In each CondenserEquipmentList,
various equipment types and names must be given. Each
type-name pair must then have a corresponding equipment
definition. This subsection lists the various equipment types
that are available and examples from an IDF. Where
appropriate, notes and comments on the input structure are
provided.
Cooling towers are components that may be assigned to
condenser loops. The cooling tower is modeled as a counterflow
heat exchanger with a single-speed fan (induced draft
configuration) based on Merkel’s theory. The user must define
tower performance via one of two methods: design heat transfer
coefficient-area product (UA) and design water flow rate, or
nominal tower capacity at a specific rating point. Regardless
of which method is chosen, the design airflow rate and
corresponding fan power must be specified. The model will also
account for tower performance in the “free convection” regime,
when the tower fan is off but the water pump remains on and
heat transfer still occurs (albeit at a low level). If the
user wants the model to account for “free convection”, they
must specify the corresponding airflow rate and heat transfer
coefficient-area product (UA), or the nominal tower capacity
during this mode of operation.
The cooling tower seeks to maintain the temperature of the
water exiting the cooling tower at (or below) a set point. The
set point schedule value is defined by the field “Condenser
Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop
object. The model first checks to determine the impact of
“free convection”, if specified by the user, on the tower
exiting water temperature. If the exiting water temperature
based on “free convection” is at or below the set point, then
the tower fan is not turned on. If the exiting water
temperature based on “free convection” is below the set point,
the tower will operate in FluidBypass mode – portion of the
water goes through the tower media and gets cooled while the
remaining water flow gets bypassed, two water flows then mix
together trying to meet the water setpoint temperature. If the
exiting water temperature remains above the set point after
“free convection” is modeled, then the tower fan is turned on
to reduce the exiting water temperature to the set point. If
the capacity control is FanCycling, the model assumes that
part-load operation is represented by a simple linear
interpolation between two steady-state regimes (i.e., tower
fan on for the entire simulation timestep and tower fan off
for the entire simulation timestep). Cyclic losses are not
taken into account. If the capacity control is FluidBypass,
the model determines the fraction of water flow to be bypassed
while the remaining water goes through the tower cooling media
and gets cooled, then the two water flows mix to meet the
setpoint temperature. In this case, the fan runs at full speed
for the entire timestep.
Cooling towers here are “wet” and consume water through
evaporation, drift, and blowdown. The model can be used to
predict water consumed by the towers. The last six input
fields are optional and provide methods of controlling details
of the water consumption calculations. The user can specify
connections to the rest of the buildings water system by
providing the name of a water storage tanks
(i.e. WaterUse:Storage objects).
For the operation of multi-cell towers, the first step is
to determine the number of cells to operate based on the cell
control method – between the minimum number of cells subject
to the maximum water flow rate fraction per cell, and maximum
number of cells subject to the minimum water flow rate
fraction per cell. If the calculated cells do not meet the
loads, additional cells will be operating to help meet the
loads. Inside each cell, the existing capacity controls still
apply.
For multi-cell towers, the following inputs are assumed to
be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power
at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal
Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common
basin)
This numeric field contains the design water flow rate
through the tower in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the tower
(not the flow rate of water being sprayed on the outside of
the heat exchange coil). If the input field “Performance Input
Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow
rate greater than zero must be defined or the field can be
autosized. If autosized, a Plant Sizing object must be defined
and the design water flow rate is derived from the design load
to be rejected by the condenser loop and the design loop delta
T (Ref. Sizing and Input for Design Calculations and Component
Autosizing sections). If “Performance Input Method” is
specified as “NominalCapacity”, then this field must be left
blank since the model automatically assumes a water flow rate
of 5.382E-8 m3/s per watt (3 gpm/ton) of tower capacity
specified in the field “Nominal Capacity”.
This numeric field contains the design air flow rate
induced by the tower fan in m\(^{3}\)/s. A value greater than
zero must be defined regardless of the tower performance input
method. Alternately, this field can be autosized. If
autosized, the design air flow rate is calculated as
follows:
This numeric field contains the fan power (in watts) at the
design air flow rate specified in the previous field. A value
greater than zero must be specified regardless of the tower
performance input method, or this field can be autosized. If
autosized, the fan power is calculated as follows:
If”Performance Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the design air and water flow rates specified
above. If the input field “Performance Input Method” is
specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a
UA value greater than zero but less than or equal to 300,000
must be defined, or the field can be autosized. If autosized,
a Plant Sizing object must be defined and the design tower UA
value is derived from the design load to be rejected by the
condenser loop and the design loop delta T (Ref. Sizing and
Input for Design Calculations and Component Autosizing
sections), assuming a tower water inlet temperature of 35C and
tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance
Input Method” is specified as “NominalCapacity”, then this
field must be left blank since the model automatically
calculates the tower UA based on the tower capacity specified
in the field “Nominal Capacity”.
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in
the “free convection” regime (water flow exists but tower fan
is turned off). This value must be less than the value
specified for the field “Design Air Flow Rate”. This field may
be autocalculated, in which case it is set to a fraction of
the “Design Air Flow Rate” determined in the following input
field. If the user does not wish to model “free convection”
and is using the Performance Input Method
“UFactorTimesAreaAndDesignWaterFlowRate”, then this field
should be set to 0.0. If the user specifies the U-Factor Times
Area Value at Free Convection Air Flow Rate or Free Convection
Capacity as a value greater than zero, then the free
convection air flow rate must be specified greater than
0.0.
Field:
Free Convection Regime Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime air flow rate. The
default is 0.1.
Field:
Free Convection Regime U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (W/K) when the tower is in the “free
convection” regime (water flow exists but tower fan is turned
off). This value must be less than the value specified for the
field “U-Factor Times Area Value at Design Air Flow Rate”.
This field may be autosized, in which case it is set to a
fraction of the “U-Factor Times Area Value at Design Air Flow
Rate” determined in the following input field. If the user
does not wish to model “free convection” and is using the
Performance Input Method
“UFactorTimesAreaAndDesignWaterFlowRate”, then this field
should be set to 0.0. If “Performance Input Method” is
specified as “NominalCapacity”, then this field must be left
blank since the model automatically calculates the tower UA
based on the tower capacity specified in the field “Free
Convection Capacity”.\
Field:
Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime U-Factor times area
value. The default is 0.1.
This alpha field contains the method by which the user will
specify tower performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“NominalCapacity”. If this field is left
blank in the input data file, the default input method is
assumed to be
“UFactorTimesAreaAndDesignWaterFlowRate”. If
the method
“UFactorTimesAreaAndDesignWaterFlowRate” is
selected, then the user must enter design UA values, design
water flow rates and air flow rates as described for the
previous input fields. If the method “NominalCapacity” is
selected then the fields “Design Water Flow Rate”, “U-Factor
Times Area Value at Design Air Flow Rate” and “U-Factor Times
Area Value at Free Convection Air Flow Rate” must be left
blank, but the fields “Nominal Capacity” and “Free Convection
Capacity” must be entered as described below.
Field:
Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of
actual tower heat rejection to nominal capacity. This ratio
is defined at entering water at 35C (95F), leaving water at
29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F)
drybulb temperatures. Historically this ratio has been set at
1.25 based on the assumption that the tower must dissipate
0.25 W of compressor power for every what of heat removed at
the chiller evaporator. The default is 1.25.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts, with
entering water at 35C (95F), leaving water at 29.4C (85F),
entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb
temperatures. The design water flow rate is assumed to be
5.382E-8 m\(^{3}\)/s per watt
of nominal capacity (3 gpm/ton). The value in the previous
field times this nominal tower capacity gives the actual tower
heat rejection at these operating conditions (based on
historical assumption that the tower must dissipate additional
heat from the compressor heat for heat removed at the
evaporator).
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts when the
tower is in the “free convection” regime (water flow exists
but tower fan is turned off), with entering water at 35C
(95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The design
water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal
tower capacity (input field above). The heat rejection
capacity and nominal capacity sizing ratio is applied to this
free convection tower capacity to give the actual tower heat
rejection at these operating conditions (typical value is 1.25
based on historical assumption that the tower must dissipate
0.25W of compressor heat for every watt of heat removed by the
evaporator). The value specified for this field must be less
than the value specified for the field “Tower Nominal
Capacity”. If the user does not wish to model “free
convection”, then this field should be set to 0.0. If the user
specifies a value greater than zero, then the “Air Flow Rate
in Free Convection Regime” field must contain a value greater
than zero. This field can be automatically calculated using
the sizing factor in the following field.
This numeric field specifies the design approach
temperature of the tower corresponding to the design inlet air
wet-bulb temperature and the design temperature range. The
approach temperature should be the outlet water temperature
minus the inlet air wet-bulb temperature at design conditions.
This parameter is autosizable and when autosized it is set to
3.9 °C.
This numeric field specifies the design temperature range
of the tower corresponding to the design inlet air wet-bulb
temperature and the design approach temperature. The design
range should be the inlet water temperature minus the outlet
water temperature at design conditions. This parameter is
autosizable and when autosized it is set to 5.5 °C.
This numeric field contains the capacity of the tower’s
electric basin heater in watts per degree Kelvin. This field
is used in conjunction with the Basin Heater Setpoint
Temperature described in the following field. The basin heater
electric power is equal to this field multiplied by the
difference between the basin heater set point temperature and
the outdoor dry-bulb temperature. The basin heater only
operates when the tower fan is off and water is not flowing
through the tower, regardless of the basin heater schedule
described below. The basin heater capacity must be greater
than or equal to zero, with a default value of zero if this
field is left blank.
This numeric field contains the set point temperature (°C)
for the basin heater described in the previous field. The
basin heater is active when the outdoor air dry-bulb
temperature falls below this setpoint temperature, as long as
the tower fan is off and water is not flowing through the
tower. This set point temperature must be greater than or
equal to 2˚C, and the default value is 2˚C if this field is
left blank.
This alpha field contains the name of the basin heater
operating schedule. The basin heater operating schedule is
assumed to be an on/off schedule and the heater is available
to operate any time the schedule value is greater than 0. The
basin heater operates when scheduled on and the outdoor air
dry-bulb temperature is below the set point temperature
described in the previous field. If this field is left blank,
the basin heater is available to operate throughout the
simulation. Regardless of this schedule, the basin heater may
only operate when the cooling tower fan is off and water is
not flowing through the tower.
This field is used to choose which method is used to model
the amount of water evaporated by the cooling tower. There are
two options: LossFactor or
SaturatedExit. The default is SaturatedExit.
The user-defined loss factor is entered in the following
field. By assuming that the air leaving the tower is
saturated, the evaporation can be directly calculated using
moist air engineering calculations with data available within
the cooling tower model (and does not require additional user
input).
This field is used to specify the rate of water evaporated
from the cooling tower and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The
evaporation loss is then calculated as a fraction of the
circulating condenser water flow and varies with the
temperature change in the condenser water. The value entered
here is in units of percent-per-degree Kelvin. The evaporation
rate will equal this value times each degree Kelvin of
temperature drop in the condenser water. Typical values are
from 0.15 to 0.27 [percent/K]. The default is 0.2.
This field is used to specify the rate of water lost to the
exiting air as entrained droplets [%]. The drift loss is a
percent of the condenser water flow. Typical values for towers
with efficient drift eliminators are between 0.002 and 0.2% of
the condenser water flow rate. The default value is
0.008%.
This field specifies which method is used to determine
blowdown rates. There two options
ConcentrationRatio or
ScheduledRate. The choice will determine
which of the two models below is used. The default is
ConcentrationRatio.
This field is used to dynamically adjust the rate of
blowdown in the cooling tower as a function of the rate of
evaporation. Blowdown is water intentionally drained from the
tower in order to offset the build up of solids in the water
that would otherwise occur because of evaporation. The value
entered here is dimensionless. It can be characterized as the
ratio of solids in the blowdown water to solids in the make up
water. Typical values for tower operation are 3 to 5. The
default value is 3.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m\(^{3}\)/s) flushed from the basin
on a periodic basis to purge the tower of mineral scale
build-up and other contaminants. This schedule is only used if
the Blowdown Calculation Mode is set to ScheduledRate. The
amount of water use due to blowdown depends on the makeup
water quality and is specific to each geographical location.
Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is
in addition to the amount of water lost to the atmosphere due
to evaporation and/or drift. Since blowdown occurs when the
basin water contaminant concentration is high, blowdown only
occurs when the cooling tower is active and water is flowing
through the tower (regardless of the water usage defined by
this schedule).
This field is optional. It is used to describe where the
tower obtains water used for evaporative cooling. If blank or
omitted, then the tower will obtain water directly from the
mains. If the name of a WaterUse:Storage
object is used here, then the tower will obtain its water from
that tank. If a tank is specified, the tower will attempt to
obtain all the water it uses from the tank. However if the
tank cannot provide all the water the tower needs, then the
tower will still operate and obtain the rest of the water it
needs from the mains (referred to as ‘Starved’ water).
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
cooling tower. If this field is left blank, the outdoor air
conditions entering the cooling tower are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
This alpha field contains the cooling capacity control for
the cooling tower. Two choices are available:
FanCycling and FluidBypass.
During part-load conditions, there are two ways to maintain
the exiting water temperature at the setpoint: either cycling
the tower fan, or bypassing portion of the tower water with a
three-way valve. For FluidBypass, the tower fan still runs at
full speed for the entire timestep, but only portion of the
water flow goes through the cooling tower media to get cooled
while the remaining portion of the water flow gets bypassed.
Two water flows then mix at the common water sump to meet the
setpoint temperature.
This integer field contains the number of cells in the
multi-cell cooling tower. If not entered, the program will
assume it is a single-cell cooling tower
This alpha field specifies the method used to control the
number of cells used to meet the load, the two choices
are:
MinimalCell : the program will use minimal
number of cells needed, all other cells will be shut down with
no water flow. It will attempt to use as few cells as possible
to cool the fluid. In no case, however, will the flow per cell
be allowed to exceed its maximum value defined by the
Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible
will be turned on. In no case, however, will the flow per cell
be allowed to drop below its minimum value specified by the
Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is
MaximalCell.
Field:
Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest
fraction of the design water flow rate. Flows less than this
value will commonly result in fluid distribution problems; the
pressure at each nozzle will be too weak for the fluid to be
sprayed out in the correct pattern, not all the fill would be
wet. If this field is left blank, the default value is
0.33.
Field:
Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction
of the design water flow rate. If this field is left blank,
the default value is 2.5.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature. For this component
the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Design Air Flow Rate;
3. Fan Power at Design Air Flow Rate;
4. U-Factor Times Area Value at Design Air Flow
Rate;
5. Air Flow Rate in Free Convection Regime;
6. U-Factor Times Area Value at Free Convection Air Flow
Rate.
Note that the U-Factor Times Area Value at Design Air Flow
Rate is not multiplied by the Sizing Factor. Instead
the design tower load is multiplied by the sizing factor and
the design UA then calculated as usual. The U-Factor Times
Area Value at Free Convection Air Flow Rate is set to 10% of
the new design Tower UA.
This optional field allows you to specify a user-defined
end-use subcategory, e.g., “Process”. A new meter for
reporting is created for each unique subcategory (ref: Output:Meter
objects). Any text may be used here to further subcategorize
the end-uses in the ABUPS End Uses by Subcategory table and in
the LEED Summary EAp2-4/5 Performance Rating Method Compliance
table. If this field is omitted or blank, the cooling tower
will be assigned to the “General” end-use subcategory.
Three examples of an IDF specification for this object are
shown below:
CoolingTower:SingleSpeed,
My Tower, !- Name
Condenser Tower Inlet Node, !- Water Inlet Node Name
Condenser Tower Outlet Node,!- Water Outlet Node Name
.0011, !- Design Water Flow Rate {m3/s}
16.0, !- Design Air Flow Rate {m3/s}
10000., !- Design Fan Power {W}
3500., !- Design U-Factor Times Area Value {W/K}
0.0, !- Free Convection Air Flow Rate {m3/s}
, !- Free Convection Air Flow Rate Sizing Factor
0.0, !- Free Convection U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
, !- Nominal Capacity {W}
, !- Free Convection Capacity {W}
, !- Free Convection Nominal Capacity Sizing Factor
, !- Design Inlet Air Dry-Bulb Temperature {C}
, !- Design Inlet Air Wet-Bulb Temperature {C}
, !- Design Approach Temperature {deltaC}
, !- Design Range Temperature {deltaC}
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
, !- Drift Loss Percent {percent}
, !- Blowdown Calculation Mode
, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
, !- Outdoor Air Inlet Node Name
FluidBypass, !- Capacity Control
4, !- Number of Cells
MinimalCell, !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.0000; !- Sizing Factor
CoolingTower:SingleSpeed,
My Tower, !- Name
Condenser Tower Inlet Node, !- Water Inlet Node Name
Condenser Tower Outlet Node,!- Water Outlet Node Name
, !- Design Water Flow Rate {m3/s}
Autosize, !- Design Air Flow Rate {m3/s}
1000., !- Design Fan Power {W}
, !- Design U-Factor Times Area Value {W/K}
autocalculate, !- Free Convection Air Flow Rate {m3/s}
, !- Free Convection Air Flow Rate Sizing Factor
autocalculate, !- Free Convection U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
NominalCapacity, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
95250., !- Nominal Capacity {W}
9525.; !- Free Convection Capacity {W}
CoolingTower:SingleSpeed,
TowerWaterSys CoolTower, !- Name
TowerWaterSys Pump-TowerWaterSys CoolTowerNode, !- Water Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node, !- Water Outlet Node Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- Design Air Flow Rate {m3/s}
AUTOSIZE, !- Design Fan Power {W}
AUTOSIZE, !- Design U-Factor Times Area Value {W/K}
autocalculate, !- Free Convection Air Flow Rate {m3/s}
, !- Free Convection Air Flow Rate Sizing Factor
autocalculate, !- Free Convection U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
, !- Nominal Capacity {W}
, !- Free Convection Capacity {W}
, !- Free Convection Nominal Capacity Sizing Factor
, !- Design Inlet Air Dry-Bulb Temperature {C}
, !- Design Inlet Air Wet-Bulb Temperature {C}
, !- Design Approach Temperature {deltaC}
, !- Design Range Temperature {deltaC}
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
SaturatedExit, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
0.0080, !- Drift Loss Percent {percent}
ConcentrationRatio, !- Blowdown Calculation Mode
3.0000, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
TowerWaterSys CoolTower OA ref Node, !- Outdoor Air Inlet Node Name
FanCycling, !- Capacity Control
4, !- Number of Cells
MinimalCell, !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.0000; !- Sizing Factor
OutdoorAir:Node,
TowerWaterSys CoolTower OA ref Node; !- Name
These outputs are the electric power input to the tower
fans. Consumption is metered on HeatRejection:Electricity,
Electricity:Plant, and Electricity:Facility.
Cooling
Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower
basin heater. Consumption is metered on
HeatRejection:Electricity, Electricity:Plant, and
Electricity:Facility
Cooling
Tower Make Up Water Volume Flow Rate [m3/s][LINK]
These outputs are the water consumed by the wet cooling
tower for external water sprays used to augment heat transfer.
This is the total of evaporation, drift, and blowdown.
Cooling
Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
These outputs provide the breakdown of the different
components of water use during cooling tower operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to
feed the cooling tower.
If a water storage tank is used to provide water to the
tower, then the following output variables will also be
available.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank
connections was not able to provide. The starved water is
assumed to come from the mains. The tower’s operation is not
affected by a lack of storage tank water.
This represents the fraction of a fluid bypassing the tower
when a mixture of the tower fluid and tower return water is
able to meet the set point temperature.
The two-speed cooling tower is modeled in a similar fashion
to the single-speed tower. The cooling tower is modeled as a
counterflow heat exchanger with a two-speed fan (induced draft
configuration) based on Merkel’s theory. The user must define
tower performance via one of two methods: heat transfer
coefficient-area product (UA) and design water flow rate, or
nominal tower capacity at a specific rating point. Regardless
of which method is chosen, the airflow rate and corresponding
fan power at both high and low fan speed must be specified.
The model will also account for tower performance in the “free
convection” regime, when the tower fan is off but the water
pump remains on and heat transfer still occurs (albeit at a
low level). If the user wants the model to account for “free
convection”, they must specify the corresponding air flow rate
and heat transfer coefficient-area product (UA), or the
nominal tower capacity during this mode of operation.
The cooling tower seeks to maintain the temperature of the
water exiting the cooling tower at (or below) a set point. The
set point schedule value is defined by the field “Condenser
Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop
object. The model first checks to determine the impact of
“free convection”, if specified by the user, on the tower
exiting water temperature. If the exiting water temperature
based on “free convection” is at or below the set point, then
the tower fan is not turned on. If the exiting water
temperature remains above the set point after “free
convection” is modeled, then the tower fan is turned on at low
speed to reduce the exiting water temperature. If operating
the tower fan at low speed does not reduce the exiting water
temperature to the set point, then the tower fan is increased
to its high speed.
The model assumes that part-load operation is represented
by a simple linear interpolation between two steady-state
regimes (i.e., tower fan at high speed for the entire
simulation timestep and tower fan at low speed for the entire
simulation timestep, or tower fan at low speed for the entire
simulation timestep and tower fan off for the entire
simulation timestep). Cyclic losses are not taken into
account.
Cooling towers here are “wet” and consume water through
evaporation, drift, and blowdown. The model can be used to
predict water consumed by the towers. The last six input
fields are optional and provide methods of controlling details
of the water consumption calculations. The user can specify
connections to the rest of the buildings water system by
providing the name of a WaterUse:Storage
object.
For the operation of multi-cell towers, the first step is
to determine the number of cells to operate based on the cell
control method – between the minimum number of cells subject
to the maximum water flow rate fraction per cell, and maximum
number of cells subject to the minimum water flow rate
fraction per cell. If the calculated cells do not meet the
loads, additional cells will be operating to help meet the
loads. Inside each cell, the existing capacity controls still
apply.
For multi-cell towers, the following inputs are assumed to
be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power
at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal
Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common
basin)
This numeric field contains the design water flow rate
through the tower in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the tower
(not the flow rate of water being sprayed on the outside of
the heat exchange coil). If the input field “Performance Input
Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow
rate greater than zero must be defined or the field can be
autosized. If autosized, a Plant Sizing object must be defined
and the design water flow rate is derived from the design load
to be rejected by the condenser loop and the design loop delta
T (Ref. Sizing and Input for Design Calculations and Component
Autosizing sections). If “Performance Input Method” is
specified as “NominalCapacity”, then this field must be left
blank since the model automatically assumes a design water
flow rate of 5.382E-8 m3/s per watt (3 gpm/ton) of tower
capacity specified in the field “Tower High-Speed Nominal
Capacity”.
This numeric field contains the tower air flow rate at high
fan speed in m\(^{3}\)/s. A
value greater than zero must be defined regardless of the
tower performance input method. Alternately, this field can be
autosized. If autosized, the design air flow rate is
calculated as follows:
where a fan pressure rise of 190 Pascals and total fan
efficiency of 0.5 are assumed.
Field: High Fan Speed Fan
Power
This numeric field contains the fan power (in Watts) at the
high-speed air flow rate specified in the previous field. A
value greater than zero must be specified regardless of the
tower performance input method, or this field can be
autosized. If autosized, the fan power is calculated as
follows:
If”Performance Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then
Field:
High Fan Speed U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per degree Celsius
corresponding to the high-speed air flow rate and design water
flow rate specified above. If the input field “Performance
Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value
greater than zero but less than or equal to 300,000 must be
defined, or the field can be autosized. If autosized, a Plant
Sizing object must be defined and the tower UA value at high
fan speed is derived from the design load to be rejected by
the condenser loop and the design loop delta T (Ref. Sizing
and Input for Design Calculations and Component Autosizing
sections), assuming a tower water inlet temperature of 35C and
tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance
Input Method” is specified as “NominalCapacity”, then this
field must be left blank since the model automatically
calculates the tower UA based on the capacity specified in the
field “High-Speed Nominal Capacity”.
This numeric field contains the tower air flow rate at low
fan speed in m\(^{3}\)/s.
This value must be greater than zero, less than the value
specified for the field “Air Flow Rate at High Fan Speed”, and
greater than the value specified for the field “Air Flow Rate
in Free Convection Regime”. This field may be autocalculated,
in which case it is set to a fraction of the “Air Flow Rate at
High Fan Speed” determined in the next field.
Field:
Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the low fan speed air flow rate. The default is
0.5.
This numeric field contains the fan power (in Watts) at the
low-speed air flow rate specified in the previous field. This
value must be specified greater than zero or the field may be
autocalculated, in which case it is set to a fraction of the
“Fan Power at High Fan Speed” determined in the next
field.
Field:
Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the low speed fan power. The default is 0.16.
Field:
Low Fan Speed U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per degree Celsius
corresponding to the design water flow rate and low-speed air
flow rate specified above. If the input field “Performance
Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, this value must be
greater than zero but less than or equal to 300,000, less than
the value specified for the field “U-Factor Times Area Value
at High Fan Speed”, and greater than the value specified for
the field “U-Factor Times Area Value at Free Convection Air
Flow Rate”. This field may be autocalculated, in which case it
is set to a fraction of the “U-Factor Times Area Value at High
Fan Speed” determined in the following field. If “Performance
Input Method” is specified as “NominalCapacity”, then this
field must be left blank since the model automatically
calculates the tower UA based on the tower capacity specified
in the field “Low Speed Nominal Capacity”.
Field:
Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the low speed heat transfer coefficient-area
product (UA). The default is 0.6.
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in
the “free convection” regime (water flow exists but tower fan
is turned off). This value must be less than the value
specified for the field “Air Flow Rate at Low Fan Speed”. This
field may be autocalculated, in which case it is set to a
fraction of the “Air Flow Rate at High Fan Speed” determined
in the following field. If the user does not wish to model
“free convection” and is using the Performance Input Method
“UFactorTimesAreaAndDesignWaterFlowRate”, then this field
should be set to 0.0. If the user specifies the U-Factor Times
Area Value at Free Convection Air Flow Rate or Free Convection
Capacity as a value greater than zero, then the free
convection air flow rate must be specified greater than
0.0.
Field:
Free Convection Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime air flow rate. The
default is 0.1.
Field:
Free ConvectionU-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (W/°C) when the tower is in the “free
convection” regime (water flow exists but tower fan is turned
off). This value must be less than the value specified for the
field “U-Factor Times Area Value at Low Fan Speed”. This field
may be autocalculated, in which case it is set to a fraction
of the “U-Factor Times Area Value at High Fan Speed”
determined in the following field. If the user does not wish
to model “free convection” and is using the Performance Input
Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this
field should be set to 0.0. If “Performance Input Method” is
specified as “NominalCapacity”, then this field must be left
blank since the model automatically calculates the tower UA
based on the tower capacity specified in the field “Free
Convection Capacity”.
Field:
Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime U-Factor times area
value. The default is 0.1.
This alpha field contains the method by which the user will
specify tower performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”.
If this field is left blank in the input data file, the
default input method is assumed to be
“UFactorTimesAreaAndDesignWaterFlowRate”. If the method
“UFactorTimesAreaAndDesignWaterFlowRate” is selected, then the
user must enter UA values, design water flow rate and air flow
rates as described for the previous input fields. If the
method “NominalCapacity” is selected then the fields “Design
Water Flow Rate”, “U-Factor Times Area Value at High Fan
Speed”, “U-Factor Times Area Value at Low Fan Speed” and
“U-Factor Times Area Value at Free Convection Air Flow Rate”
must be left blank, but the fields “High Speed Nominal
Capacity”, “Low Speed Nominal Capacity” and “Free Convection
Capacity” must be entered as described below.
Field:
Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of
actual tower heat rejection to nominal capacity. This ratio
is defined at entering water at 35C (95F), leaving water at
29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F)
drybulb temperatures. Historically this ratio has been set at
1.25 based on the assumption that the tower must dissipate
0.25 W of compressor power for every what of heat removed at
the chiller evaporator. The default is 1.25.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts under
high-speed fan operation, with entering water at 35C (95F),
leaving water at 29.4C (85F), entering air at 25.6C (78F)
wetbulb and 35C (95F) drybulb temperatures. The design water
flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed
nominal capacity (3 gpm/ton). The Heat Rejection Capacity and
Nominal Capacity Sizing Ratio set in the previous field is
applied to this nominal tower capacity to give the actual
tower heat rejection at these operating.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts under
low-speed fan operation, with entering water at 35C (95F),
leaving water at 29.4C (85F), entering air at 25.6C (78F)
wetbulb and 35C (95F) drybulb temperatures. The design water
flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed
nominal tower capacity (input field above). The Heat Rejection
Capacity and Nominal Capacity Sizing Ratio is applied to this
nominal tower capacity to give the actual tower heat rejection
at these operating conditions. The value specified for this
field must be greater than zero but less than the value
specified for the field “High-Speed Nominal Capacity”. This
field may be autocalculated, in which case it is set to a
fraction of the High Speed Nominal Capacity determined in the
following field.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts when the
tower is in the “free convection” regime (water flow exists
but tower fan is turned off), with entering water at 35C
(95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The design
water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed
nominal tower capacity (input field above). The Heat Rejection
Capacity and Nominal Capacity Sizing Ratio is applied to this
free convection tower capacity to give the actual tower heat
rejection at these operating conditions.The value specified
for this field must be less than the value specified for the
field “Tower Low-Speed Nominal Capacity”. If the user does not
wish to model “free convection”, then this field should be set
to 0.0. If the user specifies a value greater than zero, then
the “Air Flow Rate in Free Convection Regime” field must
contain a value greater than zero. This field may be
autocalculated, in which case it is set to a fraction of the
High Speed Nominal Capacity determined in the following
field.
This numeric field specifies the design approach
temperature of the tower corresponding to the design inlet air
wet-bulb temperature and the design temperature range. The
approach temperature should be the outlet water temperature
minus the inlet air wet-bulb temperature at design conditions.
This parameter is autosizable and when autosized it is set to
3.9 °C.
This numeric field specifies the design temperature range
of the tower corresponding to the design inlet air wet-bulb
temperature and the design approach temperature. The design
range should be the inlet water temperature minus the outlet
water temperature at design conditions. This parameter is
autosizable and when autosized it is set to 5.5 °C.
This numeric field contains the capacity of the tower’s
electric basin heater in watts per degree Kelvin. This field
is used in conjunction with the Basin Heater Setpoint
Temperature described in the following field. The basin heater
electric power is equal to this field multiplied by the
difference between the basin heater set point temperature and
the outdoor dry-bulb temperature. The basin heater only
operates when the tower fan is off and water is not flowing
through the tower, regardless of the basin heater schedule
described below. The basin heater capacity must be greater
than or equal to zero, with a default value of zero if this
field is left blank.
This numeric field contains the set point temperature (˚C)
for the basin heater described in the previous field. The
basin heater is active when the outdoor air dry-bulb
temperature falls below this setpoint temperature, as long as
the tower fan is off and water is not flowing through the
tower. This set point temperature must be greater than or
equal to 2˚C, and the default value is 2˚C if this field is
left blank.
This alpha field contains the name of the basin heater
operating schedule. The basin heater operating schedule is
assumed to be an on/off schedule and the heater is available
to operate any time the schedule value is greater than 0. The
basin heater operates when scheduled on and the outdoor air
dry-bulb temperature is below the set point temperature
described in the previous field. If this field is left blank,
the basin heater is available to operate throughout the
simulation. Regardless of this schedule, the basin heater may
only operate when the cooling tower fan is off and water is
not flowing through the tower.
This field is used to choose which method is used to model
the amount of water evaporated by the cooling tower. There are
two options: LossFactor or
SaturatedExit. The default is SaturatedExit.
The user-defined loss factor is entered in the following
field. By assuming that the air leaving the tower is
saturated, the evaporation can be directly calculated using
moist air engineering calculations with data available within
the cooling tower model (and does not require additional user
input).
