Group – Node-Branch
Management[LINK]
Nodes, Branch
Lists and Branches define
the topography of the HVAC connections.
For convenience, the NodeList
object can be used to identify all the nodes for a particular
use. A node list is not always required. The advantage of
listing all the nodes in this manner is that input fields in
other objects that ask for a node name can refer to either a
single node or a list of nodes using this object.
There are other lines of input syntax that require the use
of a NodeList
as part of the input. These syntax items include: OutdoorAir:NodeList
and the SetpointManager objects. In these two cases, the use
of a NodeList
statement is mandatory if there is more than one node in this
particular “list”. For example, if the outside air only has a
single inlet node, then the name of that node can replace the
node list name in the input syntax. As a result of this
mandatory specification of node lists for certain types of
input, nodes can, obviously, and may be members of more than
one list.
This alpha designation must be unique among all the Node
List Names. It is used as reference in various objects
(e.g. OutdoorAir:NodeList).
Field: Node
<#> Name (up to 25 allowed)[LINK]
Each unique Node identifier creates a Node structure with
various attributes depending on the type of node. Typical
values include Temperature, Mass Flow Rate, and Temperature
Set Point. The alpha designators are associated with a
particular node.
Though each NodeList
is limited to 25 nodes, several node lists may be entered if
you choose to identify all the nodes up front. For
example:
NodeList, Nodes1-25,
NODE_1,NODE_2,NODE_3,NODE_4,NODE_5,NODE_6,NODE_7,NODE_8,NODE_9,NODE_10,
NODE_11,NODE_12,NODE_13,NODE_14,NODE_15,NODE_16,NODE_17,NODE_18,NODE_19,NODE_20,
NODE_21,NODE_22,NODE_23,NODE_24,NODE_25;
NodeList, Nodes26-49,NODE_26,NODE_27,NODE_28,NODE_29,NODE_30,
NODE_31,NODE_32,NODE_33,NODE_34,NODE_35,NODE_36,NODE_37,NODE_38,NODE_39,NODE_40,
NODE_41,NODE_42,NODE_43,NODE_44,NODE_45,NODE_46,NODE_47,NODE_48,NODE_49;
A simple detail of Nodes and numbers assigned appears in
the eplusout.bnd file:
! <Node>,<NodeNumber>,<Node Name>,<Node Fluid Type>,<\# Times Node Referenced After Definition>
Node,1,OUTSIDE AIR INLET NODE 1,Air,2
Node,2,VAV SYS 1 INLET NODE,Air,3
Node,3,MIXED AIR NODE 1,Air,5
Node,4,MAIN COOLING COIL 1 OUTLET NODE,Air,3
Node,5,MAIN HEATING COIL 1 OUTLET NODE,Air,4
Node,6,VAV SYS 1 OUTLET NODE,Air,7
In addition, properties of each node is available during
the simulation:
HVAC,Average,System Node Temperature [C]
HVAC,Average,System Node Last Timestep
Temperature [C]
HVAC,Average,System Node Mass Flow Rate [kg/s]
HVAC,Average,System Node Humidity Ratio
[kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Temperature
[C]
HVAC,Average,System Node Setpoint High Temperature
[C]
HVAC,Average,System Node Setpoint Low Temperature
[C]
HVAC,Average,System Node Setpoint Humidity Ratio
[kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Minimum Humidity
Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Maximum Humidity
Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Relative Humidity [%]
HVAC,Average,System Node Pressure [Pa]
HVAC,Average,System Node Standard Density Volume Flow
Rate [m3/s]
HVAC,Average,System Node Enthalpy [J/kg]
HVAC,Average,System Node Last Timestep
Enthalpy [J/kg]
HVAC,Average,System Node Wetbulb Temperature
[C]
HVAC,Average,System Node Dewpoint Temperature
[C]
HVAC,Average,System Node Quality []
HVAC,Average,System Node Height [m]
HVAC,Average,System Node Specific Heat
[J/kg-K]
The following node variable is also available for
system nodes that are for “air”:
HVAC, Average, System Node Current Density Volume Flow
Rate [m3/s]
HVAC, Average, System Node Current Density
[kg/m3]
The following node variables are “advanced” and
normally used for debugging unusual cases:
HVAC,Average,System Node Minimum Temperature
[C]
HVAC,Average,System Node Maximum Temperature
[C]
HVAC,Average,System Node Minimum Limit Mass Flow Rate
[kg/s]
HVAC,Average,System Node Maximum Limit Mass Flow Rate
[kg/s]
HVAC,Average,System Node Minimum Available Mass Flow
Rate [kg/s]
HVAC,Average,System Node Maximum Available Mass Flow
Rate [kg/s]
HVAC,Averge,System Node Requested Mass Flow Rate
[kg/s]
HVAC,Average,System Node Setpoint Mass Flow Rate
[kg/s]
The following node variable reports node carbon
dioxide concentration when carbon dioxide is simulated (ref.
ZoneAirContaminantBalance):
- HVAC,Average,System Node CO2 Concentration [ppm]
The following node variable reports node generic
contaminant concentration when generic contaminant is
simulated (ref. ZoneAirContaminantBalance):
- HVAC,Average,System Node Generic Air Contaminant
Concentration [ppm]
System Node Temperature
[C][LINK]
The current temperature at a system node in degrees C. For
air nodes, this is the dry-bulb temperature.
System Node
Last Timestep Temperature [C][LINK]
The temperature at a system node for the previous
timestep.
System Node Mass Flow
Rate [kg/s][LINK]
The current mass flow rate at a system node in kg/s.
System
Node Humidity Ratio [kgWater/kgDryAir][LINK]
The current humidity ratio at a system node in
kg-water/kg-dry-air. Not applicable for liquid nodes.
System Node
Setpoint Temperature [C][LINK]
The current setpoint temperature at a system node in
degrees C. Some controllers and equipment types sense this
single setpoint.
System Node
Setpoint High Temperature [C][LINK]
The current upper setpoint temperature at a system node in
degrees C. Some controllers and equipment types use dual
setpoints at a single node.
System Node
Setpoint Low Temperature [C][LINK]
The current lower setpoint temperature at a system node in
degrees C. Some controllers and equipment types use dual
setpoints at a single node.
System
Node Setpoint Humidity Ratio [kgWater/kgDryAir][LINK]
The current humidity ratio setpoint at a system node in
kg-water/kg-dry-air. Some controllers and equipment types
sense this single setpoint. Not applicable for liquid
nodes.
System
Node Setpoint Minimum Humidity Ratio [kgWater/kgDryAir][LINK]
The current minimum desired humidity ratio at a system node
in kg-water/kg-dry-air. Some controllers and equipment types
use the min/max values as dual setpoints at a single node. Not
applicable for liquid nodes.
System
Node Setpoint Maximum Humidity Ratio [kgWater/kgDryAir][LINK]
The current maximum desired humidity ratio at a system node
in kg-water/kg-dry-air. Some controllers and equipment types
use the min/max values as dual setpoints at a single node. Not
applicable for liquid nodes.
System Node Relative
Humidity [%][LINK]
The current relative humidity (calculated from the node
temperature, node humidity ratio and standard barometric
pressure for the location). Not applicable for liquid
nodes.
System Node Pressure
[Pa][LINK]
The current pressure at a system node in Pa.
System
Node Standard Density Volume Flow Rate [m\(^{3}\)/s][LINK]
The current volume flow rate at a system node in m\(^{3}\)/s. This is report is
calculated from the mass flow using standardized values for
density that do not vary over time (except for steam which
varies with quality). For water nodes this density is
determined at a temperature of 5.05ºC. For air nodes this
density is determined for dry air at the standard barometric
pressure for the location’s elevation, and a temperature of
20.0ºC. For air nodes, also see the report “System Node
Current Density Volume Flow Rate.”
System Node Enthalpy
[J/kg][LINK]
The current enthalpy at a system node in J/kg.
System Node
Last Timestep Enthalpy [J/kg][LINK]
The enthalpy at the system node for the previous timestep
in Joules per kilogram.
System Node Wetbulb
Temperature [C][LINK]
The current wet-bulb temperature at a system node in
degrees C. Not applicable for liquid nodes.
System Node
Dewpoint Temperature [C][LINK]
The current dewpoint temperature at a system node in
degrees C. It is calculated from the System Node Temperature,
the System Node Humidity Ratio and the Site Outdoor Air
Barometric Pressure. Not applicable for liquid nodes.
System Node Quality [][LINK]
The current system node vapor fraction/percent
{0.0-1.0}.
System Node Height [m][LINK]
The current system node height {m}. Only applicable to
outdoor air nodes.
System Node Specific
Heat [J/kg-K][LINK]
The current specific heat capacity of the fluid at the node
in units of J/kg-K. Not available for steam nodes.
Additional Node Reporting for Air
Nodes
The following system node variable is available for nodes
with a fluid type of air.
System
Node Current Density Volume Flow Rate [m\(^{3}\)/s][LINK]
The current volume flow rate at a system node in m\(^{3}\)/s based on the current
density. This report differs from the one called “System Node
Standard Density Volume Flow Rate” in that it uses an air
density calculated for the current moist air conditions rather
than a standard density.
System Node Current
Density [kg/m3][LINK]
The current air density at a system node in kg/m3. This is
the density used to calculate the volume flow rate above. The
density is calculated using current outdoor air barometric
pressure and the drybulb temperature and humidity ratio at the
air node.
Advanced Node Reporting
The following system node variables are available when you
request “Diagnostics, DisplayAdvancedReportVariable;”. They
are normally used for debugging unusual system cases and may
not be available for all systems. Also, their definitions may
change based on the usage in the system.
System Node Minimum
Temperature [C][LINK]
System Node Maximum
Temperature [C][LINK]
These node variables represent the min/max of loops or
branches.
System
Node Minimum Limit Mass Flow Rate [kg/s][LINK]
System
Node Maximum Limit Mass Flow Rate [kg/s][LINK]
These node variables hold the maximum possible and the
minimum allowable flow rates for a particular component. As
such, they represent the “hardware limit” on the flow rate for
the component. By convention, these variables are stored at
the component inlet node. Since components share their nodes
(the outlet node of one component is the inlet node of the
next component), the protocol must be strictly followed. These
variables are set by each component based on the design flow
limits of the equipment.
System
Node Minimum Available Mass Flow Rate [kg/s][LINK]
System
Node Maximum Available Mass Flow Rate [kg/s][LINK]
These node variables represent the loop or
branch maximum and minimum flow rate for the current
configuration of the loop on which the component resides. The
central plant routines manage these variables dynamically to
resolve flow rates through branches located inside splitters
and mixers.
System Node
Setpoint Mass Flow Rate [kg/s][LINK]
The current mass flow rate setpoint at a system node in
kg/s. Some controllers and equipment types sense this single
setpoint.
System Node
Requested Mass Flow Rate [kg/s][LINK]
This output is the current mass flow rate request at a
system node in kg/s. Only used for plant simulations and
nodes. This is the mass flow rate “requested” by a
component. This is a record of what the component wanted
which can be useful for diagnostics when the actual simulated
flow is different than expected. This value is also used to
determine overall loop flow rates.
System Node CO2
Concentration [ppm][LINK]
The average carbon dioxide concentration, in parts per
million (ppm), at a system node for the timestep being
reported.
