Group – Hybrid Model[LINK]
This object provides a hybrid model feature to enhance
energy simulations for existing buildings by inversely solving
hard-to-measure model input parameters. More specifically,
zone internal thermal mass, air infiltration rate (ACH), and
people count are usually hard to be measured directly yet
important in building energy simulations. The hybrid model
takes measured zone air temperature, humidity ratio, or
CO\(_2\) concentration as
inputs and inversely solve those unknown parameters based on
the zone air heat, moisture, or CO\(_2\) balance algorithms. The
inversely solved internal thermal mass, air infiltration rate,
and people count can then be used to substitute the original
simplified assumptions to enhance the energy simulation.
The name of the HybridModel:Zone
object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: Zone) and
attaches a particular hybrid model input to a thermal zone in
the building.
Field:
Calculate Zone Internal Thermal Mass[LINK]
This field is used to provide an option to calculate the
temperature capacity multiplier (Ref:
ZoneCapacitanceMultiplier:ResearchSpecial). The temperature
capacity multiplier is represented as internal thermal mass
multiplier in the hybrid model. When YES is selected, the
hybrid model calculates the multiplier based on the inverse
heat balance algorithm using the measured zone air
temperature.
Field:
Calculate Zone Air Infiltration Rate[LINK]
This field is used to provide an option to calculate the
zone air infiltration rate - air change per hour (ACH). When
YES is selected, the hybrid model calculates the zone air
infiltration rate based on one of the following balance
equations: 1. Heat balance equations, 2. Moisture balance
equations, 3. CO\(_2\)
balance equations when the corresponding data requirements are
met. The HybridModel will be activated with the following
options:
1. When Zone
Measured Air Temperature Schedule Name is provided, it will
calculate the zone air infiltration rate assuming the HVAC
system is free-floating using the zone sensible heat balance
algorithms;
2. When Zone
Measured Air Temperature Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air Temperature Schedule Name are provided, it
will calculate the zone air infiltration rate assuming the
HVAC is on. In this case, the zone air supply air temperature
and mass flow rate in the zone sensible heat balance
algorithms will be overwritten by the input data;
3. When Zone
Measured Air Humidity Ratio Schedule Name is provided, it will
calculate the zone air infiltration rate assuming the HVAC
system is free-floating using the zone moisture balance
algorithms;
4. When Zone
Measured Air Humidity Ratio Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air Humidity Ratio Schedule Name are provided, it
will calculate the zone air infiltration rate assuming the
HVAC is on. In this case, the zone air supply air humidity
ratio and mass flow rate in the zone moisture balance
algorithms will be overwritten by the input data;
5. When Zone
Measured Air CO\(_2\)
concentration Schedule Name is provided, it will calculate the
zone air infiltration rate assuming the HVAC system is
free-floating using the zone CO\(_2\) balance algorithms;
6. When Zone
Measured Air CO\(_2\)
concentration Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air CO\(_2\)
Concentration Schedule Name are provided, it will calculate
the zone air infiltration rate assuming the HVAC is on. In
this case, the zone air supply air CO\(_2\) concentration and mass flow
rate in the zone CO\(_2\)
balance algorithms will be overwritten by the input data;
When YES is selected for Calculate Zone
Internal Thermal Mass, this field will be treated as NO.
Field:
Calculate Zone People Count[LINK]
This field is used to provide an option to calculate the
zone people count. When YES is selected, the hybrid model
calculates the zone people count based on one of the following
balance equations: 1. heat balance equations, 2. Moisture
balance equations, 3. CO\(_2\) balance equations when the
corresponding data requirements are met. The HybridModel will
be activated with the following options:
1. When Zone
Measured Air Temperature Schedule Name is provided, it will
calculate the zone people count assuming the HVAC system is
free-floating using the zone sensible heat balance algorithms.
The default people activity level is 130 W. The default
sensible heat fraction is 0.6.The default radiant heat
fraction is 0.7. Zone
Input People
Activity Level Schedule Name, Zone
Input People
Sensible Heat Fraction Schedule Name, and Zone
Input People
Radiant Heat Fraction Schedule Name are optional. When
provided, the default values will be overwritten.
