The WINDOW program is published from LBNL at http://windows.lbl.gov/software. More
specifics on the program and its details are shown in the
Input Output Reference under “Importing Windows from WINDOW
program” topic.
The other “older” option for creating data for EnergyPlus
is to use the “EnergyPlus” option above and create a
WindowDataFile. The general format of this data is described
in the following paragraphs and must use the Construction:WindowDataFile
object and an external file to be used in EnergyPlus. While
this is a convenient small file (that can contain multiple
windows), there is no way to import this file back into WINDOW
and obtain the above, more preferred method.
Please note that there is a bug in WINDOW 5 that causes two
of the lines in the EnergyPlus data file to be joined. This
bug is fixed in versions of Window
5.02 (and above). To be sure, you can check the data file for
a line that looks like:
GLAZING SYSTEM OPTICAL DATA
Angle 0 10 20 30 40 50 60 70
80 90 Hemis
The fixed version of the program will not show the above
line; rather, there will be two lines such as shown below. If
you have the above condition, with an editor you would break
this into two lines:
GLAZING SYSTEM OPTICAL DATA
Angle 0 10 20 30 40 50 60 70
80 90 Hemis
In EnergyPlus, the Window
data file is searched for each “Construction:WindowDataFile”
object in the EnergyPlus input. This object has a very simple
form:
FileName; ! Default is Window5DataFile.dat in the “run”
folder.
If there is a window called ConstructionName on the Window
data file, the data for that window is read from the file and
the following EnergyPlus objects and their names are created.
The “W5” prefixed to these names indicates that the object
originated in the Window5 data file.
WindowMaterial:Glazing
for each of the glass layers. They will be named
W5:ConstructionName:GLASS1,
W5:ConstructionName:GLASS2 , etc.
An entry on the WINDOW data file usually has just one
glazing system. It is also possible to have an entry with two
glazing systems separated by a horizontal or vertical mullion.
In this case, the two glazing systems can have different
dimensions and different properties. For example, one of the
two glazing systems could be single glazed and the other could
be double glazed. An example of the two glazing system case
is given in the sample WINDOW data file shown below (although
in this case the properties of the two glazing systems are the
same).
EnergyPlus handles the “one glazing system” and “two
glazing systems” cases differently. If there is one glazing
system, the glazing system height and width from the Window5
data file are not used. Instead, the window dimensions are
obtained from the window vertices that have been specified on
the IDF file. However, a warning message will result if the
height or width calculated from the window’s vertex inputs
differs from the corresponding Window5 data file values by
more than 10%. This warning is given since the effective frame
and edge-of-glass conductances on the WINDOW data file can
depend on the window dimensions if the frame is non-uniform,
i.e., consists of sections with different values of width,
projection, or thermal properties.
If the WINDOW data file entry has two glazing systems,
System1 and System2, the following happens, as shown in the
figure below. Assume that the original window is called
WinOriginal. System1 is assigned to WinOriginal. Then
EnergyPlus automatically creates a second window, called
WinOriginal:2, and assigns System2 to it. The dimensions of
WinOriginal are ignored; the dimensions of System1 on the data
file are assigned to it, but the position of the lower
left-hand vertex of WinOriginal is retained. The dimensions of
System2 on the data file are assigned to WinOriginal:2. The
lower left-hand vertex of WinOriginal:2 is determined from the
mullion orientation and width.
Note: WinOriginal would have been the IDF window
definition – it’s dimensions will be overridden by the systems
dimensions from the Window
data file. Two windows will be made and called WinOriginal and
WinOriginal:2.
Window Glazing system with dual
glazing constructions
The Window
Data File contains no information on shading devices. See
“Specify the Material
Name of the Shading Device” under WindowShadingControl
for a method to attach a shading layer to windows read in from
this file.
Following is an example WINDOW data file for a slider
window with two identical double low-E glazing systems
separated by a horizontal mullion. Each system has a frame and
divider. Note that all dimensions, such as glazing height and
width, are in millimeters; when EnergyPlus reads the file
these are converted to meters. Following the data file example
is a description of the contents of the file. That data used
by EnergyPlus is shown in bold.