System
Node Generic Air Contaminant Concentration [ppm][LINK]
The average generic contaminant concentration, in parts per
million (ppm), at a system node for the timestep being
reported.
A branch list is intended to define the branches or
portions of a particular loop that are present on an
individual plant or condenser loop. Thus, the BranchList
syntax simply provides a list of branch names (see Branch
syntax) that then refer to more detailed syntax in another
part of the input file. The syntax for describing a list of
branches is given below.
Branches in BranchList
objects should be listed in flow order: inlet branch, then
parallel branches, then outlet branch. Branches (within a
splitter/mixer) are simulated in the order listed.
A unique name to identify the branch list.
Field: Branch <#> Name[LINK]
Branch
name in the list. As noted above, Branches in BranchList
objects MUST be listed in flow order: inlet branch, then
parallel branches, then outlet branch. Branches are simulated
in the order listed.
An example of this statement in an IDF is:
BranchList, Cooling Supply Side Branches,
CW Pump Branch,
Little Chiller Branch,
Big Chiller Branch,
Purchased Cooling Branch,
Supply Bypass Branch,
Cooling Supply Outlet;
No output directly related to Branch
Lists current is presented.
Branches can be considered the mid-level grouping of items
in the EnergyPlus HVAC loop scheme. Components are the lowest
level of information. A collection of components in series
forms a branch. Every branch must have at least one component,
but it may have several components in series. The air loop
also has “unitary” objects that are compound objects that wrap
components and when they are used it is the unitary objects
that appear on the Branch
and not the child components. The Branch
defines the order that components appear on the branch.
Moreover, a collection of branches and their connecting
information form a loop. Therefore, a branch is a collection
of components while a loop is a collection of branches. Thus,
components are specified for particular HVAC loops by
assigning them to branches and then connecting those branches
together to form a loop.
For hydronic plant systems, the Branch
object is used on both the demand side and the supply side of
the plant loop. For HVAC air systems, the Branch
object is only used to describe the components on the supply
side of an air loop. The demand side of the air loop does not
use the Branch
object. The outside air system appears on a Branch
object but it does not use a Branch
object itself to describe the components that included in the
outside air system. So-called “ZoneHVAC:*” equipment, HVAC
equipment directly associated with a zone, do not use the Branch
object.
It should be noted that each component also has at least
two nodes associated with it—an inlet node and an outlet node.
These nodes, by default, are also part of the branch to which
their components are assigned. Although it may appear
redundant to list the node names in both the Branch
and in the component object being referenced, this is needed
because many components are connected to more than one loop at
a time and the node names are needed here to distinguish which
portion of the component is being attached to this particular
branch and its loop. It should be noted that each branch must
have at least one component on it. A “null” branch such as one
where the first component on the loop is in reality a splitter
or mixer should be defined as a single Pipe component for
plant, or a single Duct
component for air systems.
This alpha field is the unique, user-defined name that
allows the branch to be referenced by other elements such as
the PlantLoop
and CondenserLoop
statements.
Field: Pressure Drop
Curve Name[LINK]
This is an optional field used to specify pressure drop
information for this particular branch. Currently this is only
available in plant/condenser fluid loops: PlantLoop
and CondenserLoop.
Air loops require a full airflow network, so this field is
ignored if found on an air loop. The value entered for this
field must match a pressure curve object also found in the
input. This curve can be of the type: Curve:Linear,
Curve:Quadratic,
Curve:Cubic,
Curve:Exponent,
or Curve:Functional:PressureDrop.
In order to then perform a pressure simulation for the loop
that this branch is located on, a flag must be set in the loop
object. Reference the PlantLoop
and CondenserLoop
field “Pressure Simulation Type” for allowable settings. See
the Engineering Reference document for further information on
pressure simulation in plant loops.
Field Set (Branch
Specifications)[LINK]
Following the two introductory items, there are groups of 4
repeated items: a type, a name, inlet and outlet node names.
All of these items refer to one particular component on the
branch. The first component defined by these items will be the
first component on this branch, etc. through the end of the
list. This object is extensible and can use as many field
sets as needed by repeating the last four fields.
Field: Component
<#> Object Type[LINK]
This field is the component object type (object class
name). The component type refers to other elements within the
input file and specifies what kind of component this is. The
objects in the Group – Plant Equipment section are valid here
when the Branch
is used in Plant specifications. Fans, coils, unitary systems,
and Outside Air Systems are also valid component types for the
Branch
object. Pipes or Ducts are also valid for this field. No
splitter or mixer type objects are allowed.
Field: Component <#>
Name[LINK]
The component name is the unique, user-defined reference
name to distinguish between potentially multiple occurrences
of a particular component type in an input file. The set of
component type and component name must be unique. (You can
only have 1 Boiler object with name MYBOILER).
Field: Component
<#> Inlet Node Name[LINK]
This field references an inlet node name that will be found
in the actual component specification. The inlet node, and
the outlet node specified in the next field, should correspond
to component model’s connections that are intended for the
loop that this Branch
is assigned to. For example a water-cooled chiller will have
two inlet nodes, one for chilled water return and one for
condenser water return and so the chiller will appear on two
Branch
objects accordingly.
Field: Component
<#> Outlet Node Name[LINK]
This field references an outlet node name that will be
found in the actual component specification.
An example of this statement in an IDF is:
Branch,
Air Loop Main Branch, !- Branch Name
, !- Pressure Drop Curve Name
AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, !- Comp1 Type
GasHeat CBVAV System, !- Comp1 Name
Air Loop Inlet Node, !- Comp1 Inlet Node Name
Air Loop Outlet Node; !- Comp1 Outlet Node Name
And a more complex one:
BRANCH,
Air Loop Main Branch, !- Branch Name
, !- Pressure Drop Curve Name
FAN:ConstantVolume, !- Comp1 Type
Supply Fan 1, !- Comp1 Name
Air Loop Inlet Node, !- Comp1 Inlet Node Name
Cooling Coil Air Inlet Node, !- Comp1 Outlet Node Name
COIL:Water:DetailedFlatCooling, !- Comp2 Type
Detailed Cooling Coil, !- Comp2 Name
Cooling Coil Air Inlet Node, !- Comp2 Inlet Node Name
Air Loop Outlet Node; !- Comp2 Outlet Node Name
The components on a branch are in series and that list is
in simulation and connection order. Each branch must obey the
rules: the outlet for component 1 has to have the same node
name as the inlet for component 2, and so forth.
Eplusout.err contains the test for “individual branch
integrity”:
************* Testing Individual Branch Integrity
************* Testing Branch = AIR LOOP MAIN BRANCH
************* ....passed
************* Testing Branch = COOLING DEMAND INLET
************* ....passed
************* Testing Branch = COOLING COIL BRANCH
************* ....passed
************* Testing Branch = DEMAND BYPASS BRANCH
************* ....passed
************* Testing Branch = COOLING DEMAND OUTLET
************* ....passed
************* Testing Branch = COOLING SUPPLY OUTLET
************* ....passed
The addition of pressure simulation for branches in fluid
loops brings a new output at the branch level:
- HVAC,Average,Plant Branch Pressure Difference [Pa]
Plant Branch
Pressure Difference [Pa][LINK]
This field allows the user to output the pressure drop of a
particular branch on a plant loop or condenser loop. This
output is only recognized if a valid pressure simulation is
being performed. To do this, the user must specify a pressure
simulation type as an input in the PlantLoop
or CondenserLoop
object.
ConnectorList[LINK]
A connector list is a collection of either one or two
connection devices (Connector:Mixer or Connector:Splitter).
Due to the definition of a loop in EnergyPlus, there is a
maximum of one mixer and one splitter allowed for each loop
segment. This limitation still allows a tremendous amount of
flexibility to the user and can also still be solved within a
reasonable amount of time and without a complex solver
routine. The connection list simply allows the specification
of the types and names of these devices. This allows the main
loop statements to have the flexibility to have multiple lists
that can have one or more item.
This field is an identifying name that will be referenced
to main loop statements using this connector list. The name
must be unique among connector list names.
Field-Set:
Connection Object Type and Identifying Name (up to 2
allowed)[LINK]
Depending on the loop, either one or two of the connectors
will be specified. If this particular loop only has a single
connector (either Connector:Mixer
or Connector:Splitter), then only the first two items (type of
connection and identifying name of connector) are included. If
both a mixer and splitter are present, the additional type of
connection and identifying name must be included. Note that
the order that the items appear is inconsequential—either the
Connector:Mixer
or the Connector:Splitter
may appear first. This will not affect the simulation.
Field: Connector 1
Object Type[LINK]
This field contains the connector type Connector:Mixer
or Connector:Splitter.
Field: Connector 1 Name[LINK]
This field is an identifying name for the connector. It
will be used by other objects in the input file.
Field:
Connector 2 Object Type (optional)[LINK]
This field contains the connector type Connector:Mixer
or Connector:Splitter.
Field: Connector 2
Name (optional)[LINK]
This field is an identifying name for the connector. It
will be used by other objects in the input file.
An example of this statement in an IDF is:
ConnectorList LIST, Cooling Supply Side Connectors,
Connector:Splitter, CW Loop Splitter,
Connector:Mixer, CW Loop Mixer;
No output directly related to Connector Lists is currently
presented.
Plant Loop Connectors[LINK]
The connector list described in the preceding subsection
determines how the branches of a particular loop will be
hooked together. These connections can be classified either as
a separation of a single stream into several outlet streams
(splitter) or the merging of several streams into a single
outlet stream (mixer). Due to the limitation per branch of a
single splitter and a single mixer, the connector list can
only have two pieces of equipment as a maximum. The names
defined for either/both the splitter or/and the mixer refer
then to “component” definitions as described in the next two
subsections.
The format of both the Connector:Splitter
and Connector:Mixer
statements is similar. Both begin with an identifying name
followed by the branch name of the “single side” of the
component. In the case of the splitter, this is the inlet
since the inlet stream is broken into several outlet streams.
In the case of the mixer, this is the outlet since several
streams are mixed together to form a single outlet. The
remaining list of up to 50 names is simply the branch names of
the outlet legs in the case of the splitter and inlet legs in
the case of the mixer. No control logic is assume in these
components—a determination of how much air to split in which
direction using the splitter must be defined by other
components.
Connector:Splitter[LINK]
A Connector:Splitter
is used to take a single fluid stream or branch and split it
into more than one outlet branches. This input object is used
purely to connect the inlet and outlet branches.
This alpha field contains the identifying name for the
Splitter.
Field: Inlet Branch Name[LINK]
This alpha field contains the identifying name for the
Splitter Inlet Branch.
Field: Outlet Branch
<x> Name[LINK]
This alpha field contains the identifying names for the
Splitter Outlet Branches and you enter as many outlet branches
as needed.
Connector:Mixer[LINK]
A Connector:Mixer
is used to combine or mix several inlet branches into a single
outlet branch. This input object is used purely to connect the
inlet branches with the outlet branch.
This alpha field contains the identifying name for the
Mixer.
Field: Outlet Branch
Name[LINK]
This alpha field contains the identifying name for the
Mixer Outlet Branch.
Field: Inlet Branch
<x> Name[LINK]
This alpha field contains the identifying names for the
Mixer Inlet Branches and you enter as many inlet branch names
as needed..
