Multipliers are used in EnergyPlus for convenience in
modeling. Though window multipliers are useful for any size
building when you have multiple windows on a façade, zone
multipliers are more useful in large buildings with several to
many stories.
Zone
multipliers are designed as a “multiplier” for floor area,
zone loads, and energy consumed by internal gains. It takes
the calculated load for the zone and multiplies it, sending
the multiplied load to the attached HVAC system. The HVAC
system size is specified to meet the entire multiplied zone
load and will report the amount of the load met in the
Zone/Sys Sensible Heating or Cooling Energy/Rate report
variable. Autosizing automatically accounts for multipliers.
Metered energy consumption by internal gains objects such as
Lights
or Electric Equipment will be multiplied.
To illustrate the benefits (and comparison of results), the
MultiStory.idf example file was used. The MultiStory file is a
9 zone, 10 story/floored building with heating
(ZoneHVAC:Baseboard:Convective:Electric object) and cooling
(ZoneHVAC:WindowAirConditioner object). The middle zone of
each floor in the original represents 4 zones (multiplier = 4)
and the middle floor (ZoneGroup) represents 8 floors
(ZoneGroup multiplier = 8). Clone representations were made
for comparisons:
Original Multistory
IDF
In the figure above, each “middle” zone represents 4
zones. The middle “floor” represents 8 floors. Additionally,
each of the windows has a multiplier of 4 – so each window
represents 4 windows of the same size. For the Multistory
file, the Zone
object for the center zones has the multiplier of 4. And for
the center floors, the ZoneList
and ZoneGroup
objects to collect the zones and apply multipliers. The top
floor then uses the Zone
object multiplier for the center zones. Specifically:
<snip>
Zone,
Gnd Center Zone, !- Name
0.0, !- Direction of Relative North {deg}
8.0, 0.0, 0.0, !- Origin [X,Y,Z] {m}
1, !- Type
4, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate; !- Volume {m3}
<snip>
ZoneGroup,
Mid Floor, !- Zone Group Name
Mid Floor List, !- Zone List Name
8; !- Zone List Multiplier
ZoneList,
Mid Floor List, !- Zone List Name
Mid West Zone, !- Zone 1 Name
Mid Center Zone, !- Zone 2 Name
Mid East Zone; !- Zone 3 Name
<snip>
Zone,
Top Center Zone, !- Name
0.0, !- Direction of Relative North {deg}
8.0, !- X Origin {m}
0.0, !- Y Origin {m}
22.5, !- Z Origin {m}
1, !- Type
4, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate; !- Volume {m3}
For comparison purposes, clones of the middle zones were
done.
Multistory with cloned middle
zones.
And, finally, the entire building was created:
Multistory building – fully
cloned.
The building is autosized. For convenience in comparison,
the extreme summer and winter days were used for autosizing
and the simulation was run for the 5 United States weather
files that are included in the EnergyPlus release: Chicago IL;
San Francisco CA; Golden CO; Tampa FL; and Washington DC.
Comparisons were done with the Zone
Group Loads values (Zone Group Sensible Heating Energy and Zone
Group Sensible Cooling Energy) as well as meter values for
Electricity. Using the regression testing limits that are used
during EnergyPlus development testing (i.e. small differences
are within .001 or .5%; big differences are greater than those
limits).
For the purposes of dicussion, the buildings will be
called: Multistory 1 – the original 9 zone building (with
multipliers and groups) ref: Figure 1; Multistory
2 – the building shown in Figure 2.
Multistory with cloned middle zones.; Multistory 3 – the fully
configured building – ref Figure 3.
The following table illustrates the regression testing for
Multistory 2 and Multistory 3, group loads and meters versus
Multistory 1 results. For these tables, the location
indicators refer to the following EnergyPlus weather files:
Chicago (USA IL Chicago-OHare.Intl.AP.725300 TMY3), San
Francisco (USA CA San.Francisco.Intl.AP.724940 TMY3),
Colorado(USA CO Golden-NREL.724666 TMY3), Tampa (USA FL
Tampa.Intl.AP.722110 TMY3), and Washington DC(USA VA
Sterling-Washington.Dulles.Intl.AP.724030 TMY3).