2. When Zone
Measured Air Temperature Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air Temperature Schedule Name are provided, it
will calculate the zone people count assuming the HVAC is on.
In this case, the zone air supply air temperature and mass
flow rate in the zone sensible heat balance algorithms will be
overwritten by the input data.The default people activity
level is 130 W. The default sensible heat fraction is 0.6.The
default radiant heat fraction is 0.7. Zone
Input People
Activity Level Schedule Name, Zone
Input People
Sensible Heat Fraction Schedule Name, and Zone
Input People
Radiant Heat Fraction Schedule Name are optional. When
provided, the default values will be overwritten.
3. When Zone
Measured Air Humidity Ratio Schedule Name is provided, it will
calculate the zone people count assuming the HVAC system is
free-floating using the zone moisture balance algorithms.The
default people activity level is 130 W. The default sensible
heat fraction is 0.6.The default radiant heat fraction is 0.7.
Zone
Input People
Activity Level Schedule Name, Zone
Input People
Sensible Heat Fraction Schedule Name, and Zone
Input People
Radiant Heat Fraction Schedule Name are optional. When
provided, the default values will be overwritten.
4. When Zone
Measured Air Humidity Ratio Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air Humidity Ratio Schedule Name are provided, it
will calculate the zone people count assuming the HVAC is on.
In this case, the zone air supply air humidity ratio and mass
flow rate in the zone moisture balance algorithms will be
overwritten by the input data.The default people activity
level is 130 W. The default sensible heat fraction is 0.6.The
default radiant heat fraction is 0.7. Zone
Input People
Activity Level Schedule Name, Zone
Input People
Sensible Heat Fraction Schedule Name, and Zone
Input People
Radiant Heat Fraction Schedule Name are optional. When
provided, the default values will be overwritten.
5. When Zone
Measured Air CO\(_2\)
concentration Schedule Name is provided, it will calculate the
zone people count assuming the HVAC system is free-floating
using the zone CO\(_2\)
balance algorithms. The default people activity level is 130
W. The default single person CO\(_2\) generation is 0.0000000382
[m\(^3\)/(s*W)]. Zone
Input People
Activity Level Schedule Name, Zone
Input People
CO\(_2\) Generation Rate
Schedule Name are optional. When provided, the default values
will be overwritten.
6. When Zone
Measured Air CO\(_2\)
concentration Schedule Name, Zone
Input Supply Air Mass Flow Rate Schedule Name, and Zone
Input Supply Air CO\(_2\)
Concentration Schedule Name are provided, it will calculate
the zone people count assuming the HVAC is on. In this case,
the zone air supply air CO\(_2\) concentration and mass flow
rate in the zone CO\(_2\)
balance algorithms will be overwritten by the input data. The
default people activity level is 130 W. The default single
person CO\(_2\) generation is
0.0000000382 [m\(^3\)/(s*W)].
Zone
Input People
Activity Level Schedule Name, Zone
Input People
CO\(_2\) Generation Rate
Schedule Name are optional. When provided, the default values
will be overwritten.
When YES is selected for Calculate Zone
Internal Thermal Mass or Calculate Zone
Air Infiltration Rate, this field will be treated as NO.
Field:
Zone Measured Air Temperature Schedule Name[LINK]
This field is the name of the schedule object which
contains the zone air temperature measurement data. The date
range of the schedule should cover the start and end date of
the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
Field:
Zone Measured Air Humidity Ratio Schedule Name[LINK]
This field is the name of the schedule object which
contains the zone air humidity ration measurement data. The
date range of the schedule should cover the start and end date
of the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
Field:
Zone Measured Air CO\(_2\)
concentration Schedule Name[LINK]
This field is the name of the schedule object which
contains the zone air CO\(_2\) concentration measurement
data. The date range of the schedule should cover the start
and end date of the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
This field is the name of the schedule referenced by a
Schedule object which contains the people activity level data.
The date range of the schedule should cover the start and end
date of the HybridModel.
This field is the name of the schedule referenced by a
Schedule object which contains the people sensible heat
fraction data. The date range of the schedule should cover the
start and end date of the HybridModel.