An example of these statements in an IDF is:
Connector:Splitter,
CW Loop Splitter,
CW Pump Branch,
Little Chiller Branch,
Big Chiller Branch,
Purchased Cooling Branch,
Supply Bypass Branch;
Connector:Mixer,
CW Loop Mixer,
Cooling Supply Outlet,
Little Chiller Branch,
Big Chiller Branch,
Purchased Cooling Branch,
Supply Bypass Branch;
Pipe:Adiabatic[LINK]
In reality, every component is connected to its closest
neighbors via a pipe or a duct. At the current time, such
detail is not needed in EnergyPlus. Thus, the Pipe:Adiabatic
component is currently used more as a connection device (for
branches that really do not have any components associated
with them) or as a bypass than anything else. As such, its
input is very simple and its algorithm is equally simple. The
current algorithm for a pipe is simply to pass the inlet
conditions to the outlet of the pipe component.
This alpha field is used as an identifying field for the
pipe.
Field: Inlet Node Name[LINK]
This alpha field is used as an identifying field for the
pipe inlet node.
Field: Outlet Node
Name[LINK]
This alpha field is used as an identifying field for the
pipe outlet node.
An example of this statement in an IDF is:
Pipe:Adiabatic,
Demand Side Inlet Pipe,
CW Demand Inlet Node,
CW Demand Entrance Pipe Outlet Node;
There are no outputs directly related to Pipes.
Pipe:Adiabatic:Steam[LINK]
To connect the various components in a steam system
regardless of it being the condensate or the steam side of the
loop steam pipe needs to be used. In reality, every component
is connected to its closest neighbors via a pipe or a duct. At
the current time, such detail is not needed in EnergyPlus.
Thus, the Pipe:Adiabatic:Steam
component is currently used more as a connection device (for
branches that really do not have any components associated
with them). As such, its input is very simple and its
algorithm is equally simple. The current algorithm for a pipe
is simply to pass the inlet conditions to the outlet of the
pipe component.
This alpha field is used as an identifying field for the
steam pipe.
Field: Inlet Node
Name[LINK]
This alpha field is used as an identifying field for the
steam pipe inlet node.
Field: Outlet Node
Name[LINK]
This alpha field is used as an identifying field for the
steampipe outlet node.
An example of this statement in an IDF is:
Pipe:Adiabatic:Steam,
Steam Demand 1 Steam Inlet Pipe, !- PipeName
Steam Demand 1 Steam Demand Inlet Node, !- Inlet Node Name
Steam Demand 1 Steam Demand Entrance Pipe Outlet Node; !- Outlet Node Name
There are no outputs directly related to Steam Pipes.
This object specifies inputs which are used to simulate the
heat transfer from a plant loop pipe placed in a zone or when
a user schedule is used to specify an environment.
The data definition for object is shown below.
This alpha field is used as an identifying field for the
pipe.
Field: Construction
Name[LINK]
This alpha field references a ‘wall’ construction object
that gives a layer-by-layer description of the pipe wall and
its insulation. The construction object follows standard
conventions, describing material properties for each layer
beginning with the outermost insulation layer and ending with
the pipe wall layer.
Field: Fluid Inlet
Node Name[LINK]
This alpha field contains the name of the pipe fluid inlet
node.
Field: Fluid Outlet
Node Name[LINK]
This alpha field contains the name of the pipe fluid outlet
node.
Field: Environment Type[LINK]
Environment type is the environment in which the pipe is
placed. It can be either Zone
or Schedule. If specified as Zone,
a zone name must be specified in the next field. If specified
as Schedule, the Ambient Temperature Zone
can be left blank, while a schedule must be specified for the
temperature and air velocity.
Field: Ambient
Temperature Zone Name[LINK]
If Zone
is specified as the environment type, this field is used to
specify the name of the zone in which the pipe is located.
The zone temperature is used to calculate the heat transfer
rate from the pipe.
Field:
Ambient Temperature Schedule Name[LINK]
If Schedule is specified as the
environment type, this field is used to specify the name of
the temperature schedule that gives the ambient air
temperature surrounding the pipe. This temperature is used as
the outside boundary condition to calculate heat transfer from
the pipe.
Field:
Ambient Air Velocity Schedule Name[LINK]
If Schedule is specified as the
environment type, this field is used to specify the name of
the velocity schedule that gives the air velocity near the
pipe. This velocity is used to calculate the convection heat
transfer coefficient used in the pipe heat transfer
calculation.
Field: Pipe Inside
Diameter[LINK]
This field is used to enter the inside diameter of the pipe
in units of m. Pipe inside diameter must be a positive
number.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in units
of m. Pipe length must be a positive number.
An example of this object in an IDF is:
Pipe:Indoor,
Pipe Heat Transfer Towers, !- name of outside panel heat exchanger
Insulated Pipe, !- Construction name
Condenser Tower Outlet Node, !- Comp1 Inlet Node Name
HTPipe Outlet Node, !- Comp1 Outlet Node Name
Water, !- Fluid name
Zone, !- field Ambient Temperature Outside Air Node name
0.05, !- Pipe Inside Diameter (thickness in construction data)
100.0; !- pipe length
HVAC,Average, Pipe Fluid Heat Transfer Rate
[W]
HVAC,Average, Pipe Ambient Heat Transfer Rate
[W]
HVAC,SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC,SUM, Pipe Ambient Heat Transfer Energy
[J]
HVAC,Average, Pipe Mass Flow Rate [kg/s]
HVAC,Average, Pipe Inlet Temperature [C]
HVAC,Average, Pipe Outlet Temperature [C]
HVAC,Average, Pipe Volume Flow Rate [m3/s]
Pipe Fluid Heat
Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in
the fluid from pipe inlet to outlet.
Pipe Ambient Heat
Transfer Rate [W][LINK]
The output provides the amount of heat loss/gain from pipe
wall to the environment.
Pipe Fluid Heat
Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and
outlet. It is metered on EnergyTransfer with an end use of
Pipes.
Pipe Ambient Heat
Transfer Energy [J][LINK]
Total energy lost from the external pipe surface.
Pipe Mass Flow Rate
[kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Inlet Temperature
[C][LINK]
Pipe Outlet Temperature
[C][LINK]
Temperature of fluid at entering and exiting of pipe.
Pipe Volume Flow Rate
[m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
This object specifies inputs which are used to simulate the
heat transfer from a plant loop pipe placed in an outdoor
environment.
This alpha field is used as an identifying field for the
pipe.
Field: Construction
Name[LINK]
This alpha field references a ‘wall’ construction object
that gives a layer-by-layer description of the pipe wall and
its insulation. The construction object follows standard
conventions, describing material properties for each layer
beginning with the outermost insulation layer and ending with
the pipe wall layer.
Field: Fluid Inlet
Node Name[LINK]
This alpha field contains the name of the pipe fluid inlet
node.
Field: Fluid
Outlet Node Name[LINK]
This alpha field contains the name of the pipe fluid outlet
node.
Field:
Ambient Temperature Outside Air Node Name[LINK]
Ambient temperature outdoor air node is a node representing
outdoor air with which pipe transfers heat. The node should be
included in an outdoor air node list.
Field: Pipe Inside
Diameter[LINK]
This field is used to enter the inside diameter of the pipe
in units of m. Pipe inside diameter must be a positive
quantity.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in units
of m. Pipe length must be a positive quantity.
An example of this statement in an IDF is:
Pipe:Outdoor,
Pipe Heat Transfer Towers, !- name of outside panel heat exchanger
Insulated Pipe, !- Construction name
Condenser Tower Outlet Node, !- Comp1 Inlet Node Name
HTPipe Outlet Node, !- Comp1 Outlet Node Name
Water, !- Fluid name
PipeHeatTransfer Inlet Node, !- field Ambient Temperature Outside Air Node name
0.05, !- Pipe Inside Diameter (thickness given in construction data)
100.0; !- pipe length
HVAC,Average, Pipe Fluid Heat Transfer Rate
[W]
HVAC,SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC,Average, Pipe Mass Flow Rate [kg/s]
HVAC,Average, Pipe Inlet Temperature [T]
HVAC,Average, Pipe Outlet Temperature [T]
HVAC,Average, Pipe Volume Flow Rate [m3/s]
Pipe Fluid Heat
Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in
the fluid from pipe inlet to outlet.
Pipe Fluid Heat
Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and
outlet. It is metered on EnergyTransfer with an end use of
Pipes.
Pipe Mass Flow Rate
[kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Inlet Temperature
[C][LINK]
Pipe Outlet Temperature
[C][LINK]
Temperature of fluid at entering and exiting of pipe.
Pipe Volume Flow Rate
[m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
Pipe:Underground[LINK]
This object specifies inputs which are used to simulate the
heat transfer from a plant loop pipe placed underground.
This alpha field is used as an identifying field for the
pipe.
Field: Construction
Name[LINK]
This alpha field references a basic construction object
that gives a layer-by-layer description of the pipe wall and
insulation. The construction object follows standard
conventions, describing material properties for each layer
beginning with the outermost layer, the insulation, if it
exists, and ending with the pipe wall layer. The construction
object may have either one or two layers. If only one, then
the material must be the pipe wall. If two, then insulation
is utilized.
Field: Fluid Inlet Node
Name[LINK]
This alpha field contains the name of the pipe fluid inlet
node.
Field: Fluid Outlet Node
Name[LINK]
This alpha field contains the name of the pipe fluid
outlet node.
Field: Sun Exposure[LINK]
This alpha field allows the user to specify one of two
options: NoSun or SunExposed. For SunExposed, the simulation
includes diffuse and beam solar effects on the ground
surface. For NoSun, no solar effects are included.
Field: Pipe Inside
Diameter[LINK]
This field is used to enter the inside diameter of the
pipe in units of m. Pipe inside diameter must be a positive
quantity.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in
units of {m}. Pipe length must be a positive quantity.
Field: Soil Material
Name[LINK]
This references a Material
object that contains the soil properties and thickness. Note
that when defining the soil layer, the thickness should be the
thickness of soil between the pipe wall and the ground
surface.
Field:
Type of Undisturbed Ground Temperature Object[LINK]
This is the type of undisturbed ground temperature object
that is used to determine the ground temperature.
Field:
Name of Undisturbed Ground Temperature Object[LINK]
This is the name of the undisturbed ground temperature
object that is used to determine the ground temperature.
An example of this object in an IDF is:
Pipe:Underground,
Pipe Heat Transfer Towers, !- Name of Pipe
Insulated Buried Pipe, !- Construction Name
Condenser Tower Outlet Node, !- Inlet Node Name
HTPipe Outlet Node, !- Outlet Node Name
Water, !- Fluid Name
SunExposed, !- Sun Exposure
0.05, !- Pipe Inside Diameter
20.0, !- Pipe Length
Buried Pipe Soil, !- Soil Material
Site:GroundTemperature:Undisturbed:KusudaAchenbach, !- Type of Undisturbed Ground Temperature Object
KATemps; !- Name of Undisturbed Ground Temperature Object
Construction,
Insulated Buried Pipe, !- Name
Buried Pipe Insulation, !- Layer #1
Buried Pipe Steel; !- Layer #2
Material,
Buried Pipe Soil, !- Name
Smooth, !- Roughness
1.5, !- Thickness {m}
0.36, !- Conductivity {W/m-K}
2000.0, !- Density {kg/m3}
1200.0, !- Specific Heat {J/kg-K}
0.9, !- Thermal Absorptance
0.5, !- Solar Absorptance
0.5; !- Visible Absorptance
HVAC, Average, Pipe Fluid Heat Transfer Rate
[W]
HVAC, SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC, Average, Pipe Mass Flow Rate [kg/s]
HVAC, Average, Pipe Volume Flow Rate [m3/s]
HVAC, Average, Pipe Inlet Temperature [C]
HVAC, Average, Pipe Outlet Temperature [C]
Pipe Fluid Heat
Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in
the fluid from pipe inlet to outlet.