This field is used to specify the rate of water evaporated
from the cooling tower and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The evaporation loss is
then calculated as a fraction of the circulating condenser
water flow and varies with the temperature change in the
condenser water. The value entered here is in units of
percent-per-degree Kelvin. The evaporation rate will equal
this value times each degree Kelvin of temperature drop in the
condenser water. Typical values are from 0.15 to 0.27
[percent/K]. The default is 0.2.
This field is used to specify the rate of water lost to the
exiting air as entrained droplets [%]. The drift loss is a
percent of the condenser water flow. Typical values for towers
with efficient drift eliminators are between 0.002 and 0.2% of
the condenser water flow rate. The default value is
0.008%.
This field specifies which method is used to determine
blowdown rates. There two options ConcentrationRatio or
ScheduledRate. The choice will determine which of the two
models below is used. The default is ConcentrationRatio
This field is used to dynamically adjust the rate of
blowdown in the cooling tower as a function of the rate of
evaporation. Blowdown is water intentionally drained from the
tower in order to offset the build up of solids in the water
that would otherwise occur because of evaporation. The value
entered here is dimensionless. It can be characterized as the
ratio of solids in the blowdown water to solids in the make up
water. Typical values for tower operation are 3 to 5. The
default value is 3.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m\(^{3}\)/s) flushed from the basin
on a periodic basis to purge the tower of mineral scale
build-up and other contaminants. This schedule is only used if
the Blowdown Calculation mode is set to ScheduledRate. The
amount of water use due to blowdown depends on the makeup
water quality and is specific to each geographical location.
Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is
in addition to the amount of water lost to the atmosphere due
to evaporation and/or drift. Since blowdown occurs when the
basin water contaminant concentration is high, blowdown only
occurs when the cooling tower is active and water is flowing
through the tower (regardless of the water usage defined by
this schedule).
This field is optional. It is used to describe where the
tower obtains water used for evaporative cooling. If blank or
omitted, then the tower will obtain water directly from the
mains. If the name of a WaterUse:Storage
object is used here, then the tower will obtain its water from
that tank. If a tank is specified, the tower will attempt to
obtain all the water it uses from the tank. However if the
tank cannot provide all the water the tower needs, then the
tower will still operate and obtain the rest of the water it
needs from the mains (referred to as ‘Starved’ water).
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
cooling tower. If this field is left blank, the outdoor air
conditions entering the cooling tower are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
This integer field contains the number of cells in the
multi-cell cooling tower. If not entered, the program will
assume it is a single-cell cooling tower
This alpha field specifies the method used to control the
number of cells used to meet the load, the two choices
are:
MinimalCell: the program will use minimal
number of cells needed, all other cells will be shut down with
no water flow. It will attempt to use as few cells as possible
to cool the fluid. In no case, however, will the flow per cell
be allowed to exceed its maximum value defined by the
Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible
will be turned on. In no case, however, will the flow per cell
be allowed to drop below its minimum value specified by the
Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is
MaximalCell.
Field:
Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest
fraction of the design water flow rate. Flows less than this
value will commonly result in fluid distribution problems; the
pressure at each nozzle will be too weak for the fluid to be
sprayed out in the correct pattern, not all the fill would be
wet. If this field is left blank, the default value is
0.33.
Field:
Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction
of the design water flow rate. If this field is left blank,
the default value is 2.5.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature.For this component
the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Air Flow Rate at High Fan Speed;
3. Fan Power at High Fan Speed;
4. U-Factor Times Area Value at High Fan Speed;
5. Air Flow Rate at Low Fan Speed;
6. Fan Power at Low Fan Speed;
7. U-Factor Times Area Value at Low Fan Speed;
8. Air Flow Rate in Free Convection Regime;
9. U-Factor Times Area Value at Free Convection Air Flow
Rate.
Note that the U-Factor Times Area Value at High Fan Speed
is not multiplied by the Sizing Factor. Instead the
design tower load is multiplied by the sizing factor and the
design UA then calculated as usual. The U-Factor Times Area
Value at Low Fan Speed is set to a fraction of the full load
design UA determined by the field Low Fan Speed U-Factor Times
Area Sizing Factor. The U-Factor Times Area Value at Free
Convection Air Flow Rate is set to a fraction of the design
Tower UA determined by the field Free Convection Air U-Factor
Times Area Value Sizing Factor.
This optional field allows you to specify a user-defined
end-use subcategory, e.g., “Process”. A new meter for
reporting is created for each unique subcategory (ref: Output:Meter
objects). Any text may be used here to further subcategorize
the end-uses in the ABUPS End Uses by Subcategory table and in
the LEED Summary EAp2-4/5 Performance Rating Method Compliance
table. If this field is omitted or blank, the cooling tower
will be assigned to the “General” end-use subcategory.
Four examples of an IDF specification for this object are
shown below:
CoolingTower:TwoSpeed,
My Tower, !- Name
Condenser Tower Inlet Node, !- Water Inlet Node Name
Condenser Tower Outlet Node,!- Water Outlet Node Name
.0011, !- Design Water Flow Rate {m3/s}
16.0, !- High Fan Speed Air Flow Rate {m3/s}
10000., !- High Fan Speed Fan Power {W}
3500., !- High Fan Speed U-Factor Times Area Value {W/K}
8.0, !- Low Fan Speed Air Flow Rate {m3/s}
, !- Low Fan Speed Air Flow Rate Sizing Factor
1600., !- Low Fan Speed Fan Power {W}
, !- Low Fan Speed Fan Power Sizing Factor
2100., !- Low Fan Speed U-Factor Times Area Value {W/K}
, !- Low Fan Speed U-Factor Times Area Sizing Factor
1.6, !- Free Convection Regime Air Flow Rate {m3/s}
, !- Free Convection Regime Air Flow Rate Sizing Factor
350., !- Free Convection Regime U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
UFactorTimesAreaAndDesignWaterFlowRate; !- Performance Input Method
CoolingTower:TwoSpeed,
My Tower, !- Name
Condenser Tower Inlet Node, !- Water Inlet Node Name
Condenser Tower Outlet Node,!- Water Outlet Node Name
, !- Design Water Flow Rate {m3/s}
8.0, !- High Fan Speed Air Flow Rate {m3/s}
500, !- High Fan Speed Fan Power {W}
, !- High Fan Speed U-Factor Times Area Value {W/K}
4.0, !- Low Fan Speed Air Flow Rate {m3/s}
, !- Low Fan Speed Air Flow Rate Sizing Factor
125, !- Low Fan Speed Fan Power {W}
, !- Low Fan Speed Fan Power Sizing Factor
, !- Low Fan Speed U-Factor Times Area Value {W/K}
, !- Low Fan Speed U-Factor Times Area Sizing Factor
0.8, !- Free Convection Regime Air Flow Rate {m3/s}
, !- Free Convection Regime Air Flow Rate Sizing Factor
, !- Free Convection Regime U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
NominalCapacity, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
20000.0, !- High Speed Nominal Capacity {W}
10000.0, !- Low Speed Nominal Capacity {W}
, !- Low Speed Nominal Capacity Sizing Factor
2000.0, !- Free Convection Nominal Capacity {W}
; !- Free Convection Nominal Capacity Sizing Factor
CoolingTower:TwoSpeed,
Big Tower1, !- Name
Condenser Tower Inlet Node, !- Water Inlet Node Name
Condenser Tower Outlet Node,!- Water Outlet Node Name
, !- Design Water Flow Rate {m3/s}
8.0, !- High Fan Speed Air Flow Rate {m3/s}
500, !- High Fan Speed Fan Power {W}
, !- High Fan Speed U-Factor Times Area Value {W/K}
4.0, !- Low Fan Speed Air Flow Rate {m3/s}
, !- Low Fan Speed Air Flow Rate Sizing Factor
125, !- Low Fan Speed Fan Power {W}
, !- Low Fan Speed Fan Power Sizing Factor
, !- Low Fan Speed U-Factor Times Area Value {W/K}
, !- Low Fan Speed U-Factor Times Area Sizing Factor
0.8, !- Free Convection Regime Air Flow Rate {m3/s}
, !- Free Convection Regime Air Flow Rate Sizing Factor
, !- Free Convection Regime U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
NominalCapacity, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
20000.0, !- High Speed Nominal Capacity {W}
10000.0, !- Low Speed Nominal Capacity {W}
, !- Low Speed Nominal Capacity Sizing Factor
2000.0, !- Free Convection Nominal Capacity {W}
, !- Free Convection Nominal Capacity Sizing Factor
, !- Design Inlet Air Dry-Bulb Temperature {C}
, !- Design Inlet Air Wet-Bulb Temperature {C}
, !- Design Approach Temperature {deltaC}
, !- Design Range Temperature {deltaC}
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
SaturatedExit, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
0.0080, !- Drift Loss Percent {percent}
ConcentrationRatio, !- Blowdown Calculation Mode
3.0000, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
Recovery Tank; !- Supply Water Storage Tank Name
CoolingTower:TwoSpeed,
TowerWaterSys CoolTower, !- Name
TowerWaterSys Pump-TowerWaterSys CoolTowerNode, !- Water Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node, !- Water Outlet Node Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- High Fan Speed Air Flow Rate {m3/s}
AUTOSIZE, !- High Fan Speed Fan Power {W}
AUTOSIZE, !- High Fan Speed U-Factor Times Area Value {W/K}
autocalculate, !- Low Fan Speed Air Flow Rate {m3/s}
, !- Low Fan Speed Air Flow Rate Sizing Factor
autocalculate, !- Low Fan Speed Fan Power {W}
, !- Low Fan Speed Fan Power Sizing Factor
autocalculate, !- Low Fan Speed U-Factor Times Area Value {W/K}
, !- Low Fan Speed U-Factor Times Area Sizing Factor
autocalculate, !- Free Convection Regime Air Flow Rate {m3/s}
, !- Free Convection Regime Air Flow Rate Sizing Factor
autocalculate, !- Free Convection Regime U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
, !- High Speed Nominal Capacity {W}
, !- Low Speed Nominal Capacity {W}
, !- Low Speed Nominal Capacity Sizing Factor
, !- Free Convection Nominal Capacity {W}
, !- Free Convection Nominal Capacity Sizing Factor
, !- Design Inlet Air Dry-Bulb Temperature {C}
, !- Design Inlet Air Wet-Bulb Temperature {C}
, !- Design Approach Temperature {deltaC}
, !- Design Range Temperature {deltaC}
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
SaturatedExit, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
0.0080, !- Drift Loss Percent {percent}
ConcentrationRatio, !- Blowdown Calculation Mode
3.0000, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
TowerWaterSys CoolTower OA ref Node, !- Outdoor Air Inlet Node Name
4, !- Number of Cells
MinimalCell, !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.0000; !- Sizing Factor
These outputs are the electric power input to the tower
fans. Consumption is metered on HeatRejection:Electricity,
Electricity:Plant, and Electricity:Facility.
Cooling
Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower
basin heater. Consumption is metered on
HeatRejection:Electricity, Electricity:Plant, and
Electricity:Facility
Cooling
Tower Make Up Water Volume Flow Rate [m3/s][LINK]
These outputs are the water consumed by the wet cooling
tower for external water sprays used to augment heat transfer.
This is the total of evaporation, drift, and blowdown.
Cooling
Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
These outputs provide the breakdown of the different
components of water use during cooling tower operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to
feed the cooling tower. If a water storage tank is used to
provide water to the tower, then the following output
variables will also be available.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank
connections was not able to provide. The starved water is
assumed to come from the mains. The tower’s operation is not
affected by a lack of storage tank water.
This variable speed tower model is based on Merkel’s theory
and is similar to the single-speed and two-speed tower
models. The open wet cooling tower is modeled as a counter
flow heat exchanger with a variable-speed fan drawing air
through the tower (induced-draft configuration). The model
also includes a “free convection” regime where cooling tower
performance is modeled with the fan off.
For this model, Merkel’s theory is modified to include
adjustments developed by Scheier to alter the heat transfer
effectiveness based on current wetbulb, air flow rates, and
water flow rates. The input requires performance curves or
lookup tables to describe these three adjustment factors.
For a multi-cell tower, the capacity and air/water flow
rate inputs are for the entire tower.
This alpha field contains the method by which the user will
specify tower performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“NominalCapacity”. If this field is left
blank in the input data file, the default input method is
assumed to be “NominalCapacity”. If the
method “UFactorTimesAreaAndDesignWaterFlowRate” is selected,
then the user must enter design UA values, design water flow
rates and air flow rates as described for the previous input
fields. If the method “NominalCapacity” is selected then the
fields “Design Water Flow Rate”, “U-Factor Times Area Value at
Design Air Flow Rate” and “U-Factor Times Area Value at Free
Convection Air Flow Rate” must be left blank, but the fields
“Nominal Capacity” and “Free Convection Capacity” must be
entered as described below.
Field:
Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of
actual tower heat rejection to nominal capacity. This ratio
is defined at entering water at 35C (95F), leaving water at
29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F)
drybulb temperatures. Historically this ratio has been set at
1.25 based on the assumption that the tower must dissipate
0.25 W of compressor power for every what of heat removed at
the chiller evaporator. The default is 1.25.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts under
full-speed fan operation, with entering water at 35C (95F),
leaving water at 29.4C (85F), entering air at 25.6C (78F)
wetbulb and 35C (95F) drybulb temperatures. The Heat Rejection
Capacity and Nominal Capacity Sizing Ratio set in the previous
field is applied to this nominal tower capacity to give the
actual tower heat rejection at these operating conditions.
This field can be autosized, in which case a Sizing:Plant
object is needed for the condenser loop.
This numeric input field contains the “nominal” heat
rejection capacity of the cooling tower in watts when the
tower is in the “free convection” regime (water flow exists
but tower fan is turned off), with entering water at 35C
(95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The Heat
Rejection Capacity and Nominal Capacity Sizing Ratio is
applied to this free convection tower capacity to give the
actual tower heat rejection at these operating conditions.The
value specified for this field must be less than the value
specified for the field “Tower Low-Speed Nominal Capacity”. If
the user does not wish to model “free convection”, then this
field should be set to 0.0. If the user specifies a value
greater than zero, then the “Air Flow Rate in Free Convection
Regime” field must contain a value greater than zero. This
field may be autocalculated, in which case it is set to a
fraction of the High Speed Nominal Capacity determined in the
following field.
This numeric field contains the design water flow rate
through the tower in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the tower. If
the input field “Performance Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow
rate greater than zero must be defined or the field can be
autosized. If autosized, a Sizing:Plant
object must be defined and the design water flow rate is
derived from the design load to be rejected by the condenser
loop and the design loop delta T (Ref. Sizing and Input for
Design Calculations and Component Autosizing sections). If
“Performance Input Method” is specified as “NominalCapacity”,
then this field can be autocalculated using the sizing factor
in the following field.
Field:
Design Water Flow Rate per Unit of Nominal Capacity[LINK]
This numeric field contains a scalable sizing factor for
design water flow rate that scales with nominal capacity, in
units of m\(^{3}\)/s/W. The
default value is 5.382*10\(^{-8}\). This field is only used
if the previous field is set to autocalculate and performance
input method is NominalCapacity. (If the performance input
method is set to UFactorTimesAreaAndDesignWaterFlowRate then
the design water flow rate is obtained from the plant sizing
result.)
This numeric field contains the tower air flow rate at full
fan speed, in m\(^{3}\)/s.
The value can be autocalculated, in which case the air flow
rate is based off of the scalable sizing factor in the
following input field.
Field:
Design Air Flow Rate Per Unit of Nominal Capacity[LINK]
This numeric field contains the sizing factor to use when
calculating the design air flow rate from the nominal
capacity, in units of m\(^{3}\)/s/W. The default is
2.76316*10\(^{-5}\). When
this field is left blank, then the default value is used but
the flow rate is also scaled to account for elevation (with
larger volume flow rates at higher altitudes). When a hard
value is entered, even if it is the same as the default, then
the design air flow rate is not also adjusted for elevation
and the scaling factor is used directly.
This numeric field contains the minimum air flow rate
ratio. The tower fan is allowed to operate between the ratio
defined here and a maximum air flow rate ratio of 1.0 (which
corresponds to the design [maximum] tower air flow rate).
Below this value the tower is assumed to operate in the “free
convection” regime with the tower fan off. The minimum air
flow rate ratio must be greater than or equal to 0.1 and less
than or equal to 0.5, with a default value of 0.2 if the field
is left blank.
This numeric field contains the fan power in watts at the
design (maximum) air flow rate through the tower. A value
greater than zero must be specified or this field can be
autocalculated. When the field is autocalculated the following
input field is used to size the fan power based on nominal
capacity.
Field:
Design Fan Power Per Unit of Nominal Capacity[LINK]
This numeric field contains the sizing factor to use when
calculating the design fan power from the nominal capacity, in
units of Watts per Watt. This field is only used if the
previous is set to autocalculate. The default values is
0.0105.
Field:
Fan Power Modifier Function of Air Flow Rate Ratio Curve
Name[LINK]
This alpha field contains the name of a curve or table
object that describes fan power ratio (fan power/design fan
power) as a function of air flow rate ratio (air flow
rate/design air flow rate). The curve or table object must be
for one independent variable, typically a cubic, and should be
normalized to 1.0 at an air flow rate ratio of 1.0. This
field is required.
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in
the “free convection” regime (water flow exists but tower fan
is turned off). This value must be less than the value
specified for the field “Design Air Flow Rate”. This field may
be autocalculated, in which case it is set to a fraction of
the “Design Air Flow Rate” determined in the following input
field. If the user does not wish to model “free convection”
and is using the Performance Input Method
“UFactorTimesAreaAndDesignWaterFlowRate”, then this field
should be set to 0.0. If the user specifies the U-Factor Times
Area Value at Free Convection Air Flow Rate or Free Convection
Capacity as a value greater than zero, then the free
convection air flow rate must be specified greater than
0.0.
Field:
Free Convection Regime Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime air flow rate. The
default is 0.1.
Field:
Design Air Flow Rate U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the design air and water flow rates specified
above. If the input field “Performance Input Method” is
specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a
UA value greater than zero but less than or equal to 300,000
must be defined, or the field can be autosized. If autosized,
a Plant Sizing object must be defined and the design tower UA
value is derived from the design load to be rejected by the
condenser loop and the design loop delta T (Ref. Sizing and
Input for Design Calculations and Component Autosizing
sections), assuming a tower water inlet temperature of 35C and
tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance
Input Method” is specified as “NominalCapacity”, then this
field must be left blank since the model automatically
calculates the tower UA based on the tower capacity specified
in the field “Nominal Capacity”.
Field:
Free Convection Regime U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (W/K) when the tower is in the “free
convection” regime (water flow exists but tower fan is turned
off). This value must be less than the value specified for the
field “U-Factor Times Area Value at Design Air Flow Rate”.
This field may be autosized, in which case it is set to a
fraction of the “U-Factor Times Area Value at Design Air Flow
Rate” determined in the following input field. If the user
does not wish to model “free convection” and is using the
Performance Input Method
“UFactorTimesAreaAndDesignWaterFlowRate”, then this field
should be set to 0.0. If “Performance Input Method” is
specified as “NominalCapacity”, then this field must be left
blank since the model automatically calculates the tower UA
based on the tower capacity specified in the field “Free
Convection Capacity”.
Field:
Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the free convection regime U-Factor times area
value. The default is 0.1. This field is only used if the
previous field is set to autocalculate and the performance
input method is UFactorTimesAreaAndDesignWaterFlowRate.
Field:
U-Factor Times Area Modifier Function of Air Flow Ratio Curve
Name[LINK]
This alpha field contains the name of a curve or table
object that describes how the UA value varies as a function of
air flow rate ratio (air flow rate/design air flow rate). The
result of this curve is multiplied by the design UA value to
adjust for air flow rate, along with the two other modifiers
discussed below. The curve or table object must be for one
independent variable and should be normalized to 1.0 at an air
flow rate ratio of 1.0. This field is required.
Field:
U-Factor Times Area Modifier Function of Wetbulb Temperature
Difference Curve Name[LINK]
This alpha field contains the name of a curve or table
object that describes how the UA value varies as a function of
the current wetbulb temperature. The result of this curve is
multiplied by the design UA value to adjust for wetbulb
temperatures that differ from design conditions at 25.56°C
(78°F), along with the two other modifiers discussed in the
previous and following fields. The independent variable is
the design wetbulb minus the current outdoor air wetbulb, in
units of degrees Celsius. The curve or table object must be
for one independent variable and should be normalized to 1.0
at a wetbulb temperature difference of 0.0. This field is
required.
Field:
U-Factor Times Area Modifier Function of Water Flow Ratio
Curve Name[LINK]
This alpha field contains the name of a curve or table
object that describes how the UA value varies as a function of
the current water flow rate ratio (water flow rate/design
water flow rate). The result of this curve is multiplied by
the design UA value to adjust for water flow rates that differ
from design level, along with the other two modifiers
discussed above. The curve or table object must be for one
independent variable and should be normalized to 1.0 at a
water flow ratio of 1.0. This field is required
Field:
Design Inlet Air Dry-Bulb Temperature[LINK]
This numeric field specifies the design inlet air dry-bulb
temperature of the tower. The default is 35.0 °C.
Field:
Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the design inlet air wet-bulb
temperature of the tower. The default is 25.6 °C.
This numeric field specifies the design approach
temperature of the tower corresponding to the design inlet air
wet-bulb temperature and the design temperature range. The
approach temperature should be the outlet water temperature
minus the inlet air wet-bulb temperature at design conditions.
This parameter is autosizable and when autosized it is set to
3.9 °C.
This numeric field specifies the design temperature range
of the tower corresponding to the design inlet air wet-bulb
temperature and the design approach temperature. The design
range should be the inlet water temperature minus the outlet
water temperature at design conditions. This parameter is
autosizable and when autosized it is set to 5.5 °C.
This numeric field contains the capacity of the tower’s
electric basin heater in watts per degree Kelvin. This field
is used in conjunction with the Basin Heater Setpoint
Temperature described in the following field. The basin heater
electric power is equal to this field multiplied by the
difference between the basin heater set point temperature and
the outdoor dry-bulb temperature. The basin heater only
operates when the tower fan is off and water is not flowing
through the tower, regardless of the basin heater schedule
described below. The basin heater capacity must be greater
than or equal to zero, with a default value of zero if this
field is left blank.
This numeric field contains the set point temperature (˚C)
for the basin heater described in the previous field. The
basin heater is active when the outdoor air dry-bulb
temperature falls below this setpoint temperature, as long as
the tower fan is off and water is not flowing through the
tower. This set point temperature must be greater than or
equal to 2˚C, and the default value is 2˚C if this field is
left blank.
This alpha field contains the name of the basin heater
operating schedule. The basin heater operating schedule is
assumed to be an on/off schedule and the heater is available
to operate any time the schedule value is greater than 0. The
basin heater operates when scheduled on and the outdoor air
dry-bulb temperature is below the set point temperature
described in the previous field. If this field is left blank,
the basin heater is available to operate throughout the
simulation. Regardless of this schedule, the basin heater may
only operate when the cooling tower fan is off and water is
not flowing through the tower.
This field is used to choose which method is used to model
the amount of water evaporated by the cooling tower. There are
two options: LossFactor or
SaturatedExit. The default is SaturatedExit.
The user-defined loss factor is entered in the following
field. By assuming that the air leaving the tower is
saturated, the evaporation can be directly calculated using
moist air engineering calculations with data available within
the cooling tower model (and does not require additional user
input).
This field is used to specify the rate of water evaporated
from the cooling tower and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The
evaporation loss is then calculated as a fraction of the
circulating condenser water flow and varies with the
temperature change in the condenser water. The value entered
here is in units of percent-per-degree Kelvin. The evaporation
rate will equal this value times each degree Kelvin of
temperature drop in the condenser water. Typical values are
from 0.15 to 0.27 [percent/K]. The default is 0.2.
This field is used to specify the rate of water lost to the
exiting air as entrained droplets [%]. The drift loss is a
percent of the condenser water flow. Typical values for towers
with efficient drift eliminators are between 0.002 and 0.2% of
the condenser water flow rate. The default value is
0.008%.
This field specifies which method is used to determine
blowdown rates. There two options
ConcentrationRatio or
ScheduledRate. The choice will determine
which of the two models below is used. The default is
ConcentrationRatio.
This field is used to dynamically adjust the rate of
blowdown in the cooling tower as a function of the rate of
evaporation. Blowdown is water intentionally drained from the
tower in order to offset the build up of solids in the water
that would otherwise occur because of evaporation. The value
entered here is dimensionless. It can be characterized as the
ratio of solids in the blowdown water to solids in the make up
water. Typical values for tower operation are 3 to 5. The
default value is 3.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m\(^{3}\)/s) flushed from the basin
on a periodic basis to purge the tower of mineral scale
build-up and other contaminants. This schedule is only used if
the Blowdown Calculation Mode is set to ScheduledRate. The
amount of water use due to blowdown depends on the makeup
water quality and is specific to each geographical location.
Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is
in addition to the amount of water lost to the atmosphere due
to evaporation and/or drift. Since blowdown occurs when the
basin water contaminant concentration is high, blowdown only
occurs when the cooling tower is active and water is flowing
through the tower (regardless of the water usage defined by
this schedule).
This field is optional. It is used to describe where the
tower obtains water used for evaporative cooling. If blank or
omitted, then the tower will obtain water directly from the
mains. If the name of a WaterUse:Storage
object is used here, then the tower will obtain its water from
that tank. If a tank is specified, the tower will attempt to
obtain all the water it uses from the tank. However if the
tank cannot provide all the water the tower needs, then the
tower will still operate and obtain the rest of the water it
needs from the mains (referred to as ‘Starved’ water).
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
cooling tower. If this field is left blank, the outdoor air
conditions entering the cooling tower are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
This integer field contains the number of cells in the
multi-cell cooling tower. If not entered, the program will
assume it is a single-cell cooling tower
This alpha field specifies the method used to control the
number of cells used to meet the load, the two choices
are:
MinimalCell : the program will use minimal
number of cells needed, all other cells will be shut down with
no water flow. It will attempt to use as few cells as possible
to cool the fluid. In no case, however, will the flow per cell
be allowed to exceed its maximum value defined by the
Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible
will be turned on. In no case, however, will the flow per cell
be allowed to drop below its minimum value specified by the
Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is
MaximalCell.
Field:
Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest
fraction of the design water flow rate. Flows less than this
value will commonly result in fluid distribution problems; the
pressure at each nozzle will be too weak for the fluid to be
sprayed out in the correct pattern, not all the fill would be
wet. If this field is left blank, the default value is
0.33.
Field:
Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction
of the design water flow rate. If this field is left blank,
the default value is 2.5.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature.
This optional field allows you to specify a user-defined
end-use subcategory, e.g., “Process”. A new meter for
reporting is created for each unique subcategory (ref: Output:Meter
objects). Any text may be used here to further subcategorize
the end-uses in the ABUPS End Uses by Subcategory table and in
the LEED Summary EAp2-4/5 Performance Rating Method Compliance
table. If this field is omitted or blank, the cooling tower
will be assigned to the “General” end-use subcategory.
An example IDF specification follows.
CoolingTower:VariableSpeed:Merkel,
Big Tower1, !- Name
Condenser Tower 1 Inlet Node, !- Water Inlet Node Name
Condenser Tower 1 Outlet Node, !- Water Outlet Node Name
NominalCapacity, !- Performance Input Method
1.25, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
20000.0, !- Nominal Capacity {W}
autocalculate, !- Free Convection Nominal Capacity {W}
0.1, !- Free Convection Nominal Capacity Sizing Factor
autocalculate, !- Design Water Flow Rate {m3/s}
5.382E-8, !- Design Water Flow Rate per Unit of Nominal Capacity {m3/s-W}
autocalculate, !- Design Air Flow Rate {m3/s}
2.76316E-5, !- Design Air Flow Rate Per Unit of Nominal Capacity {m3/s-W}
0.2, !- Minimum Air Flow Rate Ratio
autocalculate, !- Design Fan Power {W}
0.0105, !- Design Fan Power Per Unit of Nominal Capacity {dimensionless}
VS tower fan power mod func air flow ratio, !- Fan Power Modifier Function of Air Flow Rate Ratio Curve Name
autocalculate, !- Free Convection Regime Air Flow Rate {m3/s}
0.1, !- Free Convection Regime Air Flow Rate Sizing Factor
, !- Design Air Flow Rate U-Factor Times Area Value {W/K}
, !- Free Convection Regime U-Factor Times Area Value {W/K}
, !- Free Convection U-Factor Times Area Value Sizing Factor
VS tower UA mod func air flow ratio, !- U-Factor Times Area Modifier Function of Air Flow Ratio Curve Name
VS tower UA mod func wetbulb difference, !- U-Factor Times Area Modifier Function of Wetbulb Temperature Difference Curve Name
VS tower UA mod func water flow ratio, !- U-Factor Times Area Modifier Function of Water Flow Ratio Curve Name
, !- Design Inlet Air Dry-Bulb Temperature {C}
, !- Design Inlet Air Wet-Bulb Temperature {C}
, !- Design Approach Temperature {deltaC}
, !- Design Range Temperature {deltaC}
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
, !- Drift Loss Percent {percent}
, !- Blowdown Calculation Mode
, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
, !- Outdoor Air Inlet Node Name
, !- Number of Cells
, !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.0; !- Sizing Factor
Curve:Cubic,
VS tower fan power mod func air flow ratio, !- Name
0.02, !- Coefficient1 Constant
0.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0.98, !- Coefficient4 x**3
0.2, !- Minimum Value of x
1.0, !- Maximum Value of x
0.0, !- Minimum Curve Output
1.0, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Dimensionless; !- Output Unit Type
Curve:Quadratic,
VS tower UA mod func air flow ratio, !- Name
0.0, !- Coefficient1 Constant
1.3, !- Coefficient2 x
-0.3, !- Coefficient3 x**2
0.2, !- Minimum Value of x
1.0, !- Maximum Value of x
0.0, !- Minimum Curve Output
1.0, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Dimensionless; !- Output Unit Type
Curve:Linear,
VS tower UA mod func wetbulb difference, !- Name
1.0, !- Coefficient1 Constant
0.0081, !- Coefficient2 x
-10, !- Minimum Value of x
25.0, !- Maximum Value of x
0.85, !- Minimum Curve Output
1.3, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Dimensionless; !- Output Unit Type
Curve:Quadratic,
VS tower UA mod func water flow ratio, !- Name
0.1082, !- Coefficient1 Constant
1.667, !- Coefficient2 x
-0.7713, !- Coefficient3 x**2
0.3, !- Minimum Value of x
1.0, !- Maximum Value of x
0.5, !- Minimum Curve Output
1.1, !- Maximum Curve Output
Dimensionless, !- Input Unit Type for X
Dimensionless; !- Output Unit Type
These outputs are the electric power input to the tower
fans. Consumption is metered on HeatRejection:Electricity,
Electricity:Plant, and Electricity:Facility.
Cooling
Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower
basin heater. Consumption is metered on
HeatRejection:Electricity, Electricity:Plant, and
Electricity:Facility
Cooling
Tower Make Up Water Volume Flow Rate [m3/s][LINK]
These outputs are the water consumed by the wet cooling
tower for external water sprays used to augment heat transfer.
This is the total of evaporation, drift, and blowdown.
Cooling
Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
These outputs provide the breakdown of the different
components of water use during cooling tower operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to
feed the cooling tower. If a water storage tank is used to
provide water to the tower, then the following output
variables will also be available.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank
connections was not able to provide. The starved water is
assumed to come from the mains. The tower’s operation is not
affected by a lack of storage tank water.
The variable speed tower model is based on empirical curve
fits of manufacturer’s performance data or field measurements.
