois body surface area
m\(^{2}\)
-
-
H
Internal heat production rate of
an occupant per unit area = M – W
W/m\(^{2}\)
-
IntHeatProd
I\(_{cl}\)
Thermal resistance of the
clothing
clo
-
CloUnit
M
Metabolic rate per unit
area
W/m\(^{2}\)
-
ActLevel
P\(_{a}\)
Water vapor pressure in ambient
air
Torr
-
VapPress
T\(_{a}\)
Air temperature
\(^{\circ}\)C
-
AirTemp
T\(_{cr}\)
Core or internal
temperature
\(^{\circ}\)C
-
CoreTemp
T\(_{r}\)
Mean radiant temperature
\(^{\circ}\)C
-
RadTemp
T\(_{sk}\)
Skin temperature
\(^{\circ}\)C
-
-
v
Relative air velocity
m/s
-
AirVel
W
The rate of heat loss due to the
performance of work
W/m\(^{2}\)
-
WorkEff
w
Skin wettedness
-
-
-
Mathematical
Models for Predicting Thermal Comfort[LINK]
Many researchers have been exploring ways to predict the
thermal sensation of people in their environment based on the
personal, environmental and physiological variables that
influence thermal comfort. From the research done, some
mathematical models that simulate occupants’ thermal response
to their environment have been developed. Most thermal comfort
prediction models use a seven or nine point thermal sensation
scale, as in the following tables.
Seven point Thermal Sensation Scale
Sensation
Description
3
Hot
2
Warm
1
slightly warm
0
neutral
-1
slightly cool
-2
cool
-3
cold
Nine point Thermal Sensation Scale
Sensation Value
Description
4
very hot
3
hot
2
warm
1
slightly warm
0
neutral
-1
slightly cool
-2
cool
-3
cold
-4
very cold
The most notable models have been developed by P.O. Fanger
(the Fanger Comfort Model), the J. B. Pierce Foundation (the
Pierce Two-Node Model), and researchers at Kansas State
University (the KSU Two-Node Model). Berglund (1978) presents
a detailed description of the theory behind these three
models.
Note for all Thermal Comfort reporting: Though the
published values for thermal comfort “vote” have a discrete
scale (e.g. –3 to +3 or –4 to +4), the calculations in
EnergyPlus are carried out on a continuous scale and, thus,
reporting may be “off the scale” with specific conditions
encountered in the space. This is not necessarily an error in
EnergyPlus – rather a different approach that does not take
the “limits” of the discrete scale values into account.
The main similarity of the three models is that all three
apply an energy balance to a person and use the energy
exchange mechanisms along with experimentally derived
physiological parameters to predict the thermal sensation and
the physiological response of a person due to their
environment. The models differ somewhat in the physiological
models that represent the human passive system (heat transfer
through and from the body) and the human control system (the
neural control of shivering, sweating and skin blood flow).
The models also differ in the criteria used to predict thermal
sensation. However, all three models use information from the
People
statement and the thermal comfort model is selected via the People
statement in a user’s input file. Scheduled parameters such as
the activity level, work efficiency, air velocity, and
clothing insulation level all have a direct bearing on the
thermal comfort models. For more information on the input of
these parameters, see the People
statement in the EnergyPlus Input/Output Reference. For more
information on how each individual thermal comfort model uses
these parameters, please consult the next several
sections.
Fanger’s Comfort model was the first human comfort model
that was developed. It was first published in 1967 (Fanger
1967), then updated in 1970 (Fanger 1970), and helped set the
stage for the Pierce and KSU models. The mathematical model
developed by P.O. Fanger is probably the most well known of
the three models and is the easiest to use because it has been
put in both chart and graph form.
Fanger developed the model based on the research he
performed at Kansas State University and the Technical
University of Denmark. Fanger used the seven-point form of a
thermal sensation scale along with numerous experiments
involving human subjects in various environments. He related
the subjects’ response to various environmental variables
which influence the condition of thermal comfort. Fanger’s
model is based upon an energy analysis that takes into account
all the modes of energy loss (L) from the body, including: the
convection and radiant heat loss from the outer surface of the
clothing, the heat loss by water vapor diffusion through the
skin, the heat loss by evaporation of sweat from the skin
surface, the latent and dry respiration heat loss and the heat
transfer from the skin to the outer surface of the clothing.
The model assumes that the person is thermally at steady state
with the interior environment.
The Fanger model was developed using the thermal sensation
votes from subjects at KSU and in Denmark, and the Predicted
Mean Vote (PMV) thermal sensation scale is based on how the
energy loss (L) deviates from the metabolic rate (M) in the
following form:
\[PMV = (0.303{e^{ - 0.036M}} +
0.028)(H - L)\]
In the EnergyPlus source code, PMV is calculated using the
following equations in conjunction with the equations shown
above:
The Pierce Two-Node model was developed at the John B.
Pierce Foundation at Yale University. The model has been
continually expanding since its first publication in 1970
(Gagge et.al. 1970). The most recent version on the model
appears in the 1986 ASHRAE Transactions (Gagge et.al.
1986).
The Pierce model thermally lumps the human body as two
isothermal, concentric compartments, one representing the
internal section or core (where all the metabolic heat is
assumed to be generated) and the other representing the skin.
This allows the passive heat conduction from the core
compartment to the skin to be taken into account. The boundary
line between the two compartments changes with the skin blood
flow rate per unit skin surface area (SKBF in L/h•m\(^{2}\)) and is described by \(\alpha\) – the fraction of total
body mass attributed to the skin compartment (Doherty and
Arens 1988).
Furthermore, the model takes into account the deviations of
the core, skin, and mean body temperature weighted by alpha
from their respective setpoints. Thermoregulatory effector
mechanisms (regulatory sweating, skin blood flow, and
shivering) are defined in terms of thermal signals from the
core, skin and body in \(^{\circ}\)C (Doherty and Arens
1988) by the following equations:
\[SI{G_{cr}} = {T_{cr}} -
36.8\]
\[SI{G_{sk}} = {T_{sk}} -
33.7\]
\[SI{G_b} = {T_b} -
36.49\]
In the EnergyPlus code, when SkinTemp is greater than
SkinTempSet (33.7\(^{\circ}\)C), then
SkinThermSigWarm = SkinTemp - SkinTempSet and SkinThermSigCold
= 0.0. Otherwise, when SkinTemp is less than or equal to
SkinTempSet, then SkinThermSigWarm = 0.0 and SkinThermSigCold
= SkinTempSet - SkinTemp.
In the EnergyPlus code, when CoreTemp is greater than
CoreTempSet (36.8\(^{\circ}\)C), then
CoreThermSigWarm = CoreTemp - CoreTempSet and CoreThermSigCold
= 0.0. Otherwise, when CoreTemp is less than or equal to
CoreTempSet, then CoreThermSigWarm = 0.0 and CoreThermSigCold
= CoreTempSet - CoreTemp.
In the EnergyPlus code, when AvgBodyTemp is greater than
AvgBodyTempSet(36.49\(^{\circ}\)C), then
BodyThermSigWarm = AvgBodyTemp - AvgBodyTempSet and
BodyThermSigCold = 0.0. Otherwise, when AvgBodyTemp is less
than or equal to AvgBodyTempSet, then BodyThermSigWarm = 0.0
and BodyThermSigCold = AvgBodyTempSet-AvgBodyTemp.
The skin blood flow rate in L/hr\(\cdot\)m\(^{2}\) is calculated using:
The latest version of the Pierce model (Fountain and
Huizenga 1997) discusses the concepts of SET* and ET*. The
Pierce model converts the actual environment into a “standard
environment” at a Standard Effective Temperature, SET*. SET*
is the dry-bulb temperature of a hypothetical environment at
50% relative humidity for subjects wearing clothing that would
be standard for the given activity in the real environment.
Furthermore, in this standard environment, the same
physiological strain, i.e. the same skin temperature, skin
wettedness and heat loss to the environment, would exist as in
the real environment. The Pierce model also converts the
actual environment into a environment at an Effective
Temperature, ET*, that is the dry-bulb temperature of a
hypothetical environment at 50% relative humidity and uniform
temperature (T\(_a\) = MRT)
where the subjects would experience the same physiological
strain as in the real environment.
In the latest version of the model, it is suggested that
the classical Fanger PMV be modified by using ET* or SET*
instead of the operative temperature. This gives a new index
PMV* which is proposed for dry or humid environments. It is
also suggested that PMV* is very responsive to the changes in
vapor permeation efficiency of the occupants clothing.
\[M = {M_{act}} +
{M_{shiv}}\]
which in the EnergyPlus code takes on the form ActLevel =
ActLevel + ActShiv.
In Pierce model, the convective heat transfer coefficient,
h\(_{c}\), varies with the
air velocity around body and metabolic rate. The model uses
the maximum value of following equations:
\[{h_c} = 8.6 \times
{v^{_{0.53}}}\]
\[{h_c} = 5.66{(M/58.2 -
0.85)^{0.39}}\]
In the EnergyPlus code, the following equations are used to
calculate h\(_{c}\) or
Hc:
Hc = 8.6*AirVel**0.53 where AirVel is reset to 0.137 if it
drops below this value
HcAct = 5.66*(ActMet - 0.85)**0.39 when ActMet is greater
than 0.9
When ActMet is greater than 0.9, EnergyPlus uses the larger
value of Hc and HcAct for h\(_{c}\).
Also, in the model, the radiant heat transfer coefficient,
h\(_{r}\), is defined by
following equation (Doherty and Arens 1988):
The total evaporative heat loss from the skin, E\(_{sk}\), includes evaporation of
water produced by regulatory sweating, E\(_{rsw}\), and evaporation of
water vapor that diffuses through the skin surface, E\(_{diff}\).
\[{E_{sk}} = {E_{rsw}} +
{E_{diff}}\]
\[{E_{rsw}} = 0.68 \times
S{W_{reg}}\]
\[{E_{diff}} = {w_{diff}} \times
{E_{\max }}\]
Within the EnergyPlus source code, these equations are
shown as:
The Pierce model has one additional heat flow term
describing the heat transfer between the internal core
compartment and the outer skin shell (Doherty and Arens
1988).
where 5.28 is the average body tissue conductance in
W/m\(^2 \cdot\) K and 1.163
is the thermal capacity of blood in W \(\cdot\) h/L \(\cdot\) K.