Pipe Fluid Heat
Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and
outlet. It is metered on
EnergyTransfer with an end use of Pipes.
Pipe Mass Flow Rate
[kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Volume Flow Rate
[m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
Pipe Inlet Temperature
[C][LINK]
Pipe Outlet Temperature
[C][LINK]
Temperature of fluid at entrance and exit of pipe.
PipingSystem:Underground
Class Objects[LINK]
Objects in this class are used to simulate the heat
transfer processes of a piping system placed underground,
which may or may not be in contact with a number of zone
surfaces. There are three related objects, all of which are
prefixed with PipingSystem:Underground :
PipingSystem:Underground:Domain[LINK]
This section documents the domain object, which is used to
specify information for the overall ground domain, including
thermal properties, mesh parameters, and surface
interaction.
This alpha field is used as an identifying field for the
ground domain.
Field: XMax, YMax, ZMax[LINK]
These numeric fields are used to specify the overall domain
size, in each of the three Cartesian dimensions. The domain
will be meshed from {x, y, z} = {0, 0, 0} to {Xmax, Ymax,
Zmax}.
Note that for this object, the x-z plane lies parallel to
the ground surface, such that the y-dimension can be thought
of as representing the burial depth. This is in contrast to
the way building surface coordinates are defined with the x-y
plane lying parallel to the ground. Also note that any pipe
segments that end up being used in a ground domain will be
placed axially in the z-dimension. Thus, pipe flow will
always be in either the positive z or negative z
direction.
Field:
X-Direction Mesh Density Parameter[LINK]
This numeric integer field represents the number of cells
to be placed between any two “domain partitions” during mesh
development. A domain partition may be thought of as a
basement wall/floor, or a pipe. Once these components are
laid out in the domain, this field number of cells are placed
between the partitions. Further information on this is found
in the engineering reference manual.
Field: X-Direction Mesh
Type[LINK]
This alpha field represents the type of mesh to create when
placing cells between “domain partitions.” Two options are
available: “uniform” and “symmetricgeometric.” For uniform,
the cells are placed in the region with all cells having equal
size. For symmetric-geometric, the cells are compressed
toward the partitions so that there are more cells on either
side of the mesh region. This can help focus computational
intensity on the boundary areas where it is likely more
desired. For symmetric-geometric mesh distribution, the mesh
density parameter should be an even number to provide the
symmetric condition.
Field:
X-Direction Geometric Coefficient[LINK]
This numeric field represents the compression of cell
distribution if the x-direction mesh type is set to
“symmetricgeometric.” If the mesh type is uniform, this field
is not interpreted. For symmetric geometric, a value in this
field equal to 1 would result in a uniform distribution, while
a value of 2 would provide a highly skewed distribution.
Field:
Y-Direction Mesh Density Parameter[LINK]
See Field: X-Direction Mesh Density Parameter.
Field: Y-Direction Mesh
Type[LINK]
See Field: X-Direction Mesh Type.
Field:
Y-Direction Geometric Coefficient[LINK]
See Field: X-Direction Geometric Coefficient.
Field:
Z-Direction Mesh Density Parameter[LINK]
See Field: X-Direction Mesh Density Parameter.
Field: Z-Direction Mesh
Type[LINK]
See Field: X-Direction Mesh Type.
Field:
Z-Direction Geometric Coefficient[LINK]
See Field: X-Direction Geometric Coefficient.
Field: Soil
Thermal Conductivity[LINK]
The thermal conductivity of the soil, in W/m-K.
Field: Soil Density[LINK]
The bulk density of the soil, in kg/m3.
Field: Soil Specific
Heat[LINK]
The specific heat of dry soil, in J/kg-K. If moisture is
defined in this object, moisture and freezing effects are
accounted for by varying the specific heat value.
Field:
Soil Moisture Content Volume Fraction[LINK]
A nominal value of soil moisture content to be used when
evaluating soil thermal properties.
Field:
Soil Moisture Content Volume Fraction at Saturation[LINK]
A nominal value of soil moisture content when the soil is
saturated, this is used in evaluating thermal properties of
freezing soil
Field:
Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to
determine ground temperature for the farfield boundary
conditions.
Field:
Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used
to determine ground temperature for the farfield boundary
conditions.
Field:
This Domain Includes Basement Surface Interaction[LINK]
A yes/no field stating whether zone surfaces should be
coupled to this domain.
Field:
Width of Basement Floor in Ground Domain[LINK]
If this domain does include basement interaction, this
represents the width of the domain cutaway to include the
basement. In essence, this is the width of basement floor to
include in the ground simulation. This width should
include the basement wall thickness.
Field:
Width of Basement Floor in Ground Domain[LINK]
If this domain does include basement interaction, this
represents the depth of the domain cutaway to include the
basement. In essence, this is the burial depth of the
basement to include in the ground simulation. This depth
should include the basement floor thickness.
Field:
Shift Pipe X Coordinates By Basement Width[LINK]
If this domain does include basement interaction, this flag
specifies whether the pipe segment X-values should then be
shifted by the basement width. In essence, this specifies the
reference point for pipe segment x-values: if NO then the
reference is domain x = 0, if YES then the reference is the
basement width point.
Field:
Name of Basement Wall Boundary Condition Model[LINK]
The name of an OtherSideConditions model defined in the
input file and referenced by the surfaces which should be
included as “wall surfaces” for the basement interaction part
of the ground heat transfer model.
Field:
Name of Basement Wall Boundary Condition Model[LINK]
The name of an OtherSideConditions model defined in the
input file and referenced by the surfaces which should be
included as “floor surfaces” for the basement interaction part
of the ground heat transfer model.
Field:
Convergence Criterion for the Outer Cartesian Domain Iteration
Loop[LINK]
The maximum temperature deviation within any cell between
one iteration and another to decide that the Cartesian domain
has converged to within tolerance. A smaller value will
improve accuracy and computation time. A smaller value should
be accompanied by a higher number of iterations if maximum
accuracy is desired.
Field:
Maximum Iterations in the Outer Cartesian Domain Iteration
Loop[LINK]
The maximum number of iterations to make when performing
temperature updates of the Cartesian coordinate system. The
actual number of iterations made will of course depend on
transient conditions and convergence tolerance.
Field:
Evapotranspiration Ground Cover Parameter[LINK]
Numeric field specifies the ground cover effects used in
the evapotranspiration model at the ground surface heat
balance. The values range from 0 (solid, nonpermeable ground
surface) to 1.5 (wild growth).
Field:
Number of Pipe Circuits Entered for this Domain[LINK]
The number of pipe circuit objects which will be defined in
the following fields.
Field: Pipe
Circuit <#>[LINK]
A PipingSystem:Underground:PipeCircuit
to be included in this domain. This indicates that the pipe
circuit and all of the underlying pipe segments will be
included during mesh development and heat transfer
calculations within this domain. This object is extensible,
so any number of pipe circuits can be added, assuming all
underlying pipe segments do not cause any conflicts for the
mesh development engine (overlapping pipes, etc.).
PipingSystem:Underground:PipeCircuit[LINK]
This section documents the pipe circuit object, which is
used to specify information for the plant loop topology, such
as inlet and outlet connections. This object also groups
together pipe segments to define flow paths within a given
pipe circuit.
This alpha field is used as an identifying field for the
pipe circuit.
Field: Pipe
Thermal Conductivity[LINK]
The thermal conductivity of the pipe, in W/m-K.
Field: Pipe Density[LINK]
The bulk density of the pipe, in kg/m3.
Field: Pipe Specific
Heat[LINK]
The specific heat of the pipe, in J/kg-K.
Field: Pipe Inner
Diameter[LINK]
The inner diameter of the pipe, in m.
Field: Pipe Outer
Diameter[LINK]
The outer diameter of the pipe, in m.
Field: Design Flow
Rate[LINK]
The “design” flow in this pipe circuit, in m3/s. This is
the flow which this component will request during the
simulation. Of course, other components and overall plant
management will decide the flow actually given to this
component.
Field: Circuit Inlet
Node Name[LINK]
The inlet node name for this circuit, which is used when
placing this circuit on a branch on a plant or condenser
loop.
Field: Circuit Outlet
Node Name[LINK]
The outlet node name for this circuit, which is used when
placing this circuit on a branch on a plant or condenser
loop.
Field:
Convergence Criterion for the Inner Radial Iteration Loop[LINK]
The maximum temperature deviation within any cell between
one iteration and another to decide that the radial domain has
converged to within tolerance. A smaller value will improve
accuracy and computation time. A smaller value should be
accompanied by a higher number of iterations if maximum
accuracy is desired.
Field:
Maximum Iterations in the Inner Radial Iteration Loop[LINK]
The maximum number of iterations to make when performing
temperature updates of the radial coordinate system. The
actual number of iterations made will of course depend on
transient conditions and convergence tolerance.
Field:
Number of Soil Nodes in the Inner Radial Near Pipe Mesh
Region[LINK]
The number of soil nodes to discretize pipe cells. More
information on mesh development is provided in the engineering
reference manual.
Field:
Radial Thickness of Inner Radial Near Pipe Mesh Region[LINK]
The radial distance used to discretize pipe cells. More
information on mesh development is provided in the engineering
reference manual.
Field:
Number of Pipe Segments Entered for this Pipe Circuit[LINK]
The number of pipe segment objects which will be defined
in the following fields.
Field: Pipe
Segment <#>[LINK]
A PipingSystem:Underground:PipeSegment
to be included in this pipe circuit. The circuit is set up so
that flow passes through the N segments in the order
they are entered here. This object is extensible, so
additional fields of this type can be added to the end of this
object.
PipingSystem:Underground:PipeSegment[LINK]
This section documents the pipe segment object, which is
used to specify information for a single pipe segment placed
at some x, y coordinate in the ground. The flow direction is
also defined in this object to allow for careful description
of varying flow paths. This can be useful for accounting for
short circuiting effects if two pipes are placed in
counterflow vs. parallel flow.
This alpha field is used as an identifying field for the
pipe segment.
Field: X Position[LINK]
This numeric field represents the x-direction placement of
the pipe. If no basement is included in the simulation, this
is measured from x = 0. If a basement is included, and the
domain object specifies that pipes should be shifted, this is
measured from the basement wall.
Field: Y Position[LINK]
This numeric field represents the burial depth of the pipe,
measured from the ground surface. This will always be a
positive number.
Field: Flow Direction[LINK]
This alpha field is used to define the flow direction
within this pipe segment. The choices are “increasing” or
“decreasing.” These can be chosen carefully to encapsulate
specific short-circuiting effects due to varying flow
configurations (circuiting).