The user specifies tower performance at design conditions, and
empirical curves are used to determine the approach
temperature and fan power at off-design conditions. The user
defines tower performance by entering the inlet air wet-bulb
temperature, tower range, and tower approach temperature at
the design conditions. The corresponding water flow rate
(within ±25% of the tower’s rated water mass flow rate), air
flow rate, and fan power must also be specified. The model
will account for tower performance in the “free convection”
regime, when the tower fan is off but the water pump remains
on and heat transfer still occurs (albeit at a low level).
Basin heater operation and makeup water usage (due to
evaporation, drift, and blowdown) are also modeled.
The cooling tower seeks to maintain the temperature of the
water exiting the cooling tower at (or below) a set point. The
set point schedule is defined by the field “Condenser Loop
Temperature Setpoint Node Name or Reference” for the CondenserLoop
object. The model first checks to determine the impact of
“free convection” on the tower exiting water temperature. If
the exiting water temperature based on “free convection” is at
or below the set point, then the variable-speed tower fan is
not turned on. If the exiting water temperature is above the
set point after “free convection” is modeled, then the
variable-speed tower fan is turned on to reduce the exiting
water temperature. Tower fan power is calculated based on the
tower air flow rate required to achieve the exiting water set
point temperature.
Cooling towers here are “wet” and consume water through
evaporation, drift, and blowdown. The model can be used to
predict water consumed by the towers. The last six input
fields are optional and provide methods of controlling details
of the water consumption calculations. The user can specify
connections to the rest of the buildings water system by
providing the name of a WaterUse:Storage
object.
For the operation of multi-cell towers, the first step is
to determine the number of cells to operate based on the cell
control method – between the minimum number of cells subject
to the maximum water flow rate fraction per cell, and maximum
number of cells subject to the minimum water flow rate
fraction per cell. If the calculated cells do not meet the
loads, additional cells will be operating to help meet the
loads. Inside each cell, the existing capacity controls still
apply.
For multi-cell towers, the following inputs are assumed to
be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power
at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal
Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common
basin)
This alpha field contains the type of empirical model used
to simulate the tower’s thermal performance (approach
temperature). Valid choices for this field are
“CoolToolsCrossFlow”, “CoolToolsUserDefined”, “YorkCalc”, or
“YorkCalcUserDefined”. “CoolToolsCrossFlow” and “YorkCalc” are
empirical models with the equation form and model coefficients
already defined within EnergyPlus. If “CoolToolsUserDefined”
or “YorkCalcUserDefined” is selected, the user must specify a
valid Model Coefficient Name in the next input field to
reference an appropriate CoolingTowerPerformance:CoolTools
or CoolingTowerPerformance:YorkCalc
object. If a user-defined model type is selected and the
specified Model Coefficient Name is not found in the input
data file (idf), then a severe message is issued and the
simulation will terminate.
This alpha field contains the identifying name for the
object(s) CoolingTowerPerformance:CoolTools
or CoolingTowerPerformance:YorkCalc.
A single model coefficient object may be used to define
coefficients for multiple variable speed cooling tower objects
(i.e., the same name may be used in this input field for more
than one variable speed tower). This field is only used when
the field Tower Model Type described above is set to
“CoolToolsUserDefined” or “YorkCalcUserDefined”, and should be
left blank otherwise.
Field:
Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the inlet air wet-bulb
temperature (˚C) at design conditions. This design temperature
should correspond with the design values for range
temperature, approach temperature, water flow rate, and air
flow rate specified in the following fields. The minimum value
for this field is 20˚C and the default value is 25.6˚C if this
field is left blank.
This numeric field specifies the tower approach temperature
(˚C) at design conditions. The approach temperature is the
outlet water temperature minus the inlet air wet-bulb
temperature. The design approach temperature should correspond
with the design values for inlet air wet-bulb temperature,
range temperature, water flow rate, and air flow rate
specified for this tower. The value for this field must be
greater than 0˚C and the default value is 3.9˚C if this field
is left blank.
This numeric field specifies the range temperature (˚C) at
design conditions. The range temperature is defined as the
inlet water temperature minus the outlet water temperature.
The design range temperature should correspond with the design
values for inlet air wet-bulb temperature, approach
temperature, water flow rate, and air flow rate specified for
this tower. The value for this field must be greater than 0˚C
and the default value is 5.6˚C if this field is left
blank.
This numeric field contains the design water flow rate
through the tower in m\(^{3}\)/s. The value entered
should be within ±25% of the tower’s rated water mass flow
rate as specified by the manufacturer if Model Type is
“CoolToolsCrossFlow” or “YorkCalc”. This constraint may be
different for Model Type “CoolToolsUserDefined” or
“YorkCalcUserDefined” (ref. CoolingTowerPerformance:CoolTools
or CoolingTowerPerformance:YorkCalc).
This value is the flow rate of the condenser loop water
being cooled by the tower. A value greater than zero must be
specified or this field can be autosized. A Plant Sizing
object must be defined if the field is autosized and the
design water flow rate is then derived from the design load to
be rejected by the condenser loop and the design loop delta T
(Ref. Sizing and Input for Design Calculations and Component
Autosizing sections). The design water flow rate should
correspond with the design values specified for the inlet air
wet-bulb temperature, approach temperature, range temperature,
and air flow rate. When this field is not autosized, the
condenser loop flow rate specified in other objects should be
within ±25% of the tower’s rated water flow rate (different
range is permissible if Model Type is “User Defined”).
This numeric field contains the design (maximum) air flow
rate through the tower in m\(^{3}\)/s. A value greater than
zero must be specified or this field can be autosized.
Autosizing of this field does not require a Plant Sizing
object since the design air flow rate is assumed to be the
design fan power multiplied by a total fan efficiency of 0.5
and divided by a fan pressure rise of 190 Pascals. A
correction for altitude is also included as follows:
This numeric field contains the fan power in watts at the
design (maximum) air flow rate through the tower. A value
greater than zero must be specified or this field can be
autosized. If autosized, a Plant Sizing object must be defined
and the fan power is calculated as follows:
Field:
Fan Power Ratio Function of Air Flow Rate Ratio Curve
Name[LINK]
This alpha field contains the curve object name for fan
power ratio (fan power/design fan power) as a function of air
flow rate ratio (air flow rate/design air flow rate) [ref.
Performance Curves]. The curve object must be a cubic curve
and should be normalized to 1.0 at an air flow rate ratio of
1.0. If this field is left blank, a theoretical fan curve is
assumed where fan power ratio is directly proportional to the
air flow rate ratio cubed.
This numeric field contains the minimum air flow rate
ratio. The tower fan is allowed to operate between the ratio
defined here and a maximum air flow rate ratio of 1.0 (which
corresponds to the design [maximum] tower air flow rate).
Below this value, the tower is assumed to operate either in
the “free convection” regime with the tower fan off, or the
tower fan is cycled on/off to maintain the exiting water set
point temperature. The minimum air flow rate ratio must be
greater than or equal to 0.2 and less than or equal to 0.5,
with a default value of 0.2 if the field is left blank.
Field:
Fraction of Tower Capacity in Free Convection Regime[LINK]
This numeric field contains the fraction of tower capacity
available in the free convection regime (i.e., when the tower
fan is off but water continues to flow through the tower). The
tower fan does not operate when the free convection tower
capacity is able to meet or exceed the exiting water set point
temperature. The air flow rate through the tower in the free
convection regime is assumed to be this same fraction of the
tower design air flow rate. The fraction of tower capacity in
free convection regime must be greater than or equal to 0 and
less than or equal to 0.2, with a default value of 0.125 if
this field is left blank.
This numeric field contains the capacity of the tower’s
electric basin heater in watts per degree Kelvin. This field
is used in conjunction with the Basin Heater Setpoint
Temperature described in the following field. The basin heater
electric power is equal to this field multiplied by the
difference between the basin heater set point temperature and
the outdoor dry-bulb temperature. The basin heater only
operates when the tower fan is off and water is not flowing
through the tower, regardless of the basin heater schedule
described below. The basin heater capacity must be greater
than or equal to zero, with a default value of zero if this
field is left blank.
This numeric field contains the set point temperature (˚C)
for the basin heater described in the previous field. The
basin heater is active when the outdoor air dry-bulb
temperature falls below this setpoint temperature, as long as
the tower fan is off and water is not flowing through the
tower. This set point temperature must be greater than or
equal to 2˚C, and the default value is 2˚C if this field is
left blank.
This alpha field contains the name of the basin heater
operating schedule. The basin heater operating schedule is
assumed to be an on/off schedule and the heater is available
to operate any time the schedule value is greater than 0. The
basin heater operates when scheduled on and the outdoor air
dry-bulb temperature is below the set point temperature
described in the previous field. If this field is left blank,
the basin heater is available to operate throughout the
simulation. Regardless of this schedule, the basin heater may
only operate when the cooling tower fan is off and water is
not flowing through the tower.
This field is used to choose which method is used to model
the amount of water evaporated by the cooling tower. There are
two options: LossFactor or
SaturatedExit. The default is SaturatedExit.
The user-defined loss factor is entered in the following
field. By assuming that the air leaving the tower is
saturated, the evaporation can be directly calculated using
moist air engineering calculations with data available within
the cooling tower model (and does not require additional user
input).
This field is used to specify the rate of water evaporated
from the cooling tower and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The evaporation loss is
then calculated as a fraction of the circulating condenser
water flow and varies with the temperature change in the
condenser water. The value entered here is in units of
percent-per-degree Kelvin. The evaporation rate will equal
this value times each degree Kelvin of temperature drop in the
condenser water. Typical values are from 0.15 to 0.27
[percent/K]. The default is 0.2.
This numeric field contains the percent (%) of design water
flow rate lost to the atmosphere at the design air flow rate
due to drift, which is water droplets that are entrained in
the airstream as it passes through the tower. Drift is assumed
to vary directly with tower air flow rate ratio, and is in
addition to the amount of water lost to the atmosphere due to
evaporation and/or blowdown. Typical values for water usage
due to drift are from 0.05 to 0.2% of the total water
circulation rate with currently-available drift eliminators
from tower manufacturers. The value entered in this field must
be greater than or equal to zero, and the default value is
0.008%.
This field specifies which method is used to determine
blowdown rates. There two options ‘ConcentrationRatio’ or
‘ScheduledRate’. The choice will determine which of the two
models below is used. The default is ConcentrationRatio.
This field is used to dynamically adjust the rate of
blowdown in the cooling tower as a function of the rate of
evaporation. Blowdown is water intentionally drained from the
tower in order to offset the build up of solids in the water
that would otherwise occur because of evaporation. The value
entered here is dimensionless. It can be characterized as the
ratio of solids in the blowdown water to solids in the make up
water. Typical values for tower operation are 3 to 5. The
default value is 3.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m\(^{3}\)/s) flushed from the basin
on a periodic basis to purge the condenser loop of mineral
scale build-up and other contaminants. The amount of water use
due to blowdown depends on the makeup water quality and is
specific to each geographical location. Typical values range
from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is
in addition to the amount of water lost to the atmosphere due
to evaporation and/or drift. Since blowdown occurs when the
basin water contaminant concentration is high, blowdown only
occurs when the cooling tower is active and water is flowing
through the tower (regardless of the water usage defined by
this schedule).
This field is optional. It is used to describe where the
tower obtains water used for evaporative cooling. If blank or
omitted, then the tower will obtain water directly from the
mains. If the name of a WaterUser:Storage object is used here,
then the tower will obtain its water from that tank. If a tank
is specified, the tower will attempt to obtain all the water
it uses from the tank. However if the tank cannot provide all
the water the tower needs, then the tower will still operate
and obtain the rest of the water it needs from the mains
(referred to as ‘Starved’ water).
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
cooling tower. If this field is left blank, the outdoor air
conditions entering the cooling tower are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
This integer field contains the number of cells in the
multi-cell cooling tower. If not entered, the program will
assume it is a single-cell cooling tower
This alpha field specifies the method used to control the
number of cells used to meet the load, the two choices
are:
MinimalCell: the program will use minimal
number of cells needed, all other cells will be shut down with
no water flow. It will attempt to use as few cells as possible
to cool the fluid. In no case, however, will the flow per cell
be allowed to exceed its maximum value defined by the
Maximum Water Flow Rate Fraction.
MaximalCel : As many cells as possible
will be turned on. In no case, however, will the flow per cell
be allowed to drop below its minimum value specified by the
Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is
MaximalCell.
Field:
Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest
fraction of the design water flow rate. Flows less than this
value will commonly result in fluid distribution problems; the
pressure at each nozzle will be too weak for the fluid to be
sprayed out in the correct pattern, not all the fill would be
wet. If this field is left blank, the default value is
0.33.
Field:
Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction
of the design water flow rate. If this field is left blank,
the default value is 2.5.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature.For this component
the inputs that would be altered by the sizing factor are:
This optional field allows you to specify a user-defined
end-use subcategory, e.g., “Process”. A new meter for
reporting is created for each unique subcategory (ref: Output:Meter
objects). Any text may be used here to further subcategorize
the end-uses in the ABUPS End Uses by Subcategory table and in
the LEED Summary EAp2-4/5 Performance Rating Method Compliance
table. If this field is omitted or blank, the cooling tower
will be assigned to the “General” end-use subcategory.
An example IDF specification for this object is shown
below:
CoolingTower:VariableSpeed,
Big Tower1, !- Tower Name
Condenser 1 Inlet Node, !- Water Inlet Node Name
Condenser 1 Outlet Node, !- Water Outlet Node Name
YorkCalc, !- Tower Model Type
, !- Tower Model Coefficient Name
25.5556, !- Design Inlet Air Wet-Bulb Temperature {C}
3.8889, !- Design Approach Temperature {C}
5.5556, !- Design Range Temperature {C}
0.0015, !- Design Water Flow Rate {m3/s}
1.6435, !- Design Air Flow Rate {m3/s}
275, !- Design Fan Power {W}
FanRatioCurve, !- Fan Power Ratio - function of Air Flow Rate Curve Name
0.2, !- Minimum Air Flow Rate Ratio
0.125, !- Fraction of Tower Capacity in Free Convection Regime
450.0, !- Basin Heater Capacity {W/K}
4.5, !- Basin Heater Set Point Temperature {C}
BasinSchedule, !- Basin Heater Operating Schedule Name
SaturatedExit, !- Evaporation Loss Mode
, !- Evaporation Loss Factor
0.05, !- Makeup Water Usage due to Drift {percent}
ScheduledRate, !- Blowdown Calculation Mode
BlowDownSchedule, !- Schedule Name for Makeup Water Usage due to Blowdown
, !- Name of Water Storage Tank for Supply
, !- Outdoor Air Inlet Node Name
4, !- Number of Cells
MinimalCell, !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.000; !- Sizing Factor
These outputs are the electric power input to the tower
fan. Consumption is metered on HeatRejection:Electricity,
Electricity:Plant, and Electricity:Facility.
This is the on/off cycling rate of the tower fan when free
convection cannot meet the set point temperature and the tower
capacity at the minimum air flow rate ratio drives the tower
exiting water temperature below the set point temperature. The
fan part-load ratio is calculated as the ratio of the exiting
water temperature in the free convection regime minus the
exiting water temperature set point divided by the exiting
water temperature in the free convection regime minus the
exiting water temperature at the minimum air flow rate ratio.
If tower air flow is at or above the minimum air flow rate
ratio, then the tower fan part-load ratio is 1.0.
This is the ratio of air flow through the tower to the
design air flow rate. During times when the tower can maintain
the condenser loop set point temperature using free convection
(when the fan in not operating), the air flow rate ratio is
assumed to be equal to the field Fraction of Tower Capacity in
Free Convection Regime. During times when the fan cycles
on/off to maintain the outlet water set point temperature, the
air flow rate ratio is calculated as the summation of Fan
Part-Load Ratio multiplied by the Minimum Air Flow Rate Ratio
and (1.0 - Fan Part-Load Ratio) multiplied by the fraction of
Tower Capacity in Free Convection Regime.
Cooling
Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower
basin heater. Consumption is metered on
HeatRejection:Electricity, Electricity:Plant, and
Electricity:Facility.
Cooling
Tower Make Up Water Volume Flow Rate [m3/s][LINK]
These outputs are the water consumed by the wet cooling
tower for external water sprays used to augment heat transfer.
This is the total of evaporation, drift, and blowdown.
Cooling
Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
These outputs provide the breakdown of the different
components of water use during cooling tower operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to
feed the cooling tower. If a water storage tank is used to
provide water to the tower, then the following output
variables will also be available.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank
connections was not able to provide. The starved water is
assumed to come from the mains. The tower’s operation is not
affected by a lack of storage tank water.
Variable speed cooling towers can be modeled by EnergyPlus
with user-selectable performance based on the CoolTools
correlation, YorkCalc correlation, or user-defined
coefficients for either the CoolTools or YorkCalc
correlations.The empirical CoolTools tower correlation uses a
set of 35 coefficients to model the thermal performance
(approach temperature) of a cooling tower based on four
independent variables. If the user specifies Model Type =
CoolToolsCrossFlow in the CoolingTower:VariableSpeed
object, then the 35 coefficients derived for the CoolTools
simulation model are used and these coefficients are already
defined within EnergyPlus. If the user specifies Model Type =
CoolToolsUserDefined, then the user must enter a CoolingTowerPerformance:CoolTools
object to define the 35 coefficients that will be used by the
CoolTools correlation.
The user must specify a name for the model coefficient
object, and this name must be used in the CoolingTower:VariableSpeed
object (field Model Coefficient Name) to tell the program to
use these coefficients. Next, the user enters the minimum and
maximum values for inlet air wet-bulb temperature, range
temperature, approach temperature, and water mass flow rate
ratio to specify the valid range for which the model
coefficients were derived. For all of these variables, the
program issues warnings if the actual values are beyond the
minimum/maximum values specified. For inlet air wet-bulb
temperature and water mass flow rate ratio, the values of
these variables used in the calculation of approach
temperature are limited to be within the valid minimum/maximum
range specified. For approach and range, the warnings are
issued if the values are beyond the specified minimum/maximum
range but the actual values are still used.
The CoolTools correlation has four independent variables:
inlet air wet-bulb temperature (Twb), tower range temperature
(Tr), water flow rate ratio (FRwater), and air flow rate ratio
(FRair). Temperatures are in units of ˚C and flow rate ratios
are dimensionless (actual flow rate divided by design flow
rate). Using these independent variables, tower approach
temperature (˚C) is calculated as follows:
This object allows the user to specify model coefficients
for use with the CoolTools correlation shown above. It is
recommended that a broad set of cooling tower performance data
be used to generate these model coefficients. The data set
used to create the model coefficients should cover the entire
range of water and air flow rate ratios and inlet air
wet-bulb, range, and approach temperatures expected during the
simulation.
This alpha field contains the identifying name for the
variable speed cooling tower model coefficients.
Field:
Minimum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the minimum inlet air wet-bulb
temperature to be used by the model (approach temperature
correlation). Inlet air wet-bulb temperatures less than this
value will not be used; instead, the minimum inlet air
wet-bulb temperature specified here will be used by the
correlation and a warning will be issued.
Field:
Maximum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the maximum inlet air wet-bulb
temperature to be used by the model (approach temperature
correlation). Inlet air wet-bulb temperatures greater than
this value will not be used; instead, the maximum inlet air
wet-bulb temperature specified here will be used by the
correlation and a warning will be issued.
This numeric field contains the minimum range temperature
(inlet water temperature minus outlet water temperature) to be
used by the empirical model. If the range temperature is less
than this value the actual range temperature is still passed
to the empirical model but a warning will be issued.
This numeric field contains the maximum range temperature
(inlet water temperature minus outlet water temperature) to be
used by the empirical model. If the range temperature is
greater than this value the actual range temperature is still
passed to the empirical model but a warning will be
issued.
This numeric field contains the minimum approach
temperature (outlet water temperature minus inlet air wet-bulb
temperature) to be used by the empirical model. If the
calculated approach temperature is less than this value then
the calculated value is still used but a warning will be
issued.
This numeric field contains the maximum approach
temperature (outlet water temperature minus inlet air wet-bulb
temperature) to be used by the empirical model. If the
calculated approach temperature is greater than this value
then the calculated value is still used but a warning will be
issued.
This numeric field contains the minimum water flow rate
ratio (ratio of actual water flow rate to rated water flow
rate) to be used by the empirical model. Water flow rate
ratios less than this value will not be used; instead, the
minimum water flow rate ratio specified here will be used by
the model and a warning will be issued.
This numeric field contains the maximum water flow rate
ratio (ratio of actual water flow rate to rated water flow
rate) to be used by the empirical model. Water flow rate
ratios greater than this value will not be used; instead, the
maximum water flow rate ratio specified here will be used by
the model and a warning will be issued.
Variable speed cooling towers can be modeled by EnergyPlus
with user-selectable performance based on the CoolTools
correlation, YorkCalc correlation, or user-defined
coefficients for either the CoolTools or YorkCalc
correlations.The empirical YorkCalc tower correlation uses a
set of 27 coefficients to model the thermal performance
(approach temperature) of a variable speed cooling tower based
on three independent variables. If the user specifies Tower
Model Type = YorkCalc in the CoolingTower:VariableSpeed
object, then the 27 coefficients derived for the YorkCalc
simulation model are used and these coefficients are already
defined within EnergyPlus. If the user specifies Tower Model
Type = YorkCalcUserDefined, then the user must enter a CoolingTowerPerformance:YorkCalc
object to define the 27 coefficients that will be used by the
YorkCalc correlation.
The user must specify a name for the model coefficient
object, and this name must be used in the CoolingTower:VariableSpeed
object (field Model Coefficient Name) to tell the program to
use these coefficients. Next, the user enters the minimum and
maximum values for inlet air wet-bulb temperature, range
temperature, approach temperature, and water mass flow rate
ratio to specify the valid range for which the model
coefficients were derived. The user also specifies the maximum
valid liquid-to-gas ratio. For all of these variables, the
program issues warnings if the actual values are beyond the
minimum/maximum values specified. For inlet air wet-bulb
temperature and water mass flow rate ratio, the values of
these variables used in the calculation of approach
temperature are limited to be within the valid minimum/maximum
range specified. For approach, range, and liquid-to-gas ratio
the warnings are issued if the values are beyond the specified
minimum/maximum range but the actual values are still
used.
The YorkCalc correlation has three independent variables:
inlet air wet-bulb temperature (Twb), tower range temperature
(Tr), and the liquid-to-gas ratio (ratio of water flow rate
ratio to air flow rate ratio = LGRatio). Temperatures are in
units of ˚C and liquid-to-gas ratio is dimensionless. Using
these independent variables, an approach temperature (˚C) is
calculated as follows:
This object allows the user to specify model coefficients
for use with the YorkCalc correlation shown above. It is
recommended that a broad set of cooling tower performance data
be used to generate these model coefficients. The data set
used to create the model coefficients should cover the entire
range of water and air flow rate ratios and inlet air
wet-bulb, range, and approach temperatures expected during the
simulation.
This alpha field contains the identifying name for the
variable speed cooling tower model coefficients.
Field:
Minimum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the minimum inlet air wet-bulb
temperature to be used by the model (approach temperature
correlation). Inlet air wet-bulb temperatures less than this
value will not be used; instead, the minimum inlet air
wet-bulb temperature specified here will be used by the
correlation and a warning will be issued.
Field:
Maximum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the maximum inlet air wet-bulb
temperature to be used by the model (approach temperature
correlation). Inlet air wet-bulb temperatures greater than
this value will not be used; instead, the maximum inlet air
wet-bulb temperature specified here will be used by the model
and a warning will be issued.
This numeric field contains the minimum range temperature
(inlet water temperature minus outlet water temperature) to be
used by the empirical model. If the range temperature is less
than this value the actual range temperature is still passed
to the empirical model but a warning will be issued.
This numeric field contains the maximum range temperature
(inlet water temperature minus outlet water temperature) to be
used by the empirical model. If the range temperature is
greater than this value the actual range temperature is still
passed to the empirical model but a warning will be
issued.
This numeric field contains the minimum approach
temperature (outlet water temperature minus inlet air wet-bulb
temperature) to be used by the empirical model. If the
calculated approach temperature is less than this value then
the calculated value is still used but a warning will be
issued.
This numeric field contains the maximum approach
temperature (outlet water temperature minus inlet air wet-bulb
temperature) to be used by the empirical model. If the
calculated approach temperature is greater than this value
then the calculated value is still used but a warning will be
issued.
This numeric field contains the minimum water flow rate
ratio (ratio of actual water flow rate to rated water flow
rate) to be used by the empirical model. Water flow rate
ratios less than this value will not be used; instead, the
minimum water flow rate ratio specified here will be used by
the model and a warning will be issued.
This numeric field contains the maximum water flow rate
ratio (ratio of actual water flow rate to rated water flow
rate) to be used by the empirical model. Water flow rate
ratios greater than this value will not be used; instead, the
maximum water flow rate ratio specified here will be used by
the model and a warning will be issued.
This numeric field contains the maximum liquid-to-gas ratio
(ratio of actual water flow rate ratio [capped to be within
the minimum/maximum water flow rate ratio defined above as
necessary] to actual air flow rate ratio) to be used by the
empirical model. If the liquid-to-gas ratio is greater than
this value the actual liquid to gas ratio is still passed to
the empirical model but a warning will be issued.
Evaporative fluid coolers are components that may be
assigned to condenser loops. The Evaporative fluid cooler is
modeled as a counter flow heat exchanger with single-speed
fans (induced draft configuration). The user must define fluid
cooler performance via one of three methods: design heat
transfer coefficient-area product (UA) and design water flow
rate, or standard fluid cooler design capacity at a specific
rating point or design capacity at non standard conditions.
Regardless of which method is chosen, the design airflow rate
and corresponding fan power must be specified.
The evaporative fluid cooler seeks to maintain the
temperature of the water exiting the evaporative fluid cooler
at (or below) a set point. The set point schedule value is
defined by the field “Condenser Loop Temperature Setpoint Node
Name or Reference” for the CondenserLoop
object. The model first checks to see whether inlet water
temperature is at or below the set point. If so, then the
fluid cooler fan is not turned on and all the flow goes
through bypass. If the inlet water temperature is above the
set point then the fluid cooler fan is turned on to reduce the
exiting water temperature to the set point. If the capacity
control is FanCycling, the model assumes that part-load
operation is represented by a simple linear interpolation
between two steady-state regimes (i.e., fluid cooler fan on
for the entire simulation timestep and fluid cooler fan off
for the entire simulation timestep). Cyclic losses are not
taken into account. If the capacity control is FluidBypass,
the model determines the fraction of water flow to be bypassed
while the remaining water goes through the fluid cooler
cooling media and gets cooled, then the two water flows mix to
meet the setpoint temperature. In this case, the fan runs at
full speed for the entire timestep.
Evaporative fluid coolers consume water through
evaporation, drift, and blowdown. The model can be used to
predict water consumed by the fluid coolers. For this purpose,
the last seven input fields can either be provided in the
input or if nothing is specified then the default values for
these fields will be used. These fields provide the methods of
controlling details of the water consumption calculations. The
user can specify connections to the rest of the building’s
water system by providing the name of a water storage tanks
(i.e. WaterUse:Storage objects). The schematic of the system
is shown below:
Schematic diagram for
evaporative fluid cooler [fig:schematic-diagram-for-evaporative-fluid]
This numeric field contains the design air flow rate
induced by the fluid cooler fan in m\(^{3}\)/s. The field must contain
a value greater than zero regardless of the fluid cooler
performance input method. Alternately, this field can be
autosized. See Engineering Reference document for autosizing
calculations.
This numeric field contains the fan power (in watts) at the
design air flow rate specified in the previous field. The
field must contain a value greater than zero regardless of the
fluid cooler performance input method. Alternately, this field
can be autosized. See Engineering Reference document for
autosizing calculations.
This numeric field contains the design spray water flow
rate through the fluid cooler in m\(^{3}\)/s. A value greater than
zero must be specified regardless of the performance input
method,
This alpha field contains the method by which the user will
specify fluid cooler performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“StandardDesignCapacity” or “UserSpecifiedDesignCapacity”.
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
fluid cooler. If this field is left blank, the outdoor air
conditions entering the fluid cooler are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
Field:
Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of
actual tower heat rejection to nominal capacity. This ratio
is defined at entering water at 35C (95F), leaving water at
29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F)
drybulb temperatures. Historically this ratio has been set at
1.25 based on the assumption that the tower must dissipate
0.25 W of compressor power for every what of heat removed at
the chiller evaporator. The default is 1.25.
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts, with entering water at
35C (95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The design
water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal
capacity (3 gpm/ton). 125% of this capacity gives the actual
fluid cooler heat rejection at these operating conditions
(based on historical assumption that the evaporative fluid
cooler must dissipate 0.25W of compressor heat for every watt
of heat removed by the evaporator). This field is only used
for performance input method = “StandardDesignCapacity”. For
other input methods this field is ignored. The standard
conditions mentioned above for “standard design capacity” are
already specified in the EnergyPlus. So the input fields such
as design entering water temp., design entering air wet-bulb
and dry-bulb temp. and design water flow rate, if provided in
the input, will be ignored for the StandardDesignCapacity
performance input method. Also, the standard conditions are
for water as a fluid type so this performance input method can
only be used with water as a fluid type (ref. CondenserLoop
object).
Field:
Design Air Flow Rate U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the design air and water flow rates specified
above. If the input field “Performance Input Method” is
specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a
UA value greater than zero but less than or equal to 300,000
must be defined, or the field can be autosized. If autosized,
a Plant Sizing object must be defined and the design fluid
cooler UA value is derived from the design load to be rejected
by the condenser loop and the design loop delta T (Ref. Sizing
and Input for Design Calculations and Component Autosizing
sections), the fluid cooler inlet air dry-bulb and wetbulb
temperature are taken from the input. This field is only used
for performance input method = ”
UFactorTimesAreaAndDesignWaterFlowRate”. For other performance
input methods, this field is ignored.
This numeric field contains the design water flow rate
through the fluid cooler in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the fluid
cooler. This field is ignored for the “StandardDesignCapacity”
performance input method. If autosized, a Plant Sizing object
must be defined and the design water flow rate is derived from
the design load to be rejected by the condenser loop and the
design loop delta T (Ref. Sizing and Input for Design
Calculations and Component Autosizing sections).
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts. Design conditions for
this capacity i.e. entering air dry-bulb temperature, entering
air wet-bulb temperature and entering water temperature must
be provided in the input. Only used for Performance Input
Method = UserSpecifiedDesignCapacity; for other performance
input methods this field is ignored.
This numeric field contains entering water temperature at
nominal conditions in degrees Celsius. The design entering
water temperature must be greater than the design entering air
temperature. Only used for Performance Input Method =
UserSpecifiedDesignCapacity; for other performance input
methods this field is ignored. This field is autosizable and
defaults to autosize (which means it will take the value from
the corresponding Sizing:Plant
object).
This numeric field contains entering air dry-bulb
temperature at nominal conditions in degrees Celsius. The
design entering air temperature must be greater than the
design entering air wet-bulb temperature. Only used for
Performance Input Method = UserSpecifiedDesignCapacity; for
other performance input methods this field is ignored. This
field defaults to 35.0C.
Field:Design
Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb
temperature at nominal conditions in degrees Celsius. The
design entering air wet-bulb temperature must be less than the
design entering air (dry-bulb) temperature. Only used for
Performance Input Method = UserSpecifiedDesignCapacity; for
other performance input methods this field is ignored. This
field defaults to 25.6C.