Thus, individual heat balance equations for core and skin
compartments are expressed using this term, Q\(_{c-s}\). New temperatures of
core, skin and body are calculated for each iteration from
rates of heat storage in the core and skin.
Besides PMV*, the Pierce Two Node Model uses the indices
TSENS and DISC as predictors of thermal comfort. Where TSENS
is the classical index used by the Pierce foundation and is a
function of the mean body temperature. DISC is defined as the
relative thermoregulatory strain that is needed to bring about
a state of comfort and thermal equilibrium. DISC is a function
of the heat stress and heat strain in hot environments and
equal to TSENS in cold environments. In summary, the Pierce
Model, for our purposes, uses four thermal comfort indices;
PMVET–a function of ET*, PMVSET–a function of SET*, TSENS and
DISC.
\[{T_{b - c}} = (0.185/58.2)(M -
W) + 36.313\]
\[{T_{b - h}} = (0.359/58.2)(M -
W) + 36.664\]
When \({T_b} \le {T_{b -
c}}\), TSENS is calculated using:
\[TSEN{S_c} = 0.68175({T_b} -
{T_{b - c}})\]
Otherwise, when \({T_b} >
{T_{b - c}}\), TSENS is calculated using:
The KSU Two-Node Model, developed at Kansas State
University, was published in 1977 (Azer and Hsu 1977). The KSU
model is quite similar to that of the Pierce Foundation. The
main difference between the two models is that the KSU model
predicts thermal sensation (TSV) differently for warm and cold
environment.
The KSU Two-Node Model is based on the changes that occur
in the thermal conductance between the core and the skin
temperature in cold environments. In warm environments, the
thermal conductance of the model is based on changes in the
skin wettedness.
In this model, metabolic heat production is generated in
the core which exchanges energy with the environment by
respiration, and the skin exchanges energy with the interior
environment by convection and radiation. In addition, body
heat is dissipated through the evaporation of sweat and/or
water vapor diffusion through the skin. These principles are
outlined in the following system of equations.
\[{W_{cr}}{C_{cr}}d{T_{cr}}/dt =
M - W - {Q_{res}} - KS({T_{cr}} - {T_{sk}})\]
Here, control signals, based on setpoint temperatures in
the skin and core, are introduced into the system of
equations, and these equations are integrated numerically for
small time increments or small increments in core and skin
temperature. The control signals modulate the thermoregulatory
mechanism and regulate the peripheral blood flow, the sweat
rate, and the increase of metabolic heat by active muscle
shivering. The development of the controlling functions of
skin conductance (KS), sweat rate (E\(_{sw}\)), and shivering (M\(_{shiv}\)) is based on their
correlation with the deviations in skin and core temperatures
from their setpoints.
In the KSU model, two new parameters are introduced and
used in correlating thermal sensations with their associated
physiological responses. Instead of correlating warm thermal
sensations with skin wettedness, it is correlated with a
wettedness factor defined by:
In addition, instead of correlating cold thermal sensation
with the skin temperature in the KSU model, it is correlated
with a factor identified as vasoconstriction factor defined
by:
The KSU model’s TSV was developed from experimental
conditions in all temperature ranges and for clo levels
between 0.05 clo and 0.7 clo and for activities levels ranging
from 1 to 6 mets (Berglund 1978).
Adaptive Comfort Model
Adaptive comfort model, intended for use in naturally
ventilated buildings, determines the acceptability of indoor
conditions given the monthly mean outdoor air temperature and
the indoor operative temperature. This is used as an index for
occupant adaptation to outdoor conditions, and determines the
acceptability of indoor conditions. The model also accounts
for people’s clothing adaptation in naturally conditioned
spaces by relating the acceptable range of indoor temperatures
to the outdoor climate, so it is not necessary to estimate the
clothing values for the space. No humidity or air-speed limits
are required when this option is used. This section summarizes
the adaptive comfort models based on the ASHRAE Standard
55-2010 and CEN 15251. Details are available in the two
standards.
Adaptive Comfort Model Based on ASHRAE Standard
55-2010
In ASHRAE Standard 55, the monthly mean outdoor air
temperature, used in the adaptive comfort model, is defined as
the simple running average of the previous thirty daily
average outdoor air temperatures.
The model defines two comfort regions: 80% Acceptability,
and 90% Acceptability. If the monthly mean outdoor air
temperature is not within the specified domain of 10.0 to
33.5C, the model is not applicable.
Acceptable operative
temperature ranges for naturally conditioned spaces (ASHRAE
Standard 55-2010)
The central line of the model (shown in red), or comfort
temperature, is defined as
\[{T_{ot}} = 0.31\cdot {T_o} +
17.8\]
where:
T\(_{ot}\) is the
operative temperature (\(^{\circ}\)C), calculated as the
average of the indoor air dry-bulb temperature and the mean
radiant temperature of zone inside surfaces
T\(_{o}\) is the monthly
mean outdoor air dry-bulb temperature (\(^{\circ}\)C).
If the .stat file is provided for the simulation, T\(_{o}\) is drawn directly from the
daily average temperatures in the .stat file, which provides a
value for each month. If no .stat file is provided, the
monthly mean outdoor temperature is a simple running average
of the previous thirty daily average temperatures, calculated
directly from the weather file (.epw):
T\(_{od-i}\) is defined as
the daily average temperature of the i\(^{th}\) previous day.
Note that the weather file must be a standard .epw
containing a full year of data.
The comfort regions for 80% and 90% acceptability are
symmetric about the central line.
For 90% Acceptability Limits:
\[T_{ot} = 0.31* T_{o} + 17.8 ±
2.5\]
80% Acceptability Limits:
\[T_{ot} = 0.31* T_{o} + 17.8 ±
3.5\]
If, using either method, T\(_{o}\) is less than 10\(^{\circ}\)C or greater than
33.5\(^{\circ}\)C, the model
is not applicable.
For a detailed description of this model, please see
ASHRAE Standard 55-2010, Thermal Environmental Conditions
for Human Occupancy.
Adaptive
Comfort Model Based on European Standard EN15251-2007[LINK]
The EN15251-2007 is similar to ASHRAE 55-2010, but with
slightly different curves of the indoor operative temperature
and acceptability limits (Fig. 2). The model, intended for use
in naturally ventilated buildings, determines the
acceptability of indoor conditions given the 7-day weighted
mean outdoor air temperature and the indoor operative
temperature. The 7-day weighted mean outdoor air temperature
(T\(_{rm}\)) is defined as
the weighted running average of the previous 7 daily average
outdoor air temperatures.
This weighted running average is calculated from a full
annual weather file that must be specified for the simulation.
This is used as an index for occupant adaptation to outdoor
conditions, and determines the acceptability of indoor
conditions. The model also accounts for people’s clothing
adaptation in naturally conditioned spaces by relating the
acceptable range of indoor temperatures to the outdoor
climate, so it is not necessary to estimate the clothing
values for the space. No humidity or air-speed limits are
required when this option is used. The model defines three
comfort regions: Category I (90%) Acceptability, Category II
(80%) Acceptability, and Category III (65%) Acceptability. If
T\(_{rm}\) is not within the
specified domain of 10.0 to 30.0C, the model is not
applicable.
Categories for European
Standard EN15251-2007Acceptable operative
temperature ranges for naturally conditioned spaces (CEN
EN15251-2007)
For 10\(^{\circ}\)C <
T\(_{rm}\) < 15\(^{\circ}\)C, the comfort
temperature of the lower boundaries of the comfort regions is
T\(_{comf}\) = 23.75\(^{\circ}\)C. That is, the lower
boundaries are constant according to the same ranges
above:
For Category I, 90% Acceptability Limits:
\[T_{ot} = 23.75 -
2.0\]
For Category II, 80% Acceptability Limits:
\[T_{ot} = 23.75 -
3.0\]
For Category III, 65% Acceptability Limits:
\[T_{ot} = 23.75 -
4.0\]
where:
\({T_{ot}}\) is the
operative temperature calculated as the average of the indoor
air dry-bulb temperature and the mean radiant temperature of
zone inside surfaces (\(^{\circ}\)C)
\(T_o\) is the mean
outdoor air dry-bulb temperature (\(^{\circ}\)C), calculated as the
weighted mean of the previous 7-day daily mean outdoor air
dry-bulb temperature (T\(_{od}\)) using:
In most building energy simulations, thermal comfort
condition is calculated based on the assumption that the
clothing insulation is equal to a constant value of 0.5 clo
during the cooling season and 1.0 clo during heating season.
Usually those two values are used and the change from 0.5 to 1
or vice-versa is made suddenly from one day to another. In
addition, there is no standardized guideline on how to set
clothing insulation schedules in the international standards.
This simplified assumption may lead to systems that are
incorrectly sized and operated and to the incorrect assessment
of comfort conditions. In reality, occupants frequently adjust
their clothing depending on the thermal conditions around
them, as opposed to the assumption of constant clothing
values. Therefore, the clothing insulation variation should be
captured during the building simulation to realistically model
HVAC systems. In order to overcome the limitations of the
constant clothing insulation assumption, three new predictive
clothing insulation models were developed by Schiavon and Lee
(2012) based on 6,333 selected observations taken from ASHRAE
RP-884 and RP-921 databases. The first and third models vary
the clothing insulation as a function of outdoor air
temperature measured at 6 o’clock and the second model takes
into account both 6 o’clock outdoor air temperature and indoor
operative temperature when adjusting the clothing insulation.
The dynamic clothing models should be implemented in dynamic
building energy simulation.
The model proposed to ASHRAE 55 is described below.
For t\(_{a(out,6)}\) <
-5\(^{\circ}\)C:
\[{I_{cl}} = 1.00\]
For -5\(^{\circ}\)C \(\leq\)\(t_{a(out,6)}\) < 5\(^{\circ}\)C:
where \(I_{cl}\) is the
clothing insulation value and \(t_{a(out,6)}\) is the outdoor air
temperature measured at 6 o’clock in the morning. Figure 5
illustrates the proposed clothing insulation model.
Clothing Schedule
Illustration
In Figure 4,
clothing insulation schedule for a fixed model (blue)
typically used in energy simulation software and for the
clothing model based on outdoor air temperature measured at 6
o’clock. Climate data for Chicago O’hare International Airport
has been used.
Graphical representation of the
proposed clothing insulation model
The dynamic predictive clothing insulation model is
implemented into EnergyPlus for realistic energy simulation.
Addenda A to ASHRAE 55 with the clothing model has been
approved by the ASHRAE committee and the chance to be included
in ASHRAE 55-2013 is high.