(Quantities used in EnergyPlus are in bold; others are
informative only)
Second line = version of WINDOW used to create the data
file
Date = date the data file was created
Window
name = name of this window; chosen by WINDOW5
user; EnergyPlus user enters the same name in EnergyPlus as
name of a “Construction
from Window5 Data File” object. EnergyPlus will search the
Window5 data file for an entry of this name.
Description = One-line description of the window;
this is treated as a comment.
# Glazing Systems: 1 or 2; value
is usually 1 but can be 2 if window has a horizontal or
vertical mullion that separates the window into two glazing
systems that may or may not be different.
GLAZING SYSTEM DATA
System1, System2: separate characteristics given
if window has a mullion.
Height,
*width = height and width of glazed
portion (i.e., excluding frame; and, if mullion present,
excluding mullion).
nPanes = number of glass
layers
Uval-center = center-of-glass U-value (including
air films) under standard winter conditions* (W/m2)
SC-center = center-of-glass shading coefficient
under standard summer conditions*.
SHCG-center = center-of-glass solar heat gain
coefficient under standard summer conditions*.
Tvis-center = center-of-glass visible
transmittance at normal incidence
FRAME/MULLION DATA
L,R Sill = left, right sill of frame
L,R Head = left, right header of frame
Top L, Bot L jamb = top-left, bottom-left jamb of
frame
Bot L, Bot R jamb = bottom-left, bottom-right jamb
of frame
Average frame = average
characteristics of frame for use in EnergyPlus calculation. If
mullion is present, original window is divided into two
separate windows with the same average frame (with the mullion
being split lengthwise and included in the average frame).
Width = width (m)
OutsideProj = amount of
projection from outside glass (m)
InsideProj = amount of projection
from inside glass (m)
EdgeCondRatio = ratio of
surface-to-surface edge-of-glass conductance to
surface-to-surface center-of-glass conductance (from THERM
calculation)
SolAbs = solar absorptance
VisAbs = visible
absorptance
Emiss = hemispherical thermal
emissivity
Orientation = Horizontal or
Vertical (mullion only); = None if no mullion.
DIVIDER DATA
Width through
Emiss are the same as for
FRAME/MULLION DATA
#Hor = number of horizontal
dividers
#Vert = number of vertical
dividers
Type = DividedLite or
Suspended
GLASS DATA
System1, System2: separate characteristics are
given if window has a mullion.
Cond = conductivity
(W/m-K)
Tsol = spectral-average solar transmittance
at normal incidence
Rfsol = spectral-average front solar
reflectance at normal incidence
Rbsol = spectral-average back solar
reflectance at normal incidence
Tvis = spectral-average visible
transmittance at normal incidence
Rfvis = spectral-average front visible
reflectance at normal incidence
Rbvis = spectral-average back visible
reflectance at normal incidence
Tir = hemispherical IR
transmittance
EmissF = hemispherical front
emissivity
EmissB = hemispherical back
emissivity
SpectralDataFile = name of spectral data file with
wavelength-dependent transmission and reflection data used by
WINDOW 5 to calculate the glazing system optical data. “None”
will appear here if spectral-average data for this glass layer
were used by WINDOW 5.
GAP DATA
System1, System2: separate characteristics are given if the
window has a mullion.
Thick = thickness (m)
nGasses = number of gasses (1, 2
or 3)
GasName = name of the gas
Fraction = fraction of the
gas
MolecWeight = molecular weight of
the Nth gas
(In the following, conductivity, viscosity and specific
heat as a function
of temperature, T (deg K), are expressed as A + B*T +
C*T^2)
ACond = A coeff of
conductivity (W/m-K)
BCond = B coeff of
conductivity (W/m-K^2)
CCond = C coeff of
conductivity (W/m-K^3)
AVisc = A coeff of viscosity
(g/m-s)
BVisc = B coeff of viscosity
(g/m-s-K)
CVisc = C coeff of viscosity
(g/m-s-K^2)
ASpHeat = A coeff of specific
heat (J/kg-K)
BSpHeat = B coeff of specific
heat (J/kg-K^2)
CSpHeat = C coeff of specific
heat (J/kg-K^3)
GLAZING SYSTEM OPTICAL DATA
System1, System2: separate characteristics are given if the
window has a mullion.