An example of this object in an IDF is offered here for a
foundation heat exchanger
PipingSystem:Underground:Domain,
My Piping System, !- Name
12, !- Xmax
4.5, !- Ymax
36.84, !- Zmax
2, !- XMeshCount
Uniform, !- XMeshType
, !- XGeometricCoeff
2, !- YMeshCount
Uniform, !- YMeshType
, !- YGeometricCoeff
6, !- ZMeshCount
Uniform, !- ZMeshType
, !- ZGeometricCoeff
1.08, !- GroundThermalConductivity
962, !- GroundDensity
2576, !- GroundSpecificHeat
30, !- MoistureContent
50, !- MoistureContentAtSaturation
Site:GroundTemperature:Undisturbed:KusudaAchenbach, !- Type of Undisturbed Ground Temperature Object
KATemps, !- Name of Undisturbed Ground Temperature Object
Yes, !- DomainHasBasement
6, !- BasementWidthInDomain
2.5, !- BasementDepthInDomain
Yes, !- ShiftPipeXValuesByBasementWidth
BasementWallOSCM, !- BasementWallBoundaryConditionModel
BasementFloorOSCM, !- BasementFloorBoundaryConditionModel
0.005, !- CartesianIterationConvergenceCriterion
100, !- CartesianMaxIterations
0.408, !- EvapotranspirationGroundCoverParameter
1, !- NumPipeCircuits
My Pipe Circuit; !- PipeCircuit
PipingSystem:Underground:PipeCircuit,
My Pipe Circuit, !- Name
0.3895, !- PipeThermalConductivity
641, !- PipeDensity
2405, !- PipeSpecificHeat
0.016, !- PipeInnerDiameter
0.02667, !- PipeOuterDiameter
0.004, !- DesignFlowRate
Piping System Inlet Node, !- InletNode
Piping System Outlet Node, !- OutletNode
0.001, !- RadialIterationConvergenceCriterion
100, !- RadialMaxIterations
2, !- RadialMeshCount
0.03, !- RadialMeshThickness
6, !- NumSegments
Segment 1, !- Segment1
Segment 2, !- Segment2
Segment 3, !- Segment3
Segment 4, !- Segment4
Segment 5, !- Segment5
Segment 6; !- Segment6
PipingSystem:Underground:PipeSegment,
Segment 1, !- Name
0.67, !- X
2.20, !- Burial Depth
IncreasingZ; !- Flow Direction
PipingSystem:Underground:PipeSegment,
Segment 2, !- Name
0.95, !- X
2.20, !- Burial Depth
IncreasingZ; !- Flow Direction
PipingSystem:Underground:PipeSegment,
Segment 3, !- Name
1.23, !- X
2.20, !- Burial Depth
IncreasingZ; !- Flow Direction
PipingSystem:Underground:PipeSegment,
Segment 4, !- Name
1.40, !- X
1.94, !- Burial Depth
DecreasingZ; !- Flow Direction
PipingSystem:Underground:PipeSegment,
Segment 5, !- Name
1.40, !- X
1.66, !- Burial Depth
DecreasingZ; !- Flow Direction
PipingSystem:Underground:PipeSegment,
Segment 6, !- Name
1.40, !- X
1.39, !- Burial Depth
DecreasingZ; !- Flow Direction
HVAC, Average, Pipe Circuit Mass Flow Rate
[kg/s]
HVAC, Average, Pipe Circuit Inlet Temperature
[C]
HVAC, Average, Pipe Circuit Outlet Temperature
[C]
HVAC, Average, Pipe Segment Inlet Temperature
[C]
HVAC, Average, Pipe Segment Outlet Temperature
[C]
HVAC, Average, Pipe Circuit Fluid Heat Transfer Rate
[W]
HVAC, Average, Pipe Segment Fluid Heat Transfer Rate
[W]
Pipe Circuit Mass
Flow Rate [kg/s][LINK]
The output provides the mass flow rate currently being sent
through the pipe circuit.
Pipe Circuit Inlet
Temperature [C][LINK]
Pipe Circuit Outlet
Temperature [C][LINK]
Temperature of fluid at the inlet and outlet of a given
pipe circuit.
Pipe Segment Inlet
Temperature [C][LINK]
Pipe Segment Outlet
Temperature [C][LINK]
Temperature of fluid at the inlet and outlet of a given
pipe segment.
Pipe Circuit
Fluid Heat Transfer Rate [W][LINK]
This is the fluid heat gain or loss in the pipe circuit, in
Watts.
Pipe Segment
Fluid Heat Transfer Rate [W][LINK]
This is the fluid heat gain or loss in the pipe segment, in
Watts.
The Duct
object is a component for air systems that is a direct
analogue for Pipe:Adiabatic
in the fluid loops. It is used when it is necessary (due to
the HVAC system configuration) to have a branch that has no
functional components. This case most often arises for a
bypass branch. Since every branch must have at least one
component, the Duct
component is used for this situation. The duct is an
adiabatic, pass-through component; all of its inlet conditions
are passed through unchanged to its outlet.
This is the unique name for this component. Any reference
to this component (in a BranchList,
for instance) will refer to it by this name.
Field: Inlet Node
Name[LINK]
The name of the component’s air inlet node.
Field: Outlet Node
Name[LINK]
The name of the component’s air outlet node.
Below is an example input for Duct.
DUCT,
VAV Sys 1 Bypass Duct, !- Name
VAV Sys 1 Bypass Duct Inlet Node, !- Inlet Node Name
VAV Sys 1 Bypass Duct Outlet Node;!- Outlet Node Name
There are no outputs for Duct.
Group – Node-Branch Management[LINK]
Nodes, Branch Lists and Branches define the topography of the HVAC connections.
NodeList[LINK]
For convenience, the NodeList object can be used to identify all the nodes for a particular use. A node list is not always required. The advantage of listing all the nodes in this manner is that input fields in other objects that ask for a node name can refer to either a single node or a list of nodes using this object.
There are other lines of input syntax that require the use of a NodeList as part of the input. These syntax items include: OutdoorAir:NodeList and the SetpointManager objects. In these two cases, the use of a NodeList statement is mandatory if there is more than one node in this particular “list”. For example, if the outside air only has a single inlet node, then the name of that node can replace the node list name in the input syntax. As a result of this mandatory specification of node lists for certain types of input, nodes can, obviously, and may be members of more than one list.
Inputs[LINK]
Field: Name[LINK]
This alpha designation must be unique among all the Node List Names. It is used as reference in various objects (e.g. OutdoorAir:NodeList).
Field: Node <#> Name (up to 25 allowed)[LINK]
Each unique Node identifier creates a Node structure with various attributes depending on the type of node. Typical values include Temperature, Mass Flow Rate, and Temperature Set Point. The alpha designators are associated with a particular node.
Though each NodeList is limited to 25 nodes, several node lists may be entered if you choose to identify all the nodes up front. For example:
Outputs[LINK]
A simple detail of Nodes and numbers assigned appears in the eplusout.bnd file:
In addition, properties of each node is available during the simulation:
HVAC,Average,System Node Temperature [C]
HVAC,Average,System Node Last Timestep Temperature [C]
HVAC,Average,System Node Mass Flow Rate [kg/s]
HVAC,Average,System Node Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Temperature [C]
HVAC,Average,System Node Setpoint High Temperature [C]
HVAC,Average,System Node Setpoint Low Temperature [C]
HVAC,Average,System Node Setpoint Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Minimum Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Setpoint Maximum Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,System Node Relative Humidity [%]
HVAC,Average,System Node Pressure [Pa]
HVAC,Average,System Node Standard Density Volume Flow Rate [m3/s]
HVAC,Average,System Node Enthalpy [J/kg]
HVAC,Average,System Node Last Timestep Enthalpy [J/kg]
HVAC,Average,System Node Wetbulb Temperature [C]
HVAC,Average,System Node Dewpoint Temperature [C]
HVAC,Average,System Node Quality []
HVAC,Average,System Node Height [m]
HVAC,Average,System Node Specific Heat [J/kg-K]
The following node variable is also available for system nodes that are for “air”:
HVAC, Average, System Node Current Density Volume Flow Rate [m3/s]
HVAC, Average, System Node Current Density [kg/m3]
The following node variables are “advanced” and normally used for debugging unusual cases:
HVAC,Average,System Node Minimum Temperature [C]
HVAC,Average,System Node Maximum Temperature [C]
HVAC,Average,System Node Minimum Limit Mass Flow Rate [kg/s]
HVAC,Average,System Node Maximum Limit Mass Flow Rate [kg/s]
HVAC,Average,System Node Minimum Available Mass Flow Rate [kg/s]
HVAC,Average,System Node Maximum Available Mass Flow Rate [kg/s]
HVAC,Averge,System Node Requested Mass Flow Rate [kg/s]
HVAC,Average,System Node Setpoint Mass Flow Rate [kg/s]
The following node variable reports node carbon dioxide concentration when carbon dioxide is simulated (ref. ZoneAirContaminantBalance):
The following node variable reports node generic contaminant concentration when generic contaminant is simulated (ref. ZoneAirContaminantBalance):
System Node Temperature [C][LINK]
The current temperature at a system node in degrees C. For air nodes, this is the dry-bulb temperature.
System Node Last Timestep Temperature [C][LINK]
The temperature at a system node for the previous timestep.
System Node Mass Flow Rate [kg/s][LINK]
The current mass flow rate at a system node in kg/s.
System Node Humidity Ratio [kgWater/kgDryAir][LINK]
The current humidity ratio at a system node in kg-water/kg-dry-air. Not applicable for liquid nodes.
System Node Setpoint Temperature [C][LINK]
The current setpoint temperature at a system node in degrees C. Some controllers and equipment types sense this single setpoint.
System Node Setpoint High Temperature [C][LINK]
The current upper setpoint temperature at a system node in degrees C. Some controllers and equipment types use dual setpoints at a single node.
System Node Setpoint Low Temperature [C][LINK]
The current lower setpoint temperature at a system node in degrees C. Some controllers and equipment types use dual setpoints at a single node.
System Node Setpoint Humidity Ratio [kgWater/kgDryAir][LINK]
The current humidity ratio setpoint at a system node in kg-water/kg-dry-air. Some controllers and equipment types sense this single setpoint. Not applicable for liquid nodes.
System Node Setpoint Minimum Humidity Ratio [kgWater/kgDryAir][LINK]
The current minimum desired humidity ratio at a system node in kg-water/kg-dry-air. Some controllers and equipment types use the min/max values as dual setpoints at a single node. Not applicable for liquid nodes.
System Node Setpoint Maximum Humidity Ratio [kgWater/kgDryAir][LINK]
The current maximum desired humidity ratio at a system node in kg-water/kg-dry-air. Some controllers and equipment types use the min/max values as dual setpoints at a single node. Not applicable for liquid nodes.
System Node Relative Humidity [%][LINK]
The current relative humidity (calculated from the node temperature, node humidity ratio and standard barometric pressure for the location). Not applicable for liquid nodes.
System Node Pressure [Pa][LINK]
The current pressure at a system node in Pa.
System Node Standard Density Volume Flow Rate [m\(^{3}\)/s][LINK]
The current volume flow rate at a system node in m\(^{3}\)/s. This is report is calculated from the mass flow using standardized values for density that do not vary over time (except for steam which varies with quality). For water nodes this density is determined at a temperature of 5.05ºC. For air nodes this density is determined for dry air at the standard barometric pressure for the location’s elevation, and a temperature of 20.0ºC. For air nodes, also see the report “System Node Current Density Volume Flow Rate.”