Lee KH, Schiavon S. 2013. Influence of three dynamic
predictive clothing insulation models on building energy use,
HVAC sizing and thermal comfort. Submitted to Journal. http://escholarship.org/uc/item/3sx6n876
(link to the freely available pre-print version)
There are three options to calculate mean radiant
temperature in the thermal comfort models. One is the zone
averaged MRT, another is the surface weighted MRT, and the
other is angle factor MRT. The zone averaged MRT is calculated
on the assumption that a person is in the center of a space,
whereas the surface weighted MRT is calculated in
consideration of the surface that a person is closest to, and
the angle factor MRT is calculated based on angle factors
between a person and the different surfaces in a space. Here,
the surface weighted MRT is the average temperature of the
selected surface and zone averaged MRT for the remaining
surfaces in the zone and is intended to represent conditions
in the limit as a person gets closer and closer to a
particular surface. In that limit, half of the person’s
radiant field will be dominated by that surface and the other
half will be exposed to the rest of the zone. Note that the
surface weighted MRT is only an approximation. The angle
factor MRT is the mean temperature of the surrounding surface
temperatures weighted according to the magnitude of the
respective angle factors and allows the user to more
accurately predict thermal comfort at a particular location
within a space.
Nomenclature and variable list for MRT
calculation
The radiant temperature for the "zone averaged" option is
simply calculated from the zone mean radiant temperature (MRT)
without weighting any surface temperature of the zone more
than the standard MRT calculation.
\[{T_r} = {T_{r -
avg}}\]
where the standard MRT is calculated using the following
equation summed over all zone surfaces:
In the surface weighted option, the radiant temperature is
the average temperature of the modified zone averaged MRT and
the temperature of the surface that a person is closest
to.
\[{T_r} = ({T_{r - avg*}} +
{T_{surf}})/2\]
where the modified zone averaged MRT is calculated the same
way as the standard MRT except that the surface closest to the
person is left out of the summation:
where when i is equal to the surface being used for
weighting it is not included in either summation.
When the angle factor option is requested, the radiant
temperature is the mean value of surrounding surface
temperatures weighted by the surface emissivity, the size of
the respective angle factors between a person and each
surface, and the temperature to the fourth power for the
surface.
If all surfaces have the same emissivity that is close to
unity, the emissivities in the above equation can be ignored.
However, since this is not always the case, the emissivity
terms must be included in the above equation. In addition, the
temperatures to the fourth power in the above equation could
be simplified to linear temperatures when the temperatures of
the surfaces are fairly close. However, as these temperatures
get further apart, this linear approximation becomes
increasingly poor. As a result, since there is no guarantee
that inside face surface temperatures will be close, the
fourth order temperature terms are used to calculate the
radiant temperature.
ASHRAE 55 Elevated Air
Speed Cooling Effect Model[LINK]
ASHRAE Standard 55-2017 Section 5.3 requires that the
Elevated Air Speed Comfort Zone
Method be used when average air speed \(v_{a}\) is greater than 0.10 m/s.
The method provides cooling credit for elevated air velocity
in the space. The method can be used to evaluate passive
cooling technologies such as natural ventilation, ceiling fan,
and portable fan.
The Pierce Two-Node Standard Effective Temperature (SET)
model is used to account for the cooling effect of air speeds
greater than the 0.10 m/s. Specifically, for a given set of
environmental and personal variables, including an elevated
average air speed, an average air temperature \(t_{a}\), and a mean radiant
temperature \(t_{r}\), the
SET is first calculated. Then the average air speed \(v_{a}\) is replaced by still air
(0.1 m/s), and the average air temperature and radiant
temperature are adjusted according to the cooling effect (CE).
The CE of the elevated air speed is the value that, when
subtracted equally from both the average air temperature and
the mean radiant temperature, yields the same SET under still
air as in the first SET calculation under elevated air
speed.
The following is a formal description of this process. To
define the CE, we assert that it satisfies the following:
where \(t_{a}\) is the
average air temperature, \(t_{r}\) is the mean radiant
temperature, \(v_{elev}\) is
the elevated average air speed, such that \(v_{elev} > 0.1 m/s\) , \(v_{still}\) is the elevated
average air speed (\(v_{still} = 0.1
m/s\)). The other parameters (indoor air humidity,
clothing, metabolic rate) that stay the same are denoted by
“*”.
It should be noted that \(v_{elev}\) is the relative air
velocity caused by body movement and not the air speed
measured by the air velocity sensor. It can be calculate using
the function below.
The Cooling Effect adjusted PMV/PPD for an environment with
elevated average air speed is calculated using the adjusted
average air temperature, the adjusted radiant temperature, and
still air (0.1 m/s). The following are equations to calculate
the adjusted PMV and PPD.
Draft is unwanted local cooling of the body caused by air
movement. It is most prevalent when the whole-body thermal
sensation is cool (below neutral). Draft sensation depends on
air speed, air temperature, activity, and clothing.
Sensitivity to draft is greatest where the skin is not covered
by clothing, especially the head region comprising the head,
neck, and shoulders and the leg region comprising the ankles,
feet, and legs. Draft at the lower leg region may occur in the
buildings conditioned by thermally stratified systems, such as
displacement ventilation and underfloor air distribution, or
with cold-dropping airflow along external walls and/or
windows.
The predicted percentage dissatisfied on draft at ankle
level \(PPD_{AD}\) is used as
the metric to evaluate the ankle draft risk as a function of
PMV and air speed at the ankle level (0.1 m). The following is
the equation to calculate \(PPD_{AD}\).
Where \(v_{r}\) is the
relative air velocity caused by body movement, and \(v_{ankle}\) is the air speed at
0.1 m above the floor.
This equation is only applicable for \(v_{r} < 0.2 m/s\) . And the
subject’s metabolic rate and clothing level should be kept
below 1.3 met and 0.7 clo, respectively. PPD at ankle draft
will be set to -1.0 if if these conditions are not met.
It should be noted that the metrics only measures the
predicted percentage dissatisfied on the sensation of draft.
\(PPD_{AD}\) levels at
various air speeds and thermal sensations are depicted in
Figure 6
ASHRAE. 1984. “High Intensity Infrared Radiant Heating”,
1984 Handbook of Systems and Equipment, American Society of
Heating, Refrigerating and Air Conditioning Engineers,
Atlanta, GA, Chapter 18.
ASHRAE. 1985. “Physiological Principles for Comfort and
Health,” 1985 Handbook of Fundamentals, American Society of
Heating, Refrigerating and Air Conditioning Engineers,
Atlanta, GA, Chapter 8.
ASHRAE. 1993. “Physiological Principles and Thermal
Comfort”, 1993 ASHRAE Handbook of Fundamentals, American
Society of Heating, Refrigerating and Air Conditioning
Engineers, Atlanta, GA, Chapter 8.
ASHRAE. 2010. “Standard 55-2010 – Thermal Environmental
Conditions for Human Occupancy (ANSI approved)”, American
Society of Heating, Refrigerating and Air Conditioning
Engineers, Atlanta, GA.
ASHRAE. 2017. “Standard 55-2017 – Thermal Environmental
Conditions for Human Occupancy (ANSI approved)”, American
Society of Heating, Refrigerating and Air Conditioning
Engineers, Atlanta, GA.
Azer, N.Z., Hsu, S. 1977. “The prediction of Thermal
Sensation from Simple model of Human Physiological Regulatory
Response”, ASHRAE Trans., Vol.83, Pt 1.
Berglund, Larry. 1978. “Mathematical Models for Predicting
the Thermal Comfort Response of Building
Occupants”, ASHRAE Trans., Vol.84.
Doherty, T.J., Arens, E. 1988. “Evaluation of the
Physiological Bases of Thermal Comfort Models”, ASHRAE Trans.,
Vol.94, Pt 1.
Du Bois, D. and E.F. 1916. “A Formula to Estimate
Approximate Surface Area, if Height and Weight are Known”,
Archives of internal Medicine, Vol.17.
CEN. 2007. “Standard EN15251 Indoor environmental input
parameters for design and assessment of energy performance of
buildings addressing indoor air quality, thermal environment,
lighting and acoustics”. Bruxelles: European committee for
Standardisation.
Fanger, P.O. 1970. Thermal Comfort-Analysis and
Applications in Environmental Engineering, Danish Technical
Press, Copenhagen.
Fanger, P.O. 1986. “Radiation and Discomfort”, ASHRAE
Journal. February 1986.
Fanger P.O. 1967. “Calculation of Thermal Comfort:
Introduction of a Basic Comfort Equation”, ASHRE Trans.,
Vol.73, Pt 2.
Fountain, Marc.E., Huizenga, Charlie. 1997 “A Thermal
Sensation Prediction Tool for Use by the Profession”, ASHRAE
Trans., Vol.103, Pt 2.
Gagge, A.P., Stolwijk, J. A. J., Nishi, Y. 1970. “An
Effective Temperature Scale Based on a Simple Model of Human
Physiological Regulatory Response”, ASHRAE Trans., Vol.70, Pt
1.
Gagge, A.P., Fobelets, A.P., Berglund, L. G. 1986. “A
Standard Predictive Index of Human Response to the Thermal
Environment”, ASHRAE Trans., Vol.92, Pt 2.
Hsu, S. 1977. “A Thermoregulatory Model for Heat
Acclimation and Some of its Application”, Ph. D. Dissertation,
Kansas State University.
Int-Hout, D. 1990. “Thermal Comfort Calculation / A
Computer Model”, ASHRAE Trans., Vol.96, Pt 1.
ISO. 1983. “Determination of the PMV and PPD Indices and
Specification of the Conditions for Thermal Comfort”, DIS
7730, Moderate Thermal Environment, 1983.
Liu S., Schiavon S., Kabanshi A., Nazaroff W.W. 2017.
P̈redicted percentage dissatisfied with ankle draft,̈ Indoor
Air, Vol.27.
Occupant Thermal Comfort[LINK]
The integration of a sophisticated building thermal analysis tool with thermal comfort models allows one to perform an energy analysis on a zone and simultaneously determine if the environmental control strategy will be sufficient for the occupants to be thermally comfortable. This section is intended to provide background on thermal comfort, present an overview of state of the art thermal comfort models, and present the mathematical models that have been incorporated into EnergyPlus.