This alpha field contains the cooling capacity control for
the evaporative fluid cooler. Two choices are available:
FanCycling and FluidBypass. During part-load conditions, there
are two ways to maintain the exiting water temperature at the
setpoint: either cycling the evaporative fluid cooler fan, or
bypassing portion of the evaporative fluid cooler water with a
three-way valve. For FluidBypass, the evaporative fluid cooler
fan still runs at full speed for the entire timestep, but only
portion of the water flow goes through the evaporative fluid
cooler media to get cooled while the remaining portion of the
water flow gets bypassed. Two water flows then mix at the
common water sump to meet the setpoint temperature.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature. For this component
the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Design Air Flow Rate;
3. Fan Power at Design Air Flow Rate;
4. U-Factor Times Area Value at Design Air Flow Rate;
Note that the U-Factor Times Area Value at Design Air Flow
Rate is not multiplied by the Sizing Factor. Instead the
design evaporative fluid cooler load is multiplied by the
sizing factor and the design UA then calculated as usual.
This field is used to choose which method is used to model
the amount of water evaporated by the evaporative fluid
cooler. There are two options: LossFactor or SaturatedExit.
The default is SaturatedExit. The user-defined loss factor is
entered in the following field. By assuming that the air
leaving the evaporative fluid cooler is saturated, the
evaporation can be directly calculated using moist air
engineering calculations with data available within the
evaporative fluid cooler model (and does not require
additional user input).
This field is used to specify the rate of water evaporated
from the evaporative fluid cooler and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The evaporation loss is
then calculated as a fraction of the circulating condenser
water flow and varies with the temperature change in the
condenser water. The value entered here is in units of
percent-per-kelvin. The evaporation rate will equal this value
times each degree Kelvin of temperature drop in the condenser
water. Empirical correlation is used to calculate default loss
factor if it not explicitly specified in the input file.
This field is used to specify the rate of water lost to the
exiting air as entrained droplets [%]. The drift loss is a
percent of the condenser water flow. Default value is under
investigation for now cooling tower’s evaporation loss factor
is taken as default value.
This field specifies which method is used to determine
blowdown rates. There two options ConcentrationRatio or
ScheduledRate. The choice will determine which of the two
models below is used. The default is ConcentrationRatio.
This field is used to dynamically adjust the rate of
blowdown in the evaporative fluid cooler as a function of the
rate of evaporation. Blowdown is water intentionally drained
from the evaporative fluid cooler in order to offset the build
up of solids in the water that would otherwise occur because
of evaporation. The value entered here is dimensionless. It
can be characterized as the ratio of solids in the blowdown
water to solids in the make up water. Default value is under
investigation for now cooling tower’s evaporation loss factor
is taken as default value.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m3/s) flushed from the basin on a
periodic basis to purge the evaporative fluid cooler of
mineral scale build-up and other contaminants. This schedule
is only used if the Blowdown Calculation Mode is set to
ScheduledRate. The amount of water use due to blowdown depends
on the makeup water quality and is specific to each
geographical location. Default value is under investigation
for now cooling tower’s evaporation loss factor is taken as
default value.This water usage is in addition to the amount of
water lost to the atmosphere due to evaporation and/or drift.
Since blowdown occurs when the basin water contaminant
concentration is high, blowdown only occurs when the
evaporative fluid cooler is active and water is flowing
through the evaporative fluid cooler (regardless of the water
usage defined by this schedule).
This field is optional. It is used to describe where the
evaporative fluid cooler obtains water used for evaporative
cooling. If blank or omitted, then the evaporative fluid
cooler will obtain water directly from the mains. If the name
of a WaterUse:Storage
object is used here, then the evaporative fluid cooler will
obtain its water from that tank. If a tank is specified, the
evaporative fluid cooler will attempt to obtain all the water
it uses from the tank. However if the tank cannot provide all
the water the evaporative fluid cooler needs, then the
evaporative fluid cooler will still operate and obtain the
rest of the water it needs from the mains (referred to as
‘Starved’ water).
An IDF specification for this object is shown below:
EvaporativeFluidCooler:SingleSpeed,
Big EvaporativeFluidCooler, !- Name
Condenser EvaporativeFluidcooler Inlet Node, !- Water Inlet Node Name
Condenser EvaporativeFluidcooler Outlet Node, !- Water Outlet Node Name
3.02, !- Design Air Flow Rate {m3/s}
2250, !- Design Air Flow Rate Fan Power {W}
0.002208, !- Design Spray Water Flow Rate {m3/s}
UserSpecifiedDesignCapacity,!- Performance Input Method
, !- Outdoor Air Inlet Node Name
1.25, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
, !- Standard Design Capacity {W}
, !- Design Air Flow Rate U-factor Times Area Value {W/K}
0.001703, !- Design Water Flow Rate {m3/s}
87921, !- User Specified Design Capacity {W}
46.11, !- Design Entering Water Temperature {C}
35, !- Design Entering Air Temperature {C}
25.6; !- Design Entering Air Wet-bulb Temperature {C}
These outputs provide the breakdown of the different
components of water use during fluid cooler operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
The volume of make up water provided by the mains in cubic
meters. If no Supply Water Storage Tank is specified, then all
fluid cooler make up water is provided by the mains (same as
Cooling Tower Make Up Water Volume). If a Supply Water Storage
Tank is specified, then the make up from the mains only occurs
when sufficient water supply is not available from the tank
(same as Evaporative Fluid Cooler Water Starved by Storage
Tank). This output variable is metered on
HeatRejection:MainsWater, MainsWater:Plant and
MainsWater:Facility.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Supply Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Supply Water
Storage Tank was not able to provide. The starved water is
assumed to come from the mains. The fluid cooler’s operation
is not affected by a lack of storage tank water.
The two-speed evaporative fluid cooler is modeled in a
similar fashion to the single-speed evaporative fluid cooler.
The evaporative fluid cooler is modeled as a counter flow heat
exchanger with two-speed fan (induced draft configuration. See
schematic diagram in Evaporative[FluidCooler:SingleSpeed](../input-output-reference/group-condenser-equipment.html#fluidcoolersinglespeed)
section). The user must define fluid cooler performance via
one of the three methods: design heat transfer
coefficient-area product (UA) and design water flow rate, or
standard fluid cooler design capacity at a specific rating
point or design capacity at non standard conditions.
Regardless of which method is chosen, the design airflow rate
and corresponding fan power must be specified.
The evaporative fluid cooler seeks to maintain the
temperature of the water exiting the evaporative fluid cooler
at (or below) a set point. The set point schedule value is
defined by the field “Condenser Loop Temperature Setpoint Node
Name or Reference” for the CondenserLoop
object. The model first checks to see whether inlet water
temperature is at or below the set point. If so, then the
fluid cooler fan is not turned on and all the flow goes
through bypass. If the inlet water temperature is above the
set point then the fluid cooler fan is turned on at low speed
to reduce the exiting water temperature to the set point. If
operating the fluid cooler fan at low speed does not reduce
the exiting water temperature to the set point, then the fluid
cooler fan is increased to its high speed.
The model assumes that part-load operation is represented
by a simple linear interpolation between two steady-state
regimes (i.e., fluid cooler fan at high speed for the entire
simulation timestep and fluid cooler fan at low speed for the
entire simulation timestep, or fluid cooler fan at low speed
for the entire simulation timestep and fluid cooler fan off
for the entire simulation timestep). Cyclic losses are not
taken into account.
Evaporative fluid coolers consume water through
evaporation, drift, and blowdown. The model can be used to
predict water consumed by the evaporative fluid coolers. For
this purpose, the last seven input fields can either be
provided in the input or if nothing is specified then the
default values for these fields will be used. These fields
provide methods of controlling details of the water
consumption calculations. The user can specify connections to
the rest of the buildings water system by providing the name
of a water storage tanks (i.e. WaterUse:Storage objects).
This numeric field contains the fluid cooler air flow rate
at high fan speed in m\(^{3}\)/s. A value greater than
zero must be defined regardless of fluid cooler performance
input method. Alternately, this field can be autosized. See
Engineering Reference document for fluid cooler
autosizing.
This numeric field contains the fan power (in Watts) at the
high-speed air flow rate specified in the previous field. A
value greater than zero must be specified regardless of fluid
cooler performance input method, or this field can be
autosized. See Engineering Reference document for fluid cooler
autosizing.
This numeric field contains the fluid cooler air flow rate
at low fan speed in m\(^{3}\)/s. This value must be
greater than zero, less than the value specified for the field
“Air Flow Rate at High Fan Speed”. This field may be
autocalculated, in which case it is set to a fraction of the
“Air Flow Rate at High Fan Speed” determined in the following
field.
Field:
Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor for
calculating the low fan speed air flow rate as a fraction of
the high fan speed air flow rate. The default is 0.5.
This numeric field contains the fan power (in Watts) at the
low-speed air flow rate specified in the previous field. This
value must be specified greater than zero or the field may be
autocalculated, in which case it is set to a fraction of the
“Fan Power at High Fan Speed” determined in the following
field.
Field:
Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor for
calculating the low fan speed fan power as a fraction of the
high fan speed fan power. The default is 0.16.
This numeric field contains the design spray water flow
rate through the fluid cooler in m\(^{3}\)/s. This input field must
be specified for all the performance input methods.
This alpha field contains the method by which the user will
specify fluid cooler performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“StandardDesignCapacity” or “UserSpecifiedDesignCapacity”.
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
fluid cooler. If this field is left blank, the outdoor air
conditions entering the fluid cooler are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
Field:
Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of
actual tower heat rejection to nominal capacity. This ratio
is defined at entering water at 35C (95F), leaving water at
29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F)
drybulb temperatures. Historically this ratio has been set at
1.25 based on the assumption that the tower must dissipate
0.25 W of compressor power for every what of heat removed at
the chiller evaporator. The default is 1.25.
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts, with entering water at
35C (95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The design
water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal
capacity (3 gpm/ton). The Heat Rejection Capacity and Nominal
Capacity Sizing Ratio set in the previous field is applied to
this capacity to give the actual fluid cooler heat rejection
at these operating conditions. This field is only used for
performance input method = “StandardDesignCapacity”. For other
input methods this field is ignored. The standard conditions
mentioned above for “standard design capacity” are already
specified in the EnergyPlus. So the input fields such as
design entering water temp., design entering air wet-bulb and
dry-bulb temp. and design water flow rate, if provided in the
input, will be ignored for the StandardDesignCapacity
performance input method. Also, the standard conditions are
for water as a fluid type so this performance input method can
only be used with water as a fluid type (ref. CondenserLoop
object).
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts, with entering water at
35C (95F), leaving water at 29.4C (85F), entering air at 25.6C
(78F) wetbulb and 35C (95F) drybulb temperatures. The design
water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal
capacity (3 gpm/ton). The Heat Rejection Capacity and Nominal
Capacity Sizing Ratio is applied to this capacity to give the
actual fluid cooler heat rejection at these operating
conditions. This field is only used for performance input
method = “StandardDesignCapacity”. For other input methods
this field is ignored. The standard conditions mentioned above
for “standard design capacity” are already specified in the
EnergyPlus. So the input fields such as design entering water
temp., design entering air wet-bulb and dry-bulb temp. and
design water flow rate, if provided in the input, will be
ignored for the StandardDesignCapacity performance input
method. Also, the standard conditions are for water as a fluid
type so this performance input method can only be used with
water as a fluid type (ref. CondenserLoop
object). The value specified for this field must be greater
than zero but less than the value specified for the field
“High-Speed Standard Design Capacity”. This field may be
autocalculated, in which case it is set to a fraction of the
High-Speed Standard Design Capacity determined in the
following field.
Field:
Low Speed Standard Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the Low Speed Standard Design Capacity. The
default is 0.5.
Field:
High Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the high speed design air and water flow
rates specified above. If the input field “Performance Input
Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value
greater than zero but less than or equal to 2,100,000 must be
defined, or the field can be autosized. If autosized, a Plant
Sizing object must be defined and the design fluid cooler UA
value is derived from the design load to be rejected by the
condenser loop and the design loop delta T (Ref. Sizing and
Input for Design Calculations and Component Autosizing
sections), the fluid cooler inlet air dry-bulb and wetbulb
temperature are taken from the input. This field is only used
for performance input method = ”
UFactorTimesAreaAndDesignWaterFlowRate”. For other input
methods this field is ignored.
Field:
Low Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per degree Kelvin
corresponding to the low speed design air and water flow rates
specified above. If the input field “Performance Input Method”
is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then
a UA value greater than zero but less than or equal to 300,000
and less than the value specified for the field “U-Factor
Times Area Value at High Fan Speed” must be defined. This
field may be autocalculated, in which case it is set to a
factor of the “U-Factor Times Area Value at High Fan Speed”
determined in the following field. This field is only used for
performance input method = ”
UFactorTimesAreaAndDesignWaterFlowRate”. For other input
methods this field is ignored.
Field:
Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This field contains the sizing factor to use when
calculating the Low Fan Speed U-Factor Times Area Value. The
default is 0.6.
This numeric field contains the design water flow rate
through the fluid cooler in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the fluid
cooler. This field is ignored for the “StandardDesignCapacity”
performance input method. If autosized, a Plant Sizing object
must be defined and the design water flow rate is derived from
the design load to be rejected by the condenser loop and the
design loop delta T (Ref. Sizing and Input for Design
Calculations and Component Autosizing sections).
Field:
High Speed User Specified Design Capacity[LINK]
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts. Design conditions for
this capacity i.e. entering air dry-bulb temperature, entering
air wet-bulb temperature and entering water temperature must
be provided in the input. Only used for Performance Input
Method = UserSpecifiedDesignCapacity; for other performance
input methods this field is ignored.
Field:
Low Speed User Specified Design Capacity[LINK]
This numeric input field contains the heat rejection
capacity of the fluid cooler in watts. Design conditions for
this capacity i.e. entering air dry-bulb temperature, entering
air wet-bulb temperature and entering water temperature must
be provided in the input. Only used for Performance Input
Method = UserSpecifiedDesignCapacity; for other performance
input methods this field is ignored. This field may be
autocalculated, in which case it is set to a fraction of the
“High Speed User Specified Design Capacity” determined in the
following field.
Field:
Low Speed User Specified Design Capacity Sizing Factor[LINK]
This field contains the sizing factor to use when
calculating the Low-Speed User Specified Design Capacity. The
default is 0.5.
This numeric field contains entering water temperature at
nominal conditions in degrees Celsius. The design entering
water temperature must be greater than the design entering air
temperature. Only used for Performance Input Method =
UserSpecifiedDesignCapacity; for other performance input
methods this field is ignored. This field is autosizable and
defaults to autosize (which means it will take the value from
the corresponding Sizing:Plant
object).
This numeric field contains entering air dry-bulb
temperature at nominal conditions in degrees Celsius. The
design entering air temperature must be greater than the
design entering air wet-bulb temperature. Only used for
Performance Input Method = UserSpecifiedDesignCapacity; for
other performance input methods this field is ignored. This
field defaults to 35.0C.
Field:Design
Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb
temperature at nominal conditions in degrees Celsius. The
design entering air wet-bulb temperature must be less than the
design entering air (dry-bulb) temperature. Only used for
Performance Input Method = UserSpecifiedDesignCapacity; for
other performance input methods this field is ignored. This
field defaults to 25.6C.
This optional numeric field allows the user to specify a
sizing factor for this component. The sizing factor is used
when the component design inputs are autosized: the autosizing
calculations are performed as usual and the results are
multiplied by the sizing factor. Sizing factor allows the user
to size a component to meet part of the design load while
continuing to use the autosizing feature. For this component
the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Air Flow Rate at High Fan Speed;
3. Fan Power at High Fan Speed;
4. U-Factor Times Area Value at High Fan Speed;
5. Air Flow Rate at Low Fan Speed;
6. Fan Power at Low Fan Speed;
7. U-Factor Times Area Value at Low Fan Speed;
Note that the U-Factor Times Area Value at High Fan Speed
is not multiplied by the Sizing Factor. Instead the design
evaporative fluid cooler load is multiplied by the sizing
factor and the design UA then calculated as usual. The
U-Factor Times Area Value at Low Fan Speed is set to Low Fan
Speed U-Factor Times Area Sizing Factor times the full load
design UA.
This field is used to choose which method is used to model
the amount of water evaporated by the evaporative fluid
cooler. There are two options: LossFactor or SaturatedExit.
The default is SaturatedExit. The user-defined loss factor is
entered in the following field. By assuming that the air
leaving the evaporative fluid cooler is saturated, the
evaporation can be directly calculated using moist air
engineering calculations with data available within the
evaporative fluid cooler model (and does not require
additional user input).
This field is used to specify the rate of water evaporated
from the evaporative fluid cooler and lost to the outside air
[percent/K]. This field is only used if the Evaporation
Calculation Mode is set to LossFactor. The evaporation loss is
then calculated as a fraction of the circulating condenser
water flow and varies with the temperature change in the
condenser water. The value entered here is in units of
percent-per-kelvin. The evaporation rate will equal this value
times each degree Kelvin of temperature drop in the condenser
water. Empirical correlation is used to calculate default loss
factor if it not explicitly specified in the input file.
This field is used to specify the rate of water lost to the
exiting air as entrained droplets [%]. The drift loss is a
percent of the condenser water flow. Default value is under
investigation for now cooling tower’s evaporation loss factor
is taken as default value.
This field specifies which method is used to determine
blowdown rates. There two options ConcentrationRatio or
ScheduledRate. The choice will determine which of the two
models below is used. The default is ConcentrationRatio.
This field is used to dynamically adjust the rate of
blowdown in the evaporative fluid cooler as a function of the
rate of evaporation. Blowdown is water intentionally drained
from the evaporative fluid cooler in order to offset the build
up of solids in the water that would otherwise occur because
of evaporation. The value entered here is dimensionless. It
can be characterized as the ratio of solids in the blowdown
water to solids in the make up water. Default value is under
investigation for now cooling tower’s evaporation loss factor
is taken as default value.
Field:
Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to
define the amount of water (m3/s) flushed from the basin on a
periodic basis to purge the evaporative fluid cooler of
mineral scale build-up and other contaminants. This schedule
is only used if the Blowdown Calculation Mode is set to
ScheduledRate. The amount of water use due to blowdown depends
on the makeup water quality and is specific to each
geographical location. Default value is under investigation
for now cooling tower’s evaporation loss factor is taken as
default value.This water usage is in addition to the amount of
water lost to the atmosphere due to evaporation and/or drift.
Since blowdown occurs when the basin water contaminant
concentration is high, blowdown only occurs when the
evaporative fluid cooler is active and water is flowing
through the evaporative fluid cooler (regardless of the water
usage defined by this schedule).
This field is optional. It is used to describe where the
evaporative fluid cooler obtains water used for evaporative
cooling. If blank or omitted, then the evaporative fluid
cooler will obtain water directly from the mains. If the name
of a WaterUse:Storage
object is used here, then the evaporative fluid cooler will
obtain its water from that tank. If a tank is specified, the
evaporative fluid cooler will attempt to obtain all the water
it uses from the tank. However if the tank cannot provide all
the water the evaporative fluid cooler needs, then the
evaporative fluid cooler will still operate and obtain the
rest of the water it needs from the mains (referred to as
‘Starved’ water).
Examples of an IDF specification for this object are shown
below:
EvaporativeFluidCooler:TwoSpeed,
Big EvaporativeFluidCooler, !- Name
Condenser EvaporativeFluidcooler Inlet Node, !- Water Inlet Node Name
Condenser EvaporativeFluidcooler Outlet Node, !- Water Outlet Node Name
9.911, !- High Fan Speed Air Flow Rate {m3/s}
autosize, !- High Fan Speed Fan Power {W}
4.911, !- Low Fan Speed Air Flow Rate {m3/s}
0.5, !- Low Fan Speed Air Flow Rate Sizing Factor
autosize, !- Low Fan Speed Fan Power {W}
0.16, !- Low Fan Speed Fan Power Sizing Factor
0.002208, !- Design Spray Water Flow Rate {m3/s}
UserSpecifiedDesignCapacity,!- Performance Input Method
, !- Outdoor Air Inlet Node Name
1.25, !- Heat Rejection Capacity and Nominal Capacity Sizing Ratio
, !- High Speed Standard Design Capacity {W}
, !- Low Speed Standard Design Capacity {W}
0.5, !- Low Speed Standard Capacity Sizing Factor
, !- High Fan Speed U-factor Times Area Value {W/K}
, !- Low Fan Speed U-factor Times Area Value {W/K}
0.6, !- Low Fan Speed U-Factor Times Area Sizing Factor
0.001703, !- Design Water Flow Rate {m3/s}
87921, !- High Speed User Specified Design Capacity {W}
47921, !- Low Speed User Specified Design Capacity {W}
0.5, !- Low Speed User Specified Design Capacity Sizing Factor
46.11, !- Design Entering Water Temperature {C}
35, !- Design Entering Air Temperature {C}
25.6; !- Design Entering Air Wet-bulb Temperature {C}
These outputs provide the breakdown of the different
components of water use during fluid cooler operation.
Cooling
Tower Make Up Mains Water Volume [m3][LINK]
The volume of make up water provided by the mains in cubic
meters. If no Supply Water Storage Tank is specified, then all
fluid cooler make up water is provided by the mains (same as
Cooling Tower Make Up Water Volume). If a Supply Water Storage
Tank is specified, then the make up from the mains only occurs
when sufficient water supply is not available from the tank
(same as Cooling Tower Starved Storage Tank Water Volume).
This output variable is metered on HeatRejection:MainsWater,
MainsWater:Plant and MainsWater:Facility.
Cooling
Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the
Supply Water Storage Tank.
Cooling
Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling
Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Supply Water
Storage Tank was not able to provide. The starved water is
assumed to come from the mains. The fluid cooler’s operation
is not affected by a lack of storage tank water.
Fluid coolers are components that may be assigned to
condenser loops. The Fluid cooler is modeled as a cross flow
heat exchanger (both streams unmixed) with single-speed fans
(induced draft configuration). The user must define fluid
cooler performance via one of the two methods: design heat
transfer coefficient-area product (UA) and design water flow
rate, or nominal fluid cooler capacity at a specific rating
point. Regardless of which method is chosen, the design
airflow rate and corresponding fan power must be
specified.
The fluid cooler seeks to maintain the temperature of the
water exiting the fluid cooler at (or below) a set point. The
set point schedule value is defined by the field “Condenser
Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop
object. The model assumes that part-load operation is
represented by a simple linear interpolation between two
steady-state regimes (i.e., fluid cooler fan on for the entire
simulation timestep and fluid cooler fan off for the entire
simulation timestep). Cyclic losses are not taken into
account.
This alpha field contains the method by which the user will
specify fluid cooler performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“NominalCapacity”.
Field:
Design Air Flow Rate U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the design air and water flow rates specified
above. If the input field “Performance Input Method” is
specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a
UA value greater than zero but less than or equal to 300,000
must be defined, or the field can be autosized. If autosized,
a Plant Sizing object must be defined and the design fluid
cooler UA value is derived from the design load to be rejected
by the condenser loop and the design loop delta T (Ref. Sizing
and Input for Design Calculations and Component Autosizing
sections), the fluid cooler inlet air dry-bulb and wetbulb
temperature are taken from the input. If “Performance Input
Method” is specified as “NominalCapacity”, then this field
must be left blank since the model automatically calculates
the fluid cooler UA based on the fluid cooler capacity and
nominal conditions specified in input file.
This numeric input field contains the “nominal” heat
rejection capacity of the fluid cooler in watts, Nominal
conditions i.e. entering air dry-bulb temperature, entering
air wet-bulb temperature and Entering water temperature should
be provided in the input.
This numeric field contains entering water temperature at
nominal conditions in degrees Celsius. This field must be
specified for both the performance input methods. The design
entering water temperature must be greater than the design
entering air temperature.
This numeric field contains entering air dry-bulb
temperature at nominal conditions in degrees Celsius. This
field must be specified for both the performance input
methods. The design entering air temperature must be greater
than the design entering air wet-bulb temperature.
Field:Design
Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb
temperature at nominal conditions in degrees Celsius. This
field must be specified for both the performance input
methods. The design entering air wet-bulb temperature must be
less than the design entering air (dry-bulb) temperature.
This numeric field contains the design water flow rate
through the fluid cooler in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the fluid
cooler. A water flow rate greater than zero must be defined or
the field can be autosized. If autosized, a Plant Sizing
object must be defined and the design water flow rate is
derived from the design load to be rejected by the condenser
loop and the design loop delta T (Ref. Sizing and Input for
Design Calculations and Component Autosizing sections).
This numeric field contains the design air flow rate
induced by the fluid cooler fan in m\(^{3}\)/s. A value greater than
zero must be defined regardless of the fluid cooler
performance input method. Alternately, this field can be
autosized. See Engineering Reference document for fluid cooler
autosizing.
This numeric field contains the fan power (in watts) at the
design air flow rate specified in the previous field. A value
greater than zero must be specified regardless of the
performance input method, or this field can be autosized. See
Engineering ref. for fluid cooler autosizing.
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
fluid cooler. If this field is left blank, the outdoor air
conditions entering the fluid cooler are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
An IDF specification for this object is shown below:
FluidCooler:SingleSpeed,
Big FLUIDCOOLER1, !- Name
Condenser FLUIDCOOLER 1 Inlet Node, !- Water Inlet Node Name
Condenser FLUIDCOOLER 1 Outlet Node, !- Water Outlet Node Name
NominalCapacity, !- Performance Input Method
, !- Design Air Flow Rate U-factor Times Area Value {W/K}
58601., !- Nominal Capacity {W}
51.67, !- Design Entering Water Temperature {C}
35, !- Design Entering Air Temperature {C}
25.6, !- Design Entering Air Wetbulb Temperature {C}
0.001388, !- Design Water Flow Rate{m3/s}
9.911, !- Design Air Flow Rate {m3/s}
Autosize; !- Design Air Flow Rate Fan Power {W}
The two-speed fluid cooler is modeled in a similar fashion
to the single-speed fluid cooler. The fluid cooler is modeled
as a cross flow heat exchanger (both stream unmixed) with
two-speed fans (induced draft configuration). The user must
define fluid cooler performance via one of two methods: heat
transfer coefficient-area product (UA) and design water flow
rate, or nominal fluid cooler capacity at a specific rating
point. Regardless of which method is chosen, the airflow rate
and corresponding fan power at both high and low fan speed
must be specified. The Fluid Cooler seeks to maintain the
temperature of the water exiting the Fluid Cooler at (or
below) a set point. The set point schedule is defined by the
field “Condenser Loop Temperature Setpoint Node Name or
Reference” for the CondenserLoop
object. The model first runs at low speed and calculates the
fluid cooler exiting water temperature. If the exiting water
temperature based on “low speed” is at or below the set point,
then the fluid cooler fan runs at this speed or below this
speed. If the exiting water temperature remains above the set
point after “low speed” is modeled, then the fluid cooler fan
runs at high speed to reduce the exiting water
temperature.
The model assumes that part-load operation is represented
by a simple linear interpolation between two steady-state
regimes (i.e., fluid cooler fan at high speed for the entire
simulation timestep and fluid cooler fan at low speed for the
entire simulation timestep,). Cyclic losses are not taken into
account.
This alpha field contains the method by which the user will
specify fluid cooler performance:
“UFactorTimesAreaAndDesignWaterFlowRate” or
“NominalCapacity”.
Field:
High Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per degree Celsius
corresponding to the high-speed air flow rate and design water
flow rate specified above. If the input field “Performance
Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value
greater than zero but less than or equal to 300,000 must be
defined, or the field can be autosized. If autosized, a Plant
Sizing object must be defined and the fluid cooler UA value at
high fan speed is derived from the design load to be rejected
by the condenser loop and the design loop delta T (Ref. Sizing
and Input for Design Calculations and Component Autosizing
sections), fluid cooler water inlet temperature, fluid cooler
inlet air drybulb and wetbulb are provided in the input. If
“Performance Input Method” is specified as “NominalCapacity”,
then this field must be left blank since the model
automatically calculates the fluid cooler UA based on the
capacity specified in the field “High Speed Nominal Capacity”
and nominal conditions.
Field:
Low Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer
coefficient-area product (UA) in watts per Kelvin
corresponding to the design water flow rate and low-speed air
flow rate specified above. If the input field “Performance
Input Method” is specified as
“UFactorTimesAreaAndDesignWaterFlowRate”, this value must be
greater than zero but less than or equal to 300,000, less than
the value specified for the field “U-factor Times Area Value
at High Fan Speed”. This field may be autocalculated, in which
case it is set to a factor of the “U-factor Times Area Value
at High Fan Speed” determined in the following field. If
“Performance Input Method” is specified as “NominalCapacity”,
then this field must be left blank since the model
automatically calculates the fluid cooler UA based on the
fluid cooler capacity specified in the field “Low Speed
Nominal Capacity”.
Field:
Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the Low Fan Speed U-factor Times Area Value. The
default is 0.6.
This numeric input field contains the “nominal” heat
rejection capacity of the fluid cooler in watts under
high-speed fan operation, with nominal (design) inputs
entering water temperature, entering air temperature and
entering air wet-bulb temperature. The design water flow rate
is also provided in the input.
This numeric input field contains the “nominal” heat
rejection capacity of the Fluid Cooler in watts under
low-speed fan operation, with nominal (design) inputs entering
water temperature, entering air temperature and entering air
wet-bulb temperature. The design water flow rate is also
provided in the input. The value specified for this field must
be greater than zero but less than the value specified for the
field “High Speed Nominal Capacity”. This field may be
autocalculated, in which case it is set to a fraction of the
“High Speed Nominal Capacity” determined in the following
field.
This numeric field contains entering water temperature at
nominal conditions in degrees Celsius. This field must be
specified for both the performance input methods. The design
entering water temperature must be greater than the design
entering air temperature.
This numeric field contains entering air dry-bulb
temperature at nominal conditions in degrees Celsius. This
field must be specified for both the performance input
methods. The design entering air temperature must be greater
than the design entering air wet-bulb temperature.
Field:Design
Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wet-bulb
temperature at nominal conditions in degrees Celsius. This
field must be specified for both the performance input
methods. The design entering air wet-bulb temperature must be
less than the design entering air (dry-bulb) temperature.
This numeric field contains the design water flow rate
through the fluid cooler in m\(^{3}\)/s. This value is the flow
rate of the condenser loop water being cooled by the fluid
cooler. A water flow rate greater than zero must be defined or
the field can be autosized. If autosized, a Plant Sizing
object must be defined and the design water flow rate is
derived from the design load to be rejected by the condenser
loop and the design loop delta T (Ref. Sizing and Input for
Design Calculations and Component Autosizing sections).
This numeric field contains the fluid cooler air flow rate
at high fan speed in m\(^{3}\)/s. A value greater than
zero must be defined regardless of the fluid cooler
performance input method. Alternately, this field can be
autosized. See Engineering ref. for fluid cooler
autosizing.
This numeric field contains the fan power (in Watts) at the
high-speed air flow rate specified in the previous field. A
value greater than zero must be specified regardless of the
fluid cooler performance input method, or this field can be
autosized. See Engineering ref. for fluid cooler
autosizing.
This numeric field contains the fluid cooler air flow rate
at low fan speed in m\(^{3}\)/s. This value must be
greater than zero, less than the value specified for the field
“Air Flow Rate at High Fan Speed”. This field may be
autocalculated, in which case it is set to a fraction of the
“Air Flow Rate at High Fan Speed” determined in the following
field.
Field:
Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the Low Fan Speed Air Flow Rate. The default is
0.5.
This numeric field contains the fan power (in Watts) at the
low-speed air flow rate specified in the previous field. This
value must be specified greater than zero or the field may be
autocalculated, in which case it is set to set to a fraction
of the “Fan Power at High Fan Speed” determined in the
following field.
Field:
Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor to use when
calculating the Low Fan Speed Fan Power. The default is
0.16.
This optional alpha field specifies the outdoor air node
name used to define the conditions of the air entering the
Fluid Cooler. If this field is left blank, the outdoor air
conditions entering the Fluid Cooler are taken directly from
the weather data. If this field is not blank, the node name
specified must also be specified in an OutdoorAir:Node
object where the height of the node is taken into
consideration when calculating outdoor air conditions from the
weather data. Alternately, the node name may be specified in
an OutdoorAir:NodeList
object where the outdoor air conditions are taken directly
from the weather data.