Multistory vs Multistory 2 and Multistory 3
LOCATION
MULTI-STORY 2 LOADS
MULTI-STORY 2 METER
MULTI-STORY 3 LOADS
MULTI-STORY 3 METER
Chicago
Small Diffs
Equal
Big Diffs* (76%)
Big Diffs* (62%)
San Francisco
Big Diffs* (2.43%)
Big Diffs* (0.6%)
Big Diffs* (49%)
Big Diffs* (41%)
Colorado
Small Diffs
Small Diffs
Big Diffs* (26%)
Big Diffs* (24%)
Tampa
Small Diffs
Small Diffs
Big Diffs* (6%)
Big Diffs* (2%)
Washington DC
Equal
Equal
Big Diffs* (91%)
Big Diffs* (72%)
* Big Diffs maximum occur in monthly values whereas the
runperiod values are much smaller.
To try to pare down the discrepancies shown here, the
effects of height that are used in the calculations were
removed (i.e., the Site:WeatherStation
and Site:HeightVariation
objects were entered as below to negate the effects of height
on the environmental variables such as wind and temperature).
In addition the height effect was removed from the OutdoorAir:Node
object.
Figure 10. Objects removing height from building
impacts.
With these included, the files were rerun with the
following results:
Multiplier Results with negated height
variation.
Location
Multi-story 2 Loahs
Multi-story 2 Meter
Multi-story 3 Loahs
Multi-story 3 Meter
Chicago
Small diffs
Small diffs
Small diffs
Small diffs
San Francisco
Small diffs
Small diffs
Small diffs
Small diffs
Colorado
Small diffs
Small diffs
Small diffs
Small diffs
Tampa
Small diffs
Small diffs
Small diffs
Small diffs
Washington DC
Small diffs
Small diffs
Small diffs
Small diffs
To investigate if other systems might have different
results, the Ideal Loads System was used as the system.
Similar results were found for the multipliers vs cloned
results. However, it may also be noted that the results
between the original systems (baseboard and window ac) vs the
ideal loads were very similar.
The biggest difference really comes in calculation time. As
shown in the following table,
Runtimes for Multistory files (baseboard/window
ac)
Location
Multi-story 1 (9 zones)
(mm:ss)
Multi-story 2 (18 zones)
(MM:SS)
Multi-story 3 (60 zones)
(MM:SS)
Chicago
1:05
2:14
13:15
San Francisco
1:04
2:05
13:20
Colorado
1:17
2:28
14:43
Tampa
1:11
2:21
13:43
Washington DC
1:05
2:15
13:18
Because the overall results were so similar, the run times
for the Ideal Loads runs are included:
Runtime for Multistory files (ideal loads)
Location
Multi-story 1 (9 zones)
(mm:ss)
Multi-story 2 (18 zones)
(MM:SS)
Multi-story 3 (60 zones)
(MM:SS)
Chicago
0:51
1:34
9:37
San Francisco
0:50
1:34
9:59
Colorado
0:51
1:40
10:31
Tampa
0:51
1:36
10:05
Washington DC
0:51
1:36
9:48
More zones (and, particularly more surfaces) make for
longer run times.
If the basic zone geometry is identical, make one zone,
copy & paste it as necessary, then change the Zone
Origin field to locate each zone correctly.
Do not use interzone surfaces between zones that are
multiplied. Set the adjoining surfaces to be adiabatic,
i.e. use the OtherZoneSurface exterior boundary condition with
the other surface pointing back to itself.
Locate the middle floor zones roughly halfway between
top and ground because exterior convection coefficients change
with height. Halfway should cause the differences to average
out. If you have many stories (the example only has 10
stories), consider using more middle floor zones.
Consider removing the effects of height variation for
the simulation.
Follow guidelines in HVACTemplate and other objects
about sizing if you are mixing autosize fields with hard sized
fields (recommended to “autosize” all fields rather than
mix).
All HVAC system sizes must be specified to meet the
entire multiplied zone load.
Autosizing automatically accounts for
multipliers.
Using Multipliers (Zone and/or Window)[LINK]
Background and Study using Multipliers[LINK]
Multipliers are used in EnergyPlus for convenience in modeling. Though window multipliers are useful for any size building when you have multiple windows on a façade, zone multipliers are more useful in large buildings with several to many stories.
Zone multipliers are designed as a “multiplier” for floor area, zone loads, and energy consumed by internal gains. It takes the calculated load for the zone and multiplies it, sending the multiplied load to the attached HVAC system. The HVAC system size is specified to meet the entire multiplied zone load and will report the amount of the load met in the Zone/Sys Sensible Heating or Cooling Energy/Rate report variable. Autosizing automatically accounts for multipliers. Metered energy consumption by internal gains objects such as Lights or Electric Equipment will be multiplied.