Hemisph = hemispherical (i.e.,
diffuse)
Tsol = solar transmittance
vs. angle of incidence
AbsN = solar absorptance of
Nth layer vs. angle of incidence
Rfsol = front solar
reflectance vs. angle of incidence
Rbsol = back solar
reflectance vs. angle of incidence
Tvis = visible transmittance
vs. angle of incidence
Rfvis = front visible
reflectance vs. angle of incidence
Rbvis = back visible
reflectance vs. angle of incidence
*Standard conditions are
Winter:
Indoor air temperature = 21.1C (70F)
Outdoor air temperature = -17.8C (0F)
Wind speed = 6.71 m/s (15 mph)
No solar radiation
Summer:
Indoor air temperature = 23.9C (75F)
Outdoor air temperature = 31.7C (89F)
Wind speed = 3.35 m/s (7.5 mph)
783 W/m2 (248 Btu/h-ft2) incident beam solar radiation
normal to glazing
Getting data from WINDOW program[LINK]
The WINDOW program is published from LBNL at http://windows.lbl.gov/software. More specifics on the program and its details are shown in the Input Output Reference under “Importing Windows from WINDOW program” topic.
EnergyPlus IDF Excerpt Data[LINK]
The preferred method of using WINDOW data in EnergyPlus is to excerpt or “report” a specific Window from the Window library screen (see below):
The file can then be saved at a location of your choice and added into your overall simulation IDF file.
WINDOW Data File[LINK]
The other “older” option for creating data for EnergyPlus is to use the “EnergyPlus” option above and create a WindowDataFile. The general format of this data is described in the following paragraphs and must use the Construction:WindowDataFile object and an external file to be used in EnergyPlus. While this is a convenient small file (that can contain multiple windows), there is no way to import this file back into WINDOW and obtain the above, more preferred method.
Please note that there is a bug in WINDOW 5 that causes two of the lines in the EnergyPlus data file to be joined. This bug is fixed in versions of Window 5.02 (and above). To be sure, you can check the data file for a line that looks like:
GLAZING SYSTEM OPTICAL DATA
Angle 0 10 20 30 40 50 60 70 80 90 Hemis
The fixed version of the program will not show the above line; rather, there will be two lines such as shown below. If you have the above condition, with an editor you would break this into two lines:
GLAZING SYSTEM OPTICAL DATA
Angle 0 10 20 30 40 50 60 70 80 90 Hemis
In EnergyPlus, the Window data file is searched for each “Construction:WindowDataFile” object in the EnergyPlus input. This object has a very simple form:
Construction:WindowDataFile,
ConstructionName,
FileName; ! Default is Window5DataFile.dat in the “run” folder.
If there is a window called ConstructionName on the Window data file, the data for that window is read from the file and the following EnergyPlus objects and their names are created. The “W5” prefixed to these names indicates that the object originated in the Window5 data file.
WindowMaterial:Glazing for each of the glass layers. They will be named W5:ConstructionName:GLASS1, W5:ConstructionName:GLASS2 , etc.
WindowMaterial:Gas or WindowMaterial:GasMixture for each of the gap layers. They will be named W5:ConstructionName:GAP1, W5:ConstructionName:GAP2 , etc.
WindowProperty:FrameAndDivider (if the window on the Window5 data file has a frame and/or divider). It will be named W5:ConstructionName. This WindowProperty:FrameAndDivider will be assigned to any window on the input file that has a construction called “ConstructionName” even if that window has referenced another WindowProperty:FrameAndDivider (i.e., if WindowProperty:FrameAndDivider Name for that window is specified). In this case a warning will result.
Note that:
An entry on the WINDOW data file usually has just one glazing system. It is also possible to have an entry with two glazing systems separated by a horizontal or vertical mullion. In this case, the two glazing systems can have different dimensions and different properties. For example, one of the two glazing systems could be single glazed and the other could be double glazed. An example of the two glazing system case is given in the sample WINDOW data file shown below (although in this case the properties of the two glazing systems are the same).