Examples of an IDF specification for this object are shown
below:
FluidCooler:TwoSpeed,
Big FLUIDCOOLER1, !- Name
Condenser FLUIDCOOLER 1 inlet Node, !- Water Inlet Node Name
Condenser FLUIDCOOLER 1 Outlet Node, !- Water Outlet Node Name
NominalCapacity, !- Performance Input Method
, !- High Fan Speed U-factor Times Area Value {W/K}
, !- Low Fan Speed U-factor Times Area Value {W/K}
, !- Low Fan Speed U-Factor Times Area Sizing Factor
58601., !- High Speed Nominal Capacity {W}
28601., !- Low Speed Nominal Capacity {W}
. 0.6, !- Low Speed Nominal Capacity Sizing Factor
51.67, !- Design Entering Water temperature {C}
35, !- Design Entering Air temperature {C}
25.6, !- Design Entering Air Wet-bulb temperature {C}
0.001388, !- Design Water Flow Rate {m3/s}
9.911, !- High Fan Speed Air Flow Rate {m3/s}
autosize, !- High Fan Speed Fan Power {W}
autosize, !- Low Fan Speed Air Flow Rate {m3/s}
0.5, !- Low Fan Speed Air Flow Rate Sizing Factor
autosize, !- Low Fan Speed Fan Power {W}
0.16; !- Low Fan Speed Fan Power Sizing Factor
The EnergyPlus ground loop heat exchanger is a condenser
component which serves the condenser supply side in addition
to the cooling towers and other condensing components. Figure
2
shows the Ground Heat Exchanger in the simulation
environment.
The heat exchanger response is defined by a g-function
which is a non-dimensional function that is used to calculate
the response to square heat pulses of different duration.
(This function is not the same as ‘G-factors’ referred to in
the ASHRAE Applications Handbook). This continuous function is
specified by a series of data pairs (LNTTSi,
GFNCi) where,
LNTTSi is the non-dimensional time:
ln(T/T\(_{s}\))
GFNCi is the g-function value
The g-function is different for each borehole field
configuration (i.e. a 4 \(\times\) 4 field has a different
response than a 80 \(\times\)
80 field). It is also dependent on the ratio of borehole
spacing to depth. g-function values, for accurate simulation,
have to be computed for each specific heat exchanger design.
The GroundHeatExchanger:System
object will accept four different types of input in order to
define the g-functions necessary for the ground heat exchanger
calculations.
A small number of reference datasets containing example
input data for 1 \(\times\)
2, 4 \(\times\) 4 and 8 \(\times\) 8 configurations and for
both standard and thermally enhanced grout are provided as
well.
Schematic of EnergyPlus Ground
Loop Heat Exchanger [fig:schematic-of-energyplus-ground-loop-heat]
Definitions for the input fields are provided below.
This numeric field contains the GHE design flow rate in
cubic meters per second {m\(^{3}\)/s}. The flow rate
specified is the total flow rate for the entire borehole
field. Flow will be assumed to be evenly distributed across
all boreholes.
Field:
Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to
determine ground temperature for the farfield boundary
conditions.
Field:
Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used
to determine ground temperature for the farfield boundary
conditions.
The unique name of the GroundHeatExchanger:ResponseFactors
object used to define the third-party response factors. If
present, the GHE:Vertical:Array and GHE:Vertical:Single
objects defined will be ignored.
If the GHE:ResponseFactors object is not provided, this
input will be relevant to the calculation method used to
generate the g-function values. There are three options for
this input:
“UHFcalc”
“UBHWTcalc”
“FullDesign”
The default is UHFcalc, where a g-function is computed with
the uniform heat flux boundary condition. The UBHWTcalc option
computes the g-function with a uniform borehole wall
temperature boundary condition. The g-function computed with a
uniform borehole wall temperature boundary condition is
expected to be a better approximation of the borehole physics
and is also expected to be faster to compute. The final option
of FullDesign allows a borehole field to be designed and sized
based on loads and design parameters. For a designed borehole
field, the input file should include a GHE:Vertical:Sizing
object matching the next field in this object, a full annual
weather file sizing period to allow a year of loads to be
generated, and finally hvac sizing enabled in the simulation
control object.
For borehole field design and sizing calculations, this
should be the type of an object specifying the borehole field
design parameters. Currently only GroundHeatExchanger:Vertical:Sizing:Rectangle
is supported.
For borehole field design and sizing calculations, this
should be the name of an object specifying the borehole field
design parameters. See the full documentation for GroundHeatExchanger:Vertical:Sizing:Rectangle.
The unique name of the GroundHeatExchanger:Vertical:Array
object used to define a rectangular borehole field. If
present, the GHE:Vertical:Single objects will be ignored.
The unique names of all single, vertical GLHE objects which
are used to define and arbitrarily shaped GHE array. This
field is extensible.
The following are example inputs corresponding to the input
variations allowed which were described previously. The first
example uses the GroundHeatExchanger:Vertical:Array
object. The g-functions will be generated automatically by
EnergyPlus.
GroundHeatExchanger:System,
Vertical GHE 1x4 Std, !- Name
GLHE Inlet, !- Inlet Node Name
GLHE Outlet, !- Outlet Node Name
0.00100944, !- Design Flow Rate {m3/s}
Site:GroundTemperature:Undisturbed:KusudaAchenbach, !- Undisturbed Ground Temperature Model Type
KATemps, !- Undisturbed Ground Temperature Model Name
2.5, !- Ground Thermal Conductivity {W/m-K}
2.5E+06, !- Ground Thermal Heat Capacity {J/m3-K}
, !- Response Factors Object Name
UBHWTcalc, !- g-Function Calculation Method
, !- GHE:Vertical:Sizing Object Type
, !- GHE:Vertical:Sizing Object Name
GHE-Array; !- GHE:Vertical:Array Object Name
GroundHeatExchanger:Vertical:Properties,
GHE-1 Props, !- Name
1, !- Depth of Top of Borehole {m}
100, !- Borehole Length {m}
0.114, !- Borehole Diameter {m}
0.7443, !- Grout Thermal Conductivity {W/m-K}
3.90E+06, !- Grout Thermal Heat Capacity {J/m3-K}
0.3895, !- Pipe Thermal Conductivity {W/m-K}
1.77E+06, !- Pipe Thermal Heat Capacity {J/m3-K}
0.03341, !- Pipe Outer Diameter {m}
0.002984, !- Pipe Thickness {m}
0.04913; !- U-Tube Distance {m}
GroundHeatExchanger:Vertical:Array,
GHE-Array, !- Name
GHE-1 Props, !- GHE Properties
2, !- Number of Boreholes in X Direction
2, !- Number of Boreholes in Y Direction
5; !- Borehole Spacing {m}
This is the farfield temperature used by the object which
is provided by the undisturbed ground temperature object. The
temperature is the average of the 5 evenly spaced points
between the top of the borehole and the bottom of the
borehole.
The ground loop heat exchanger can be designed and sized
using the packaged GHEDesigner library. Currently the design
is limited to rectangular borehole fields, with future
enhancements expected to allow more flexible field design. To
achieve the design, several design parameters are required,
and are supplied in this object. HVAC sizing must also be
enabled.
This alpha field contains the identifying name for the
rectangle ground heat exchanger sizing object. This name will
be referenced in a GroundHeatExchanger:System
object.
This is an example input object for the sizing
parameters:
GroundHeatExchanger:Vertical:Sizing:Rectangle,
GHE-1-Sizing, !- Name
GHE Sizing Period, !- SizingPeriod:WeatherFileDays Name
0.0005, !- Design Flow Rate Per Borehole
100.0, !- Available Borehole Field Length
100.0, !- Available Borehole Field Width
200.0, !- Maximum Number of Boreholes
3.0, !- Minimum Borehole Spacing
10.0, !- Maximum Borehole Spacing
60.0, !- Minimum Borehole Vertical Length
135.0, !- Maximum Borehole Vertical Length
5.0, !- Minimum Exiting Fluid Temperature for Sizing
35.0; !- Maximum Exiting Fluid Temperature for Sizing
This object does not have any specific output variables.
However, by using the full design approach, there may be
additional output files or sizing outputs available in the
EIO.
This numeric field indicates the depth of the top of the
borehole below the ground surface, in meters. The depth
measured from the ground surface downward is positive.
This numeric field indicates the active length of the
borehole, referenced from the starting location (potentially
below the ground surface), to the end of the borehole, in
meters.
This numeric field indicates the center-to-center borehole
spacing, in meters, which is applied to the rectangular
borehole field.
An example object is shown below.
GroundHeatExchanger:Vertical:Array,
GHE-Array, !- Name
GHE-1 Props, !- GHE Properties
2, !- Number of Boreholes in X Direction
2, !- Number of Boreholes in Y Direction
5; !- Borehole Spacing {m}
The G-Functions may be formulated slightly differently
based on the program which generated them. The original
g-functions as defined by Eskilson are based on an borehole
radius to active length ratio of 0.0005. If the physical ratio
is different from this, a correction must be applied.
EnergyPlus will apply the correction, based on the reference
ratio entered in this field. Therefore, there are two possible
input configurations.
If the g-functions have not had a correction applied,
then the g-functions are still based on a reference of 0.0005,
so use a value of 0.0005 in this field. EnergyPlus will adjust
the g-functions internally to create the properly referenced
g-function.
If the correction has already been applied, then the
input g-functions are based on a reference to the actual
(physical) radius/length ratio, so enter the physical
radius/length in this field. Entering the actual value will
nullify any internal corrections, which will avoid re-basing
the g-function set.
The software GLHEPro has been making this “pre-correction”
to the data sets since version 3.1 of that software, so this
input field should match the actual (physical) radius/length
ratio.
This numeric field contains the g-function value of the
corresponding LNTTS.
This object is extensible, so additional pairs of these
last two fields can be added to the end of this object.
An example object is shown below.
GroundHeatExchanger:ResponseFactors,
GHE-1 g-functions, !- Name
GHE-1 Props, !- GHE Properties
4, !- Number of Boreholes
0.0005, !- G-Function Reference Ratio {dimensionless}
-15.585075, !- G-Function Ln(T/Ts) Value 1
-2.672011, !- G-Function G Value 1
-15.440481, !- G-Function Ln(T/Ts) Value 2
-2.575897, !- G-Function G Value 2
-15.295888, !- G-Function Ln(T/Ts) Value 3
-2.476279, !- G-Function G Value 3
-15.151295, !- G-Function Ln(T/Ts) Value 4
-2.372609, !- G-Function G Value 4
...,
12.365217, !- G-Function G Value 70
1.112000, !- G-Function Ln(T/Ts) Value 71
12.469007, !- G-Function G Value 71
1.335000, !- G-Function Ln(T/Ts) Value 72
12.547123, !- G-Function G Value 72
1.679000; !- G-Function Ln(T/Ts) Value 73
The GroundHeatExchanger:Slinky
use the g-functions to calculate the GHX temperature response,
similar to the GroundHeatExchanger:Vertical model, however for
this model g-functions are automatically calculated by
EnergyPlus without the need of external software or data.
Horizontal slinky-loop ground heat exchangers (GHXs)
consist of coiled tubing, with the individual rings spread out
along the direction of the trench either horizontally or
vertically, as shown in Figure. A
schematic of a slinky GHX can be seen in Figure. Compared to conventional
straight tube horizontal GHXs, slinky loops have a higher tube
density; hence, with the same cooling/heating loads,
slinky-loop GHXs require less land area and excavation work
than straight tube HGHXs.
This numeric field is the design flow rate in m3/s for the
heat exchanger. The plant loop will attempt to meet this
request based on loop and flow conditions.
The pond heat exchanger model represents a shallow pond
with submerged hydronic tubes through which the heat transfer
fluid is circulated. The model represents a ‘shallow’ pond in
that no attempt is made to model any stratification effects
that may be present in deeper ponds.
This type of heat exchanger is intended to be connected to
the supply side of a condenser loop, and can be used with any
type of plant loop. The pond may be specified as the only heat
exchanger on the condenser loop (as shown in Figure 3)
or it may be connected in parallel with other condenser loop
heat exchangers (such as cooling towers, ground surface heat
exchangers) as shown in the second figure below.
Example of Pond Ground Heat
Exchanger as only heat exchanger on condenser loop [fig:example-of-pond-ground-heat-exchanger-as-only]Pond Ground Heat Exchanger with
other heat exchangers on condenser loop [fig:pond-ground-heat-exchanger-with-other-heat]
The surface heat exchanger model is to simulate hydronic
surface ground heat exchangers. This includes pavement
surfaces with embedded pipes for snow-melting or heat
rejection from hybrid ground source heat pump systems.
The heat exchanger may be ground coupled or not. In the
latter case the bottom surface is exposed to the wind but not
solar gains. This type of heat exchanger is intended to be
connected to the supply side of a condenser loop, and can be
used with any type of plant loop. The surface heat exchanger
may be specified as the only heat exchanger on the condenser
loop (as shown in the first figure below) or it may be
connected in parallel with other condenser loop heat
exchangers (such as cooling towers, ground surface heat
exchangers) as shown in the second figure below.
Example of Surface Ground Heat
Exchanger as only heat exchanger on condenser loop [fig:example-of-surface-ground-heat-exchanger]Surface Ground Heat Exchanger
with other heat exchangers on condenser loop [fig:surface-ground-heat-exchanger-with-other-heat]
This alpha field contains the construction name. It must
contain a valid “Construction”
name that is usual for Surfaces. (Ref: Group – Surface Construction
Elements).
The horizontal trench ground heat exchanger object provides
an alternate interface to the detailed
PipingSystem:Underground:* objects. The same underlying
simulation algorithm is utilized, providing a transient
numerical simulation of soil with buried pipes and a detailed
surface heat balance. The input syntax is much smaller and
useful for simple applications. For full flexibility, use the
PipingSystem:Underground:* objects to build a detailed
simulation domain and piping circuit. For information
regarding the simulation algorithms, see the engineering
reference document section covering the buried piping system
objects.
Field: Name
This alpha field is used as an identifying field for the
ground heat exchanger.
Field: Inlet Node Name
This alpha field is the name of the inlet node of this
component on a plant loop, and must match other topology
definitions such as branch objects.
Field: Outlet Node Name
This alpha field is the name of the outlet node of this
component on a plant loop, and must match other topology
definitions such as branch objects.
Field: Design Flow Rate
[m3/s]
This numeric field is the designed flow rate for this heat
exchanger; the plant loop solver will attempt to meet this
request based on flow and loop conditions.
Field: Trench Length in Pipe Axial Direction
[m]
This numeric field represents the axial length of each pipe
trench. Each pipe defined for this ground heat exchanger will
have the same length. If different pipes have different
lengths, they must use separate GroundHeatExchanger:HorizontalTrench
objects with different lengths.
Field: Number of Trenches
This integer field is the number of trenches for this heat
exchanger. Since each trench has a single pipe, this defines
the number of “pipe segments” for this overall heat
exchanger. The total piping length is then calculated as the
trench length times the number of trenches.
Field: Horizontal Spacing Between Pipes
[m]
This numeric field represents the horizontal spacing (pipe
centroid to pipe centroid) between pipes/trenches.
Field: Pipe Inner Diameter
[m]
This numeric field is the inner diameter of the pipe. The
same pipe properties are used for all pipes in this heat
exchanger.
Field: Pipe Outer Diameter
[m]
This numeric field is the outer diameter of the pipe. The
same pipe properties are used for all pipes in this heat
exchanger.
Field: Burial Depth [m]
This numeric field is the burial depth of each pipe, from
ground surface to pipe cross section centroid. The same pipe
depth is used for all pipes in this heat exchanger.
Field: Soil Thermal Conductivity
[W/mK]
This numeric field is the soil thermal conductivity.
Field: Soil Density [kg/m3]
This numeric field is the soil density.
Field: Soil Specific Heat
[J/kgK]
This numeric field is the nominal soil specific heat, but
is corrected for moisture content and in freezing
conditions.
Field: Pipe Thermal Conductivity
[W/mK]
This numeric field is the pipe thermal conductivity.
Field: Pipe Density [kg/m3]
This numeric field is the pipe density.
Field: Pipe Specific Heat
[J/kgK]
This numeric field is the pipe specific heat.
Field: Soil Moisture Content Percent
[%]
This numeric field represents the volume fraction, in
percent, of water content in the soil.
Field: Soil Moisture Content Percent at
Saturation [%]
This numeric field represents the volume fraction, in
percent, of water content in the soil which results in
saturation.
This numeric field specifies the ground cover effects used
in the evapotranspiration model at the ground surface heat
balance. The values range from 0 (solid, non-permeable ground
surface) to 1.5 (wild growth).
An example of this statement in an IDF is shown below:
GroundHeatExchanger:HorizontalTrench,
My Pipe Circuit, !- Name
Plant Supply Intermediate Node, !- Inlet Node Name
Plant Supply Outlet Node, !- Outlet Node Name
0.004, !- Design Flow Rate
75, !- Trench Length in Pipe Axial Direction
2, !- Number of Trenches
2.0, !- Horizontal Spacing Between Pipes
0.016, !- Pipe Inner Diameter
0.02667, !- Pipe Outer Diameter
1.25, !- Burial Depth
1.08, !- Soil Thermal Conductivity
962, !- Soil Density
2576, !- Soil Specific Heat
0.3895, !- Pipe Thermal Conductivity {W/m-K}
641, !- Pipe Density {kg/m3}
2405, !- Pipe Specific Heat {J/kg-K}
30, !- Soil Moisture Content Volume Fraction {percent}
50, !- Soil Moisture Content Volume Fraction at Saturation {percent}
Site:GroundTemperature:Undisturbed:KusudaAchenbach, !- Type of Undisturbed Ground Temperature Object
KATemps, !- Name of Undisturbed Ground Temperature Object
0.408; !- Evapotranspiration Ground Cover Parameter
A fluid-to-fluid heat exchanger designed to couple the
supply side of one plant or condenser loop to the demand side
of another plant or condenser loop. This heat exchanger is
fairly general and can be configured for use in any
application where any two loops need to be connected together.
The only constraints are that that one side must be connected
to the supply side of one loop and the other side connected to
the demand side of a different loop.
Because the heat exchanger is intended to be generic, its
two sides are distinguished by the nature of loop side being
connected. One side is called Loop Supply
Side to indicate the heat exchanger is situated on
the supply side of a loop. The other side is called
Loop Demand Side to indicate it is on the
demand side of a loop. The heat exchanger is intended to act
as a supply component for the loop connected to it as the
“Loop Supply Side” and as a demand component for the loop
connected to it as the “Loop Demand Side.” From the point of
view of the heat exchanger model itself, the Loop Demand Side
fluid serves as the source/sink to supply heating/cooling to
the fluid in the Loop Supply Side.
This heat exchanger can be used for a wide variety of
applications including chilled water, hot water, condenser,
ground source, primary-secondary systems, etc. Heat transfer
is calculated and reported using a sign convention from
chilled water applications where positive heat
transfer indicates energy was extracted from the Loop Supply
Side and added to the Loop Demand Side.
Note: Only hydronic “plant” fluids are
allowed (excepting Fluid Type "Steam"), no air-side
connections are possible with this heat exchanger.
The heat transfer between the two sides can be modeled
using one of seven different models for different types of
heat exchangers.
There are also eleven options for different ways to
control the heat exchanger.
One general type of control is OnOff
where the flow through the heat exchanger is either fully on
or fully off.
Another type of control is Modulated
where the flow through the Loop Demand Side is controlled to
try and meet a target setpoint or load on the Loop Supply
Side.
As of Version
8.0, this object replaces three separate objects that
were available prior to version 8.0 of
EnergyPlus.
The former HeatExchanger:Hydronic
object corresponds to a situation where the Loop Demand Side
is the demand side of condenser loop, the Loop Supply Side is
a the supply side of a chilled water loop, the control type is
“CoolingSetpointOnOffWithComponentOverride”, and the remote
override component is a chiller.
The former
HeatExchanger:WatersideEconomizer object
corresponds to a situation where the Loop Demand Side is the
demand side of condenser loop, the Loop Supply Side is a the
supply side of a chilled water loop, and the control type is
“CoolingDifferentialOnOff.”
The former HeatExchanger:Plate object
corresponds to a situation where the Loop Demand Side is the
demand side of a condenser loop, the Loop Supply Side is the
supply side of a second condenser loop, and the control type
is “UncontrolledOn.”
This field specifies the name of an availability schedule
that can be used for supervisory control of the device. If
blank, the default is that heat exchanger is always
available. If a scheduled is named here, then the heat
exchanger is available for use whenever the schedule value is
greater than zero. The heat exchanger is not available
whenever the schedule value is zero or less.
This field specifies the name of a plant system node that
connects an inlet of the heat exchanger to the demand side of
a loop. This node must be on a branch located on the demand
side of a plant or condenser loop.
This field specifies the name of a plant system node that
connects an outlet of the heat exchanger to the demand side of
a loop. This node must be on a branch located on the demand
side of a plant or condenser loop.
This field specifies the design flow rate, in m\(^{3}\)/s, of the hydronic fluid
passing through the heat exchanger on the Loop Demand Side.
This field is autosizable. When autosized, this design flow
rate is set to equal the design flow rate for the Loop Supply
Side.
This field specifies the name of a plant system node that
connects an inlet of the heat exchanger to the supply side of
a loop. This node must be on a branch located on the supply
side of a plant or condenser loop.
This field specifies the name of a plant system node that
connects an outlet of the heat exchanger to the supply side of
a loop. This node must be on a branch located on the supply
side of a plant or condenser loop.
This field specifies the design flow rate, in m\(^{3}\)/s, of the fluid passing
through the heat exchanger on the Loop Supply Side. This field
is autosizable. When autosized, this design flow rate is set
equal to the overall design flow rate of the loop that is
connected. If a sizing factor is entered in the field below,
then it is multiplied to modify the design flow rate.
This alpha field identifies the nature of heat exchanger.
Heat exchanger model type is specified by one of the following
four key word choices:
CrossFlowBothUnMixed
Specifies a single-pass, cross-flow heat exchanger. The
effectiveness will be calculated using a cross-flow heat
exchanger correlation for both streams unmixed.
CrossFlowBothMixed
Specifies a single-pass, cross-flow heat exchanger. The
effectiveness will be calculated using a cross-flow heat
exchanger correlation for both streams mixed.
CrossFlowSupplyMixedDemandUnMixed
Specifies a single-pass, cross-flow heat exchanger. The
effectiveness will be calculated using a cross-flow heat
exchanger correlation for flow mixed on the Loop Supply side
and flow unmixed on the Loop Demand Side.
CrossFlowSupplyUnMixedDemandMixed
Specifies a single-pass, cross-flow heat exchanger. The
effectiveness will be calculated using a cross-flow heat
exchanger correlation for flow unmixed on the Loop Supply side
and flow mixed on the Loop Demand Side.
CounterFlow
Specifies a counter-flow shell and tube heat exchanger (one
fluid has the opposite direction to the other fluid). The
effectiveness will be calculated using a counter-flow shell
and tube heat exchanger correlation.
ParallelFlow
Specifies a parallel-flow shell and tube heat exchanger
(both fluids have the same direction). The effectiveness will
be calculated using a parallel-flow shell and tube heat
exchanger correlation.
Ideal
Specifies an ideal heat exchanger. The effectiveness will
be set to ‘1.0’ and the specified UA will be ignored. The heat
transfer rate will be calculated as the maximum possible heat
transfer rate.
For effectiveness of each heat exchanger model type in
detail, See "Heat Exchangers: Plant Loop Fluid-to-Fluid Heat
Exchanger" Section in Engineering Reference.
Field:
Heat Exchanger U-Factor Times Area Value[LINK]
This numerical field is used to specify the overall
U-Factor Times Area (UA) {W/K} for use in the calculation of
the heat exchanger effectiveness using the appropriate D-NTU
correlation. If Ideal is specified as the
heat exchanger type, the effectiveness will be set to 1.0.
When set to autosize Heat Exchanger U-Factor Times Area Value
is calculated based on an effectiveness of 1.0 where capacity
is such that the temperatures in the Sizing:Plant
objects for the two loops can be maintained.
This field is used to specify how the heat exchanger is to
be controlled during operation. Different applications for
connecting two loops will require different control behavior
and different control options are needed depending on the
desired behavior. There are the following eleven key choice
options to choose from:
UncontrolledOn. This control mode is
applicable to situations where the heat exchanger is passively
running all the time and always transfers as much heat as
possible between the fluid streams. However there is one
aspect of control in that it will only request flow on the
Loop Demand Side when there is non-zero flow into the heat
exchanger on the Loop Supply Side. This control mode
corresponds to that available in the HeatExchanger:Plate
object prior to version 8.0.
OperationSchemeModulated. This
control mode is applicable to situations where the heat
exchanger is controlled by an operation scheme (see objects
called PlantEquipmentOperationScheme or
CondenserEquipmentOperationSchemes). When using this control
mode the heat exchanger must be listed in PlantEquipmentList
or a CondenserEquipmentList
and it serves as a supply component. The operation scheme
will dispatch a load request to the heat exchanger which it
will try meet by conditioning the fluid stream connected as
the Loop Supply Side. If the heat exchanger could exceed the
load request, then the flow through the fluid stream connected
as the Loop Demand Side will be modulated to just meet the
load request.
OperationSchemeOnOff. This control
mode is applicable to situations where the heat exchanger is
controlled by an operation scheme (see objects called
PlantEquipmentOperationScheme or
CondenserEquipmentOperationSchemes). When using this control
mode the heat exchanger must be listed in PlantEquipmentList
or a CondenserEquipmentList
and it serves as a supply component. The operation scheme
will dispatch a load request to the heat exchanger which it
will use as an on/off signal to decide if the heat exchange
should run or not. If it runs, it will run at full capacity
and may exceed the load request.
HeatingSetpointModulated. This
control mode is applicable to situations where the Loop Demand
Side can provide useful heating to the Loop Supply Side. A
heating setpoint is obtained from a node named in the
following field. If the setpoint and inlet temperatures are
such that heat exchanger could transfer heat from the Loop
Demand Side to the Loop Supply Side to meet the heating
setpoint, then the heat exchanger will run. The inlet
temperatures must differ by more than the value set in the
field called Minimum Temperature Difference to Activate Heat
Exchanger for the heat exchanger to operate. If the heat
exchanger could overshoot the setpoint, then the flow through
the fluid stream connected as the Loop Demand Side will be
modulated to just meet the setpoint.
HeatingSetpointOnOff. This control
mode is applicable to situations where the Loop Demand Side
can provide useful heating to the Loop Supply Side. A heating
setpoint is obtained from a node named in the following
field. If the setpoints and inlet temperatures are such that
heat exchanger could transfer heat from the Loop Demand Side
to the Loop Supply Side to meet the heating setpoint, then the
heat exchanger will run. The inlet temperatures must differ by
more than the value set in the field called Minimum
Temperature Difference to Activate Heat Exchanger for the heat
exchanger to operate. If it runs, it will run at full
capacity and may overshoot the setpoint.
CoolingSetpointModulated. This
control mode is applicable to situations where the Loop Demand
Side can provide useful cooling to the Loop Supply Side. A
cooling setpoint is obtained from a node named in the
following field. If the setpoints and inlet temperatures are
such that heat exchanger could transfer heat from the Loop
Supply Side to the Loop Demand Side to meet the cooling
setpoint, then the heat exchanger will run. The inlet
temperatures must differ by more than the value set in the
field called Minimum Temperature Difference to Activate Heat
Exchanger for the heat exchanger to operate. If the heat
exchanger could undershoot the setpoint, then the flow through
the fluid stream connected as the Loop Demand Side will be
modulated to just meet the setpoint.
CoolingSetpointOnOff. This control
mode is applicable to situations where the Loop Demand Side
can provide useful cooling to the Loop Supply Side. A cooling
setpoint is obtained from a node named in the following
field. If the setpoints and inlet temperatures are such that
heat exchanger could transfer heat from the Loop Supply Side
to the Loop Demand Side to meet the cooling setpoint, then the
heat exchanger will run. The inlet temperatures must differ by
more than the value set in the field called Minimum
Temperature Difference to Activate Heat Exchanger for the heat
exchanger to operate. If it runs, it will run at full capacity
and may undershoot the setpoint. This control mode
corresponds to that available in the
HeatExchanger:WatersideEconomizer object prior to version
8.0.
DualDeadbandSetpointModulated. This
control mode is applicable to situations where the Loop Demand
Side can provide either useful cooling or heating to the Loop
Supply Side. A dual deadband setpoint is obtained from a node
named in the following field. If the setpoints and inlet
temperatures are such that heat exchanger could transfer heat
from the Loop Demand Side to the Loop Supply Side to meet the
lower setpoint, then the heat exchanger will run. If the
setpoints and inlet temperatures are such that heat exchanger
could transfer heat from the Loop Supply Side to the Loop
Demand Side to meet the high setpoint, then the heat exchanger
will run. The inlet temperatures must differ by more than the
value set in the field called Minimum Temperature Difference
to Activate Heat Exchanger for the heat exchanger to operate.
If the heat exchanger could overshoot the lower setpoint, or
undershoot the higher setpoint, then the flow through the
fluid stream connected as the Loop Demand Side will be
modulated to just meet the deadband setpoint.
DualDeadbandSetpointOnOff. This
control mode is applicable to situations where the Loop Demand
Side can provide either useful cooling or heating to the Loop
Supply Side. A dual deadband setpoint is obtained from a node
named in the following field. If the setpoints and inlet
temperatures are such that heat exchanger could transfer heat
from the Loop Demand Side to the Loop Supply Side to meet the
lower setpoint, then the heat exchanger will run. If the
setpoints and inlet temperatures are such that heat exchanger
could transfer heat from the Loop Supply Side to the Loop
Demand Side to meet the high setpoint, then the heat exchanger
will run. The inlet temperatures must differ by more than the
value set in the field called Minimum Temperature Difference
to Activate Heat Exchanger for the heat exchanger to operate.
If the heat exchanger runs, it will run at full capacity and
may overshoot the lower setpoint or undershoot the higher
setpoint.
CoolingDifferentialOnOff. This
control mode is applicable to situations where the Loop Demand
Side can provide useful cooling to the Loop Supply Side. This
mode is similar to CoolingSetpointOnOff except that it ignores
any cooling setpoint and its control is based only on the
temperature difference between Loop Demand Side and the Loop
Supply Side. The inlet temperatures must differ by more than
the value set in the field called Minimum Temperature
Difference to Activate Heat Exchanger for the heat exchanger
to operate. This control mode corresponds to that available
in the HeatExchanger:WatersideEconomizer object prior to
version 8.0.
CoolingSetpointOnOffWithComponentOverride.
This control mode is applicable to situations where the heat
exchanger operation is integrated with the operation of a
specific chiller. Typically the heat exchanger and chiller are
in parallel on separate branches. When conditions are
favorable for the heat exchanger to provide cooling to the
Loop Supply Side, the heat exchanger is run and the integrated
chiller is turned off. When conditions are not favorable, the
heat exchanger is completely off and the chiller is allowed to
run as usual. A cooling setpoint is obtained from a node named
in the following field. If it runs it will run at full
capacity and may undershoot the setpoint. The chiller that is
integrated with the heat exchanger is identified by entering
the names of the chiller’s inlet nodes in the input fields
below. The control decision can be based on one of three
different temperature signals selected in the field below
called Component Override Cooling Control Temperature Mode.
The setpoint and control signal temperatures must differ by
more than the value set in the field called Minimum
Temperature Difference to Activate Heat Exchanger for the heat
exchanger to operate. This control mode corresponds to that
available in the HeatExchanger:Hydronic object prior to
version 8.0.