Thermal comfort modeling in EnergyPlus is controlled primarily by the People input object. This includes input for selecting the type of thermal comfort model that is desired by the user as well as parameters that serve as inputs to the thermal comfort models. These parameters include the activity level, the work efficiency, the air velocity and the clothing insulation level for people within the space. All four of these parameters can be scheduled. More information on the People input object can be found in the EnergyPlus Input/Output Reference. More information on how each of these parameters is used and the specific modeling equations for the thermal comfort models can be found below.
Background on Thermal Comfort Models[LINK]
Throughout the last few decades, researchers have been exploring the thermal, physiological and psychological response of people in their environment in order to develop mathematical models to predict these responses. Researchers have empirically determined building occupants’ thermal responses to the combined thermal effect of the personal, environmental and physiological variables that influence the condition of thermal comfort.
There are two personal variables that influence the condition of thermal comfort: the thermal resistance of the clothing (I\(_{cl}\)), and the metabolic rate (H/A\(_{Du}\)).
The thermal resistance of the clothing (I\(_{cl}\)) is measured in units of “clo.” The 1985 ASHRAE Handbook of Fundamentals (ASHRAE 1985) suggests multiplying the summation of the individual clothing items clo value by a factor of 0.82 to determine the overall clo value for clothing ensembles.
The metabolic rate (H/A\(_{Du}\)) is a measure of the internal heat production rate of an occupant (H) in W/hr per unit of “Dubois” body surface area (A\(_{Du}\)) in units of m\(^{2}\). The DuBois body surface area is given by:
\[{A_{Du}} = 0.202{(weight)^{0.425}}{(height)^{0.725}}\]
Using this equation, an area of 1.8 m\(^{2}\) represents the surface area of an average person of weight 70 kg and height 1.73 m (Fanger 1967). In EnergyPlus, this average person area of 1.8 m\(^{2}\) is used for the body surface area all thermal comfort models. The metabolic rate is measured in mets, where 1 met = 58.2 W/m\(^{2}\).
The environmental variables that influence the conditions of thermal comfort include:
Air Temperature (T\(_{a}\)),
Mean Radiant Temperature (T\(_{r}\)),
Relative air velocity (v),
Water vapor pressure in ambient air (P\(_{a}\)).
The Air Temperature (T\(_{a}\)), a direct environmental index, is the dry-bulb temperature of the environment. It is calculated using either the mean air temperature for the zone in question or the air temperature calculated by some of the more detailed zone air models available in EnergyPlus. The Mean Radiant Temperature (T\(_{r}\)) is a rationally derived environmental index defined as the uniform black-body temperature that would result in the same radiant energy exchange as in the actual environment. This value can be calculated in several ways as outlined in the Mean Radiant Temperature Calculation section later in this document. The Relative air velocity (v) a direct environmental index is a measure of the air motion obtainable via a hot wire or vane anemometers. The Water vapor pressure in ambient air (P\(_{a}\)) is a direct environmental index.
The physiological variables that influence the conditions of thermal comfort include:
Skin Temperature (T\(_{sk}\)),
Core or Internal Temperature (T\(_{cr}\)),
Sweat Rate,
Skin Wettedness (w),
Thermal Conductance (K) between the core and skin.
where the Skin Temperature (T\(_{sk}\)), the Core Temperature (T\(_{cr}\)) and the Sweat Rate are physiological indices. The Skin Wettedness (w) is a rationally derived physiological index defined as the ratio of the actual sweating rate to the maximum rate of sweating that would occur if the skin were completely wet.
One more consideration is important in dealing with thermal comfort - the effect of asymmetrical heating or cooling. This could occur when there is a draft or when there is a radiant flux incident on a person (which is what is of primary interest to us here). Fanger (1967) noted that the human regulatory system is quite tolerant of asymmetrical radiant flux. A reasonable upper limit on the difference in mean radiant temperature (T\(_{r}\)) from one direction to the opposing direction is 15\(^{\circ}\)C. (ASHRAE 1984). This limit is lower if there is a high air velocity in the zone.
Mathematical Models for Predicting Thermal Comfort[LINK]
Many researchers have been exploring ways to predict the thermal sensation of people in their environment based on the personal, environmental and physiological variables that influence thermal comfort. From the research done, some mathematical models that simulate occupants’ thermal response to their environment have been developed. Most thermal comfort prediction models use a seven or nine point thermal sensation scale, as in the following tables.
The most notable models have been developed by P.O. Fanger (the Fanger Comfort Model), the J. B. Pierce Foundation (the Pierce Two-Node Model), and researchers at Kansas State University (the KSU Two-Node Model). Berglund (1978) presents a detailed description of the theory behind these three models.
Note for all Thermal Comfort reporting: Though the published values for thermal comfort “vote” have a discrete scale (e.g. –3 to +3 or –4 to +4), the calculations in EnergyPlus are carried out on a continuous scale and, thus, reporting may be “off the scale” with specific conditions encountered in the space. This is not necessarily an error in EnergyPlus – rather a different approach that does not take the “limits” of the discrete scale values into account.
The main similarity of the three models is that all three apply an energy balance to a person and use the energy exchange mechanisms along with experimentally derived physiological parameters to predict the thermal sensation and the physiological response of a person due to their environment. The models differ somewhat in the physiological models that represent the human passive system (heat transfer through and from the body) and the human control system (the neural control of shivering, sweating and skin blood flow). The models also differ in the criteria used to predict thermal sensation. However, all three models use information from the People statement and the thermal comfort model is selected via the People statement in a user’s input file. Scheduled parameters such as the activity level, work efficiency, air velocity, and clothing insulation level all have a direct bearing on the thermal comfort models. For more information on the input of these parameters, see the People statement in the EnergyPlus Input/Output Reference. For more information on how each individual thermal comfort model uses these parameters, please consult the next several sections.
Fanger Comfort Model[LINK]
Fanger’s Comfort model was the first human comfort model that was developed. It was first published in 1967 (Fanger 1967), then updated in 1970 (Fanger 1970), and helped set the stage for the Pierce and KSU models. The mathematical model developed by P.O. Fanger is probably the most well known of the three models and is the easiest to use because it has been put in both chart and graph form.
Fanger Model Nomenclature List[LINK]
Description of the model and algorithm[LINK]
Fanger developed the model based on the research he performed at Kansas State University and the Technical University of Denmark. Fanger used the seven-point form of a thermal sensation scale along with numerous experiments involving human subjects in various environments. He related the subjects’ response to various environmental variables which influence the condition of thermal comfort. Fanger’s model is based upon an energy analysis that takes into account all the modes of energy loss (L) from the body, including: the convection and radiant heat loss from the outer surface of the clothing, the heat loss by water vapor diffusion through the skin, the heat loss by evaporation of sweat from the skin surface, the latent and dry respiration heat loss and the heat transfer from the skin to the outer surface of the clothing. The model assumes that the person is thermally at steady state with the interior environment.
\[M = L\]
\[L = {Q_{res}} + {Q_{dry}} + {E_{sk}}\]
\[{Q_{res}} = {E_{res}} + {C_{res}} = 0.000017M(5867 - {P_a}) + 0.0014M(34 - {T_a})\]
In the EnergyPlus source code, Q\(_{res}\), E\(_{res}\) and C\(_{res}\) are calculated using the following equations, respectively:
RespHeatLoss = LatRespHeatLoss + DryRespHeatLoss
LatRespHeatLoss = 0.000017*ActLevel*(5867. - VapPress)
DryRespHeatLoss = 0.0014*ActLevel*(34.- AirTemp)
\[{Q_{dry}} = {Q_c} + {Q_r}\]
\[{Q_c} = {h_c} \times {f_{cl}}({T_{cl}} - {T_a})\]
\[{Q_{r}}=3.96*f_{cl}*{[}(0.01*T_{cla})^{4}-(0.01*T_{ra})^{4}{]} \label{eq:FangerQr}\]
In the EnergyPlus source code, Q\(_{dry}\), Q\(_{c}\) and Q\(_{r}\) are calculated using the following equations, respectively:
DryHeatLoss = ConvHeatLoss + RadHeatLoss
ConvHeatLos = Hc*CloBodyRat*(CloSurfTemp - AirTemp)
RadHeatLoss = 3.96*CloBodyRat*[(0.01*AbsCloSurfTemp)**4 - (0.01*AbsRadTemp)**4]
\[{E_{rsw}} = 0.42(H - 58.2)~~~~for~\left(H > 58.2\right)\]
\[{E_{rsw}} = 0~~~~for~\left(H \le 58.2\right)\]
\[{E_{f}}=0.00305*(5733.0-6.99H-P_{a})\]
\[{E_{sk}} = {E_{rsw}} + {E_{diff}}\]
In the EnergyPlus source code, E\(_{rsw}\), E\(_{f}\) and E\(_{sk}\) are calculated using the following equations, respectively:
EvapHeatLossRegComf = 0.42*(IntHeatProd - ActLevelConv) or 0.0 depending on H value
EvapHeatLossDiff = 0.00305*(5733.0 - 6.99*IntHeatProd - VapPress)
EvapHeatLoss = EvapHeatLossRegComf + EvapHeatLossDiff
The Fanger model was developed using the thermal sensation votes from subjects at KSU and in Denmark, and the Predicted Mean Vote (PMV) thermal sensation scale is based on how the energy loss (L) deviates from the metabolic rate (M) in the following form:
\[PMV = (0.303{e^{ - 0.036M}} + 0.028)(H - L)\]
In the EnergyPlus source code, PMV is calculated using the following equations in conjunction with the equations shown above:
PMV = ThermSensTransCoef*(IntHeatProd - EvapHeatLoss - RespHeatLoss - DryHeatLoss)
ThermSensTransCoef = 0.303*EXP(-0.036*ActLevel) + 0.028
IntHeatProd = ActLevel - WorkEff
Predicted Percent of Dissatisfied (PPD) people at each PMV is calculated as follows:
\[PPD = 100.0 - 95.0*EXP(-0.03353{PMV^{4}} - 0.2179{PMV^{2}})\]
Pierce Two-Node Model[LINK]
The Pierce Two-Node model was developed at the John B. Pierce Foundation at Yale University. The model has been continually expanding since its first publication in 1970 (Gagge et.al. 1970). The most recent version on the model appears in the 1986 ASHRAE Transactions (Gagge et.al. 1986).