EnergyPlus handles the “one glazing system” and “two glazing systems” cases differently. If there is one glazing system, the glazing system height and width from the Window5 data file are not used. Instead, the window dimensions are obtained from the window vertices that have been specified on the IDF file. However, a warning message will result if the height or width calculated from the window’s vertex inputs differs from the corresponding Window5 data file values by more than 10%. This warning is given since the effective frame and edge-of-glass conductances on the WINDOW data file can depend on the window dimensions if the frame is non-uniform, i.e., consists of sections with different values of width, projection, or thermal properties.
If the WINDOW data file entry has two glazing systems, System1 and System2, the following happens, as shown in the figure below. Assume that the original window is called WinOriginal. System1 is assigned to WinOriginal. Then EnergyPlus automatically creates a second window, called WinOriginal:2, and assigns System2 to it. The dimensions of WinOriginal are ignored; the dimensions of System1 on the data file are assigned to it, but the position of the lower left-hand vertex of WinOriginal is retained. The dimensions of System2 on the data file are assigned to WinOriginal:2. The lower left-hand vertex of WinOriginal:2 is determined from the mullion orientation and width.
Note: WinOriginal would have been the IDF window definition – it’s dimensions will be overridden by the systems dimensions from the Window data file. Two windows will be made and called WinOriginal and WinOriginal:2.
The Window Data File contains no information on shading devices. See “Specify the Material Name of the Shading Device” under WindowShadingControl for a method to attach a shading layer to windows read in from this file.
Following is an example WINDOW data file for a slider window with two identical double low-E glazing systems separated by a horizontal mullion. Each system has a frame and divider. Note that all dimensions, such as glazing height and width, are in millimeters; when EnergyPlus reads the file these are converted to meters. Following the data file example is a description of the contents of the file. That data used by EnergyPlus is shown in bold.
Window5 Data File for EnergyPlus
<WINDOW program version>
Date : Tue Nov 13 17:07:40 2001
Window name : DoubleLowE
Description : Horizontal Slider, AA
# Glazing Systems: 2
GLAZING SYSTEM DATA: Height Width nPanes Uval-center SC-center SHGC-center Tvis-center
System1 : 1032 669 2 1.660 0.538 0.467 0.696
System2 : 1033 669 2 1.660 0.538 0.467 0.696
FRAME/MULLION DATA: Width OutsideProj InsideProj Cond EdgeCondRatio SolAbs VisAbs Emiss Orient’n (mull)
L Sill : 97.3 25.4 25.4 500.000 1.467 0.500 0.500 0.90
R Sill : 97.3 25.4 25.4 500.000 1.467 0.500 0.500 0.90
L Head : 70.2 25.4 25.4 18.822 1.490 0.500 0.500 0.90
R Head : 70.2 25.4 25.4 18.822 1.490 0.500 0.500 0.90
Top L Jamb : 54.3 25.4 25.4 31.141 1.503 0.500 0.500 0.90
Bot L Jamb : 54.3 25.4 25.4 500.000 1.494 0.500 0.500 0.90
Top R Jamb : 70.2 25.4 25.4 500.000 1.518 0.500 0.500 0.90
Bot R Jamb : 97.6 25.4 25.4 264.673 1.547 0.500 0.500 0.90
Mullion : 53.5 25.4 25.4 500.000 1.361 0.500 0.500 0.90 Horizontal
Average frame: 75.5 25.4 25.4 326.149 1.464 0.500 0.500 0.90