This field specifies the name of a plant system node
located on loop attached to the Loop Supply Side. This field
is used and required when the previous field is set to one of
the “Setpoint” control types. The node must have a
temperature setpoint placed on it by a setpoint manager (or
EMS actuator).
If the previous field is set to
DualDeadbandSetpointModulated or DeadbandSetpointOnOff then
there must be a setpoint manager that places both a high and
low setpoint on the node named in this field. (see
SetpointManager:Scheduled:DualSetpoint).
Field:
Minimum Temperature Difference to Activate Heat Exchanger[LINK]
This field specifies the value of a temperature tolerance
used in control decisions, in deg. Celsius. Whenever the
control logic needs to compare two temperatures, the value
entered in this field is used as a threshold for
comparisons.
This field specifies how the metering for heat transfer
will be accounted with respect to end uses. Although the heat
exchanger consumes no energy that needs to be metered, there
are also meters for heat transfers that apply to the model.
The nature of the end use may vary depending on the
application that the heat exchanger is being used for. The
available choices are FreeCooling, HeatRecovery,
HeatRejection, HeatRecoveryForCooling, HeatRecoveryForHeating,
and LoopToLoop.
Field:
Component Override Loop Supply Side Inlet Node Name[LINK]
This field specifies the name of an inlet node for the
remote component that will be integrated with this heat
exchanger. This inlet should be on the supply side of a loop
– typically chilled water inlet or return for a chiller. This
field and the next two are only used for the control type
called CoolingSetpointOnOffWithComponentOverride.
Field:
Component Override Loop Demand Side Inlet Node Name[LINK]
This field specifies the name of an inlet node for the
remote component that will be integrated with this heat
exchanger. This inlet should be on the demand side of a loop
– typically condenser water inlet or return for a water-cooled
chiller. This field is only used for the control type called
CoolingSetpointOnOffWithComponentOverride.
Field:
Component Override Cooling Control Temperature Mode[LINK]
This field specifies which type of temperature is used to
control a heat exchanger that uses the control type called
CoolingSetpointOnOffWithComponentOverride. There are three
options: Loop, WetBulbTemperature, and DryBulbTemperature.
The option called “Loop” directs the program to use the inlet
fluid temperature at the Loop Demand Side connection of heat
exchanger for the temperature used as a signal to be compared
with the setpoint. The option call “WetBulbTemperature” uses
the outdoor air wetbulb temperature as the signal. The option
called “DryBulbTemperature” uses the outdoor air drybulb
temperature as the signal.
This optional field can be used to modify the results of
autosize calculations. This sizing factor is used for this
heat exchanger and modifies sizing results by multiplying them
by the factor entered here. This factor is applied to the
Loop Supply Side Design Flow rate and in turn affects the heat
exchanger UA and the loop demand side flow rate which are
derived from that flow rate. This allows fine control over
the size of the heat exchanger when using autosize in those
fields.
This optional field can be used to provide supervisory
control of the heat exchanger. If either of the inlet
temperatures are below this limit (°C), the heat exchanger
will not operate.
This optional field can be used to provide supervisory
control of the heat exchanger. If either of the inlet
temperatures are above this limit (°C), the heat exchanger
will not operate.
Some example IDF input objects follow.
HeatExchanger:FluidToFluid,
CondenserLoop HX, !- Name
ALWAYS_ON, !- Availability Schedule Name
CondenserLoop HX HX Inlet Node, !- Loop Demand Side Inlet Node Name
CondenserLoop HX HX Outlet Node, !- Loop Demand Side Outlet Node Name
autosize, !- Loop Demand Side Design Flow Rate
CondenserLoop Pump- HXNode, !- Loop Supply Side Inlet Node Name
CondenserLoop HX- ChillerNode, !- Loop Supply Side Outlet Node Name
autosize, !- Loop Supply Side Design Flow Rate
CounterFlow, !- Heat Exchange Model Type
autosize, !- Heat Exchanger U-Factor Times Area Value
CoolingDifferentialOnOff, !- Control Type
, !- Heat Exchanger Setpoint Node Name
2.0, !- Minimum Temperature Difference to Activate Heat Exchanger
FreeCooling; !- Heat Transfer Metering End Use Type
HeatExchanger:FluidToFluid,
SOURCE to TRANSFER HX, !- Name
AlwaysOnSchedule, !- Availability Schedule Name
SOURCE Demand HX Inlet Node,!- Loop Demand Side Inlet Node Name
SOURCE Demand HX Outlet Node, !- Loop Demand Side Outlet Node Name
0.003, !- Loop Demand Side Design Flow Rate
TRANSFER HX Supply Inlet Node, !- Loop Supply Side Inlet Node Name
TRANSFER HX Supply Outlet Node, !- Loop Supply Side Outlet Node Name
0.003, !- Loop Supply Side Design Flow Rate
CrossFlow, !- Heat Exchange Model Type
15000, !- Heat Exchanger U-Factor Times Area Value
DualDeadbandSetpointModulated, !- Control Type
TRANSFER Supply Outlet Node,!- Heat Exchanger Setpoint Node Name
0.2, !- Minimum Temperature Difference to Activate Heat Exchanger
LoopToLoop; !- Heat Transfer Metering End Use Type
Fluid
Heat Exchanger Heat Transfer Energy [J][LINK]
These outputs are the rate and energy transferred from the
Loop Supply Side to the Loop Demand Side. The sign convention
is taken from cooling or heat rejection applications such that
positive values indicate cooling of the Loop Supply Side.
Fluid
Heat Exchanger Loop Supply Side Mass Flow Rate [kg/s][LINK]
This is the system mass flow of fluid through the heat
exchanger side connected as the Loop Supply Side, in kg/s.
Fluid
Heat Exchanger Loop Supply Side Inlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid
entering the heat exchanger on the side connected as the Loop
Supply Side.
Fluid
Heat Exchanger Loop Supply Side Outlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid
leaving the heat exchanger on the side connected as the Loop
Supply Side.
Fluid
Heat Exchanger Loop Demand Side Mass Flow Rate [kg/s][LINK]
This is the system mass flow of fluid through the heat
exchanger side connected as the Loop Demand Side, in kg/s.
Fluid
Heat Exchanger Loop Demand Side Inlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid
entering the heat exchanger on the side connected as the Loop
Demand Side.
Fluid
Heat Exchanger Loop Demand Side Outlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid
leaving the heat exchanger on the side connected as the Loop
Demand Side.
This output is a numeric flag that indicates whether or not
the heat exchanger was operating or not. If the value is 0,
then the heat exchanger was not operating. If the value is 1,
then the heat was operating.
This output is the calculated heat exchanger effectiveness
(non-dimensional). It is an intermediate value in the NTU
model calculations for heat flow rate. Values range between 0
and 1.0. A value of 1.0 indicates ideal heat transfer.
Group – Condenser Equipment[LINK]
Equipment Types[LINK]
In each CondenserEquipmentList, various equipment types and names must be given. Each type-name pair must then have a corresponding equipment definition. This subsection lists the various equipment types that are available and examples from an IDF. Where appropriate, notes and comments on the input structure are provided.
CoolingTower:SingleSpeed[LINK]
Cooling towers are components that may be assigned to condenser loops. The cooling tower is modeled as a counterflow heat exchanger with a single-speed fan (induced draft configuration) based on Merkel’s theory. The user must define tower performance via one of two methods: design heat transfer coefficient-area product (UA) and design water flow rate, or nominal tower capacity at a specific rating point. Regardless of which method is chosen, the design airflow rate and corresponding fan power must be specified. The model will also account for tower performance in the “free convection” regime, when the tower fan is off but the water pump remains on and heat transfer still occurs (albeit at a low level). If the user wants the model to account for “free convection”, they must specify the corresponding airflow rate and heat transfer coefficient-area product (UA), or the nominal tower capacity during this mode of operation.
The cooling tower seeks to maintain the temperature of the water exiting the cooling tower at (or below) a set point. The set point schedule value is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first checks to determine the impact of “free convection”, if specified by the user, on the tower exiting water temperature. If the exiting water temperature based on “free convection” is at or below the set point, then the tower fan is not turned on. If the exiting water temperature based on “free convection” is below the set point, the tower will operate in FluidBypass mode – portion of the water goes through the tower media and gets cooled while the remaining water flow gets bypassed, two water flows then mix together trying to meet the water setpoint temperature. If the exiting water temperature remains above the set point after “free convection” is modeled, then the tower fan is turned on to reduce the exiting water temperature to the set point. If the capacity control is FanCycling, the model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., tower fan on for the entire simulation timestep and tower fan off for the entire simulation timestep). Cyclic losses are not taken into account. If the capacity control is FluidBypass, the model determines the fraction of water flow to be bypassed while the remaining water goes through the tower cooling media and gets cooled, then the two water flows mix to meet the setpoint temperature. In this case, the fan runs at full speed for the entire timestep.
Cooling towers here are “wet” and consume water through evaporation, drift, and blowdown. The model can be used to predict water consumed by the towers. The last six input fields are optional and provide methods of controlling details of the water consumption calculations. The user can specify connections to the rest of the buildings water system by providing the name of a water storage tanks (i.e. WaterUse:Storage objects).
For the operation of multi-cell towers, the first step is to determine the number of cells to operate based on the cell control method – between the minimum number of cells subject to the maximum water flow rate fraction per cell, and maximum number of cells subject to the minimum water flow rate fraction per cell. If the calculated cells do not meet the loads, additional cells will be operating to help meet the loads. Inside each cell, the existing capacity controls still apply.
For multi-cell towers, the following inputs are assumed to be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common basin)
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the cooling tower.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water outlet node.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the tower in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the tower (not the flow rate of water being sprayed on the outside of the heat exchange coil). If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow rate greater than zero must be defined or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections). If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically assumes a water flow rate of 5.382E-8 m3/s per watt (3 gpm/ton) of tower capacity specified in the field “Nominal Capacity”.
Field: Design Air Flow Rate[LINK]
This numeric field contains the design air flow rate induced by the tower fan in m\(^{3}\)/s. A value greater than zero must be defined regardless of the tower performance input method. Alternately, this field can be autosized. If autosized, the design air flow rate is calculated as follows:
\[Design\;Air\;Flow\;Rate = \frac{{0.5{\rho_{air}}(Fan\;power\;at\;Design\;Air\;Flow\;Rate)}}{{190.}}\]
where a fan pressure rise of 190 Pascals and total fan efficiency of 0.5 are assumed.
Field: Design Fan Power[LINK]
This numeric field contains the fan power (in watts) at the design air flow rate specified in the previous field. A value greater than zero must be specified regardless of the tower performance input method, or this field can be autosized. If autosized, the fan power is calculated as follows:
If”Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then
\[Fan\;power = 0.0105\cdot {\rho_{water}}\cdot {C_{p,water}}\cdot Design\;Water\;Flow\;Rate\cdot Design\;Loop\Delta T\]
is used.
If”Performance Input Method” is specified as “NominalCapacity”, then
\[Fan\;power = 0.0105\cdot Tower\;Nominal\;Capacity\]
is used.
Field: Design U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design tower UA value is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), assuming a tower water inlet temperature of 35C and tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Nominal Capacity”.
Field: Free Convection Regime Air Flow Rate[LINK]
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “Design Air Flow Rate”. This field may be autocalculated, in which case it is set to a fraction of the “Design Air Flow Rate” determined in the following input field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If the user specifies the U-Factor Times Area Value at Free Convection Air Flow Rate or Free Convection Capacity as a value greater than zero, then the free convection air flow rate must be specified greater than 0.0.
Field: Free Convection Regime Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime air flow rate. The default is 0.1.
Field: Free Convection Regime U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (W/K) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “U-Factor Times Area Value at Design Air Flow Rate”. This field may be autosized, in which case it is set to a fraction of the “U-Factor Times Area Value at Design Air Flow Rate” determined in the following input field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Free Convection Capacity”.\
Field: Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime U-Factor times area value. The default is 0.1.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify tower performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”. If this field is left blank in the input data file, the default input method is assumed to be “UFactorTimesAreaAndDesignWaterFlowRate”. If the method “UFactorTimesAreaAndDesignWaterFlowRate” is selected, then the user must enter design UA values, design water flow rates and air flow rates as described for the previous input fields. If the method “NominalCapacity” is selected then the fields “Design Water Flow Rate”, “U-Factor Times Area Value at Design Air Flow Rate” and “U-Factor Times Area Value at Free Convection Air Flow Rate” must be left blank, but the fields “Nominal Capacity” and “Free Convection Capacity” must be entered as described below.
Field: Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of actual tower heat rejection to nominal capacity. This ratio is defined at entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. Historically this ratio has been set at 1.25 based on the assumption that the tower must dissipate 0.25 W of compressor power for every what of heat removed at the chiller evaporator. The default is 1.25.
Field: Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal capacity (3 gpm/ton). The value in the previous field times this nominal tower capacity gives the actual tower heat rejection at these operating conditions (based on historical assumption that the tower must dissipate additional heat from the compressor heat for heat removed at the evaporator).
Field: Free Convection Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts when the tower is in the “free convection” regime (water flow exists but tower fan is turned off), with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal tower capacity (input field above). The heat rejection capacity and nominal capacity sizing ratio is applied to this free convection tower capacity to give the actual tower heat rejection at these operating conditions (typical value is 1.25 based on historical assumption that the tower must dissipate 0.25W of compressor heat for every watt of heat removed by the evaporator). The value specified for this field must be less than the value specified for the field “Tower Nominal Capacity”. If the user does not wish to model “free convection”, then this field should be set to 0.0. If the user specifies a value greater than zero, then the “Air Flow Rate in Free Convection Regime” field must contain a value greater than zero. This field can be automatically calculated using the sizing factor in the following field.
Field: Free Convection Nominal Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Free Convection Capacity. The default is 0.1.
Field: Design Inlet Air Dry-Bulb Temperature[LINK]
This numeric field specifies the design inlet air dry-bulb temperature of the tower. The default is 35.0 °C.
Field: Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the design inlet air wet-bulb temperature of the tower. The default is 25.6 °C.
Field: Design Approach Temperature[LINK]
This numeric field specifies the design approach temperature of the tower corresponding to the design inlet air wet-bulb temperature and the design temperature range. The approach temperature should be the outlet water temperature minus the inlet air wet-bulb temperature at design conditions. This parameter is autosizable and when autosized it is set to 3.9 °C.
Field: Design Temperature Range[LINK]
This numeric field specifies the design temperature range of the tower corresponding to the design inlet air wet-bulb temperature and the design approach temperature. The design range should be the inlet water temperature minus the outlet water temperature at design conditions. This parameter is autosizable and when autosized it is set to 5.5 °C.
Field: Basin Heater Capacity[LINK]
This numeric field contains the capacity of the tower’s electric basin heater in watts per degree Kelvin. This field is used in conjunction with the Basin Heater Setpoint Temperature described in the following field. The basin heater electric power is equal to this field multiplied by the difference between the basin heater set point temperature and the outdoor dry-bulb temperature. The basin heater only operates when the tower fan is off and water is not flowing through the tower, regardless of the basin heater schedule described below. The basin heater capacity must be greater than or equal to zero, with a default value of zero if this field is left blank.
Field: Basin Heater Setpoint Temperature[LINK]
This numeric field contains the set point temperature (°C) for the basin heater described in the previous field. The basin heater is active when the outdoor air dry-bulb temperature falls below this setpoint temperature, as long as the tower fan is off and water is not flowing through the tower. This set point temperature must be greater than or equal to 2˚C, and the default value is 2˚C if this field is left blank.
Field: Basin Heater Operating Schedule Name[LINK]
This alpha field contains the name of the basin heater operating schedule. The basin heater operating schedule is assumed to be an on/off schedule and the heater is available to operate any time the schedule value is greater than 0. The basin heater operates when scheduled on and the outdoor air dry-bulb temperature is below the set point temperature described in the previous field. If this field is left blank, the basin heater is available to operate throughout the simulation. Regardless of this schedule, the basin heater may only operate when the cooling tower fan is off and water is not flowing through the tower.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the cooling tower. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the tower is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the cooling tower model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the cooling tower and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-degree Kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Typical values are from 0.15 to 0.27 [percent/K]. The default is 0.2.
Field: Drift Loss Percent[LINK]
This field is used to specify the rate of water lost to the exiting air as entrained droplets [%]. The drift loss is a percent of the condenser water flow. Typical values for towers with efficient drift eliminators are between 0.002 and 0.2% of the condenser water flow rate. The default value is 0.008%.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ConcentrationRatio or ScheduledRate. The choice will determine which of the two models below is used. The default is ConcentrationRatio.
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the cooling tower as a function of the rate of evaporation. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m\(^{3}\)/s) flushed from the basin on a periodic basis to purge the tower of mineral scale build-up and other contaminants. This schedule is only used if the Blowdown Calculation Mode is set to ScheduledRate. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the cooling tower is active and water is flowing through the tower (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the tower obtains water used for evaporative cooling. If blank or omitted, then the tower will obtain water directly from the mains. If the name of a WaterUse:Storage object is used here, then the tower will obtain its water from that tank. If a tank is specified, the tower will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the tower needs, then the tower will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the cooling tower. If this field is left blank, the outdoor air conditions entering the cooling tower are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field:Capacity Control[LINK]
This alpha field contains the cooling capacity control for the cooling tower. Two choices are available: FanCycling and FluidBypass. During part-load conditions, there are two ways to maintain the exiting water temperature at the setpoint: either cycling the tower fan, or bypassing portion of the tower water with a three-way valve. For FluidBypass, the tower fan still runs at full speed for the entire timestep, but only portion of the water flow goes through the cooling tower media to get cooled while the remaining portion of the water flow gets bypassed. Two water flows then mix at the common water sump to meet the setpoint temperature.
Field: Number of Cells[LINK]
This integer field contains the number of cells in the multi-cell cooling tower. If not entered, the program will assume it is a single-cell cooling tower
Field: Cell Control[LINK]
This alpha field specifies the method used to control the number of cells used to meet the load, the two choices are:
MinimalCell : the program will use minimal number of cells needed, all other cells will be shut down with no water flow. It will attempt to use as few cells as possible to cool the fluid. In no case, however, will the flow per cell be allowed to exceed its maximum value defined by the Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible will be turned on. In no case, however, will the flow per cell be allowed to drop below its minimum value specified by the Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is MaximalCell.
Field: Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest fraction of the design water flow rate. Flows less than this value will commonly result in fluid distribution problems; the pressure at each nozzle will be too weak for the fluid to be sprayed out in the correct pattern, not all the fill would be wet. If this field is left blank, the default value is 0.33.
Field: Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction of the design water flow rate. If this field is left blank, the default value is 2.5.
Field: Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature. For this component the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Design Air Flow Rate;
3. Fan Power at Design Air Flow Rate;
4. U-Factor Times Area Value at Design Air Flow Rate;
5. Air Flow Rate in Free Convection Regime;
6. U-Factor Times Area Value at Free Convection Air Flow Rate.
Note that the U-Factor Times Area Value at Design Air Flow Rate is not multiplied by the Sizing Factor. Instead the design tower load is multiplied by the sizing factor and the design UA then calculated as usual. The U-Factor Times Area Value at Free Convection Air Flow Rate is set to 10% of the new design Tower UA.
Field: End-Use Subcategory[LINK]
This optional field allows you to specify a user-defined end-use subcategory, e.g., “Process”. A new meter for reporting is created for each unique subcategory (ref: Output:Meter objects). Any text may be used here to further subcategorize the end-uses in the ABUPS End Uses by Subcategory table and in the LEED Summary EAp2-4/5 Performance Rating Method Compliance table. If this field is omitted or blank, the cooling tower will be assigned to the “General” end-use subcategory.
Three examples of an IDF specification for this object are shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Bypass Fraction []
HVAC,Average,Cooling Tower Fan Cycling Ratio []
HVAC,Average,Cooling Tower Operating Cells Count []
A tower uses either mains water or storage tank for make-up water.
When mains water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
When storage tank water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Drift Volume [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
IF specified:
HVAC,Average,Cooling Tower Basin Heater Electricity Rate [W]
HVAC,Sum,Cooling Tower Basin Heater Electricity Energy [J]
Cooling Tower Fan Electricity Rate [W][LINK]
Cooling Tower Fan Electricity Energy [J][LINK]
These outputs are the electric power input to the tower fans. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the tower.
Cooling Tower Inlet Temperature [C][LINK]
Cooling Tower Outlet Temperature [C][LINK]
Cooling Tower Mass Flow Rate [kg/s][LINK]
These outputs are the tower water inlet and outlet temperatures, and mass flow rate of the circulating condenser water loop.
Cooling Tower Basin Heater Electricity Rate [W][LINK]
Cooling Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower basin heater. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the water consumed by the wet cooling tower for external water sprays used to augment heat transfer. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during cooling tower operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to feed the cooling tower.
If a water storage tank is used to provide water to the tower, then the following output variables will also be available.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank connections was not able to provide. The starved water is assumed to come from the mains. The tower’s operation is not affected by a lack of storage tank water.
Cooling Tower Fan Cycling Ratio [][LINK]
This represents the fraction of a time-step when tower fan is on.
Cooling Tower Bypass Fraction [][LINK]
This represents the fraction of a fluid bypassing the tower when a mixture of the tower fluid and tower return water is able to meet the set point temperature.
Cooling Tower Operating Cells Count [][LINK]
This represents the number of cells operating at each time step.
CoolingTower:TwoSpeed[LINK]
The two-speed cooling tower is modeled in a similar fashion to the single-speed tower. The cooling tower is modeled as a counterflow heat exchanger with a two-speed fan (induced draft configuration) based on Merkel’s theory. The user must define tower performance via one of two methods: heat transfer coefficient-area product (UA) and design water flow rate, or nominal tower capacity at a specific rating point. Regardless of which method is chosen, the airflow rate and corresponding fan power at both high and low fan speed must be specified. The model will also account for tower performance in the “free convection” regime, when the tower fan is off but the water pump remains on and heat transfer still occurs (albeit at a low level). If the user wants the model to account for “free convection”, they must specify the corresponding air flow rate and heat transfer coefficient-area product (UA), or the nominal tower capacity during this mode of operation.
The cooling tower seeks to maintain the temperature of the water exiting the cooling tower at (or below) a set point. The set point schedule value is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first checks to determine the impact of “free convection”, if specified by the user, on the tower exiting water temperature. If the exiting water temperature based on “free convection” is at or below the set point, then the tower fan is not turned on. If the exiting water temperature remains above the set point after “free convection” is modeled, then the tower fan is turned on at low speed to reduce the exiting water temperature. If operating the tower fan at low speed does not reduce the exiting water temperature to the set point, then the tower fan is increased to its high speed.
The model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., tower fan at high speed for the entire simulation timestep and tower fan at low speed for the entire simulation timestep, or tower fan at low speed for the entire simulation timestep and tower fan off for the entire simulation timestep). Cyclic losses are not taken into account.
Cooling towers here are “wet” and consume water through evaporation, drift, and blowdown. The model can be used to predict water consumed by the towers. The last six input fields are optional and provide methods of controlling details of the water consumption calculations. The user can specify connections to the rest of the buildings water system by providing the name of a WaterUse:Storage object.
For the operation of multi-cell towers, the first step is to determine the number of cells to operate based on the cell control method – between the minimum number of cells subject to the maximum water flow rate fraction per cell, and maximum number of cells subject to the minimum water flow rate fraction per cell. If the calculated cells do not meet the loads, additional cells will be operating to help meet the loads. Inside each cell, the existing capacity controls still apply.
For multi-cell towers, the following inputs are assumed to be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common basin)
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the cooling tower.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water outlet node.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the tower in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the tower (not the flow rate of water being sprayed on the outside of the heat exchange coil). If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow rate greater than zero must be defined or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections). If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically assumes a design water flow rate of 5.382E-8 m3/s per watt (3 gpm/ton) of tower capacity specified in the field “Tower High-Speed Nominal Capacity”.
Field: High Fan Speed Air Flow Rate[LINK]
This numeric field contains the tower air flow rate at high fan speed in m\(^{3}\)/s. A value greater than zero must be defined regardless of the tower performance input method. Alternately, this field can be autosized. If autosized, the design air flow rate is calculated as follows:
\[Air\,Flow\,Rate\,at\,High\,Fan\,Speed\, = \,\frac{{0.5{\rho_{air}}(Fan\,Power\,at\,High\,Fan\,Speed\,)}}{{190.}}\]
where a fan pressure rise of 190 Pascals and total fan efficiency of 0.5 are assumed.
Field: High Fan Speed Fan Power
This numeric field contains the fan power (in Watts) at the high-speed air flow rate specified in the previous field. A value greater than zero must be specified regardless of the tower performance input method, or this field can be autosized. If autosized, the fan power is calculated as follows:
If”Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then
\[Fan\;powe{r_{High\;Fan\;Speed}} = 0.0105\cdot {\rho_{water}}\cdot {C_{p,water}}\cdot Design\;Water\;Flow\;Rate\cdot Design\;Loop\Delta T\]
is used.
If”Performance Input Method” is specified as “NominalCapacity”, then
\[Fan\;powe{r_{High\;Fan\;Speed}} = 0.0105\cdot Tower\;High - Speed\;Nominal\;Capacity\]
is used.
Field: High Fan Speed U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per degree Celsius corresponding to the high-speed air flow rate and design water flow rate specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the tower UA value at high fan speed is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), assuming a tower water inlet temperature of 35C and tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the capacity specified in the field “High-Speed Nominal Capacity”.
Field: Low Fan Speed Air Flow Rate[LINK]
This numeric field contains the tower air flow rate at low fan speed in m\(^{3}\)/s. This value must be greater than zero, less than the value specified for the field “Air Flow Rate at High Fan Speed”, and greater than the value specified for the field “Air Flow Rate in Free Convection Regime”. This field may be autocalculated, in which case it is set to a fraction of the “Air Flow Rate at High Fan Speed” determined in the next field.
Field: Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the low fan speed air flow rate. The default is 0.5.
Field: Low Fan Speed Fan Power[LINK]
This numeric field contains the fan power (in Watts) at the low-speed air flow rate specified in the previous field. This value must be specified greater than zero or the field may be autocalculated, in which case it is set to a fraction of the “Fan Power at High Fan Speed” determined in the next field.
Field: Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the low speed fan power. The default is 0.16.
Field: Low Fan Speed U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per degree Celsius corresponding to the design water flow rate and low-speed air flow rate specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, this value must be greater than zero but less than or equal to 300,000, less than the value specified for the field “U-Factor Times Area Value at High Fan Speed”, and greater than the value specified for the field “U-Factor Times Area Value at Free Convection Air Flow Rate”. This field may be autocalculated, in which case it is set to a fraction of the “U-Factor Times Area Value at High Fan Speed” determined in the following field. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Low Speed Nominal Capacity”.
Field: Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the low speed heat transfer coefficient-area product (UA). The default is 0.6.
Field: Free Convection Regime Air Flow Rate[LINK]
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “Air Flow Rate at Low Fan Speed”. This field may be autocalculated, in which case it is set to a fraction of the “Air Flow Rate at High Fan Speed” determined in the following field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If the user specifies the U-Factor Times Area Value at Free Convection Air Flow Rate or Free Convection Capacity as a value greater than zero, then the free convection air flow rate must be specified greater than 0.0.
Field: Free Convection Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime air flow rate. The default is 0.1.
Field: Free ConvectionU-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (W/°C) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “U-Factor Times Area Value at Low Fan Speed”. This field may be autocalculated, in which case it is set to a fraction of the “U-Factor Times Area Value at High Fan Speed” determined in the following field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Free Convection Capacity”.
Field: Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime U-Factor times area value. The default is 0.1.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify tower performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”. If this field is left blank in the input data file, the default input method is assumed to be “UFactorTimesAreaAndDesignWaterFlowRate”. If the method “UFactorTimesAreaAndDesignWaterFlowRate” is selected, then the user must enter UA values, design water flow rate and air flow rates as described for the previous input fields. If the method “NominalCapacity” is selected then the fields “Design Water Flow Rate”, “U-Factor Times Area Value at High Fan Speed”, “U-Factor Times Area Value at Low Fan Speed” and “U-Factor Times Area Value at Free Convection Air Flow Rate” must be left blank, but the fields “High Speed Nominal Capacity”, “Low Speed Nominal Capacity” and “Free Convection Capacity” must be entered as described below.
Field: Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of actual tower heat rejection to nominal capacity. This ratio is defined at entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. Historically this ratio has been set at 1.25 based on the assumption that the tower must dissipate 0.25 W of compressor power for every what of heat removed at the chiller evaporator. The default is 1.25.
Field: High Speed Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts under high-speed fan operation, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed nominal capacity (3 gpm/ton). The Heat Rejection Capacity and Nominal Capacity Sizing Ratio set in the previous field is applied to this nominal tower capacity to give the actual tower heat rejection at these operating.
Field: Low Speed Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts under low-speed fan operation, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed nominal tower capacity (input field above). The Heat Rejection Capacity and Nominal Capacity Sizing Ratio is applied to this nominal tower capacity to give the actual tower heat rejection at these operating conditions. The value specified for this field must be greater than zero but less than the value specified for the field “High-Speed Nominal Capacity”. This field may be autocalculated, in which case it is set to a fraction of the High Speed Nominal Capacity determined in the following field.
Field: Low Speed Nominal Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Speed Nominal Capacity. The default is 0.5.
Field: Free Convection Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts when the tower is in the “free convection” regime (water flow exists but tower fan is turned off), with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of high-speed nominal tower capacity (input field above). The Heat Rejection Capacity and Nominal Capacity Sizing Ratio is applied to this free convection tower capacity to give the actual tower heat rejection at these operating conditions.The value specified for this field must be less than the value specified for the field “Tower Low-Speed Nominal Capacity”. If the user does not wish to model “free convection”, then this field should be set to 0.0. If the user specifies a value greater than zero, then the “Air Flow Rate in Free Convection Regime” field must contain a value greater than zero. This field may be autocalculated, in which case it is set to a fraction of the High Speed Nominal Capacity determined in the following field.
Field: Free Convection Nominal Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Free Convection Capacity. The default is 0.1.
Field: Design Inlet Air Dry-Bulb Temperature[LINK]
This numeric field specifies the design inlet air dry-bulb temperature of the tower. The default is 35.0 °C.
Field: Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the design inlet air wet-bulb temperature of the tower. The default is 25.6 °C.
Field: Design Approach Temperature[LINK]
This numeric field specifies the design approach temperature of the tower corresponding to the design inlet air wet-bulb temperature and the design temperature range. The approach temperature should be the outlet water temperature minus the inlet air wet-bulb temperature at design conditions. This parameter is autosizable and when autosized it is set to 3.9 °C.
Field: Design Temperature Range[LINK]
This numeric field specifies the design temperature range of the tower corresponding to the design inlet air wet-bulb temperature and the design approach temperature. The design range should be the inlet water temperature minus the outlet water temperature at design conditions. This parameter is autosizable and when autosized it is set to 5.5 °C.
Field: Basin Heater Capacity[LINK]
This numeric field contains the capacity of the tower’s electric basin heater in watts per degree Kelvin. This field is used in conjunction with the Basin Heater Setpoint Temperature described in the following field. The basin heater electric power is equal to this field multiplied by the difference between the basin heater set point temperature and the outdoor dry-bulb temperature. The basin heater only operates when the tower fan is off and water is not flowing through the tower, regardless of the basin heater schedule described below. The basin heater capacity must be greater than or equal to zero, with a default value of zero if this field is left blank.
Field: Basin Heater Setpoint Temperature[LINK]
This numeric field contains the set point temperature (˚C) for the basin heater described in the previous field. The basin heater is active when the outdoor air dry-bulb temperature falls below this setpoint temperature, as long as the tower fan is off and water is not flowing through the tower. This set point temperature must be greater than or equal to 2˚C, and the default value is 2˚C if this field is left blank.