Pierce Two-Node Model Nomenclature List[LINK]
Description of the model and algorithm[LINK]
The Pierce model thermally lumps the human body as two isothermal, concentric compartments, one representing the internal section or core (where all the metabolic heat is assumed to be generated) and the other representing the skin. This allows the passive heat conduction from the core compartment to the skin to be taken into account. The boundary line between the two compartments changes with the skin blood flow rate per unit skin surface area (SKBF in L/h•m\(^{2}\)) and is described by \(\alpha\) – the fraction of total body mass attributed to the skin compartment (Doherty and Arens 1988).
\[\alpha = 0.0417737 + 0.7451832/(SKBF + 0.585417)\]
In the EnergyPlus code, \(\alpha\) or SkinMassRat is calculated using the equivalent equation:
SkinMassRat = 0.0417737 + 0.7451832/(SkinBloodFlow + 0.585417)
Furthermore, the model takes into account the deviations of the core, skin, and mean body temperature weighted by alpha from their respective setpoints. Thermoregulatory effector mechanisms (regulatory sweating, skin blood flow, and shivering) are defined in terms of thermal signals from the core, skin and body in \(^{\circ}\)C (Doherty and Arens 1988) by the following equations:
\[SI{G_{cr}} = {T_{cr}} - 36.8\]
\[SI{G_{sk}} = {T_{sk}} - 33.7\]
\[SI{G_b} = {T_b} - 36.49\]
In the EnergyPlus code, when SkinTemp is greater than SkinTempSet (33.7\(^{\circ}\)C), then SkinThermSigWarm = SkinTemp - SkinTempSet and SkinThermSigCold = 0.0. Otherwise, when SkinTemp is less than or equal to SkinTempSet, then SkinThermSigWarm = 0.0 and SkinThermSigCold = SkinTempSet - SkinTemp.
In the EnergyPlus code, when CoreTemp is greater than CoreTempSet (36.8\(^{\circ}\)C), then CoreThermSigWarm = CoreTemp - CoreTempSet and CoreThermSigCold = 0.0. Otherwise, when CoreTemp is less than or equal to CoreTempSet, then CoreThermSigWarm = 0.0 and CoreThermSigCold = CoreTempSet - CoreTemp.
In the EnergyPlus code, when AvgBodyTemp is greater than AvgBodyTempSet(36.49\(^{\circ}\)C), then BodyThermSigWarm = AvgBodyTemp - AvgBodyTempSet and BodyThermSigCold = 0.0. Otherwise, when AvgBodyTemp is less than or equal to AvgBodyTempSet, then BodyThermSigWarm = 0.0 and BodyThermSigCold = AvgBodyTempSet-AvgBodyTemp.
The skin blood flow rate in L/hr\(\cdot\)m\(^{2}\) is calculated using:
\[SKBF = (6.3 + C{}_{dil} \times SI{G_{cr}})/(1 + {S_{tr}} \times (SI{G_{sk}}))\]
In the EnergyPlus code, this equation is calculated using the following equations:
SkinBloodFlow = (6.3 + VasodilationFac)/(1. + VasoconstrictFac)
VasodilationFac = SkinBloodFlowConst*CoreWarmDelTemp
VasoconstrictFac = Str*SkinColdDelTemp
The rate of regulatory sweating in g/hr•m\(^{2}\) is calculated using:
\[S{W_{reg}} = {C_{sw}}SI{G_b}{e^{(SI{G_{sk}}/10.7)}}\]
and the shivering response in W/m\(^{2}\) is calculated using:
\[{M_{shiv}} = 19.4(SI{G_{cr}})(SI{G_{sk}})\]
In the EnergyPlus code, the sweat and shivering response determined by the above two equations are calculated using the follow expressions:
RegSweat = SweatContConst*BodyThermSigWarm*EXP(SkinThermSigWarm/10.7)
ShivResponse = 19.4*SkinThermSigCold*CoreThermSigCold
The latest version of the Pierce model (Fountain and Huizenga 1997) discusses the concepts of SET* and ET*. The Pierce model converts the actual environment into a “standard environment” at a Standard Effective Temperature, SET*. SET* is the dry-bulb temperature of a hypothetical environment at 50% relative humidity for subjects wearing clothing that would be standard for the given activity in the real environment. Furthermore, in this standard environment, the same physiological strain, i.e. the same skin temperature, skin wettedness and heat loss to the environment, would exist as in the real environment. The Pierce model also converts the actual environment into a environment at an Effective Temperature, ET*, that is the dry-bulb temperature of a hypothetical environment at 50% relative humidity and uniform temperature (T\(_a\) = MRT) where the subjects would experience the same physiological strain as in the real environment.
In the latest version of the model, it is suggested that the classical Fanger PMV be modified by using ET* or SET* instead of the operative temperature. This gives a new index PMV* which is proposed for dry or humid environments. It is also suggested that PMV* is very responsive to the changes in vapor permeation efficiency of the occupants clothing.
\[M = {M_{act}} + {M_{shiv}}\]
which in the EnergyPlus code takes on the form ActLevel = ActLevel + ActShiv.
\[L = {Q_{res}} + {Q_{dry}} + {E_{sk}} + W\]
\[\begin{array}{l}{Q_{res}} = {E_{res}} + {C_{res}} = 0.0023M(44 - {P_{a}(torr)}) + 0.0014M(34 - {T_a})\\{Q_{res}} = 0.017251M(5.8662 - {P_{a}(kPa)}) + 0.0014M(34 - {T_a})\end{array}\]
In the EnergyPlus code, the calculation of Q\(_{res}\) or RespHeatLoss is accomplished using the following equations:
RespHeatLoss = LatRespHeatLoss + DryRespHeatLoss
LatRespHeatLoss = 0.017251*ActLevel*(5.8662 - VapPress)
DryRespHeatLoss = 0.0014*ActLevel*(34.- AirTemp)
\[{Q_{dry}} = {Q_c} + {Q_r}\]
\[{Q_c} = {h_c} \times {f_{cl}}({T_{cl}} - {T_a})\]
\[{Q_r} = {h_r} \times {f_{cl}}({T_{cl}} - {T_r}) \label{eq:PierceQr}\]
Q\(_{dry}\) or DryHeatLoss is calculated in the EnergyPlus code using the following equation:
DryHeatLoss = CloBodyRat*(Hc*(CloSurfTemp - AirTemp) + Hr*(CloSurfTemp - RadTemp))
In Pierce model, the convective heat transfer coefficient, h\(_{c}\), varies with the air velocity around body and metabolic rate. The model uses the maximum value of following equations:
\[{h_c} = 8.6 \times {v^{_{0.53}}}\]
\[{h_c} = 5.66{(M/58.2 - 0.85)^{0.39}}\]
In the EnergyPlus code, the following equations are used to calculate h\(_{c}\) or Hc:
Hc = 8.6*AirVel**0.53 where AirVel is reset to 0.137 if it drops below this value
HcAct = 5.66*(ActMet - 0.85)**0.39 when ActMet is greater than 0.9
When ActMet is greater than 0.9, EnergyPlus uses the larger value of Hc and HcAct for h\(_{c}\).
Also, in the model, the radiant heat transfer coefficient, h\(_{r}\), is defined by following equation (Doherty and Arens 1988):
\[{h_r} = 4. \times {f_{eff}}\varepsilon \sigma {(({T_{cl}} + {T_r})/2 + 273.15)^3}\]
In the EnergyPlus code, h\(_{r}\) or Hr is calculated using the following equation:
Hr = 4.*RadSurfEff*StefanBoltz*((CloSurfTemp + RadTemp)/2. + TAbsConv)**3
In the Pierce model, T\(_{cl}\) in \(^{\circ}\)C is estimated by each iteration using following equation:
\[{T_{cl}} = ({T_{sk}}/{I_{cl}} + {f_{cl}}({h_c}{T_a} + {h_r}{T_r}))/(1/{I_{cl}} + {f_{cl}}({h_c} + {h_r}))\]
Or as shown in the EnergyPlus code:
CloSurfTemp = (CloCond*SkinTemp + CloBodyRat*(Hc*AirTemp+Hr*RadTemp))
/(CloCond + CloBodyRat*(Hc+Hr))
The total evaporative heat loss from the skin, E\(_{sk}\), includes evaporation of water produced by regulatory sweating, E\(_{rsw}\), and evaporation of water vapor that diffuses through the skin surface, E\(_{diff}\).
\[{E_{sk}} = {E_{rsw}} + {E_{diff}}\]
\[{E_{rsw}} = 0.68 \times S{W_{reg}}\]
\[{E_{diff}} = {w_{diff}} \times {E_{\max }}\]
Within the EnergyPlus source code, these equations are shown as:
EvapHeatLoss = EvapHeatLossRegSweat + EvapHeatLossRegDiff
RegHeatLoss = 0.68*RegSweat
DiffHeatLoss = SkinWetDiff*MaxEvapHeatLoss
where 0.68 is the passive water vapor diffusion rate in g/h·m\(^{2}\)·Torr and
\[{w_{diff}} = 0.06(1 - {w_{rsw}})\]
\[{E_{\max }} = {h_e}'({P_{sk}} - {P_a})\]
\[{w_{rsw}} = {E_{rsw}}/{E_{\max }}\]
These equations within the EnergyPlus source code appear as:
SkinWetDiff = .06*(1.-SkinWetSweat)
MaxEvapHeatLoss = (1./TotEvapHeatResist)*(SatSkinVapPress - VapPress)
SkinWetSweat = EvapHeatLossRegSweat/MaxEvapHeatLoss
The Pierce model has one additional heat flow term describing the heat transfer between the internal core compartment and the outer skin shell (Doherty and Arens 1988).
\[{Q_{crsk}} = (5.28 + 1.163SKBF)({T_{cr}} - {T_{sk}})\]
or as shown in the EnergyPlus source code:
HeatFlow = (CoreTemp-SkinTemp)*(5.28 + 1.163*SkinBloodFlow)
where 5.28 is the average body tissue conductance in W/m\(^2 \cdot\) K and 1.163 is the thermal capacity of blood in W \(\cdot\) h/L \(\cdot\) K.