DIVIDER DATA : Width OutsideProj InsideProj Cond EdgeCondRatio SolAbs VisAbs Emiss Type #Hor #Vert
System1 : 25.4 25.4 25.4 3.068 1.191 0.500 0.500 0.900 DividedLite 2 3
System2 : 25.4 25.4 25.4 3.068 1.191 0.500 0.500 0.900 DividedLite 2 3
GLASS DATA : Layer# Thickness Cond Tsol Rfsol Rbsol Tvis Rfvis Rbvis Tir EmissF EmissB SpectralDataFile
System1 : 1 3.00 0.900 0.50 0.33 0.39 0.78 0.16 0.13 0.00 0.16 0.13 CMFTIR_3.AFG
2 6.00 0.900 0.77 0.07 0.07 0.88 0.08 0.08 0.00 0.84 0.84 CLEAR_6.DAT
System2 : 1 3.00 0.900 0.50 0.33 0.39 0.78 0.16 0.13 0.00 0.16 0.13 CMFTIR_3.AFG
2 6.00 0.900 0.77 0.07 0.07 0.88 0.08 0.08 0.00 0.84 0.84 CLEAR_6.DAT
GAP DATA : Gap# Thick nGasses
System1 : 1 12.70 1
System2 : 1 12.70 1
GAS DATA : GasName Fraction MolWeight ACond BCond CCond AVisc BVisc CVisc ASpHeat BSpHeat CSpHeat
System1 Gap1 : Air 1.0000 28.97 0.002873 7.76e-5 0.0 3.723e-6 4.94e-8 0.0 1002.737 0.012324 0.0
System2 Gap1 : Air 1.0000 28.97 0.002873 7.76e-5 0.0 3.723e-6 4.94e-8 0.0 1002.737 0.012324 0.0
GLAZING SYSTEM OPTICAL DATA
Angle 0 10 20 30 40 50 60 70 80 90 Hemis
System1
Tsol 0.408 0.410 0.404 0.395 0.383 0.362 0.316 0.230 0.106 0.000 0.338
Abs1 0.177 0.180 0.188 0.193 0.195 0.201 0.218 0.239 0.210 0.001 0.201
Abs2 0.060 0.060 0.061 0.061 0.063 0.063 0.061 0.053 0.038 0.000 0.059
Rfsol 0.355 0.350 0.348 0.350 0.359 0.374 0.405 0.478 0.646 0.999 0.392
Rbsol 0.289 0.285 0.283 0.282 0.285 0.296 0.328 0.411 0.594 1.000 0.322
Tvis 0.696 0.700 0.690 0.677 0.660 0.625 0.548 0.399 0.187 0.000 0.581
Rfvis 0.207 0.201 0.198 0.201 0.212 0.234 0.278 0.374 0.582 0.999 0.260
Rbvis 0.180 0.174 0.173 0.176 0.189 0.215 0.271 0.401 0.648 1.000 0.251
System2
Tsol 0.408 0.410 0.404 0.395 0.383 0.362 0.316 0.230 0.106 0.000 0.338
Abs1 0.177 0.180 0.188 0.193 0.195 0.201 0.218 0.239 0.210 0.001 0.201
Abs2 0.060 0.060 0.061 0.061 0.063 0.063 0.061 0.053 0.038 0.000 0.059
Rfsol 0.355 0.350 0.348 0.350 0.359 0.374 0.405 0.478 0.646 0.999 0.392
Rbsol 0.289 0.285 0.283 0.282 0.285 0.296 0.328 0.411 0.594 1.000 0.322
Tvis 0.696 0.700 0.690 0.677 0.660 0.625 0.548 0.399 0.187 0.000 0.581
Rfvis 0.207 0.201 0.198 0.201 0.212 0.234 0.278 0.374 0.582 0.999 0.260
Rbvis 0.180 0.174 0.173 0.176 0.189 0.215 0.271 0.401 0.648 1.000 0.251
Description of Contents of WINDOW Data File
(Quantities used in EnergyPlus are in bold; others are informative only)
Second line = version of WINDOW used to create the data file
Date = date the data file was created
Window name = name of this window; chosen by WINDOW5 user; EnergyPlus user enters the same name in EnergyPlus as name of a “Construction from Window5 Data File” object. EnergyPlus will search the Window5 data file for an entry of this name.
Description = One-line description of the window; this is treated as a comment.
# Glazing Systems: 1 or 2; value is usually 1 but can be 2 if window has a horizontal or vertical mullion that separates the window into two glazing systems that may or may not be different.
GLAZING SYSTEM DATA
System1, System2: separate characteristics given if window has a mullion.
Height, *width = height and width of glazed portion (i.e., excluding frame; and, if mullion present, excluding mullion).
nPanes = number of glass layers
Uval-center = center-of-glass U-value (including air films) under standard winter conditions* (W/m2)
SC-center = center-of-glass shading coefficient under standard summer conditions*.