Field: Basin Heater Operating Schedule Name[LINK]
This alpha field contains the name of the basin heater operating schedule. The basin heater operating schedule is assumed to be an on/off schedule and the heater is available to operate any time the schedule value is greater than 0. The basin heater operates when scheduled on and the outdoor air dry-bulb temperature is below the set point temperature described in the previous field. If this field is left blank, the basin heater is available to operate throughout the simulation. Regardless of this schedule, the basin heater may only operate when the cooling tower fan is off and water is not flowing through the tower.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the cooling tower. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the tower is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the cooling tower model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the cooling tower and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-degree Kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Typical values are from 0.15 to 0.27 [percent/K]. The default is 0.2.
Field: Drift Loss Percent[LINK]
This field is used to specify the rate of water lost to the exiting air as entrained droplets [%]. The drift loss is a percent of the condenser water flow. Typical values for towers with efficient drift eliminators are between 0.002 and 0.2% of the condenser water flow rate. The default value is 0.008%.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ConcentrationRatio or ScheduledRate. The choice will determine which of the two models below is used. The default is ConcentrationRatio
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the cooling tower as a function of the rate of evaporation. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m\(^{3}\)/s) flushed from the basin on a periodic basis to purge the tower of mineral scale build-up and other contaminants. This schedule is only used if the Blowdown Calculation mode is set to ScheduledRate. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the cooling tower is active and water is flowing through the tower (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the tower obtains water used for evaporative cooling. If blank or omitted, then the tower will obtain water directly from the mains. If the name of a WaterUse:Storage object is used here, then the tower will obtain its water from that tank. If a tank is specified, the tower will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the tower needs, then the tower will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the cooling tower. If this field is left blank, the outdoor air conditions entering the cooling tower are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field: Number of Cells[LINK]
This integer field contains the number of cells in the multi-cell cooling tower. If not entered, the program will assume it is a single-cell cooling tower
Field: Cell Control[LINK]
This alpha field specifies the method used to control the number of cells used to meet the load, the two choices are:
MinimalCell: the program will use minimal number of cells needed, all other cells will be shut down with no water flow. It will attempt to use as few cells as possible to cool the fluid. In no case, however, will the flow per cell be allowed to exceed its maximum value defined by the Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible will be turned on. In no case, however, will the flow per cell be allowed to drop below its minimum value specified by the Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is MaximalCell.
Field: Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest fraction of the design water flow rate. Flows less than this value will commonly result in fluid distribution problems; the pressure at each nozzle will be too weak for the fluid to be sprayed out in the correct pattern, not all the fill would be wet. If this field is left blank, the default value is 0.33.
Field: Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction of the design water flow rate. If this field is left blank, the default value is 2.5.
Field: Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature.For this component the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Air Flow Rate at High Fan Speed;
3. Fan Power at High Fan Speed;
4. U-Factor Times Area Value at High Fan Speed;
5. Air Flow Rate at Low Fan Speed;
6. Fan Power at Low Fan Speed;
7. U-Factor Times Area Value at Low Fan Speed;
8. Air Flow Rate in Free Convection Regime;
9. U-Factor Times Area Value at Free Convection Air Flow Rate.
Note that the U-Factor Times Area Value at High Fan Speed is not multiplied by the Sizing Factor. Instead the design tower load is multiplied by the sizing factor and the design UA then calculated as usual. The U-Factor Times Area Value at Low Fan Speed is set to a fraction of the full load design UA determined by the field Low Fan Speed U-Factor Times Area Sizing Factor. The U-Factor Times Area Value at Free Convection Air Flow Rate is set to a fraction of the design Tower UA determined by the field Free Convection Air U-Factor Times Area Value Sizing Factor.
Field: End-Use Subcategory[LINK]
This optional field allows you to specify a user-defined end-use subcategory, e.g., “Process”. A new meter for reporting is created for each unique subcategory (ref: Output:Meter objects). Any text may be used here to further subcategorize the end-uses in the ABUPS End Uses by Subcategory table and in the LEED Summary EAp2-4/5 Performance Rating Method Compliance table. If this field is omitted or blank, the cooling tower will be assigned to the “General” end-use subcategory.
Four examples of an IDF specification for this object are shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Fan Cycling Ratio []
HVAC,Average,Cooling Tower Operating Cells Count []
HVAC,Average,Cooling Tower Fan Speed Level []
HVAC,Average,Cooling Tower Bypass Fraction []
A tower uses either mains water or storage tank for make-up water.
When mains water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
When storage tank water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Drift Volume [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
IF specified:
HVAC,Average,Cooling Tower Basin Heater Electricity Rate [W]
HVAC,Sum,Cooling Tower Basin Heater Electricity Energy [J]
Cooling Tower Fan Electricity Rate [W][LINK]
Cooling Tower Fan Electricity Energy [J][LINK]
These outputs are the electric power input to the tower fans. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the tower.
Cooling Tower Inlet Temperature [C][LINK]
Cooling Tower Outlet Temperature [C][LINK]
Cooling Tower Mass Flow Rate [kg/s][LINK]
These outputs are the tower water inlet and outlet temperatures, and mass flow rate.
Cooling Tower Basin Heater Electricity Rate [W][LINK]
Cooling Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower basin heater. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the water consumed by the wet cooling tower for external water sprays used to augment heat transfer. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during cooling tower operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to feed the cooling tower. If a water storage tank is used to provide water to the tower, then the following output variables will also be available.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank connections was not able to provide. The starved water is assumed to come from the mains. The tower’s operation is not affected by a lack of storage tank water.
Cooling Tower Fan Cycling Ratio [][LINK]
This represents the fraction of a time-step when tower fan is on. The fan can cycle at both speeds.
Cooling Tower Operating Cells Count [][LINK]
This represents the number of cells operating at each time step.
Cooling Tower Fan Speed Level [][LINK]
This represents the fan speed operating at each time step: 2 for High Speed, 1 for Low Speed, and 0 when the fan is OFF.
CoolingTower:VariableSpeed:Merkel[LINK]
This variable speed tower model is based on Merkel’s theory and is similar to the single-speed and two-speed tower models. The open wet cooling tower is modeled as a counter flow heat exchanger with a variable-speed fan drawing air through the tower (induced-draft configuration). The model also includes a “free convection” regime where cooling tower performance is modeled with the fan off.
For this model, Merkel’s theory is modified to include adjustments developed by Scheier to alter the heat transfer effectiveness based on current wetbulb, air flow rates, and water flow rates. The input requires performance curves or lookup tables to describe these three adjustment factors.
For a multi-cell tower, the capacity and air/water flow rate inputs are for the entire tower.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the cooling tower.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water outlet node.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify tower performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”. If this field is left blank in the input data file, the default input method is assumed to be “NominalCapacity”. If the method “UFactorTimesAreaAndDesignWaterFlowRate” is selected, then the user must enter design UA values, design water flow rates and air flow rates as described for the previous input fields. If the method “NominalCapacity” is selected then the fields “Design Water Flow Rate”, “U-Factor Times Area Value at Design Air Flow Rate” and “U-Factor Times Area Value at Free Convection Air Flow Rate” must be left blank, but the fields “Nominal Capacity” and “Free Convection Capacity” must be entered as described below.
Field: Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of actual tower heat rejection to nominal capacity. This ratio is defined at entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. Historically this ratio has been set at 1.25 based on the assumption that the tower must dissipate 0.25 W of compressor power for every what of heat removed at the chiller evaporator. The default is 1.25.
Field: Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts under full-speed fan operation, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The Heat Rejection Capacity and Nominal Capacity Sizing Ratio set in the previous field is applied to this nominal tower capacity to give the actual tower heat rejection at these operating conditions. This field can be autosized, in which case a Sizing:Plant object is needed for the condenser loop.
Field: Free Convection Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the cooling tower in watts when the tower is in the “free convection” regime (water flow exists but tower fan is turned off), with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The Heat Rejection Capacity and Nominal Capacity Sizing Ratio is applied to this free convection tower capacity to give the actual tower heat rejection at these operating conditions.The value specified for this field must be less than the value specified for the field “Tower Low-Speed Nominal Capacity”. If the user does not wish to model “free convection”, then this field should be set to 0.0. If the user specifies a value greater than zero, then the “Air Flow Rate in Free Convection Regime” field must contain a value greater than zero. This field may be autocalculated, in which case it is set to a fraction of the High Speed Nominal Capacity determined in the following field.
Field: Free Convection Nominal Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Free Convection Capacity. The default is 0.1.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the tower in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the tower. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a water flow rate greater than zero must be defined or the field can be autosized. If autosized, a Sizing:Plant object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections). If “Performance Input Method” is specified as “NominalCapacity”, then this field can be autocalculated using the sizing factor in the following field.
Field: Design Water Flow Rate per Unit of Nominal Capacity[LINK]
This numeric field contains a scalable sizing factor for design water flow rate that scales with nominal capacity, in units of m\(^{3}\)/s/W. The default value is 5.382*10\(^{-8}\). This field is only used if the previous field is set to autocalculate and performance input method is NominalCapacity. (If the performance input method is set to UFactorTimesAreaAndDesignWaterFlowRate then the design water flow rate is obtained from the plant sizing result.)
Field: Design Air Flow Rate[LINK]
This numeric field contains the tower air flow rate at full fan speed, in m\(^{3}\)/s. The value can be autocalculated, in which case the air flow rate is based off of the scalable sizing factor in the following input field.
Field: Design Air Flow Rate Per Unit of Nominal Capacity[LINK]
This numeric field contains the sizing factor to use when calculating the design air flow rate from the nominal capacity, in units of m\(^{3}\)/s/W. The default is 2.76316*10\(^{-5}\). When this field is left blank, then the default value is used but the flow rate is also scaled to account for elevation (with larger volume flow rates at higher altitudes). When a hard value is entered, even if it is the same as the default, then the design air flow rate is not also adjusted for elevation and the scaling factor is used directly.
Field: Minimum Air Flow Rate Ratio[LINK]
This numeric field contains the minimum air flow rate ratio. The tower fan is allowed to operate between the ratio defined here and a maximum air flow rate ratio of 1.0 (which corresponds to the design [maximum] tower air flow rate). Below this value the tower is assumed to operate in the “free convection” regime with the tower fan off. The minimum air flow rate ratio must be greater than or equal to 0.1 and less than or equal to 0.5, with a default value of 0.2 if the field is left blank.
Field: Design Fan Power[LINK]
This numeric field contains the fan power in watts at the design (maximum) air flow rate through the tower. A value greater than zero must be specified or this field can be autocalculated. When the field is autocalculated the following input field is used to size the fan power based on nominal capacity.
Field: Design Fan Power Per Unit of Nominal Capacity[LINK]
This numeric field contains the sizing factor to use when calculating the design fan power from the nominal capacity, in units of Watts per Watt. This field is only used if the previous is set to autocalculate. The default values is 0.0105.
Field: Fan Power Modifier Function of Air Flow Rate Ratio Curve Name[LINK]
This alpha field contains the name of a curve or table object that describes fan power ratio (fan power/design fan power) as a function of air flow rate ratio (air flow rate/design air flow rate). The curve or table object must be for one independent variable, typically a cubic, and should be normalized to 1.0 at an air flow rate ratio of 1.0. This field is required.
Field: Free Convection Regime Air Flow Rate[LINK]
This numeric field contains the air flow rate (m\(^{3}\)/s) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “Design Air Flow Rate”. This field may be autocalculated, in which case it is set to a fraction of the “Design Air Flow Rate” determined in the following input field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If the user specifies the U-Factor Times Area Value at Free Convection Air Flow Rate or Free Convection Capacity as a value greater than zero, then the free convection air flow rate must be specified greater than 0.0.
Field: Free Convection Regime Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime air flow rate. The default is 0.1.
Field: Design Air Flow Rate U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design tower UA value is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), assuming a tower water inlet temperature of 35C and tower inlet air at 35C drybulb/25.6C wetbulb. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Nominal Capacity”.
Field: Free Convection Regime U-Factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (W/K) when the tower is in the “free convection” regime (water flow exists but tower fan is turned off). This value must be less than the value specified for the field “U-Factor Times Area Value at Design Air Flow Rate”. This field may be autosized, in which case it is set to a fraction of the “U-Factor Times Area Value at Design Air Flow Rate” determined in the following input field. If the user does not wish to model “free convection” and is using the Performance Input Method “UFactorTimesAreaAndDesignWaterFlowRate”, then this field should be set to 0.0. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the tower UA based on the tower capacity specified in the field “Free Convection Capacity”.
Field: Free Convection U-Factor Times Area Value Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the free convection regime U-Factor times area value. The default is 0.1. This field is only used if the previous field is set to autocalculate and the performance input method is UFactorTimesAreaAndDesignWaterFlowRate.
Field: U-Factor Times Area Modifier Function of Air Flow Ratio Curve Name[LINK]
This alpha field contains the name of a curve or table object that describes how the UA value varies as a function of air flow rate ratio (air flow rate/design air flow rate). The result of this curve is multiplied by the design UA value to adjust for air flow rate, along with the two other modifiers discussed below. The curve or table object must be for one independent variable and should be normalized to 1.0 at an air flow rate ratio of 1.0. This field is required.
Field: U-Factor Times Area Modifier Function of Wetbulb Temperature Difference Curve Name[LINK]
This alpha field contains the name of a curve or table object that describes how the UA value varies as a function of the current wetbulb temperature. The result of this curve is multiplied by the design UA value to adjust for wetbulb temperatures that differ from design conditions at 25.56°C (78°F), along with the two other modifiers discussed in the previous and following fields. The independent variable is the design wetbulb minus the current outdoor air wetbulb, in units of degrees Celsius. The curve or table object must be for one independent variable and should be normalized to 1.0 at a wetbulb temperature difference of 0.0. This field is required.
Field: U-Factor Times Area Modifier Function of Water Flow Ratio Curve Name[LINK]
This alpha field contains the name of a curve or table object that describes how the UA value varies as a function of the current water flow rate ratio (water flow rate/design water flow rate). The result of this curve is multiplied by the design UA value to adjust for water flow rates that differ from design level, along with the other two modifiers discussed above. The curve or table object must be for one independent variable and should be normalized to 1.0 at a water flow ratio of 1.0. This field is required
Field: Design Inlet Air Dry-Bulb Temperature[LINK]
This numeric field specifies the design inlet air dry-bulb temperature of the tower. The default is 35.0 °C.
Field: Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the design inlet air wet-bulb temperature of the tower. The default is 25.6 °C.
Field: Design Approach Temperature[LINK]
This numeric field specifies the design approach temperature of the tower corresponding to the design inlet air wet-bulb temperature and the design temperature range. The approach temperature should be the outlet water temperature minus the inlet air wet-bulb temperature at design conditions. This parameter is autosizable and when autosized it is set to 3.9 °C.
Field: Design Temperature Range[LINK]
This numeric field specifies the design temperature range of the tower corresponding to the design inlet air wet-bulb temperature and the design approach temperature. The design range should be the inlet water temperature minus the outlet water temperature at design conditions. This parameter is autosizable and when autosized it is set to 5.5 °C.
Field: Basin Heater Capacity[LINK]
This numeric field contains the capacity of the tower’s electric basin heater in watts per degree Kelvin. This field is used in conjunction with the Basin Heater Setpoint Temperature described in the following field. The basin heater electric power is equal to this field multiplied by the difference between the basin heater set point temperature and the outdoor dry-bulb temperature. The basin heater only operates when the tower fan is off and water is not flowing through the tower, regardless of the basin heater schedule described below. The basin heater capacity must be greater than or equal to zero, with a default value of zero if this field is left blank.
Field: Basin Heater Setpoint Temperature[LINK]
This numeric field contains the set point temperature (˚C) for the basin heater described in the previous field. The basin heater is active when the outdoor air dry-bulb temperature falls below this setpoint temperature, as long as the tower fan is off and water is not flowing through the tower. This set point temperature must be greater than or equal to 2˚C, and the default value is 2˚C if this field is left blank.
Field: Basin Heater Operating Schedule Name[LINK]
This alpha field contains the name of the basin heater operating schedule. The basin heater operating schedule is assumed to be an on/off schedule and the heater is available to operate any time the schedule value is greater than 0. The basin heater operates when scheduled on and the outdoor air dry-bulb temperature is below the set point temperature described in the previous field. If this field is left blank, the basin heater is available to operate throughout the simulation. Regardless of this schedule, the basin heater may only operate when the cooling tower fan is off and water is not flowing through the tower.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the cooling tower. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the tower is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the cooling tower model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the cooling tower and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-degree Kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Typical values are from 0.15 to 0.27 [percent/K]. The default is 0.2.
Field: Drift Loss Percent[LINK]
This field is used to specify the rate of water lost to the exiting air as entrained droplets [%]. The drift loss is a percent of the condenser water flow. Typical values for towers with efficient drift eliminators are between 0.002 and 0.2% of the condenser water flow rate. The default value is 0.008%.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ConcentrationRatio or ScheduledRate. The choice will determine which of the two models below is used. The default is ConcentrationRatio.
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the cooling tower as a function of the rate of evaporation. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m\(^{3}\)/s) flushed from the basin on a periodic basis to purge the tower of mineral scale build-up and other contaminants. This schedule is only used if the Blowdown Calculation Mode is set to ScheduledRate. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the cooling tower is active and water is flowing through the tower (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the tower obtains water used for evaporative cooling. If blank or omitted, then the tower will obtain water directly from the mains. If the name of a WaterUse:Storage object is used here, then the tower will obtain its water from that tank. If a tank is specified, the tower will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the tower needs, then the tower will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the cooling tower. If this field is left blank, the outdoor air conditions entering the cooling tower are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field: Number of Cells[LINK]
This integer field contains the number of cells in the multi-cell cooling tower. If not entered, the program will assume it is a single-cell cooling tower
Field: Cell Control[LINK]
This alpha field specifies the method used to control the number of cells used to meet the load, the two choices are:
MinimalCell : the program will use minimal number of cells needed, all other cells will be shut down with no water flow. It will attempt to use as few cells as possible to cool the fluid. In no case, however, will the flow per cell be allowed to exceed its maximum value defined by the Maximum Water Flow Rate Fraction.
MaximalCell: As many cells as possible will be turned on. In no case, however, will the flow per cell be allowed to drop below its minimum value specified by the Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is MaximalCell.
Field: Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest fraction of the design water flow rate. Flows less than this value will commonly result in fluid distribution problems; the pressure at each nozzle will be too weak for the fluid to be sprayed out in the correct pattern, not all the fill would be wet. If this field is left blank, the default value is 0.33.
Field: Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction of the design water flow rate. If this field is left blank, the default value is 2.5.
Field: Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature.
Field: End-Use Subcategory[LINK]
This optional field allows you to specify a user-defined end-use subcategory, e.g., “Process”. A new meter for reporting is created for each unique subcategory (ref: Output:Meter objects). Any text may be used here to further subcategorize the end-uses in the ABUPS End Uses by Subcategory table and in the LEED Summary EAp2-4/5 Performance Rating Method Compliance table. If this field is omitted or blank, the cooling tower will be assigned to the “General” end-use subcategory.
An example IDF specification follows.
Outputs[LINK]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Operating Cells Count []
HVAC,Average,Cooling Tower Fan Speed Ratio []
A tower uses either mains water or storage tank for make-up water.
When mains water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
When storage tank water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Drift Volume [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
IF specified:
HVAC,Average,Cooling Tower Basin Heater Electricity Rate [W]
HVAC,Sum,Cooling Tower Basin Heater Electricity Energy [J]
Cooling Tower Fan Electricity Rate [W][LINK]
Cooling Tower Fan Electricity Energy [J][LINK]
These outputs are the electric power input to the tower fans. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the tower.
Cooling Tower Inlet Temperature [C][LINK]
Cooling Tower Outlet Temperature [C][LINK]
Cooling Tower Mass Flow Rate [kg/s][LINK]
These outputs are the tower water inlet and outlet temperatures, and mass flow rate.
Cooling Tower Fan Speed Ratio[LINK]
This output is the air flow ratio. The current air flow rate divided by the design air flow rate with values from 0.0 to 1.0.
Cooling Tower Operating Cells Count [][LINK]
This represents the number of cells operating at each time step.
Cooling Tower Basin Heater Electricity Rate [W][LINK]
Cooling Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower basin heater. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the water consumed by the wet cooling tower for external water sprays used to augment heat transfer. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during cooling tower operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to feed the cooling tower. If a water storage tank is used to provide water to the tower, then the following output variables will also be available.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank connections was not able to provide. The starved water is assumed to come from the mains. The tower’s operation is not affected by a lack of storage tank water.
CoolingTower:VariableSpeed[LINK]
The variable speed tower model is based on empirical curve fits of manufacturer’s performance data or field measurements. The user specifies tower performance at design conditions, and empirical curves are used to determine the approach temperature and fan power at off-design conditions. The user defines tower performance by entering the inlet air wet-bulb temperature, tower range, and tower approach temperature at the design conditions. The corresponding water flow rate (within ±25% of the tower’s rated water mass flow rate), air flow rate, and fan power must also be specified. The model will account for tower performance in the “free convection” regime, when the tower fan is off but the water pump remains on and heat transfer still occurs (albeit at a low level). Basin heater operation and makeup water usage (due to evaporation, drift, and blowdown) are also modeled.
The cooling tower seeks to maintain the temperature of the water exiting the cooling tower at (or below) a set point. The set point schedule is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first checks to determine the impact of “free convection” on the tower exiting water temperature. If the exiting water temperature based on “free convection” is at or below the set point, then the variable-speed tower fan is not turned on. If the exiting water temperature is above the set point after “free convection” is modeled, then the variable-speed tower fan is turned on to reduce the exiting water temperature. Tower fan power is calculated based on the tower air flow rate required to achieve the exiting water set point temperature.
Cooling towers here are “wet” and consume water through evaporation, drift, and blowdown. The model can be used to predict water consumed by the towers. The last six input fields are optional and provide methods of controlling details of the water consumption calculations. The user can specify connections to the rest of the buildings water system by providing the name of a WaterUse:Storage object.
For the operation of multi-cell towers, the first step is to determine the number of cells to operate based on the cell control method – between the minimum number of cells subject to the maximum water flow rate fraction per cell, and maximum number of cells subject to the minimum water flow rate fraction per cell. If the calculated cells do not meet the loads, additional cells will be operating to help meet the loads. Inside each cell, the existing capacity controls still apply.
For multi-cell towers, the following inputs are assumed to be for the entire tower including all cells:
Design Water Flow Rate; Design Air Flow Rate; Fan Power at Design Air Flow Rate;
Air Flow Rate in Free Convection Regime; Nominal Capacity; Free Convection Capacity
BASIN HEATER (we assume that there is a common basin)
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the variable speed cooling tower.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the cooling tower’s water outlet node.
Field: Model Type[LINK]
This alpha field contains the type of empirical model used to simulate the tower’s thermal performance (approach temperature). Valid choices for this field are “CoolToolsCrossFlow”, “CoolToolsUserDefined”, “YorkCalc”, or “YorkCalcUserDefined”. “CoolToolsCrossFlow” and “YorkCalc” are empirical models with the equation form and model coefficients already defined within EnergyPlus. If “CoolToolsUserDefined” or “YorkCalcUserDefined” is selected, the user must specify a valid Model Coefficient Name in the next input field to reference an appropriate CoolingTowerPerformance:CoolTools or CoolingTowerPerformance:YorkCalc object. If a user-defined model type is selected and the specified Model Coefficient Name is not found in the input data file (idf), then a severe message is issued and the simulation will terminate.
Field: Model Coefficient Name[LINK]
This alpha field contains the identifying name for the object(s) CoolingTowerPerformance:CoolTools or CoolingTowerPerformance:YorkCalc. A single model coefficient object may be used to define coefficients for multiple variable speed cooling tower objects (i.e., the same name may be used in this input field for more than one variable speed tower). This field is only used when the field Tower Model Type described above is set to “CoolToolsUserDefined” or “YorkCalcUserDefined”, and should be left blank otherwise.
Field: Design Inlet Air Wet-Bulb Temperature[LINK]
This numeric field specifies the inlet air wet-bulb temperature (˚C) at design conditions. This design temperature should correspond with the design values for range temperature, approach temperature, water flow rate, and air flow rate specified in the following fields. The minimum value for this field is 20˚C and the default value is 25.6˚C if this field is left blank.
Field: Design Approach Temperature[LINK]
This numeric field specifies the tower approach temperature (˚C) at design conditions. The approach temperature is the outlet water temperature minus the inlet air wet-bulb temperature. The design approach temperature should correspond with the design values for inlet air wet-bulb temperature, range temperature, water flow rate, and air flow rate specified for this tower. The value for this field must be greater than 0˚C and the default value is 3.9˚C if this field is left blank.
Field: Design Range Temperature[LINK]
This numeric field specifies the range temperature (˚C) at design conditions. The range temperature is defined as the inlet water temperature minus the outlet water temperature. The design range temperature should correspond with the design values for inlet air wet-bulb temperature, approach temperature, water flow rate, and air flow rate specified for this tower. The value for this field must be greater than 0˚C and the default value is 5.6˚C if this field is left blank.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the tower in m\(^{3}\)/s. The value entered should be within ±25% of the tower’s rated water mass flow rate as specified by the manufacturer if Model Type is “CoolToolsCrossFlow” or “YorkCalc”. This constraint may be different for Model Type “CoolToolsUserDefined” or “YorkCalcUserDefined” (ref. CoolingTowerPerformance:CoolTools or CoolingTowerPerformance:YorkCalc).
This value is the flow rate of the condenser loop water being cooled by the tower. A value greater than zero must be specified or this field can be autosized. A Plant Sizing object must be defined if the field is autosized and the design water flow rate is then derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections). The design water flow rate should correspond with the design values specified for the inlet air wet-bulb temperature, approach temperature, range temperature, and air flow rate. When this field is not autosized, the condenser loop flow rate specified in other objects should be within ±25% of the tower’s rated water flow rate (different range is permissible if Model Type is “User Defined”).
Field: Design Air Flow Rate[LINK]
This numeric field contains the design (maximum) air flow rate through the tower in m\(^{3}\)/s. A value greater than zero must be specified or this field can be autosized. Autosizing of this field does not require a Plant Sizing object since the design air flow rate is assumed to be the design fan power multiplied by a total fan efficiency of 0.5 and divided by a fan pressure rise of 190 Pascals. A correction for altitude is also included as follows:
\[Design\;Air\;Flow\;Rate = \frac{{0.5(Fan\;power\;at\;Design\;Air\;Flow\;Rate)}}{{190.}}\left( {\frac{{101325.}}{{{P_{atm}}}}} \right)\]
Field: Design Fan Power[LINK]
This numeric field contains the fan power in watts at the design (maximum) air flow rate through the tower. A value greater than zero must be specified or this field can be autosized. If autosized, a Plant Sizing object must be defined and the fan power is calculated as follows:
\[Design\,fan\;power = 0.0105\cdot {\rho_{water}}\cdot {C_{p,water}}\cdot Design\;Water\;Flow\;Rate\cdot Design\;Loop\Delta T\]
Field: Fan Power Ratio Function of Air Flow Rate Ratio Curve Name[LINK]
This alpha field contains the curve object name for fan power ratio (fan power/design fan power) as a function of air flow rate ratio (air flow rate/design air flow rate) [ref. Performance Curves]. The curve object must be a cubic curve and should be normalized to 1.0 at an air flow rate ratio of 1.0. If this field is left blank, a theoretical fan curve is assumed where fan power ratio is directly proportional to the air flow rate ratio cubed.
Field: Minimum Air Flow Rate Ratio[LINK]
This numeric field contains the minimum air flow rate ratio. The tower fan is allowed to operate between the ratio defined here and a maximum air flow rate ratio of 1.0 (which corresponds to the design [maximum] tower air flow rate). Below this value, the tower is assumed to operate either in the “free convection” regime with the tower fan off, or the tower fan is cycled on/off to maintain the exiting water set point temperature. The minimum air flow rate ratio must be greater than or equal to 0.2 and less than or equal to 0.5, with a default value of 0.2 if the field is left blank.
Field: Fraction of Tower Capacity in Free Convection Regime[LINK]
This numeric field contains the fraction of tower capacity available in the free convection regime (i.e., when the tower fan is off but water continues to flow through the tower). The tower fan does not operate when the free convection tower capacity is able to meet or exceed the exiting water set point temperature. The air flow rate through the tower in the free convection regime is assumed to be this same fraction of the tower design air flow rate. The fraction of tower capacity in free convection regime must be greater than or equal to 0 and less than or equal to 0.2, with a default value of 0.125 if this field is left blank.
Field: Basin Heater Capacity[LINK]
This numeric field contains the capacity of the tower’s electric basin heater in watts per degree Kelvin. This field is used in conjunction with the Basin Heater Setpoint Temperature described in the following field. The basin heater electric power is equal to this field multiplied by the difference between the basin heater set point temperature and the outdoor dry-bulb temperature. The basin heater only operates when the tower fan is off and water is not flowing through the tower, regardless of the basin heater schedule described below. The basin heater capacity must be greater than or equal to zero, with a default value of zero if this field is left blank.
Field: Basin Heater Setpoint Temperature[LINK]
This numeric field contains the set point temperature (˚C) for the basin heater described in the previous field. The basin heater is active when the outdoor air dry-bulb temperature falls below this setpoint temperature, as long as the tower fan is off and water is not flowing through the tower. This set point temperature must be greater than or equal to 2˚C, and the default value is 2˚C if this field is left blank.
Field: Basin Heater Operating Schedule Name[LINK]
This alpha field contains the name of the basin heater operating schedule. The basin heater operating schedule is assumed to be an on/off schedule and the heater is available to operate any time the schedule value is greater than 0. The basin heater operates when scheduled on and the outdoor air dry-bulb temperature is below the set point temperature described in the previous field. If this field is left blank, the basin heater is available to operate throughout the simulation. Regardless of this schedule, the basin heater may only operate when the cooling tower fan is off and water is not flowing through the tower.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the cooling tower. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the tower is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the cooling tower model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the cooling tower and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-degree Kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Typical values are from 0.15 to 0.27 [percent/K]. The default is 0.2.
Field: Drift Loss Percent[LINK]
This numeric field contains the percent (%) of design water flow rate lost to the atmosphere at the design air flow rate due to drift, which is water droplets that are entrained in the airstream as it passes through the tower. Drift is assumed to vary directly with tower air flow rate ratio, and is in addition to the amount of water lost to the atmosphere due to evaporation and/or blowdown. Typical values for water usage due to drift are from 0.05 to 0.2% of the total water circulation rate with currently-available drift eliminators from tower manufacturers. The value entered in this field must be greater than or equal to zero, and the default value is 0.008%.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ‘ConcentrationRatio’ or ‘ScheduledRate’. The choice will determine which of the two models below is used. The default is ConcentrationRatio.
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the cooling tower as a function of the rate of evaporation. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m\(^{3}\)/s) flushed from the basin on a periodic basis to purge the condenser loop of mineral scale build-up and other contaminants. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Typical values range from 0.0002 to 0.0013 m\(^{3}\)/s (17.3 to 112.3 m\(^{3}\)/day). This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the cooling tower is active and water is flowing through the tower (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the tower obtains water used for evaporative cooling. If blank or omitted, then the tower will obtain water directly from the mains. If the name of a WaterUser:Storage object is used here, then the tower will obtain its water from that tank. If a tank is specified, the tower will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the tower needs, then the tower will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the cooling tower. If this field is left blank, the outdoor air conditions entering the cooling tower are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field: Number of Cells[LINK]
This integer field contains the number of cells in the multi-cell cooling tower. If not entered, the program will assume it is a single-cell cooling tower
Field: Cell Control[LINK]
This alpha field specifies the method used to control the number of cells used to meet the load, the two choices are:
MinimalCell: the program will use minimal number of cells needed, all other cells will be shut down with no water flow. It will attempt to use as few cells as possible to cool the fluid. In no case, however, will the flow per cell be allowed to exceed its maximum value defined by the Maximum Water Flow Rate Fraction.