Thus, individual heat balance equations for core and skin compartments are expressed using this term, Q\(_{c-s}\). New temperatures of core, skin and body are calculated for each iteration from rates of heat storage in the core and skin.
\[{S_{sk}} = {Q_{c - s}} - {Q_c} - {Q_r} - {E_{sk}}\]
\[{S_{cr}} = M - W - {Q_{res}} - {Q_{c - s}}\]
These equations are represented by the following source code lines in EnergyPlus:
SkinHeatStorage = HeatFlow - DryHeatLoss - EvapHeatLoss
CoreHeatStorage = IntHeatProd - RespHeatLoss - HeatFlow
As a result, PMV evaluated for ET* and SET* can be calculated using:
\[PMVET = (0.303{e^{ - 0.036M}} + 0.028)(H - {L_{ET*}})\]
\[PMVSET = (0.303{e^{ - 0.036M}} + 0.028)(H - {L_{SET*}})\]
These equations are represented by the following lines of source code in EnergyPlus:
ThermSensTransCoef = 0.303*EXP(-0.036*ActLevel) + 0.028
PMVET = ThermSensTransCoef*(IntHeatProd - EvapHeatLossDiff - EvapHeatLossRegComf
- RespHeatLoss - DryHeatLossET)
PMVSET = ThermSensTransCoef*(IntHeatProd - EvapHeatLossDiff
- EvapRegHeatLossRegComf - RespHeatLoss - DryHeatLossSET)
Besides PMV*, the Pierce Two Node Model uses the indices TSENS and DISC as predictors of thermal comfort. Where TSENS is the classical index used by the Pierce foundation and is a function of the mean body temperature. DISC is defined as the relative thermoregulatory strain that is needed to bring about a state of comfort and thermal equilibrium. DISC is a function of the heat stress and heat strain in hot environments and equal to TSENS in cold environments. In summary, the Pierce Model, for our purposes, uses four thermal comfort indices; PMVET–a function of ET*, PMVSET–a function of SET*, TSENS and DISC.
\[{T_{b - c}} = (0.185/58.2)(M - W) + 36.313\]
\[{T_{b - h}} = (0.359/58.2)(M - W) + 36.664\]
When \({T_b} \le {T_{b - c}}\), TSENS is calculated using:
\[TSEN{S_c} = 0.68175({T_b} - {T_{b - c}})\]
Otherwise, when \({T_b} > {T_{b - c}}\), TSENS is calculated using:
\[TSEN{S_h} = 4.7({T_b} - {T_{b - c}})/({T_{b - h}} - {T_{b - c}})\]
Finally, DISC is calculated using the following equation:
\[DISC = 5.({E_{rsw}} - {E_{rsw - comf}})/({E_{\max }} - {E_{rsw - comf}} - {E_{diff}})\]
These final equations for the Pierce Two Node Model are calculated using the following lines of source code:
AvgBodyTempLow = (0.185/ActLevelConv)*IntHeatProd + 36.313
AvgBodyTempHigh = (0.359/ActLevelConv)*IntHeatProd + 36.664
TSENS = .68175*(AvgBodyTemp-AvgBodyTempLow)
TSENS = 4.7*(AvgBodyTemp-AvgBodyTempLow)/(AvgBodyTempHigh-AvgBodyTempLow)
DISC = 5.*(EvapHeatLossRegSweat-EvapHeatLossRegComf)
/(MaxEvapHeatLoss-EvapHeatLossRegComf-DiffHeatLoss)
KSU Two-Node Model[LINK]
The KSU Two-Node Model, developed at Kansas State University, was published in 1977 (Azer and Hsu 1977). The KSU model is quite similar to that of the Pierce Foundation. The main difference between the two models is that the KSU model predicts thermal sensation (TSV) differently for warm and cold environment.
KSU Two Node Model Nomenclature List[LINK]
Description of the model and algorithm[LINK]
The KSU Two-Node Model is based on the changes that occur in the thermal conductance between the core and the skin temperature in cold environments. In warm environments, the thermal conductance of the model is based on changes in the skin wettedness.
In this model, metabolic heat production is generated in the core which exchanges energy with the environment by respiration, and the skin exchanges energy with the interior environment by convection and radiation. In addition, body heat is dissipated through the evaporation of sweat and/or water vapor diffusion through the skin. These principles are outlined in the following system of equations.
\[{W_{cr}}{C_{cr}}d{T_{cr}}/dt = M - W - {Q_{res}} - KS({T_{cr}} - {T_{sk}})\]
\[{W_{sk}}{C_{sk}}d{T_{sk}}/dt = KS({T_{cr}} - {T_{sk}}) - {Q_{dry}} - {E_{sk}}\]
where Q\(_{res}\) and Q\(_{dry}\) are calculated using:
\[{Q_{res}} = {E_{res}} + {C_{res}} = 0.0023M(44 - {P_{a}(torr)}) + 0.0014M(34 - {T_a})\]
\[{Q_{dry}} = {Q_c} + {Q_r} = {h_{}}{f_{cl}}{F_{cl}}({T_{sk}} - {T_o}) \label{eq:KSU2NodeQdry}\]
The calculation of Q\(_{res}\) (RespHeatLoss) and Q\(_{dry}\) (DryHeatLoss) in the source code are accomplished through the following equations:
RespHeatLoss = LatRespHeatLoss + DryRespHeatLoss
LatRespHeatLoss = 0.0023*ActLevelTot*(44. - VapPress)
DryRespHeatLoss = 0.0014*ActLevelTot*(34. - AirTemp)
DryHeatLoss = H*CloBodyRat*CloThermEff*(SkinTemp - OpTemp)
In the equation for Q\(_{dry}\), h and T\(_{o}\) are calculated using:
\[h = {h_c} + {h_r}\]
\[{h_c} = 8.3\sqrt v\]
\[{h_r} ={\epsilon_{avg}}(3.87 + 0.031{T_r})\]
\[{T_o} = ({h_c}{T_a} + {h_r}{T_r})/({h_c} + {h_r})\]
These equations are represented by the following source code equations:
H = Hc + Hr
Hc = 8.3*SQRT(AirVel) where AirVel is reset to 0.137 if it drops below this value
Hr = EmissAvg*(3.87 + 0.031*RadTemp)
OpTemp = (Hc*AirTemp + Hr*RadTemp)/H
In the KSU Two-Node Model, evaporative heat losses are defined by these equations:
\[For \left({E_{sw}} \le {E_{\max }}\right),~{E_{sk}} = {E_{sw}} + (1 - {w_{rsw}}){E_{diff}}\]
\[For \left({E_{sw}} > {E_{\max }}\right),~{E_{sk}} = {E_{\max }}\]
\[{E_{diff}} = 0.408({P_{sk}} - {P_a})\]
\[{E_{\max }} = 2.2{h_c}{F_{pcl}}({P_{sk}} - {P_a})\]
These equations are shown in the EnergyPlus source code as:
EvapHeatLoss = SkinWetSweat*EvapHeatLossMax+(1. - SkinWetSweat)*EvapHeatLossDiff
SkinWetSweat = EvapHeatLossDrySweat/EvapHeatLossMax
EvapHeatLossDiff = 0.408*(SkinVapPress - VapPress)
EvapHeatLossMax = 2.2*Hc*(SkinVapPress - VapPress)*CloPermeatEff
Here, control signals, based on setpoint temperatures in the skin and core, are introduced into the system of equations, and these equations are integrated numerically for small time increments or small increments in core and skin temperature. The control signals modulate the thermoregulatory mechanism and regulate the peripheral blood flow, the sweat rate, and the increase of metabolic heat by active muscle shivering. The development of the controlling functions of skin conductance (KS), sweat rate (E\(_{sw}\)), and shivering (M\(_{shiv}\)) is based on their correlation with the deviations in skin and core temperatures from their setpoints.
\[KS = 5.3 + \frac{\left[ 6.75+42.45\left( T_{cr}-36.98 \right)+8.15\left( T_{cr}-35.15 \right)^{0.8}\left( T_{sk}-33.8 \right) \right]}{1+0.4\left( 32.1-T_{sk} \right)}\]
\[E_{sw} = \phi \frac{\left[ 260\left( T_{cr} - 36.9 \right) + 26\left( T_{sk} - 33.8 \right) \right] \exp\left[ \left( T_{sk} - 33.8 \right)/8.5 \right]}{1.0 + 0.05\left( 33.37 - T_{sk} \right)^{2.4}}\]
\[{M_{shiv}} = 20(36.9 - {T_{cr}})(32.5 - {T_{sk}}) + 5(32.5 - {T_{sk}})\]
where \(\phi = 1.0\) for \(w \le 0.4\) and when \(w > 0.4\):
\[\phi = 0.5 + 0.5\exp [ - 5.6(w - 0.4)]\]
Within EnergyPlus, these variables are calculated using the following source code equations:
SkinCndctDilation = 42.45*CoreSignalWarmMax+8.15*CoreSignalSkinSens**0.8*SkinSignalWarmMax
SkinCndctConstriction = 1.0 + 0.4*SkinSignalColdMax
ThermCndct = 5.3+(6.75+SkinCndctDilation)/SkinCndctConstriction
WeighFac = 260.+70.*AcclPattern where the pattern of acclimation is assumed to be zero in the equation for E\(_{sw}\) above
SweatCtrlFac = 1. + 0.05*SkinSignalSweatColdMax**2.4
EvapHeatLossDrySweat = ((WeighFac*CoreSignalSweatMax+0.1*WeighFac*SkinSignalSweatMax)
*EXP(SkinSignalSweatMax/8.5))/SweatCtrlFac
SweatSuppFac = 1. for \(w \le 0.4\)
SweatSuppFac = 0.5 + 0.5*EXP(-5.6*SkinWetSignal) for \(w > 0.4\)
ShivResponse = 20.*CoreSignalShivMax*SkinSignalShivMax + 5.*SkinSignalShivMax
In the KSU model, two new parameters are introduced and used in correlating thermal sensations with their associated physiological responses. Instead of correlating warm thermal sensations with skin wettedness, it is correlated with a wettedness factor defined by:
\[{\varepsilon_{wsw}} = ({w_{rsw}} - {w_{rsw - o}})/(1.0 - {w_{rsw - o}})\]
where:
\[{w_{wsw}} = {E_{sw}}/{E_{\max }}\]
\[{w_{rsw - o}} = 0.2 + 0.4\{ 1.0 - \exp [ - 0.6(H/58.2 - 1.0)]\}\]
The wettedness factor is calculated using the following EnergyPlus equations:
SkinWetFac = (SkinWetSweat - SkinWetNeut)/(1. - SkinWetNeut)
SkinWetSweat = DrySweatRate/EvapHeatLossMax
SkinWetNeut = 0.02 + 0.4*(1.-EXP(-0.6*(IntHeatProdMetMax - 1.)))