To illustrate the benefits (and comparison of results), the MultiStory.idf example file was used. The MultiStory file is a 9 zone, 10 story/floored building with heating (ZoneHVAC:Baseboard:Convective:Electric object) and cooling (ZoneHVAC:WindowAirConditioner object). The middle zone of each floor in the original represents 4 zones (multiplier = 4) and the middle floor (ZoneGroup) represents 8 floors (ZoneGroup multiplier = 8). Clone representations were made for comparisons:
In the figure above, each “middle” zone represents 4 zones. The middle “floor” represents 8 floors. Additionally, each of the windows has a multiplier of 4 – so each window represents 4 windows of the same size. For the Multistory file, the Zone object for the center zones has the multiplier of 4. And for the center floors, the ZoneList and ZoneGroup objects to collect the zones and apply multipliers. The top floor then uses the Zone object multiplier for the center zones. Specifically:
For comparison purposes, clones of the middle zones were done.
And, finally, the entire building was created:
The building is autosized. For convenience in comparison, the extreme summer and winter days were used for autosizing and the simulation was run for the 5 United States weather files that are included in the EnergyPlus release: Chicago IL; San Francisco CA; Golden CO; Tampa FL; and Washington DC.
Comparisons were done with the Zone Group Loads values (Zone Group Sensible Heating Energy and Zone Group Sensible Cooling Energy) as well as meter values for Electricity. Using the regression testing limits that are used during EnergyPlus development testing (i.e. small differences are within .001 or .5%; big differences are greater than those limits).
For the purposes of dicussion, the buildings will be called: Multistory 1 – the original 9 zone building (with multipliers and groups) ref: Figure 1; Multistory 2 – the building shown in Figure 2. Multistory with cloned middle zones.; Multistory 3 – the fully configured building – ref Figure 3.
The following table illustrates the regression testing for Multistory 2 and Multistory 3, group loads and meters versus Multistory 1 results. For these tables, the location indicators refer to the following EnergyPlus weather files: Chicago (USA IL Chicago-OHare.Intl.AP.725300 TMY3), San Francisco (USA CA San.Francisco.Intl.AP.724940 TMY3), Colorado(USA CO Golden-NREL.724666 TMY3), Tampa (USA FL Tampa.Intl.AP.722110 TMY3), and Washington DC(USA VA Sterling-Washington.Dulles.Intl.AP.724030 TMY3).
* Big Diffs maximum occur in monthly values whereas the runperiod values are much smaller.
To try to pare down the discrepancies shown here, the effects of height that are used in the calculations were removed (i.e., the Site:WeatherStation and Site:HeightVariation objects were entered as below to negate the effects of height on the environmental variables such as wind and temperature). In addition the height effect was removed from the OutdoorAir:Node object.
Figure 10. Objects removing height from building impacts.
With these included, the files were rerun with the following results:
To investigate if other systems might have different results, the Ideal Loads System was used as the system. Similar results were found for the multipliers vs cloned results. However, it may also be noted that the results between the original systems (baseboard and window ac) vs the ideal loads were very similar.
The biggest difference really comes in calculation time. As shown in the following table,
Because the overall results were so similar, the run times for the Ideal Loads runs are included:
More zones (and, particularly more surfaces) make for longer run times.
Guidelines for Using Multipliers and Groups[LINK]
If the basic zone geometry is identical, make one zone, copy & paste it as necessary, then change the Zone Origin field to locate each zone correctly.
Do not use interzone surfaces between zones that are multiplied. Set the adjoining surfaces to be adiabatic, i.e. use the OtherZoneSurface exterior boundary condition with the other surface pointing back to itself.
Locate the middle floor zones roughly halfway between top and ground because exterior convection coefficients change with height. Halfway should cause the differences to average out. If you have many stories (the example only has 10 stories), consider using more middle floor zones.
Consider removing the effects of height variation for the simulation.
Follow guidelines in HVACTemplate and other objects about sizing if you are mixing autosize fields with hard sized fields (recommended to “autosize” all fields rather than mix).
All HVAC system sizes must be specified to meet the entire multiplied zone load.
Autosizing automatically accounts for multipliers.