System Node Enthalpy [J/kg][LINK]
The current enthalpy at a system node in J/kg.
System Node Last Timestep Enthalpy [J/kg][LINK]
The enthalpy at the system node for the previous timestep in Joules per kilogram.
System Node Wetbulb Temperature [C][LINK]
The current wet-bulb temperature at a system node in degrees C. Not applicable for liquid nodes.
System Node Dewpoint Temperature [C][LINK]
The current dewpoint temperature at a system node in degrees C. It is calculated from the System Node Temperature, the System Node Humidity Ratio and the Site Outdoor Air Barometric Pressure. Not applicable for liquid nodes.
System Node Quality [][LINK]
The current system node vapor fraction/percent {0.0-1.0}.
System Node Height [m][LINK]
The current system node height {m}. Only applicable to outdoor air nodes.
System Node Specific Heat [J/kg-K][LINK]
The current specific heat capacity of the fluid at the node in units of J/kg-K. Not available for steam nodes.
Additional Node Reporting for Air Nodes
The following system node variable is available for nodes with a fluid type of air.
System Node Current Density Volume Flow Rate [m\(^{3}\)/s][LINK]
The current volume flow rate at a system node in m\(^{3}\)/s based on the current density. This report differs from the one called “System Node Standard Density Volume Flow Rate” in that it uses an air density calculated for the current moist air conditions rather than a standard density.
System Node Current Density [kg/m3][LINK]
The current air density at a system node in kg/m3. This is the density used to calculate the volume flow rate above. The density is calculated using current outdoor air barometric pressure and the drybulb temperature and humidity ratio at the air node.
Advanced Node Reporting
The following system node variables are available when you request “Diagnostics, DisplayAdvancedReportVariable;”. They are normally used for debugging unusual system cases and may not be available for all systems. Also, their definitions may change based on the usage in the system.
System Node Minimum Temperature [C][LINK]
System Node Maximum Temperature [C][LINK]
These node variables represent the min/max of loops or branches.
System Node Minimum Limit Mass Flow Rate [kg/s][LINK]
System Node Maximum Limit Mass Flow Rate [kg/s][LINK]
These node variables hold the maximum possible and the minimum allowable flow rates for a particular component. As such, they represent the “hardware limit” on the flow rate for the component. By convention, these variables are stored at the component inlet node. Since components share their nodes (the outlet node of one component is the inlet node of the next component), the protocol must be strictly followed. These variables are set by each component based on the design flow limits of the equipment.
System Node Minimum Available Mass Flow Rate [kg/s][LINK]
System Node Maximum Available Mass Flow Rate [kg/s][LINK]
These node variables represent the loop or branch maximum and minimum flow rate for the current configuration of the loop on which the component resides. The central plant routines manage these variables dynamically to resolve flow rates through branches located inside splitters and mixers.
System Node Setpoint Mass Flow Rate [kg/s][LINK]
The current mass flow rate setpoint at a system node in kg/s. Some controllers and equipment types sense this single setpoint.
System Node Requested Mass Flow Rate [kg/s][LINK]
This output is the current mass flow rate request at a system node in kg/s. Only used for plant simulations and nodes. This is the mass flow rate “requested” by a component. This is a record of what the component wanted which can be useful for diagnostics when the actual simulated flow is different than expected. This value is also used to determine overall loop flow rates.
System Node CO2 Concentration [ppm][LINK]
The average carbon dioxide concentration, in parts per million (ppm), at a system node for the timestep being reported.
System Node Generic Air Contaminant Concentration [ppm][LINK]
The average generic contaminant concentration, in parts per million (ppm), at a system node for the timestep being reported.
BranchList[LINK]
A branch list is intended to define the branches or portions of a particular loop that are present on an individual plant or condenser loop. Thus, the BranchList syntax simply provides a list of branch names (see Branch syntax) that then refer to more detailed syntax in another part of the input file. The syntax for describing a list of branches is given below.
Branches in BranchList objects should be listed in flow order: inlet branch, then parallel branches, then outlet branch. Branches (within a splitter/mixer) are simulated in the order listed.
Inputs[LINK]
Field: Name[LINK]
A unique name to identify the branch list.
Field: Branch <#> Name[LINK]
Branch name in the list. As noted above, Branches in BranchList objects MUST be listed in flow order: inlet branch, then parallel branches, then outlet branch. Branches are simulated in the order listed.
An example of this statement in an IDF is:
Outputs[LINK]
No output directly related to Branch Lists current is presented.
Branch[LINK]
Branches can be considered the mid-level grouping of items in the EnergyPlus HVAC loop scheme. Components are the lowest level of information. A collection of components in series forms a branch. Every branch must have at least one component, but it may have several components in series. The air loop also has “unitary” objects that are compound objects that wrap components and when they are used it is the unitary objects that appear on the Branch and not the child components. The Branch defines the order that components appear on the branch. Moreover, a collection of branches and their connecting information form a loop. Therefore, a branch is a collection of components while a loop is a collection of branches. Thus, components are specified for particular HVAC loops by assigning them to branches and then connecting those branches together to form a loop.
For hydronic plant systems, the Branch object is used on both the demand side and the supply side of the plant loop. For HVAC air systems, the Branch object is only used to describe the components on the supply side of an air loop. The demand side of the air loop does not use the Branch object. The outside air system appears on a Branch object but it does not use a Branch object itself to describe the components that included in the outside air system. So-called “ZoneHVAC:*” equipment, HVAC equipment directly associated with a zone, do not use the Branch object.
It should be noted that each component also has at least two nodes associated with it—an inlet node and an outlet node. These nodes, by default, are also part of the branch to which their components are assigned. Although it may appear redundant to list the node names in both the Branch and in the component object being referenced, this is needed because many components are connected to more than one loop at a time and the node names are needed here to distinguish which portion of the component is being attached to this particular branch and its loop. It should be noted that each branch must have at least one component on it. A “null” branch such as one where the first component on the loop is in reality a splitter or mixer should be defined as a single Pipe component for plant, or a single Duct component for air systems.
Inputs[LINK]
Field: Name[LINK]
This alpha field is the unique, user-defined name that allows the branch to be referenced by other elements such as the PlantLoop and CondenserLoop statements.
Field: Pressure Drop Curve Name[LINK]
This is an optional field used to specify pressure drop information for this particular branch. Currently this is only available in plant/condenser fluid loops: PlantLoop and CondenserLoop. Air loops require a full airflow network, so this field is ignored if found on an air loop. The value entered for this field must match a pressure curve object also found in the input. This curve can be of the type: Curve:Linear, Curve:Quadratic, Curve:Cubic, Curve:Exponent, or Curve:Functional:PressureDrop. In order to then perform a pressure simulation for the loop that this branch is located on, a flag must be set in the loop object. Reference the PlantLoop and CondenserLoop field “Pressure Simulation Type” for allowable settings. See the Engineering Reference document for further information on pressure simulation in plant loops.
Field Set (Branch Specifications)[LINK]
Following the two introductory items, there are groups of 4 repeated items: a type, a name, inlet and outlet node names. All of these items refer to one particular component on the branch. The first component defined by these items will be the first component on this branch, etc. through the end of the list. This object is extensible and can use as many field sets as needed by repeating the last four fields.
Field: Component <#> Object Type[LINK]
This field is the component object type (object class name). The component type refers to other elements within the input file and specifies what kind of component this is. The objects in the Group – Plant Equipment section are valid here when the Branch is used in Plant specifications. Fans, coils, unitary systems, and Outside Air Systems are also valid component types for the Branch object. Pipes or Ducts are also valid for this field. No splitter or mixer type objects are allowed.
Field: Component <#> Name[LINK]
The component name is the unique, user-defined reference name to distinguish between potentially multiple occurrences of a particular component type in an input file. The set of component type and component name must be unique. (You can only have 1 Boiler object with name MYBOILER).
Field: Component <#> Inlet Node Name[LINK]
This field references an inlet node name that will be found in the actual component specification. The inlet node, and the outlet node specified in the next field, should correspond to component model’s connections that are intended for the loop that this Branch is assigned to. For example a water-cooled chiller will have two inlet nodes, one for chilled water return and one for condenser water return and so the chiller will appear on two Branch objects accordingly.
Field: Component <#> Outlet Node Name[LINK]
This field references an outlet node name that will be found in the actual component specification.
An example of this statement in an IDF is:
And a more complex one:
Outputs[LINK]
The components on a branch are in series and that list is in simulation and connection order. Each branch must obey the rules: the outlet for component 1 has to have the same node name as the inlet for component 2, and so forth.
Eplusout.err contains the test for “individual branch integrity”:
The addition of pressure simulation for branches in fluid loops brings a new output at the branch level:
Plant Branch Pressure Difference [Pa][LINK]
This field allows the user to output the pressure drop of a particular branch on a plant loop or condenser loop. This output is only recognized if a valid pressure simulation is being performed. To do this, the user must specify a pressure simulation type as an input in the PlantLoop or CondenserLoop object.
ConnectorList[LINK]
A connector list is a collection of either one or two connection devices (Connector:Mixer or Connector:Splitter). Due to the definition of a loop in EnergyPlus, there is a maximum of one mixer and one splitter allowed for each loop segment. This limitation still allows a tremendous amount of flexibility to the user and can also still be solved within a reasonable amount of time and without a complex solver routine. The connection list simply allows the specification of the types and names of these devices. This allows the main loop statements to have the flexibility to have multiple lists that can have one or more item.
Inputs[LINK]
Field: Name[LINK]
This field is an identifying name that will be referenced to main loop statements using this connector list. The name must be unique among connector list names.
Field-Set: Connection Object Type and Identifying Name (up to 2 allowed)[LINK]
Depending on the loop, either one or two of the connectors will be specified. If this particular loop only has a single connector (either Connector:Mixer or Connector:Splitter), then only the first two items (type of connection and identifying name of connector) are included. If both a mixer and splitter are present, the additional type of connection and identifying name must be included. Note that the order that the items appear is inconsequential—either the Connector:Mixer or the Connector:Splitter may appear first. This will not affect the simulation.
Field: Connector 1 Object Type[LINK]
This field contains the connector type Connector:Mixer or Connector:Splitter.
Field: Connector 1 Name[LINK]
This field is an identifying name for the connector. It will be used by other objects in the input file.
Field: Connector 2 Object Type (optional)[LINK]
This field contains the connector type Connector:Mixer or Connector:Splitter.
Field: Connector 2 Name (optional)[LINK]
This field is an identifying name for the connector. It will be used by other objects in the input file.
An example of this statement in an IDF is:
Outputs[LINK]
No output directly related to Connector Lists is currently presented.
Plant Loop Connectors[LINK]
The connector list described in the preceding subsection determines how the branches of a particular loop will be hooked together. These connections can be classified either as a separation of a single stream into several outlet streams (splitter) or the merging of several streams into a single outlet stream (mixer). Due to the limitation per branch of a single splitter and a single mixer, the connector list can only have two pieces of equipment as a maximum. The names defined for either/both the splitter or/and the mixer refer then to “component” definitions as described in the next two subsections.