In addition, instead of correlating cold thermal sensation with the skin temperature in the KSU model, it is correlated with a factor identified as vasoconstriction factor defined by:
\[{\varepsilon_{vc}} = (K{S_o} - KS)/(K{S_o} - K{S_{( - 4)}})\]
or in the source code:
VasoconstrictFac=(ThermCndctNeut-ThermCndct)/(ThermCndctNeut-ThermCndctMin)
Thus, for a cold environment, TSV is a function of a vasoconstriction factor (\({\varepsilon_{vc}}\)):
\[TSV = - 1.46 \times {\varepsilon_{vc}} + 3.75 \times {\varepsilon_{vc}}^2 - 6.17 \times {\varepsilon_{vc}}^3\]
and for the warm environments, TSV is defined as:
\[TSV = [5.0 - 6.56(RH - 0.5)] \times {\varepsilon_{wsw}}\]
In EnergyPlus, these two equations for TSV in cold and warm environments, respectively, show up as:
TSV = -1.46153*VasoconstrictFac + 3.74721*VasoconstrictFac**2
- 6.168856*VasoconstrictFac**3
TSV = (5. - 6.56*(RelHum - 0.50))*SkinWetFac
The KSU model’s TSV was developed from experimental conditions in all temperature ranges and for clo levels between 0.05 clo and 0.7 clo and for activities levels ranging from 1 to 6 mets (Berglund 1978).
Adaptive Comfort Model
Adaptive comfort model, intended for use in naturally ventilated buildings, determines the acceptability of indoor conditions given the monthly mean outdoor air temperature and the indoor operative temperature. This is used as an index for occupant adaptation to outdoor conditions, and determines the acceptability of indoor conditions. The model also accounts for people’s clothing adaptation in naturally conditioned spaces by relating the acceptable range of indoor temperatures to the outdoor climate, so it is not necessary to estimate the clothing values for the space. No humidity or air-speed limits are required when this option is used. This section summarizes the adaptive comfort models based on the ASHRAE Standard 55-2010 and CEN 15251. Details are available in the two standards.
Adaptive Comfort Model Based on ASHRAE Standard 55-2010
In ASHRAE Standard 55, the monthly mean outdoor air temperature, used in the adaptive comfort model, is defined as the simple running average of the previous thirty daily average outdoor air temperatures.
The model defines two comfort regions: 80% Acceptability, and 90% Acceptability. If the monthly mean outdoor air temperature is not within the specified domain of 10.0 to 33.5C, the model is not applicable.
The central line of the model (shown in red), or comfort temperature, is defined as
\[{T_{ot}} = 0.31\cdot {T_o} + 17.8\]
where:
T\(_{ot}\) is the operative temperature (\(^{\circ}\)C), calculated as the average of the indoor air dry-bulb temperature and the mean radiant temperature of zone inside surfaces
T\(_{o}\) is the monthly mean outdoor air dry-bulb temperature (\(^{\circ}\)C).
If the .stat file is provided for the simulation, T\(_{o}\) is drawn directly from the daily average temperatures in the .stat file, which provides a value for each month. If no .stat file is provided, the monthly mean outdoor temperature is a simple running average of the previous thirty daily average temperatures, calculated directly from the weather file (.epw):
\[{T_o} = \frac{{\left( {{T_{od - 1}} + {T_{od - 2}} + ... + {T_{od - 30}}} \right)}}{{30}}\]
\[{T_o} = (1 - \alpha )\cdot {T_{od - 1}} + \alpha \cdot {T_{od - 1}}\]
\[\alpha = \frac{{29}}{{30}}\]
T\(_{od-i}\) is defined as the daily average temperature of the i\(^{th}\) previous day.
Note that the weather file must be a standard .epw containing a full year of data.
The comfort regions for 80% and 90% acceptability are symmetric about the central line.
For 90% Acceptability Limits:
\[T_{ot} = 0.31* T_{o} + 17.8 ± 2.5\]
80% Acceptability Limits:
\[T_{ot} = 0.31* T_{o} + 17.8 ± 3.5\]
If, using either method, T\(_{o}\) is less than 10\(^{\circ}\)C or greater than 33.5\(^{\circ}\)C, the model is not applicable.
For a detailed description of this model, please see ASHRAE Standard 55-2010, Thermal Environmental Conditions for Human Occupancy.
Adaptive Comfort Model Based on European Standard EN15251-2007[LINK]
The EN15251-2007 is similar to ASHRAE 55-2010, but with slightly different curves of the indoor operative temperature and acceptability limits (Fig. 2). The model, intended for use in naturally ventilated buildings, determines the acceptability of indoor conditions given the 7-day weighted mean outdoor air temperature and the indoor operative temperature. The 7-day weighted mean outdoor air temperature (T\(_{rm}\)) is defined as the weighted running average of the previous 7 daily average outdoor air temperatures.
This weighted running average is calculated from a full annual weather file that must be specified for the simulation. This is used as an index for occupant adaptation to outdoor conditions, and determines the acceptability of indoor conditions. The model also accounts for people’s clothing adaptation in naturally conditioned spaces by relating the acceptable range of indoor temperatures to the outdoor climate, so it is not necessary to estimate the clothing values for the space. No humidity or air-speed limits are required when this option is used. The model defines three comfort regions: Category I (90%) Acceptability, Category II (80%) Acceptability, and Category III (65%) Acceptability. If T\(_{rm}\) is not within the specified domain of 10.0 to 30.0C, the model is not applicable.
For the central line (shown as red in Figure 3):
\[T_{ot} = 0.33*T_o + 18.8\]
For Category I, 90% Acceptability Limits:
\[T_{ot} = 0.33*T_o + 18.8 \pm 2.0\]
For Category II, 80% Acceptability Limits:
\[T_{ot} = 0.33*T_o + 18.8 \pm 3.0\]
For Category III, 65% Acceptability Limits:
\[T_{ot} = 0.33*T_o + 18.8 \pm 4.0\]
For 10\(^{\circ}\)C < T\(_{rm}\) < 15\(^{\circ}\)C, the comfort temperature of the lower boundaries of the comfort regions is T\(_{comf}\) = 23.75\(^{\circ}\)C. That is, the lower boundaries are constant according to the same ranges above:
For Category I, 90% Acceptability Limits:
\[T_{ot} = 23.75 - 2.0\]
For Category II, 80% Acceptability Limits:
\[T_{ot} = 23.75 - 3.0\]
For Category III, 65% Acceptability Limits:
\[T_{ot} = 23.75 - 4.0\]
where:
\({T_{ot}}\) is the operative temperature calculated as the average of the indoor air dry-bulb temperature and the mean radiant temperature of zone inside surfaces (\(^{\circ}\)C)
\(T_o\) is the mean outdoor air dry-bulb temperature (\(^{\circ}\)C), calculated as the weighted mean of the previous 7-day daily mean outdoor air dry-bulb temperature (T\(_{od}\)) using:
\[T_{o} = (1 - \alpha) * \{T_{od-1} + \alpha * T_{od-2} + \alpha^{2} * T_{od-3} + \alpha^{3} * T_{od-4} + \alpha^{4} * T_{od-5} + \alpha^{5} * T_{od-6} + \alpha^{6} * T_{od-7}\}\]
\[T_{o} = (1 - \alpha) * T_{od-1} + \alpha * T_{o-1}\]
\[\alpha = 0.8\]
Dynamic Clothing Model[LINK]
In most building energy simulations, thermal comfort condition is calculated based on the assumption that the clothing insulation is equal to a constant value of 0.5 clo during the cooling season and 1.0 clo during heating season. Usually those two values are used and the change from 0.5 to 1 or vice-versa is made suddenly from one day to another. In addition, there is no standardized guideline on how to set clothing insulation schedules in the international standards. This simplified assumption may lead to systems that are incorrectly sized and operated and to the incorrect assessment of comfort conditions. In reality, occupants frequently adjust their clothing depending on the thermal conditions around them, as opposed to the assumption of constant clothing values. Therefore, the clothing insulation variation should be captured during the building simulation to realistically model HVAC systems. In order to overcome the limitations of the constant clothing insulation assumption, three new predictive clothing insulation models were developed by Schiavon and Lee (2012) based on 6,333 selected observations taken from ASHRAE RP-884 and RP-921 databases. The first and third models vary the clothing insulation as a function of outdoor air temperature measured at 6 o’clock and the second model takes into account both 6 o’clock outdoor air temperature and indoor operative temperature when adjusting the clothing insulation. The dynamic clothing models should be implemented in dynamic building energy simulation.
The model proposed to ASHRAE 55 is described below.
For t\(_{a(out,6)}\) < -5\(^{\circ}\)C:
\[{I_{cl}} = 1.00\]
For -5\(^{\circ}\)C \(\leq\) \(t_{a(out,6)}\) < 5\(^{\circ}\)C:
\[{I_{cl}} = 0.818 - 0.0364{\rm{*}}{t_{a\left( {out,6} \right)}}\]
For 5\(^{\circ}\)C \(\leq\) t\(_{a(out,6)}\) < 26\(^{\circ}\)C:
\[{I_{cl}} = {10^{\left( { - 0.1635 - 0.0066{\rm{*}}{t_{a\left( {out,6} \right)}}} \right)}}\]
Or for t\(_{a(out,6)}\) \(\geq\) 26\(^{\circ}\)C:
\[{I_{cl}} = 0.46\]
where \(I_{cl}\) is the clothing insulation value and \(t_{a(out,6)}\) is the outdoor air temperature measured at 6 o’clock in the morning. Figure 5 illustrates the proposed clothing insulation model.
In Figure 4, clothing insulation schedule for a fixed model (blue) typically used in energy simulation software and for the clothing model based on outdoor air temperature measured at 6 o’clock. Climate data for Chicago O’hare International Airport has been used.
The dynamic predictive clothing insulation model is implemented into EnergyPlus for realistic energy simulation. Addenda A to ASHRAE 55 with the clothing model has been approved by the ASHRAE committee and the chance to be included in ASHRAE 55-2013 is high.