This field is the name of the schedule referenced by a
Schedule object which contains the radiant heat fraction of
the sensible heat data. The date range of the schedule should
cover the start and end date of the HybridModel.
This field is the name of the schedule referenced by a
Schedule object which contains a single person’s CO\(_2\) generation rate data. The
date range of the schedule should cover the start and end date
of the HybridModel.
This field is the name of the schedule object which
contains the measured supply air temperature data. The date
range of the schedule should cover the start and end date of
the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
This field is the name of the schedule object which
contains the measured supply air mass flow rate data. The date
range of the schedule should cover the start and end date of
the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
This field is the name of the schedule object which
contains the measured supply air humidity ratio data. The date
range of the schedule should cover the start and end date of
the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
This field is the name of the schedule object which
contains the measured supply air CO\(_2\) concentration data. The date
range of the schedule should cover the start and end date of
the HybridModel. A Schedule:File
object is recommended for inputing the time-series
measurements. When a schedule:file object is provided, all the
rows for a whole year should be in the file, the rows outside
of the start and end date range of the HybridModel should be
zeros.
Field: Begin Month[LINK]
This numeric field should contain the starting month number
(1 = January, 2 = February, etc.) for the period of the
measured data during which the hybrid model will be
active.
Field: Begin Day of
Month[LINK]
This numeric field should contain the starting day of the
starting month (must be valid for month) for the period of the
measured data during which the hybrid model will be
active.
Field: End Month[LINK]
This numeric field should contain the ending month number
(1 = January, 2 = February, etc.) for the period of the
measured data during which the hybrid model will be
active.
Field: End Day of
Month[LINK]
This numeric field should contain the ending day of the
ending month (must be valid for month) for the period of the
measured data during which the hybrid model will be
active.
Examples of the object in an IDF are:
HybridModel:Zone,
ZONE 1 HybridModel, !- Name
ZONE 1, !- Zone Name
Yes, !- Calculate Zone Internal Thermal Mass
No, !- Calculate Zone Air Infiltration Rate
No, !- Calculate Zone People Count
, !- Zone Measured Air Temperature Schedule Name
, !- Zone Measured Air Humidity Ratio Schedule Name
ZONE 1_MeasuredCO2Concentration, !- Zone Measured Air CO2 Concentration Schedule Name
, !- Zone Input People Activity Schedule Name
, !- Zone Input People Sensible Heat Fraction Schedule Name
, !- Zone Input People Radiant Heat Fraction Schedule Name
, !- Zone Input People CO2 Generation Rate Schedule Name
, !- Zone Input Supply Air Temperature Schedule Name
, !- Zone Input Supply Air Mass Flow Rate Schedule Name
, !- Zone Input Supply Air Humidity Ratio Schedule Name
, !- Zone Input Supply Air CO2 Concentration Schedule Name
1, !- Begin Month
1, !- Begin Day of Month
12, !- End Month
31; !- End Day of Month
HybridModel:Zone,
ZONE 1 HybridModel, !- Name
ZONE 1, !- Zone Name
No, !- Calculate Zone Internal Thermal Mass
Yes, !- Calculate Zone Air Infiltration Rate
No, !- Calculate Zone People Count
, !- Zone Measured Air Temperature Schedule Name
, !- Zone Measured Air Humidity Ratio Schedule Name