The format of both the Connector:Splitter and Connector:Mixer statements is similar. Both begin with an identifying name followed by the branch name of the “single side” of the component. In the case of the splitter, this is the inlet since the inlet stream is broken into several outlet streams. In the case of the mixer, this is the outlet since several streams are mixed together to form a single outlet. The remaining list of up to 50 names is simply the branch names of the outlet legs in the case of the splitter and inlet legs in the case of the mixer. No control logic is assume in these components—a determination of how much air to split in which direction using the splitter must be defined by other components.
Connector:Splitter[LINK]
A Connector:Splitter is used to take a single fluid stream or branch and split it into more than one outlet branches. This input object is used purely to connect the inlet and outlet branches.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the Splitter.
Field: Inlet Branch Name[LINK]
This alpha field contains the identifying name for the Splitter Inlet Branch.
Field: Outlet Branch <x> Name[LINK]
This alpha field contains the identifying names for the Splitter Outlet Branches and you enter as many outlet branches as needed.
Connector:Mixer[LINK]
A Connector:Mixer is used to combine or mix several inlet branches into a single outlet branch. This input object is used purely to connect the inlet branches with the outlet branch.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the Mixer.
Field: Outlet Branch Name[LINK]
This alpha field contains the identifying name for the Mixer Outlet Branch.
Field: Inlet Branch <x> Name[LINK]
This alpha field contains the identifying names for the Mixer Inlet Branches and you enter as many inlet branch names as needed..
An example of these statements in an IDF is:
Pipe:Adiabatic[LINK]
In reality, every component is connected to its closest neighbors via a pipe or a duct. At the current time, such detail is not needed in EnergyPlus. Thus, the Pipe:Adiabatic component is currently used more as a connection device (for branches that really do not have any components associated with them) or as a bypass than anything else. As such, its input is very simple and its algorithm is equally simple. The current algorithm for a pipe is simply to pass the inlet conditions to the outlet of the pipe component.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe.
Field: Inlet Node Name[LINK]
This alpha field is used as an identifying field for the pipe inlet node.
Field: Outlet Node Name[LINK]
This alpha field is used as an identifying field for the pipe outlet node.
An example of this statement in an IDF is:
Outputs[LINK]
There are no outputs directly related to Pipes.
Pipe:Adiabatic:Steam[LINK]
To connect the various components in a steam system regardless of it being the condensate or the steam side of the loop steam pipe needs to be used. In reality, every component is connected to its closest neighbors via a pipe or a duct. At the current time, such detail is not needed in EnergyPlus. Thus, the Pipe:Adiabatic:Steam component is currently used more as a connection device (for branches that really do not have any components associated with them). As such, its input is very simple and its algorithm is equally simple. The current algorithm for a pipe is simply to pass the inlet conditions to the outlet of the pipe component.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the steam pipe.
Field: Inlet Node Name[LINK]
This alpha field is used as an identifying field for the steam pipe inlet node.
Field: Outlet Node Name[LINK]
This alpha field is used as an identifying field for the steampipe outlet node.
An example of this statement in an IDF is:
Outputs[LINK]
There are no outputs directly related to Steam Pipes.
Pipe:Indoor[LINK]
This object specifies inputs which are used to simulate the heat transfer from a plant loop pipe placed in a zone or when a user schedule is used to specify an environment.
The data definition for object is shown below.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe.
Field: Construction Name[LINK]
This alpha field references a ‘wall’ construction object that gives a layer-by-layer description of the pipe wall and its insulation. The construction object follows standard conventions, describing material properties for each layer beginning with the outermost insulation layer and ending with the pipe wall layer.
Field: Fluid Inlet Node Name[LINK]
This alpha field contains the name of the pipe fluid inlet node.
Field: Fluid Outlet Node Name[LINK]
This alpha field contains the name of the pipe fluid outlet node.
Field: Environment Type[LINK]
Environment type is the environment in which the pipe is placed. It can be either Zone or Schedule. If specified as Zone, a zone name must be specified in the next field. If specified as Schedule, the Ambient Temperature Zone can be left blank, while a schedule must be specified for the temperature and air velocity.
Field: Ambient Temperature Zone Name[LINK]
If Zone is specified as the environment type, this field is used to specify the name of the zone in which the pipe is located. The zone temperature is used to calculate the heat transfer rate from the pipe.
Field: Ambient Temperature Schedule Name[LINK]
If Schedule is specified as the environment type, this field is used to specify the name of the temperature schedule that gives the ambient air temperature surrounding the pipe. This temperature is used as the outside boundary condition to calculate heat transfer from the pipe.
Field: Ambient Air Velocity Schedule Name[LINK]
If Schedule is specified as the environment type, this field is used to specify the name of the velocity schedule that gives the air velocity near the pipe. This velocity is used to calculate the convection heat transfer coefficient used in the pipe heat transfer calculation.
Field: Pipe Inside Diameter[LINK]
This field is used to enter the inside diameter of the pipe in units of m. Pipe inside diameter must be a positive number.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in units of m. Pipe length must be a positive number.
An example of this object in an IDF is:
Outputs[LINK]
HVAC,Average, Pipe Fluid Heat Transfer Rate [W]
HVAC,Average, Pipe Ambient Heat Transfer Rate [W]
HVAC,SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC,SUM, Pipe Ambient Heat Transfer Energy [J]
HVAC,Average, Pipe Mass Flow Rate [kg/s]
HVAC,Average, Pipe Inlet Temperature [C]
HVAC,Average, Pipe Outlet Temperature [C]
HVAC,Average, Pipe Volume Flow Rate [m3/s]
Pipe Fluid Heat Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in the fluid from pipe inlet to outlet.
Pipe Ambient Heat Transfer Rate [W][LINK]
The output provides the amount of heat loss/gain from pipe wall to the environment.
Pipe Fluid Heat Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and outlet. It is metered on EnergyTransfer with an end use of Pipes.
Pipe Ambient Heat Transfer Energy [J][LINK]
Total energy lost from the external pipe surface.
Pipe Mass Flow Rate [kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Inlet Temperature [C][LINK]
Pipe Outlet Temperature [C][LINK]
Temperature of fluid at entering and exiting of pipe.
Pipe Volume Flow Rate [m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
Pipe:Outdoor[LINK]
This object specifies inputs which are used to simulate the heat transfer from a plant loop pipe placed in an outdoor environment.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe.
Field: Construction Name[LINK]
This alpha field references a ‘wall’ construction object that gives a layer-by-layer description of the pipe wall and its insulation. The construction object follows standard conventions, describing material properties for each layer beginning with the outermost insulation layer and ending with the pipe wall layer.
Field: Fluid Inlet Node Name[LINK]
This alpha field contains the name of the pipe fluid inlet node.
Field: Fluid Outlet Node Name[LINK]
This alpha field contains the name of the pipe fluid outlet node.
Field: Ambient Temperature Outside Air Node Name[LINK]
Ambient temperature outdoor air node is a node representing outdoor air with which pipe transfers heat. The node should be included in an outdoor air node list.
Field: Pipe Inside Diameter[LINK]
This field is used to enter the inside diameter of the pipe in units of m. Pipe inside diameter must be a positive quantity.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in units of m. Pipe length must be a positive quantity.
An example of this statement in an IDF is:
Outputs[LINK]
HVAC,Average, Pipe Fluid Heat Transfer Rate [W]
HVAC,SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC,Average, Pipe Mass Flow Rate [kg/s]
HVAC,Average, Pipe Inlet Temperature [T]
HVAC,Average, Pipe Outlet Temperature [T]
HVAC,Average, Pipe Volume Flow Rate [m3/s]
Pipe Fluid Heat Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in the fluid from pipe inlet to outlet.
Pipe Fluid Heat Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and outlet. It is metered on EnergyTransfer with an end use of Pipes.
Pipe Mass Flow Rate [kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Inlet Temperature [C][LINK]
Pipe Outlet Temperature [C][LINK]
Temperature of fluid at entering and exiting of pipe.
Pipe Volume Flow Rate [m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
Pipe:Underground[LINK]
This object specifies inputs which are used to simulate the heat transfer from a plant loop pipe placed underground.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe.
Field: Construction Name[LINK]
This alpha field references a basic construction object that gives a layer-by-layer description of the pipe wall and insulation. The construction object follows standard conventions, describing material properties for each layer beginning with the outermost layer, the insulation, if it exists, and ending with the pipe wall layer. The construction object may have either one or two layers. If only one, then the material must be the pipe wall. If two, then insulation is utilized.
Field: Fluid Inlet Node Name[LINK]
This alpha field contains the name of the pipe fluid inlet node.
Field: Fluid Outlet Node Name[LINK]
This alpha field contains the name of the pipe fluid outlet node.
Field: Sun Exposure[LINK]
This alpha field allows the user to specify one of two options: NoSun or SunExposed. For SunExposed, the simulation includes diffuse and beam solar effects on the ground surface. For NoSun, no solar effects are included.
Field: Pipe Inside Diameter[LINK]
This field is used to enter the inside diameter of the pipe in units of m. Pipe inside diameter must be a positive quantity.
Field: Pipe Length[LINK]
This field is used to enter the length of the pipe in units of {m}. Pipe length must be a positive quantity.
Field: Soil Material Name[LINK]
This references a Material object that contains the soil properties and thickness. Note that when defining the soil layer, the thickness should be the thickness of soil between the pipe wall and the ground surface.
Field: Type of Undisturbed Ground Temperature Object[LINK]
This is the type of undisturbed ground temperature object that is used to determine the ground temperature.
Field: Name of Undisturbed Ground Temperature Object[LINK]
This is the name of the undisturbed ground temperature object that is used to determine the ground temperature.
An example of this object in an IDF is:
Outputs[LINK]
HVAC, Average, Pipe Fluid Heat Transfer Rate [W]
HVAC, SUM, Pipe Fluid Heat Transfer Energy [J]
HVAC, Average, Pipe Mass Flow Rate [kg/s]
HVAC, Average, Pipe Volume Flow Rate [m3/s]
HVAC, Average, Pipe Inlet Temperature [C]
HVAC, Average, Pipe Outlet Temperature [C]
Pipe Fluid Heat Transfer Rate [W][LINK]
The output provides the total amount of heat loss/gain in the fluid from pipe inlet to outlet.
Pipe Fluid Heat Transfer Energy [J][LINK]
Total energy fluid has lost/gained between pipe inlet and outlet. It is metered on
EnergyTransfer with an end use of Pipes.
Pipe Mass Flow Rate [kg/s][LINK]
Mass flow rate of the fluid in the pipe.
Pipe Volume Flow Rate [m3/s][LINK]
Fluid volumetric flow rate, (mass flow rate / density)
Pipe Inlet Temperature [C][LINK]
Pipe Outlet Temperature [C][LINK]
Temperature of fluid at entrance and exit of pipe.
PipingSystem:Underground Class Objects[LINK]
Objects in this class are used to simulate the heat transfer processes of a piping system placed underground, which may or may not be in contact with a number of zone surfaces. There are three related objects, all of which are prefixed with PipingSystem:Underground :
PipingSystem:Underground:Domain
PipingSystem:Underground:PipeCircuit
PipingSystem:Underground:PipeSegment
PipingSystem:Underground:Domain[LINK]
This section documents the domain object, which is used to specify information for the overall ground domain, including thermal properties, mesh parameters, and surface interaction.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the ground domain.