References[LINK]
Schiavon S, Lee KH. 2013. Dynamic predictive clothing insulation models based on outdoor air and indoor operative temperatures. Building and Environment. Volume 59, 250-260. http://dx.doi.org/10.1016/j.buildenv.2012.08.024 (link to the journal) http://escholarship.org/uc/item/3338m9qf (link to the freely available pre-print version)
Lee KH, Schiavon S. 2013. Influence of three dynamic predictive clothing insulation models on building energy use, HVAC sizing and thermal comfort. Submitted to Journal. http://escholarship.org/uc/item/3sx6n876 (link to the freely available pre-print version)
Mean Radiant Temperature Calculation[LINK]
There are three options to calculate mean radiant temperature in the thermal comfort models. One is the zone averaged MRT, another is the surface weighted MRT, and the other is angle factor MRT. The zone averaged MRT is calculated on the assumption that a person is in the center of a space, whereas the surface weighted MRT is calculated in consideration of the surface that a person is closest to, and the angle factor MRT is calculated based on angle factors between a person and the different surfaces in a space. Here, the surface weighted MRT is the average temperature of the selected surface and zone averaged MRT for the remaining surfaces in the zone and is intended to represent conditions in the limit as a person gets closer and closer to a particular surface. In that limit, half of the person’s radiant field will be dominated by that surface and the other half will be exposed to the rest of the zone. Note that the surface weighted MRT is only an approximation. The angle factor MRT is the mean temperature of the surrounding surface temperatures weighted according to the magnitude of the respective angle factors and allows the user to more accurately predict thermal comfort at a particular location within a space.
Description of the model and algorithm[LINK]
The radiant temperature for the "zone averaged" option is simply calculated from the zone mean radiant temperature (MRT) without weighting any surface temperature of the zone more than the standard MRT calculation.
\[{T_r} = {T_{r - avg}}\]
where the standard MRT is calculated using the following equation summed over all zone surfaces:
\[{T_{r - avg}} = \frac{\sum{{{\epsilon}_{i}}{{A}_{i}}{{T}_{i}}}}{\sum{{{\epsilon}_{i}}{{A}_{i}}}}\]
In the surface weighted option, the radiant temperature is the average temperature of the modified zone averaged MRT and the temperature of the surface that a person is closest to.
\[{T_r} = ({T_{r - avg*}} + {T_{surf}})/2\]
where the modified zone averaged MRT is calculated the same way as the standard MRT except that the surface closest to the person is left out of the summation:
\[{T_{r - avg*}} = \frac{\sum{{{\epsilon}_{i*}}{{A}_{i*}}{{T}_{i*}}}}{\sum{{{\epsilon}_{i*}}{{A}_{i*}}}}\]
where when i is equal to the surface being used for weighting it is not included in either summation.
When the angle factor option is requested, the radiant temperature is the mean value of surrounding surface temperatures weighted by the surface emissivity, the size of the respective angle factors between a person and each surface, and the temperature to the fourth power for the surface.
\[{T_r} = \frac{\sum{{\epsilon_{i}}{F_{i}}{\left( {T_{i}} \right)^4}}}{\sum{{\epsilon_{i}}{F_{i}}}}\]
If all surfaces have the same emissivity that is close to unity, the emissivities in the above equation can be ignored. However, since this is not always the case, the emissivity terms must be included in the above equation. In addition, the temperatures to the fourth power in the above equation could be simplified to linear temperatures when the temperatures of the surfaces are fairly close. However, as these temperatures get further apart, this linear approximation becomes increasingly poor. As a result, since there is no guarantee that inside face surface temperatures will be close, the fourth order temperature terms are used to calculate the radiant temperature.
ASHRAE 55 Elevated Air Speed Cooling Effect Model[LINK]
ASHRAE Standard 55-2017 Section 5.3 requires that the Elevated Air Speed Comfort Zone Method be used when average air speed \(v_{a}\) is greater than 0.10 m/s. The method provides cooling credit for elevated air velocity in the space. The method can be used to evaluate passive cooling technologies such as natural ventilation, ceiling fan, and portable fan.
Description of the model and algorithm[LINK]
The Pierce Two-Node Standard Effective Temperature (SET) model is used to account for the cooling effect of air speeds greater than the 0.10 m/s. Specifically, for a given set of environmental and personal variables, including an elevated average air speed, an average air temperature \(t_{a}\), and a mean radiant temperature \(t_{r}\), the SET is first calculated. Then the average air speed \(v_{a}\) is replaced by still air (0.1 m/s), and the average air temperature and radiant temperature are adjusted according to the cooling effect (CE). The CE of the elevated air speed is the value that, when subtracted equally from both the average air temperature and the mean radiant temperature, yields the same SET under still air as in the first SET calculation under elevated air speed.
The following is a formal description of this process. To define the CE, we assert that it satisfies the following:
\[SET(t_{a}, t_{r}, v_{elev}, *) = SET(t_{a} - CE, t_{r} - CE, v_{still}, *)\]
where \(t_{a}\) is the average air temperature, \(t_{r}\) is the mean radiant temperature, \(v_{elev}\) is the elevated average air speed, such that \(v_{elev} > 0.1 m/s\) , \(v_{still}\) is the elevated average air speed (\(v_{still} = 0.1 m/s\)). The other parameters (indoor air humidity, clothing, metabolic rate) that stay the same are denoted by “*”.
It should be noted that \(v_{elev}\) is the relative air velocity caused by body movement and not the air speed measured by the air velocity sensor. It can be calculate using the function below.
\[v_{elev} = max(v_{measured}, v_{measured} + 0.3 * (met - 1))\]
where \(met\) is the metabolic rate in [met].
The Cooling Effect adjusted PMV/PPD for an environment with elevated average air speed is calculated using the adjusted average air temperature, the adjusted radiant temperature, and still air (0.1 m/s). The following are equations to calculate the adjusted PMV and PPD.
\[PMV_{adj} = PMV(t_{a} - CE, t_{r} - CE, v_{still}, *)\]
\[PPD_{adj} = 100 - 95 * exp(-0.03353 * {PMV_{adj}}^4 - 0.2179 * {PMV_{adj}}^2)\]
ASHRAE 55 Ankle Draft Risk Model[LINK]
Draft is unwanted local cooling of the body caused by air movement. It is most prevalent when the whole-body thermal sensation is cool (below neutral). Draft sensation depends on air speed, air temperature, activity, and clothing. Sensitivity to draft is greatest where the skin is not covered by clothing, especially the head region comprising the head, neck, and shoulders and the leg region comprising the ankles, feet, and legs. Draft at the lower leg region may occur in the buildings conditioned by thermally stratified systems, such as displacement ventilation and underfloor air distribution, or with cold-dropping airflow along external walls and/or windows.
Description of the model and algorithm[LINK]
The predicted percentage dissatisfied on draft at ankle level \(PPD_{AD}\) is used as the metric to evaluate the ankle draft risk as a function of PMV and air speed at the ankle level (0.1 m). The following is the equation to calculate \(PPD_{AD}\).
\[PMV_{vr} = PMV(t_{a}, t_{r}, v_{r}, *)\]
\[PPD_{ad} = \frac{exp(-2.58 + 3.05 * v_{ankle} - 1.06 * PMV_{vr})}{1 + exp(-2.58 + 3.05 * v_{ankle} - 1.06 * PMV_{vr}} * 100\]
Where \(v_{r}\) is the relative air velocity caused by body movement, and \(v_{ankle}\) is the air speed at 0.1 m above the floor.
This equation is only applicable for \(v_{r} < 0.2 m/s\) . And the subject’s metabolic rate and clothing level should be kept below 1.3 met and 0.7 clo, respectively. PPD at ankle draft will be set to -1.0 if if these conditions are not met.
It should be noted that the metrics only measures the predicted percentage dissatisfied on the sensation of draft. \(PPD_{AD}\) levels at various air speeds and thermal sensations are depicted in Figure 6
References[LINK]
ASHRAE. 1984. “High Intensity Infrared Radiant Heating”, 1984 Handbook of Systems and Equipment, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA, Chapter 18.
ASHRAE. 1985. “Physiological Principles for Comfort and Health,” 1985 Handbook of Fundamentals, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA, Chapter 8.
ASHRAE. 1993. “Physiological Principles and Thermal Comfort”, 1993 ASHRAE Handbook of Fundamentals, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA, Chapter 8.
ASHRAE. 2010. “Standard 55-2010 – Thermal Environmental Conditions for Human Occupancy (ANSI approved)”, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA.
ASHRAE. 2017. “Standard 55-2017 – Thermal Environmental Conditions for Human Occupancy (ANSI approved)”, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA.
Azer, N.Z., Hsu, S. 1977. “The prediction of Thermal Sensation from Simple model of Human Physiological Regulatory Response”, ASHRAE Trans., Vol.83, Pt 1.
Berglund, Larry. 1978. “Mathematical Models for Predicting the Thermal Comfort Response of Building Occupants”, ASHRAE Trans., Vol.84.
Doherty, T.J., Arens, E. 1988. “Evaluation of the Physiological Bases of Thermal Comfort Models”, ASHRAE Trans., Vol.94, Pt 1.
Du Bois, D. and E.F. 1916. “A Formula to Estimate Approximate Surface Area, if Height and Weight are Known”, Archives of internal Medicine, Vol.17.
CEN. 2007. “Standard EN15251 Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics”. Bruxelles: European committee for Standardisation.
Fanger, P.O. 1970. Thermal Comfort-Analysis and Applications in Environmental Engineering, Danish Technical Press, Copenhagen.
Fanger, P.O. 1986. “Radiation and Discomfort”, ASHRAE Journal. February 1986.
Fanger P.O. 1967. “Calculation of Thermal Comfort: Introduction of a Basic Comfort Equation”, ASHRE Trans., Vol.73, Pt 2.
Fountain, Marc.E., Huizenga, Charlie. 1997 “A Thermal Sensation Prediction Tool for Use by the Profession”, ASHRAE Trans., Vol.103, Pt 2.
Gagge, A.P., Stolwijk, J. A. J., Nishi, Y. 1970. “An Effective Temperature Scale Based on a Simple Model of Human Physiological Regulatory Response”, ASHRAE Trans., Vol.70, Pt 1.
Gagge, A.P., Fobelets, A.P., Berglund, L. G. 1986. “A Standard Predictive Index of Human Response to the Thermal Environment”, ASHRAE Trans., Vol.92, Pt 2.
Hsu, S. 1977. “A Thermoregulatory Model for Heat Acclimation and Some of its Application”, Ph. D. Dissertation, Kansas State University.
Int-Hout, D. 1990. “Thermal Comfort Calculation / A Computer Model”, ASHRAE Trans., Vol.96, Pt 1.
ISO. 1983. “Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort”, DIS 7730, Moderate Thermal Environment, 1983.
Liu S., Schiavon S., Kabanshi A., Nazaroff W.W. 2017. P̈redicted percentage dissatisfied with ankle draft,̈ Indoor Air, Vol.27.