ZONE 1_MeasuredCO2Concentration, !- Zone Measured Air CO2 Concentration Schedule Name
, !- Zone Input People Activity Schedule Name
, !- Zone Input People Sensible Heat Fraction Schedule Name
, !- Zone Input People Radiant Heat Fraction Schedule Name
, !- Zone Input People CO2 Generation Rate Schedule Name
, !- Zone Input Supply Air Temperature Schedule Name
, !- Zone Input Supply Air Mass Flow Rate Schedule Name
, !- Zone Input Supply Air Humidity Ratio Schedule Name
, !- Zone Input Supply Air CO2 Concentration Schedule Name
1, !- Begin Month
1, !- Begin Day of Month
12, !- End Month
31; !- End Day of Month
HybridModel:Zone,
ZONE 2 HybridModel, !- Name
ZONE 2, !- Zone Name
No, !- Calculate Zone Internal Thermal Mass
No, !- Calculate Zone Air Infiltration Rate
Yes, !- Calculate Zone People Count
, !- Zone Measured Air Temperature Schedule Name
, !- Zone Measured Air Humidity Ratio Schedule Name
ZONE 2_MeasuredCO2Concentration, !- Zone Measured Air CO2 Concentration Schedule Name
OfficeSmall ACTIVITY_SCH, !- Zone Input People Activity Schedule Name
People Sensible Heat Fraction Sch, !- Zone Input People Sensible Heat Fraction Schedule Name
People Radiation Heat Fraction Sch, !- Zone Input People Radiant Heat Fraction Schedule Name
People CO2 Generation Rate Sch, !- Zone Input People CO2 Generation Rate Schedule Name
, !- Zone Input Supply Air Temperature Schedule Name
ZONE 2_Inlet_MassFlow, !- Zone Input Supply Air Mass Flow Rate Schedule Name
, !- Zone Input Supply Air Humidity Ratio Schedule Name
ZONE 2_Inlet_CO2, !- Zone Input Supply Air CO2 Concentration Schedule Name
1, !- Begin Month
1, !- Begin Day of Month
12, !- End Month
31; !- End Day of Month
Zone,Average,Zone Infiltration Hybrid Model Air Change Rate [ACH]
Zone,Average,Zone Infiltration Hybrid Model Mass Flow Rate [kg/s]
Zone,Average,Zone Hybrid Model People Count
Zone
Infiltration Hybrid Model Air Change Rate [ACH][LINK]
The zone infiltration air change rate calculated by the
hybrid model.
Zone
Infiltration Hybrid Model Mass Flow Rate [kg/s][LINK]
The zone infiltration air mass flow rate calculated by the
hybrid model.
Zone
Hybrid Model People Count[LINK]
The zone people count calculated by the hybrid model.
Group – Hybrid Model[LINK]
HybridModel:Zone[LINK]
This object provides a hybrid model feature to enhance energy simulations for existing buildings by inversely solving hard-to-measure model input parameters. More specifically, zone internal thermal mass, air infiltration rate (ACH), and people count are usually hard to be measured directly yet important in building energy simulations. The hybrid model takes measured zone air temperature, humidity ratio, or CO\(_2\) concentration as inputs and inversely solve those unknown parameters based on the zone air heat, moisture, or CO\(_2\) balance algorithms. The inversely solved internal thermal mass, air infiltration rate, and people count can then be used to substitute the original simplified assumptions to enhance the energy simulation.
Inputs[LINK]
Field: Name[LINK]
The name of the HybridModel:Zone object.
Field: Zone Name[LINK]
This field is the name of the thermal zone (ref: Zone) and attaches a particular hybrid model input to a thermal zone in the building.
Field: Calculate Zone Internal Thermal Mass[LINK]
This field is used to provide an option to calculate the temperature capacity multiplier (Ref: ZoneCapacitanceMultiplier:ResearchSpecial). The temperature capacity multiplier is represented as internal thermal mass multiplier in the hybrid model. When YES is selected, the hybrid model calculates the multiplier based on the inverse heat balance algorithm using the measured zone air temperature.