SHCG-center = center-of-glass solar heat gain coefficient under standard summer conditions*.
Tvis-center = center-of-glass visible transmittance at normal incidence
FRAME/MULLION DATA
L,R Sill = left, right sill of frame
L,R Head = left, right header of frame
Top L, Bot L jamb = top-left, bottom-left jamb of frame
Bot L, Bot R jamb = bottom-left, bottom-right jamb of frame
Average frame = average characteristics of frame for use in EnergyPlus calculation. If mullion is present, original window is divided into two separate windows with the same average frame (with the mullion being split lengthwise and included in the average frame).
Width = width (m)
OutsideProj = amount of projection from outside glass (m)
InsideProj = amount of projection from inside glass (m)
Cond = effective surface-to-surface conductance (from THERM calculation) (W/m2)
EdgeCondRatio = ratio of surface-to-surface edge-of-glass conductance to surface-to-surface center-of-glass conductance (from THERM calculation)
SolAbs = solar absorptance
VisAbs = visible absorptance
Emiss = hemispherical thermal emissivity
Orientation = Horizontal or Vertical (mullion only); = None if no mullion.
DIVIDER DATA
Width through Emiss are the same as for FRAME/MULLION DATA
#Hor = number of horizontal dividers
#Vert = number of vertical dividers
Type = DividedLite or Suspended
GLASS DATA
System1, System2: separate characteristics are given if window has a mullion.
Cond = conductivity (W/m-K)
Tsol = spectral-average solar transmittance at normal incidence
Rfsol = spectral-average front solar reflectance at normal incidence
Rbsol = spectral-average back solar reflectance at normal incidence
Tvis = spectral-average visible transmittance at normal incidence
Rfvis = spectral-average front visible reflectance at normal incidence
Rbvis = spectral-average back visible reflectance at normal incidence
Tir = hemispherical IR transmittance
EmissF = hemispherical front emissivity
EmissB = hemispherical back emissivity
SpectralDataFile = name of spectral data file with wavelength-dependent transmission and reflection data used by WINDOW 5 to calculate the glazing system optical data. “None” will appear here if spectral-average data for this glass layer were used by WINDOW 5.
GAP DATA
System1, System2: separate characteristics are given if the window has a mullion.
Thick = thickness (m)
nGasses = number of gasses (1, 2 or 3)
GasName = name of the gas
Fraction = fraction of the gas
MolecWeight = molecular weight of the Nth gas
(In the following, conductivity, viscosity and specific heat as a function
of temperature, T (deg K), are expressed as A + B*T + C*T^2)
ACond = A coeff of conductivity (W/m-K)
BCond = B coeff of conductivity (W/m-K^2)
CCond = C coeff of conductivity (W/m-K^3)
AVisc = A coeff of viscosity (g/m-s)
BVisc = B coeff of viscosity (g/m-s-K)
CVisc = C coeff of viscosity (g/m-s-K^2)
ASpHeat = A coeff of specific heat (J/kg-K)
BSpHeat = B coeff of specific heat (J/kg-K^2)
CSpHeat = C coeff of specific heat (J/kg-K^3)
GLAZING SYSTEM OPTICAL DATA
System1, System2: separate characteristics are given if the window has a mullion.
Hemisph = hemispherical (i.e., diffuse)
Tsol = solar transmittance vs. angle of incidence
AbsN = solar absorptance of Nth layer vs. angle of incidence
Rfsol = front solar reflectance vs. angle of incidence
Rbsol = back solar reflectance vs. angle of incidence
Tvis = visible transmittance vs. angle of incidence
Rfvis = front visible reflectance vs. angle of incidence
Rbvis = back visible reflectance vs. angle of incidence
*Standard conditions are
Winter:
Indoor air temperature = 21.1C (70F)
Outdoor air temperature = -17.8C (0F)
Wind speed = 6.71 m/s (15 mph)
No solar radiation
Summer:
Indoor air temperature = 23.9C (75F)
Outdoor air temperature = 31.7C (89F)
Wind speed = 3.35 m/s (7.5 mph)
783 W/m2 (248 Btu/h-ft2) incident beam solar radiation normal to glazing
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.