Field: XMax, YMax, ZMax[LINK]
These numeric fields are used to specify the overall domain size, in each of the three Cartesian dimensions. The domain will be meshed from {x, y, z} = {0, 0, 0} to {Xmax, Ymax, Zmax}.
Note that for this object, the x-z plane lies parallel to the ground surface, such that the y-dimension can be thought of as representing the burial depth. This is in contrast to the way building surface coordinates are defined with the x-y plane lying parallel to the ground. Also note that any pipe segments that end up being used in a ground domain will be placed axially in the z-dimension. Thus, pipe flow will always be in either the positive z or negative z direction.
Field: X-Direction Mesh Density Parameter[LINK]
This numeric integer field represents the number of cells to be placed between any two “domain partitions” during mesh development. A domain partition may be thought of as a basement wall/floor, or a pipe. Once these components are laid out in the domain, this field number of cells are placed between the partitions. Further information on this is found in the engineering reference manual.
Field: X-Direction Mesh Type[LINK]
This alpha field represents the type of mesh to create when placing cells between “domain partitions.” Two options are available: “uniform” and “symmetricgeometric.” For uniform, the cells are placed in the region with all cells having equal size. For symmetric-geometric, the cells are compressed toward the partitions so that there are more cells on either side of the mesh region. This can help focus computational intensity on the boundary areas where it is likely more desired. For symmetric-geometric mesh distribution, the mesh density parameter should be an even number to provide the symmetric condition.
Field: X-Direction Geometric Coefficient[LINK]
This numeric field represents the compression of cell distribution if the x-direction mesh type is set to “symmetricgeometric.” If the mesh type is uniform, this field is not interpreted. For symmetric geometric, a value in this field equal to 1 would result in a uniform distribution, while a value of 2 would provide a highly skewed distribution.
Field: Y-Direction Mesh Density Parameter[LINK]
See Field: X-Direction Mesh Density Parameter.
Field: Y-Direction Mesh Type[LINK]
See Field: X-Direction Mesh Type.
Field: Y-Direction Geometric Coefficient[LINK]
See Field: X-Direction Geometric Coefficient.
Field: Z-Direction Mesh Density Parameter[LINK]
See Field: X-Direction Mesh Density Parameter.
Field: Z-Direction Mesh Type[LINK]
See Field: X-Direction Mesh Type.
Field: Z-Direction Geometric Coefficient[LINK]
See Field: X-Direction Geometric Coefficient.
Field: Soil Thermal Conductivity[LINK]
The thermal conductivity of the soil, in W/m-K.
Field: Soil Density[LINK]
The bulk density of the soil, in kg/m3.
Field: Soil Specific Heat[LINK]
The specific heat of dry soil, in J/kg-K. If moisture is defined in this object, moisture and freezing effects are accounted for by varying the specific heat value.
Field: Soil Moisture Content Volume Fraction[LINK]
A nominal value of soil moisture content to be used when evaluating soil thermal properties.
Field: Soil Moisture Content Volume Fraction at Saturation[LINK]
A nominal value of soil moisture content when the soil is saturated, this is used in evaluating thermal properties of freezing soil
Field: Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: This Domain Includes Basement Surface Interaction[LINK]
A yes/no field stating whether zone surfaces should be coupled to this domain.
Field: Width of Basement Floor in Ground Domain[LINK]
If this domain does include basement interaction, this represents the width of the domain cutaway to include the basement. In essence, this is the width of basement floor to include in the ground simulation. This width should include the basement wall thickness.
Field: Width of Basement Floor in Ground Domain[LINK]
If this domain does include basement interaction, this represents the depth of the domain cutaway to include the basement. In essence, this is the burial depth of the basement to include in the ground simulation. This depth should include the basement floor thickness.
Field: Shift Pipe X Coordinates By Basement Width[LINK]
If this domain does include basement interaction, this flag specifies whether the pipe segment X-values should then be shifted by the basement width. In essence, this specifies the reference point for pipe segment x-values: if NO then the reference is domain x = 0, if YES then the reference is the basement width point.
Field: Name of Basement Wall Boundary Condition Model[LINK]
The name of an OtherSideConditions model defined in the input file and referenced by the surfaces which should be included as “wall surfaces” for the basement interaction part of the ground heat transfer model.
Field: Name of Basement Wall Boundary Condition Model[LINK]
The name of an OtherSideConditions model defined in the input file and referenced by the surfaces which should be included as “floor surfaces” for the basement interaction part of the ground heat transfer model.
Field: Convergence Criterion for the Outer Cartesian Domain Iteration Loop[LINK]
The maximum temperature deviation within any cell between one iteration and another to decide that the Cartesian domain has converged to within tolerance. A smaller value will improve accuracy and computation time. A smaller value should be accompanied by a higher number of iterations if maximum accuracy is desired.
Field: Maximum Iterations in the Outer Cartesian Domain Iteration Loop[LINK]
The maximum number of iterations to make when performing temperature updates of the Cartesian coordinate system. The actual number of iterations made will of course depend on transient conditions and convergence tolerance.
Field: Evapotranspiration Ground Cover Parameter[LINK]
Numeric field specifies the ground cover effects used in the evapotranspiration model at the ground surface heat balance. The values range from 0 (solid, nonpermeable ground surface) to 1.5 (wild growth).
Field: Number of Pipe Circuits Entered for this Domain[LINK]
The number of pipe circuit objects which will be defined in the following fields.
Field: Pipe Circuit <#>[LINK]
A PipingSystem:Underground:PipeCircuit to be included in this domain. This indicates that the pipe circuit and all of the underlying pipe segments will be included during mesh development and heat transfer calculations within this domain. This object is extensible, so any number of pipe circuits can be added, assuming all underlying pipe segments do not cause any conflicts for the mesh development engine (overlapping pipes, etc.).
PipingSystem:Underground:PipeCircuit[LINK]
This section documents the pipe circuit object, which is used to specify information for the plant loop topology, such as inlet and outlet connections. This object also groups together pipe segments to define flow paths within a given pipe circuit.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe circuit.
Field: Pipe Thermal Conductivity[LINK]
The thermal conductivity of the pipe, in W/m-K.
Field: Pipe Density[LINK]
The bulk density of the pipe, in kg/m3.
Field: Pipe Specific Heat[LINK]
The specific heat of the pipe, in J/kg-K.
Field: Pipe Inner Diameter[LINK]
The inner diameter of the pipe, in m.
Field: Pipe Outer Diameter[LINK]
The outer diameter of the pipe, in m.
Field: Design Flow Rate[LINK]
The “design” flow in this pipe circuit, in m3/s. This is the flow which this component will request during the simulation. Of course, other components and overall plant management will decide the flow actually given to this component.
Field: Circuit Inlet Node Name[LINK]
The inlet node name for this circuit, which is used when placing this circuit on a branch on a plant or condenser loop.
Field: Circuit Outlet Node Name[LINK]
The outlet node name for this circuit, which is used when placing this circuit on a branch on a plant or condenser loop.
Field: Convergence Criterion for the Inner Radial Iteration Loop[LINK]
The maximum temperature deviation within any cell between one iteration and another to decide that the radial domain has converged to within tolerance. A smaller value will improve accuracy and computation time. A smaller value should be accompanied by a higher number of iterations if maximum accuracy is desired.
Field: Maximum Iterations in the Inner Radial Iteration Loop[LINK]
The maximum number of iterations to make when performing temperature updates of the radial coordinate system. The actual number of iterations made will of course depend on transient conditions and convergence tolerance.
Field: Number of Soil Nodes in the Inner Radial Near Pipe Mesh Region[LINK]
The number of soil nodes to discretize pipe cells. More information on mesh development is provided in the engineering reference manual.
Field: Radial Thickness of Inner Radial Near Pipe Mesh Region[LINK]
The radial distance used to discretize pipe cells. More information on mesh development is provided in the engineering reference manual.
Field: Number of Pipe Segments Entered for this Pipe Circuit[LINK]
The number of pipe segment objects which will be defined in the following fields.
Field: Pipe Segment <#>[LINK]
A PipingSystem:Underground:PipeSegment to be included in this pipe circuit. The circuit is set up so that flow passes through the N segments in the order they are entered here. This object is extensible, so additional fields of this type can be added to the end of this object.
PipingSystem:Underground:PipeSegment[LINK]
This section documents the pipe segment object, which is used to specify information for a single pipe segment placed at some x, y coordinate in the ground. The flow direction is also defined in this object to allow for careful description of varying flow paths. This can be useful for accounting for short circuiting effects if two pipes are placed in counterflow vs. parallel flow.
Inputs[LINK]
Field: Name[LINK]
This alpha field is used as an identifying field for the pipe segment.
Field: X Position[LINK]
This numeric field represents the x-direction placement of the pipe. If no basement is included in the simulation, this is measured from x = 0. If a basement is included, and the domain object specifies that pipes should be shifted, this is measured from the basement wall.
Field: Y Position[LINK]
This numeric field represents the burial depth of the pipe, measured from the ground surface. This will always be a positive number.
Field: Flow Direction[LINK]
This alpha field is used to define the flow direction within this pipe segment. The choices are “increasing” or “decreasing.” These can be chosen carefully to encapsulate specific short-circuiting effects due to varying flow configurations (circuiting).
An example of this object in an IDF is offered here for a foundation heat exchanger
Outputs[LINK]
HVAC, Average, Pipe Circuit Mass Flow Rate [kg/s]
HVAC, Average, Pipe Circuit Inlet Temperature [C]
HVAC, Average, Pipe Circuit Outlet Temperature [C]
HVAC, Average, Pipe Segment Inlet Temperature [C]
HVAC, Average, Pipe Segment Outlet Temperature [C]
HVAC, Average, Pipe Circuit Fluid Heat Transfer Rate [W]
HVAC, Average, Pipe Segment Fluid Heat Transfer Rate [W]
Pipe Circuit Mass Flow Rate [kg/s][LINK]
The output provides the mass flow rate currently being sent through the pipe circuit.
Pipe Circuit Inlet Temperature [C][LINK]
Pipe Circuit Outlet Temperature [C][LINK]
Temperature of fluid at the inlet and outlet of a given pipe circuit.
Pipe Segment Inlet Temperature [C][LINK]
Pipe Segment Outlet Temperature [C][LINK]
Temperature of fluid at the inlet and outlet of a given pipe segment.
Pipe Circuit Fluid Heat Transfer Rate [W][LINK]
This is the fluid heat gain or loss in the pipe circuit, in Watts.
Pipe Segment Fluid Heat Transfer Rate [W][LINK]
This is the fluid heat gain or loss in the pipe segment, in Watts.
Duct[LINK]
The Duct object is a component for air systems that is a direct analogue for Pipe:Adiabatic in the fluid loops. It is used when it is necessary (due to the HVAC system configuration) to have a branch that has no functional components. This case most often arises for a bypass branch. Since every branch must have at least one component, the Duct component is used for this situation. The duct is an adiabatic, pass-through component; all of its inlet conditions are passed through unchanged to its outlet.
Inputs[LINK]
Field: Name[LINK]
This is the unique name for this component. Any reference to this component (in a BranchList, for instance) will refer to it by this name.
Field: Inlet Node Name[LINK]
The name of the component’s air inlet node.
Field: Outlet Node Name[LINK]
The name of the component’s air outlet node.
Below is an example input for Duct.
Outputs[LINK]
There are no outputs for Duct.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.