Field: Calculate Zone Air Infiltration Rate[LINK]
This field is used to provide an option to calculate the zone air infiltration rate - air change per hour (ACH). When YES is selected, the hybrid model calculates the zone air infiltration rate based on one of the following balance equations: 1. Heat balance equations, 2. Moisture balance equations, 3. CO\(_2\) balance equations when the corresponding data requirements are met. The HybridModel will be activated with the following options:
1. When Zone Measured Air Temperature Schedule Name is provided, it will calculate the zone air infiltration rate assuming the HVAC system is free-floating using the zone sensible heat balance algorithms;
2. When Zone Measured Air Temperature Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Temperature Schedule Name are provided, it will calculate the zone air infiltration rate assuming the HVAC is on. In this case, the zone air supply air temperature and mass flow rate in the zone sensible heat balance algorithms will be overwritten by the input data;
3. When Zone Measured Air Humidity Ratio Schedule Name is provided, it will calculate the zone air infiltration rate assuming the HVAC system is free-floating using the zone moisture balance algorithms;
4. When Zone Measured Air Humidity Ratio Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Humidity Ratio Schedule Name are provided, it will calculate the zone air infiltration rate assuming the HVAC is on. In this case, the zone air supply air humidity ratio and mass flow rate in the zone moisture balance algorithms will be overwritten by the input data;
5. When Zone Measured Air CO\(_2\) concentration Schedule Name is provided, it will calculate the zone air infiltration rate assuming the HVAC system is free-floating using the zone CO\(_2\) balance algorithms;
6. When Zone Measured Air CO\(_2\) concentration Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air CO\(_2\) Concentration Schedule Name are provided, it will calculate the zone air infiltration rate assuming the HVAC is on. In this case, the zone air supply air CO\(_2\) concentration and mass flow rate in the zone CO\(_2\) balance algorithms will be overwritten by the input data;
When YES is selected for Calculate Zone Internal Thermal Mass, this field will be treated as NO.
Field: Calculate Zone People Count[LINK]
This field is used to provide an option to calculate the zone people count. When YES is selected, the hybrid model calculates the zone people count based on one of the following balance equations: 1. heat balance equations, 2. Moisture balance equations, 3. CO\(_2\) balance equations when the corresponding data requirements are met. The HybridModel will be activated with the following options:
1. When Zone Measured Air Temperature Schedule Name is provided, it will calculate the zone people count assuming the HVAC system is free-floating using the zone sensible heat balance algorithms. The default people activity level is 130 W. The default sensible heat fraction is 0.6.The default radiant heat fraction is 0.7. Zone Input People Activity Level Schedule Name, Zone Input People Sensible Heat Fraction Schedule Name, and Zone Input People Radiant Heat Fraction Schedule Name are optional. When provided, the default values will be overwritten.
2. When Zone Measured Air Temperature Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Temperature Schedule Name are provided, it will calculate the zone people count assuming the HVAC is on. In this case, the zone air supply air temperature and mass flow rate in the zone sensible heat balance algorithms will be overwritten by the input data.The default people activity level is 130 W. The default sensible heat fraction is 0.6.The default radiant heat fraction is 0.7. Zone Input People Activity Level Schedule Name, Zone Input People Sensible Heat Fraction Schedule Name, and Zone Input People Radiant Heat Fraction Schedule Name are optional. When provided, the default values will be overwritten.
3. When Zone Measured Air Humidity Ratio Schedule Name is provided, it will calculate the zone people count assuming the HVAC system is free-floating using the zone moisture balance algorithms.The default people activity level is 130 W. The default sensible heat fraction is 0.6.The default radiant heat fraction is 0.7. Zone Input People Activity Level Schedule Name, Zone Input People Sensible Heat Fraction Schedule Name, and Zone Input People Radiant Heat Fraction Schedule Name are optional. When provided, the default values will be overwritten.
4. When Zone Measured Air Humidity Ratio Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Humidity Ratio Schedule Name are provided, it will calculate the zone people count assuming the HVAC is on. In this case, the zone air supply air humidity ratio and mass flow rate in the zone moisture balance algorithms will be overwritten by the input data.The default people activity level is 130 W. The default sensible heat fraction is 0.6.The default radiant heat fraction is 0.7. Zone Input People Activity Level Schedule Name, Zone Input People Sensible Heat Fraction Schedule Name, and Zone Input People Radiant Heat Fraction Schedule Name are optional. When provided, the default values will be overwritten.
5. When Zone Measured Air CO\(_2\) concentration Schedule Name is provided, it will calculate the zone people count assuming the HVAC system is free-floating using the zone CO\(_2\) balance algorithms. The default people activity level is 130 W. The default single person CO\(_2\) generation is 0.0000000382 [m\(^3\)/(s*W)]. Zone Input People Activity Level Schedule Name, Zone Input People CO\(_2\) Generation Rate Schedule Name are optional. When provided, the default values will be overwritten.
6. When Zone Measured Air CO\(_2\) concentration Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air CO\(_2\) Concentration Schedule Name are provided, it will calculate the zone people count assuming the HVAC is on. In this case, the zone air supply air CO\(_2\) concentration and mass flow rate in the zone CO\(_2\) balance algorithms will be overwritten by the input data. The default people activity level is 130 W. The default single person CO\(_2\) generation is 0.0000000382 [m\(^3\)/(s*W)]. Zone Input People Activity Level Schedule Name, Zone Input People CO\(_2\) Generation Rate Schedule Name are optional. When provided, the default values will be overwritten.
When YES is selected for Calculate Zone Internal Thermal Mass or Calculate Zone Air Infiltration Rate, this field will be treated as NO.
Field: Zone Measured Air Temperature Schedule Name[LINK]
This field is the name of the schedule object which contains the zone air temperature measurement data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Measured Air Humidity Ratio Schedule Name[LINK]
This field is the name of the schedule object which contains the zone air humidity ration measurement data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Measured Air CO\(_2\) concentration Schedule Name[LINK]
This field is the name of the schedule object which contains the zone air CO\(_2\) concentration measurement data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Input People Activity Level Schedule Name[LINK]
This field is the name of the schedule referenced by a Schedule object which contains the people activity level data. The date range of the schedule should cover the start and end date of the HybridModel.
Field: Zone Input People Sensible Heat Fraction Schedule Name[LINK]
This field is the name of the schedule referenced by a Schedule object which contains the people sensible heat fraction data. The date range of the schedule should cover the start and end date of the HybridModel.
Field: Zone Input People Radiant Heat Fraction Schedule Name[LINK]
This field is the name of the schedule referenced by a Schedule object which contains the radiant heat fraction of the sensible heat data. The date range of the schedule should cover the start and end date of the HybridModel.
Field: Zone Input People CO\(_2\) Generation Rate Schedule Name[LINK]
This field is the name of the schedule referenced by a Schedule object which contains a single person’s CO\(_2\) generation rate data. The date range of the schedule should cover the start and end date of the HybridModel.
Field: Zone Input Supply Air Temperature Schedule Name[LINK]
This field is the name of the schedule object which contains the measured supply air temperature data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Input Supply Air Mass Flow Rate Schedule Name[LINK]
This field is the name of the schedule object which contains the measured supply air mass flow rate data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Input Supply Air Humidity Ratio Schedule Name[LINK]
This field is the name of the schedule object which contains the measured supply air humidity ratio data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Zone Input Supply Air CO\(_2\) Concentration Schedule Name[LINK]
This field is the name of the schedule object which contains the measured supply air CO\(_2\) concentration data. The date range of the schedule should cover the start and end date of the HybridModel. A Schedule:File object is recommended for inputing the time-series measurements. When a schedule:file object is provided, all the rows for a whole year should be in the file, the rows outside of the start and end date range of the HybridModel should be zeros.
Field: Begin Month[LINK]
This numeric field should contain the starting month number (1 = January, 2 = February, etc.) for the period of the measured data during which the hybrid model will be active.
Field: Begin Day of Month[LINK]
This numeric field should contain the starting day of the starting month (must be valid for month) for the period of the measured data during which the hybrid model will be active.
Field: End Month[LINK]
This numeric field should contain the ending month number (1 = January, 2 = February, etc.) for the period of the measured data during which the hybrid model will be active.
Field: End Day of Month[LINK]
This numeric field should contain the ending day of the ending month (must be valid for month) for the period of the measured data during which the hybrid model will be active.
Examples of the object in an IDF are:
Outputs[LINK]
Zone Infiltration Hybrid Model Air Change Rate [ACH][LINK]
The zone infiltration air change rate calculated by the hybrid model.
Zone Infiltration Hybrid Model Mass Flow Rate [kg/s][LINK]
The zone infiltration air mass flow rate calculated by the hybrid model.
Zone Hybrid Model People Count[LINK]
The zone people count calculated by the hybrid model.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.