MaximalCel : As many cells as possible will be turned on. In no case, however, will the flow per cell be allowed to drop below its minimum value specified by the Minimum Water Flow Rate Fraction.
If this field is left blank, the default value is MaximalCell.
Field: Cell Minimum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable smallest fraction of the design water flow rate. Flows less than this value will commonly result in fluid distribution problems; the pressure at each nozzle will be too weak for the fluid to be sprayed out in the correct pattern, not all the fill would be wet. If this field is left blank, the default value is 0.33.
Field: Cell Maximum Water Flow Rate Fraction[LINK]
This numeric field specifies the allowable largest fraction of the design water flow rate. If this field is left blank, the default value is 2.5.
Field: Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature.For this component the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Design Air Flow Rate;
3. Design Fan Power.
Field: End-Use Subcategory[LINK]
This optional field allows you to specify a user-defined end-use subcategory, e.g., “Process”. A new meter for reporting is created for each unique subcategory (ref: Output:Meter objects). Any text may be used here to further subcategorize the end-uses in the ABUPS End Uses by Subcategory table and in the LEED Summary EAp2-4/5 Performance Rating Method Compliance table. If this field is omitted or blank, the cooling tower will be assigned to the “General” end-use subcategory.
An example IDF specification for this object is shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Fan Part Load Ratio
HVAC,Average,Cooling Tower Air Flow Rate Ratio
HVAC,Average,Cooling Tower Operating Cells Count
A tower uses either mains water or storage tank for make-up water.
When mains water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
When storage tank water is used:
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Sum,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Drift Volume [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
IF specified:
HVAC,Average,Cooling Tower Basin Heater Electricity Rate [W]
HVAC,Sum,Cooling Tower Basin Heater Electricity Energy [J]
Cooling Tower Fan Electricity Rate [W][LINK]
Cooling Tower Fan Electricity Energy [J][LINK]
These outputs are the electric power input to the tower fan. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Fan Part Load Ratio [][LINK]
This is the on/off cycling rate of the tower fan when free convection cannot meet the set point temperature and the tower capacity at the minimum air flow rate ratio drives the tower exiting water temperature below the set point temperature. The fan part-load ratio is calculated as the ratio of the exiting water temperature in the free convection regime minus the exiting water temperature set point divided by the exiting water temperature in the free convection regime minus the exiting water temperature at the minimum air flow rate ratio. If tower air flow is at or above the minimum air flow rate ratio, then the tower fan part-load ratio is 1.0.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the tower.
Cooling Tower Inlet Temperature [C][LINK]
Cooling Tower Outlet Temperature [C][LINK]
Cooling Tower Mass Flow Rate [kg/s][LINK]
These outputs are the tower water inlet and outlet temperatures, and mass flow rate of the circulating condenser water loop.
Cooling Tower Air Flow Rate Ratio [][LINK]
This is the ratio of air flow through the tower to the design air flow rate. During times when the tower can maintain the condenser loop set point temperature using free convection (when the fan in not operating), the air flow rate ratio is assumed to be equal to the field Fraction of Tower Capacity in Free Convection Regime. During times when the fan cycles on/off to maintain the outlet water set point temperature, the air flow rate ratio is calculated as the summation of Fan Part-Load Ratio multiplied by the Minimum Air Flow Rate Ratio and (1.0 - Fan Part-Load Ratio) multiplied by the fraction of Tower Capacity in Free Convection Regime.
Cooling Tower Basin Heater Electricity Rate [W][LINK]
Cooling Tower Basin Heater Electricity Energy [J][LINK]
These outputs are the electric power input to the tower basin heater. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the water consumed by the wet cooling tower for external water sprays used to augment heat transfer. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during cooling tower operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
This is the volume of water drawn from mains service to feed the cooling tower. If a water storage tank is used to provide water to the tower, then the following output variables will also be available.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Storage Tank connections was not able to provide. The starved water is assumed to come from the mains. The tower’s operation is not affected by a lack of storage tank water.
Cooling Tower Operating Cells Count [][LINK]
This represents the number of cells operating at each time step.
CoolingTowerPerformance:CoolTools[LINK]
Variable speed cooling towers can be modeled by EnergyPlus with user-selectable performance based on the CoolTools correlation, YorkCalc correlation, or user-defined coefficients for either the CoolTools or YorkCalc correlations.The empirical CoolTools tower correlation uses a set of 35 coefficients to model the thermal performance (approach temperature) of a cooling tower based on four independent variables. If the user specifies Model Type = CoolToolsCrossFlow in the CoolingTower:VariableSpeed object, then the 35 coefficients derived for the CoolTools simulation model are used and these coefficients are already defined within EnergyPlus. If the user specifies Model Type = CoolToolsUserDefined, then the user must enter a CoolingTowerPerformance:CoolTools object to define the 35 coefficients that will be used by the CoolTools correlation.
The user must specify a name for the model coefficient object, and this name must be used in the CoolingTower:VariableSpeed object (field Model Coefficient Name) to tell the program to use these coefficients. Next, the user enters the minimum and maximum values for inlet air wet-bulb temperature, range temperature, approach temperature, and water mass flow rate ratio to specify the valid range for which the model coefficients were derived. For all of these variables, the program issues warnings if the actual values are beyond the minimum/maximum values specified. For inlet air wet-bulb temperature and water mass flow rate ratio, the values of these variables used in the calculation of approach temperature are limited to be within the valid minimum/maximum range specified. For approach and range, the warnings are issued if the values are beyond the specified minimum/maximum range but the actual values are still used.
The CoolTools correlation has four independent variables: inlet air wet-bulb temperature (Twb), tower range temperature (Tr), water flow rate ratio (FRwater), and air flow rate ratio (FRair). Temperatures are in units of ˚C and flow rate ratios are dimensionless (actual flow rate divided by design flow rate). Using these independent variables, tower approach temperature (˚C) is calculated as follows:
Approach = Coeff(1) + Coeff(2)•FRair + Coeff(3)•(FRair)\(^{2}\) +
Coeff(4)•(FRair)\(^{3}\) + Coeff(5)•FRwater +
Coeff(6)•FRair•FRwater + Coeff(7)•(FRair)\(^{2}\)•FRwater +
Coeff(8)•(FRwater)\(^{2}\) + Coeff(9)•FRair•(FRwater)\(^{2}\) +
Coeff(10)•(FRwater)\(^{3}\) + Coeff(11)•Twb + Coeff(12)•FRair•Twb +
Coeff(13)•(FRair)\(^{2}\)•Twb + Coeff(14)•FRwater•Twb +
Coeff(15)•FRair•FRwater•Twb + Coeff(16)•(FRwater)\(^{2}\)•Twb +
Coeff(17)•(Twb)\(^{2}\) + Coeff(18)•FRair•(Twb)\(^{2}\) +
Coeff(19)•FRwater•(Twb)\(^{2}\) + Coeff(20)•(Twb)\(^{3}\) + Coeff(21)•Tr +
Coeff(22)•FRair•Tr + Coeff(23)•FRair•FRair•Tr +
Coeff(24)•FRwater•Tr + Coeff(25)•FRair•FRwater•Tr +
Coeff(26)•(FRwater)\(^{2}\)•Tr + Coeff(27)•Twb•Tr +
Coeff(28)•FRair•Twb•Tr + Coeff(29)•FRwater•Twb•Tr +
Coeff(30)•(Twb)\(^{2}\)•Tr + Coeff(31)•(Tr)\(^{2}\) + Coeff(32)•FRair•(Tr)\(^{2}\) +
Coeff(33)•FRwater•(Tr)\(^{2}\) + Coeff(34)•Twb•(Tr)\(^{2}\) + Coeff(35)•(Tr)\(^{3}\)
This object allows the user to specify model coefficients for use with the CoolTools correlation shown above. It is recommended that a broad set of cooling tower performance data be used to generate these model coefficients. The data set used to create the model coefficients should cover the entire range of water and air flow rate ratios and inlet air wet-bulb, range, and approach temperatures expected during the simulation.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the variable speed cooling tower model coefficients.
Field: Minimum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the minimum inlet air wet-bulb temperature to be used by the model (approach temperature correlation). Inlet air wet-bulb temperatures less than this value will not be used; instead, the minimum inlet air wet-bulb temperature specified here will be used by the correlation and a warning will be issued.
Field: Maximum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the maximum inlet air wet-bulb temperature to be used by the model (approach temperature correlation). Inlet air wet-bulb temperatures greater than this value will not be used; instead, the maximum inlet air wet-bulb temperature specified here will be used by the correlation and a warning will be issued.
Field: Minimum Range Temperature[LINK]
This numeric field contains the minimum range temperature (inlet water temperature minus outlet water temperature) to be used by the empirical model. If the range temperature is less than this value the actual range temperature is still passed to the empirical model but a warning will be issued.
Field: Maximum Range Temperature[LINK]
This numeric field contains the maximum range temperature (inlet water temperature minus outlet water temperature) to be used by the empirical model. If the range temperature is greater than this value the actual range temperature is still passed to the empirical model but a warning will be issued.
Field: Minimum Approach Temperature[LINK]
This numeric field contains the minimum approach temperature (outlet water temperature minus inlet air wet-bulb temperature) to be used by the empirical model. If the calculated approach temperature is less than this value then the calculated value is still used but a warning will be issued.
Field: Maximum Approach Temperature[LINK]
This numeric field contains the maximum approach temperature (outlet water temperature minus inlet air wet-bulb temperature) to be used by the empirical model. If the calculated approach temperature is greater than this value then the calculated value is still used but a warning will be issued.
Field: Minimum Water Flow Rate Ratio[LINK]
This numeric field contains the minimum water flow rate ratio (ratio of actual water flow rate to rated water flow rate) to be used by the empirical model. Water flow rate ratios less than this value will not be used; instead, the minimum water flow rate ratio specified here will be used by the model and a warning will be issued.
Field: Maximum Water Flow Rate Ratio[LINK]
This numeric field contains the maximum water flow rate ratio (ratio of actual water flow rate to rated water flow rate) to be used by the empirical model. Water flow rate ratios greater than this value will not be used; instead, the maximum water flow rate ratio specified here will be used by the model and a warning will be issued.
Field: Coefficient 1 to 35[LINK]
These numeric fields contain the coefficients to be used by the CoolTools approach temperature correlation shown above.
An example IDF specification for this object is shown below:
Outputs[LINK]
No additional cooling tower output variables are output when this object is used.
CoolingTowerPerformance:YorkCalc[LINK]
Variable speed cooling towers can be modeled by EnergyPlus with user-selectable performance based on the CoolTools correlation, YorkCalc correlation, or user-defined coefficients for either the CoolTools or YorkCalc correlations.The empirical YorkCalc tower correlation uses a set of 27 coefficients to model the thermal performance (approach temperature) of a variable speed cooling tower based on three independent variables. If the user specifies Tower Model Type = YorkCalc in the CoolingTower:VariableSpeed object, then the 27 coefficients derived for the YorkCalc simulation model are used and these coefficients are already defined within EnergyPlus. If the user specifies Tower Model Type = YorkCalcUserDefined, then the user must enter a CoolingTowerPerformance:YorkCalc object to define the 27 coefficients that will be used by the YorkCalc correlation.
The user must specify a name for the model coefficient object, and this name must be used in the CoolingTower:VariableSpeed object (field Model Coefficient Name) to tell the program to use these coefficients. Next, the user enters the minimum and maximum values for inlet air wet-bulb temperature, range temperature, approach temperature, and water mass flow rate ratio to specify the valid range for which the model coefficients were derived. The user also specifies the maximum valid liquid-to-gas ratio. For all of these variables, the program issues warnings if the actual values are beyond the minimum/maximum values specified. For inlet air wet-bulb temperature and water mass flow rate ratio, the values of these variables used in the calculation of approach temperature are limited to be within the valid minimum/maximum range specified. For approach, range, and liquid-to-gas ratio the warnings are issued if the values are beyond the specified minimum/maximum range but the actual values are still used.
The YorkCalc correlation has three independent variables: inlet air wet-bulb temperature (Twb), tower range temperature (Tr), and the liquid-to-gas ratio (ratio of water flow rate ratio to air flow rate ratio = LGRatio). Temperatures are in units of ˚C and liquid-to-gas ratio is dimensionless. Using these independent variables, an approach temperature (˚C) is calculated as follows:
Approach = Coeff(1) + Coeff(2)•Twb + Coeff(3)•Twb\(^{2}\) + Coeff(4)•Tr +
Coeff(5)•Twb•Tr + Coeff(6)•Twb\(^{2}\)•Tr + Coeff(7)•Tr\(^{2}\) +
Coeff(8)•Twb•Tr\(^{2}\) + Coeff(9)•Twb\(^{2}\)•Tr\(^{2}\) + Coeff(10)•LGRatio +
Coeff(11)•Twb•LGRatio + Coeff(12)•Twb\(^{2}\)•LGRatio +
Coeff(13)•Tr•LGRatio + Coeff(14)•Twb•Tr•LGRatio +
Coeff(15)•Twb\(^{2}\)•Tr•LGRatio + Coeff(16)•Tr\(^{2}\)•LGRatio +
Coeff(17)•Twb•Tr\(^{2}\)•LGRatio + Coeff(18)•Twb\(^{2}\)•Tr\(^{2}\)•LGRatio +
Coeff(19)•LGRatio\(^{2}\) + Coeff(20)•Twb•LGRatio\(^{2}\) +
Coeff(21)• Twb\(^{2}\)•LGRatio\(^{2}\) + Coeff(22)•Tr•LGRatio\(^{2}\) +
Coeff(23)•Twb•Tr•LGRatio\(^{2}\) + Coeff(24)•Twb\(^{2}\)•Tr•LGRatio\(^{2}\) +
Coeff(25)•Tr\(^{2}\)•LGRatio\(^{2}\) + Coeff(26)•Twb•Tr\(^{2}\)•LGRatio\(^{2}\) +
Coeff(27)•Twb\(^{2}\)•Tr\(^{2}\)•LGRatio\(^{2}\)
This object allows the user to specify model coefficients for use with the YorkCalc correlation shown above. It is recommended that a broad set of cooling tower performance data be used to generate these model coefficients. The data set used to create the model coefficients should cover the entire range of water and air flow rate ratios and inlet air wet-bulb, range, and approach temperatures expected during the simulation.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the variable speed cooling tower model coefficients.
Field: Minimum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the minimum inlet air wet-bulb temperature to be used by the model (approach temperature correlation). Inlet air wet-bulb temperatures less than this value will not be used; instead, the minimum inlet air wet-bulb temperature specified here will be used by the correlation and a warning will be issued.
Field: Maximum Inlet Air Wet-Bulb Temperature[LINK]
This numeric field contains the maximum inlet air wet-bulb temperature to be used by the model (approach temperature correlation). Inlet air wet-bulb temperatures greater than this value will not be used; instead, the maximum inlet air wet-bulb temperature specified here will be used by the model and a warning will be issued.
Field: Minimum Range Temperature[LINK]
This numeric field contains the minimum range temperature (inlet water temperature minus outlet water temperature) to be used by the empirical model. If the range temperature is less than this value the actual range temperature is still passed to the empirical model but a warning will be issued.
Field: Maximum Range Temperature[LINK]
This numeric field contains the maximum range temperature (inlet water temperature minus outlet water temperature) to be used by the empirical model. If the range temperature is greater than this value the actual range temperature is still passed to the empirical model but a warning will be issued.
Field: Minimum Approach Temperature[LINK]
This numeric field contains the minimum approach temperature (outlet water temperature minus inlet air wet-bulb temperature) to be used by the empirical model. If the calculated approach temperature is less than this value then the calculated value is still used but a warning will be issued.
Field: Maximum Approach Temperature[LINK]
This numeric field contains the maximum approach temperature (outlet water temperature minus inlet air wet-bulb temperature) to be used by the empirical model. If the calculated approach temperature is greater than this value then the calculated value is still used but a warning will be issued.
Field: Minimum Water Flow Rate Ratio[LINK]
This numeric field contains the minimum water flow rate ratio (ratio of actual water flow rate to rated water flow rate) to be used by the empirical model. Water flow rate ratios less than this value will not be used; instead, the minimum water flow rate ratio specified here will be used by the model and a warning will be issued.
Field: Maximum Water Flow Rate Ratio[LINK]
This numeric field contains the maximum water flow rate ratio (ratio of actual water flow rate to rated water flow rate) to be used by the empirical model. Water flow rate ratios greater than this value will not be used; instead, the maximum water flow rate ratio specified here will be used by the model and a warning will be issued.
Field: Maximum Liquid to Gas Ratio[LINK]
This numeric field contains the maximum liquid-to-gas ratio (ratio of actual water flow rate ratio [capped to be within the minimum/maximum water flow rate ratio defined above as necessary] to actual air flow rate ratio) to be used by the empirical model. If the liquid-to-gas ratio is greater than this value the actual liquid to gas ratio is still passed to the empirical model but a warning will be issued.
Field: Coefficient 1 to 27[LINK]
These numeric fields contain the coefficients to be used by the YorkCalc approach temperature correlation shown above.
An example IDF specification for this object is shown below:
Outputs[LINK]
No additional cooling tower output variables are output when this object is used.
EvaporativeFluidCooler:SingleSpeed[LINK]
Evaporative fluid coolers are components that may be assigned to condenser loops. The Evaporative fluid cooler is modeled as a counter flow heat exchanger with single-speed fans (induced draft configuration). The user must define fluid cooler performance via one of three methods: design heat transfer coefficient-area product (UA) and design water flow rate, or standard fluid cooler design capacity at a specific rating point or design capacity at non standard conditions. Regardless of which method is chosen, the design airflow rate and corresponding fan power must be specified.
The evaporative fluid cooler seeks to maintain the temperature of the water exiting the evaporative fluid cooler at (or below) a set point. The set point schedule value is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first checks to see whether inlet water temperature is at or below the set point. If so, then the fluid cooler fan is not turned on and all the flow goes through bypass. If the inlet water temperature is above the set point then the fluid cooler fan is turned on to reduce the exiting water temperature to the set point. If the capacity control is FanCycling, the model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., fluid cooler fan on for the entire simulation timestep and fluid cooler fan off for the entire simulation timestep). Cyclic losses are not taken into account. If the capacity control is FluidBypass, the model determines the fraction of water flow to be bypassed while the remaining water goes through the fluid cooler cooling media and gets cooled, then the two water flows mix to meet the setpoint temperature. In this case, the fan runs at full speed for the entire timestep.
Evaporative fluid coolers consume water through evaporation, drift, and blowdown. The model can be used to predict water consumed by the fluid coolers. For this purpose, the last seven input fields can either be provided in the input or if nothing is specified then the default values for these fields will be used. These fields provide the methods of controlling details of the water consumption calculations. The user can specify connections to the rest of the building’s water system by providing the name of a water storage tanks (i.e. WaterUse:Storage objects). The schematic of the system is shown below:
Where,
h = Enthalpy (j/kg-K)
m = mass flow rate (kg/s)
Subscripts
a = air
w = water
wb = wet-bulb
in = inlet
out = outlet
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the fluid cooler.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water outlet node.
Field: Design Air Flow Rate[LINK]
This numeric field contains the design air flow rate induced by the fluid cooler fan in m\(^{3}\)/s. The field must contain a value greater than zero regardless of the fluid cooler performance input method. Alternately, this field can be autosized. See Engineering Reference document for autosizing calculations.
Field: Design Air Flow Rate Fan Power[LINK]
This numeric field contains the fan power (in watts) at the design air flow rate specified in the previous field. The field must contain a value greater than zero regardless of the fluid cooler performance input method. Alternately, this field can be autosized. See Engineering Reference document for autosizing calculations.
Field: Design Spray Water Flow Rate[LINK]
This numeric field contains the design spray water flow rate through the fluid cooler in m\(^{3}\)/s. A value greater than zero must be specified regardless of the performance input method,
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify fluid cooler performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “StandardDesignCapacity” or “UserSpecifiedDesignCapacity”.
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the fluid cooler. If this field is left blank, the outdoor air conditions entering the fluid cooler are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field: Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of actual tower heat rejection to nominal capacity. This ratio is defined at entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. Historically this ratio has been set at 1.25 based on the assumption that the tower must dissipate 0.25 W of compressor power for every what of heat removed at the chiller evaporator. The default is 1.25.
Field: Standard Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal capacity (3 gpm/ton). 125% of this capacity gives the actual fluid cooler heat rejection at these operating conditions (based on historical assumption that the evaporative fluid cooler must dissipate 0.25W of compressor heat for every watt of heat removed by the evaporator). This field is only used for performance input method = “StandardDesignCapacity”. For other input methods this field is ignored. The standard conditions mentioned above for “standard design capacity” are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (ref. CondenserLoop object).
Field: Design Air Flow Rate U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design fluid cooler UA value is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), the fluid cooler inlet air dry-bulb and wetbulb temperature are taken from the input. This field is only used for performance input method = ” UFactorTimesAreaAndDesignWaterFlowRate”. For other performance input methods, this field is ignored.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the fluid cooler in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the fluid cooler. This field is ignored for the “StandardDesignCapacity” performance input method. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections).
Field: User Specified Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts. Design conditions for this capacity i.e. entering air dry-bulb temperature, entering air wet-bulb temperature and entering water temperature must be provided in the input. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored.
Field:Design Entering Water Temperature[LINK]
This numeric field contains entering water temperature at nominal conditions in degrees Celsius. The design entering water temperature must be greater than the design entering air temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field is autosizable and defaults to autosize (which means it will take the value from the corresponding Sizing:Plant object).
Field:Design Entering Air Temperature[LINK]
This numeric field contains entering air dry-bulb temperature at nominal conditions in degrees Celsius. The design entering air temperature must be greater than the design entering air wet-bulb temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field defaults to 35.0C.
Field:Design Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb temperature at nominal conditions in degrees Celsius. The design entering air wet-bulb temperature must be less than the design entering air (dry-bulb) temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field defaults to 25.6C.
Field: Capacity Control[LINK]
This alpha field contains the cooling capacity control for the evaporative fluid cooler. Two choices are available: FanCycling and FluidBypass. During part-load conditions, there are two ways to maintain the exiting water temperature at the setpoint: either cycling the evaporative fluid cooler fan, or bypassing portion of the evaporative fluid cooler water with a three-way valve. For FluidBypass, the evaporative fluid cooler fan still runs at full speed for the entire timestep, but only portion of the water flow goes through the evaporative fluid cooler media to get cooled while the remaining portion of the water flow gets bypassed. Two water flows then mix at the common water sump to meet the setpoint temperature.
Field: Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature. For this component the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Design Air Flow Rate;
3. Fan Power at Design Air Flow Rate;
4. U-Factor Times Area Value at Design Air Flow Rate;
Note that the U-Factor Times Area Value at Design Air Flow Rate is not multiplied by the Sizing Factor. Instead the design evaporative fluid cooler load is multiplied by the sizing factor and the design UA then calculated as usual.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the evaporative fluid cooler. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the evaporative fluid cooler is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the evaporative fluid cooler model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the evaporative fluid cooler and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Empirical correlation is used to calculate default loss factor if it not explicitly specified in the input file.
Field: Drift Loss Percent[LINK]
This field is used to specify the rate of water lost to the exiting air as entrained droplets [%]. The drift loss is a percent of the condenser water flow. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ConcentrationRatio or ScheduledRate. The choice will determine which of the two models below is used. The default is ConcentrationRatio.
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the evaporative fluid cooler as a function of the rate of evaporation. Blowdown is water intentionally drained from the evaporative fluid cooler in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m3/s) flushed from the basin on a periodic basis to purge the evaporative fluid cooler of mineral scale build-up and other contaminants. This schedule is only used if the Blowdown Calculation Mode is set to ScheduledRate. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the evaporative fluid cooler is active and water is flowing through the evaporative fluid cooler (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the evaporative fluid cooler obtains water used for evaporative cooling. If blank or omitted, then the evaporative fluid cooler will obtain water directly from the mains. If the name of a WaterUse:Storage object is used here, then the evaporative fluid cooler will obtain its water from that tank. If a tank is specified, the evaporative fluid cooler will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the evaporative fluid cooler needs, then the evaporative fluid cooler will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
An IDF specification for this object is shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Bypass Fraction []
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Evaporative Fluid Cooler Water Drift [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
If Supply Water Storage Tank Name is specified:
HVAC,Average,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Average,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
Cooling Tower Fan Electricity Rate [W][LINK]
The average electric power consumption of the fluid cooler fan in Watts for the timestep being reported.
Cooling Tower Fan Electricity Energy [J][LINK]
Fan energy use in Joules. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the average rate, in Watts, at which heat is removed from the condenser water loop by the fluid cooler for the time step being reported.
Cooling Tower Inlet Temperature [C][LINK]
The fluid temperature at the fluid cooler inlet in degrees Celsius.
Cooling Tower Outlet Temperature [C][LINK]
The fluid temperature at the fluid cooler outlet in degrees Celsius.
Cooling Tower Mass Flow Rate [kg/s][LINK]
The average fluid mass flow rate through the fluid cooler in kg/s for the time step being reported.
Cooling Tower Bypass Fraction [][LINK]
This output is the average fluid bypass fraction for the time step being reported. See Capacity Control input field.
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the external spray water consumed by the evaporative fluid cooler. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during fluid cooler operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
The volume of make up water provided by the mains in cubic meters. If no Supply Water Storage Tank is specified, then all fluid cooler make up water is provided by the mains (same as Cooling Tower Make Up Water Volume). If a Supply Water Storage Tank is specified, then the make up from the mains only occurs when sufficient water supply is not available from the tank (same as Evaporative Fluid Cooler Water Starved by Storage Tank). This output variable is metered on HeatRejection:MainsWater, MainsWater:Plant and MainsWater:Facility.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Supply Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Supply Water Storage Tank was not able to provide. The starved water is assumed to come from the mains. The fluid cooler’s operation is not affected by a lack of storage tank water.
EvaporativeFluidCooler:TwoSpeed[LINK]
The two-speed evaporative fluid cooler is modeled in a similar fashion to the single-speed evaporative fluid cooler. The evaporative fluid cooler is modeled as a counter flow heat exchanger with two-speed fan (induced draft configuration. See schematic diagram in Evaporative[FluidCooler:SingleSpeed](../input-output-reference/group-condenser-equipment.html#fluidcoolersinglespeed) section). The user must define fluid cooler performance via one of the three methods: design heat transfer coefficient-area product (UA) and design water flow rate, or standard fluid cooler design capacity at a specific rating point or design capacity at non standard conditions. Regardless of which method is chosen, the design airflow rate and corresponding fan power must be specified.
The evaporative fluid cooler seeks to maintain the temperature of the water exiting the evaporative fluid cooler at (or below) a set point. The set point schedule value is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first checks to see whether inlet water temperature is at or below the set point. If so, then the fluid cooler fan is not turned on and all the flow goes through bypass. If the inlet water temperature is above the set point then the fluid cooler fan is turned on at low speed to reduce the exiting water temperature to the set point. If operating the fluid cooler fan at low speed does not reduce the exiting water temperature to the set point, then the fluid cooler fan is increased to its high speed.
The model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., fluid cooler fan at high speed for the entire simulation timestep and fluid cooler fan at low speed for the entire simulation timestep, or fluid cooler fan at low speed for the entire simulation timestep and fluid cooler fan off for the entire simulation timestep). Cyclic losses are not taken into account.
Evaporative fluid coolers consume water through evaporation, drift, and blowdown. The model can be used to predict water consumed by the evaporative fluid coolers. For this purpose, the last seven input fields can either be provided in the input or if nothing is specified then the default values for these fields will be used. These fields provide methods of controlling details of the water consumption calculations. The user can specify connections to the rest of the buildings water system by providing the name of a water storage tanks (i.e. WaterUse:Storage objects).
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the fluid cooler.
Field: WaterInlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water outlet node.
Field: High Fan Speed Air Flow Rate[LINK]
This numeric field contains the fluid cooler air flow rate at high fan speed in m\(^{3}\)/s. A value greater than zero must be defined regardless of fluid cooler performance input method. Alternately, this field can be autosized. See Engineering Reference document for fluid cooler autosizing.
Field: High Fan Speed Fan Power[LINK]
This numeric field contains the fan power (in Watts) at the high-speed air flow rate specified in the previous field. A value greater than zero must be specified regardless of fluid cooler performance input method, or this field can be autosized. See Engineering Reference document for fluid cooler autosizing.
Field: Low Fan Speed Air Flow Rate[LINK]
This numeric field contains the fluid cooler air flow rate at low fan speed in m\(^{3}\)/s. This value must be greater than zero, less than the value specified for the field “Air Flow Rate at High Fan Speed”. This field may be autocalculated, in which case it is set to a fraction of the “Air Flow Rate at High Fan Speed” determined in the following field.
Field: Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor for calculating the low fan speed air flow rate as a fraction of the high fan speed air flow rate. The default is 0.5.
Field: Low Fan Speed Fan Power[LINK]
This numeric field contains the fan power (in Watts) at the low-speed air flow rate specified in the previous field. This value must be specified greater than zero or the field may be autocalculated, in which case it is set to a fraction of the “Fan Power at High Fan Speed” determined in the following field.
Field: Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor for calculating the low fan speed fan power as a fraction of the high fan speed fan power. The default is 0.16.
Field: Design Spray Water Flow Rate[LINK]
This numeric field contains the design spray water flow rate through the fluid cooler in m\(^{3}\)/s. This input field must be specified for all the performance input methods.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify fluid cooler performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “StandardDesignCapacity” or “UserSpecifiedDesignCapacity”.
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the fluid cooler. If this field is left blank, the outdoor air conditions entering the fluid cooler are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Field: Heat Rejection Capacity and Nominal Capacity Sizing Ratio[LINK]
This numeric field contains the value for the ratio of actual tower heat rejection to nominal capacity. This ratio is defined at entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. Historically this ratio has been set at 1.25 based on the assumption that the tower must dissipate 0.25 W of compressor power for every what of heat removed at the chiller evaporator. The default is 1.25.
Field: High Speed Standard Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal capacity (3 gpm/ton). The Heat Rejection Capacity and Nominal Capacity Sizing Ratio set in the previous field is applied to this capacity to give the actual fluid cooler heat rejection at these operating conditions. This field is only used for performance input method = “StandardDesignCapacity”. For other input methods this field is ignored. The standard conditions mentioned above for “standard design capacity” are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (ref. CondenserLoop object).
Field: Low Speed Standard Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts, with entering water at 35C (95F), leaving water at 29.4C (85F), entering air at 25.6C (78F) wetbulb and 35C (95F) drybulb temperatures. The design water flow rate is assumed to be 5.382E-8 m\(^{3}\)/s per watt of nominal capacity (3 gpm/ton). The Heat Rejection Capacity and Nominal Capacity Sizing Ratio is applied to this capacity to give the actual fluid cooler heat rejection at these operating conditions. This field is only used for performance input method = “StandardDesignCapacity”. For other input methods this field is ignored. The standard conditions mentioned above for “standard design capacity” are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (ref. CondenserLoop object). The value specified for this field must be greater than zero but less than the value specified for the field “High-Speed Standard Design Capacity”. This field may be autocalculated, in which case it is set to a fraction of the High-Speed Standard Design Capacity determined in the following field.
Field: Low Speed Standard Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Speed Standard Design Capacity. The default is 0.5.
Field: High Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the high speed design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 2,100,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design fluid cooler UA value is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), the fluid cooler inlet air dry-bulb and wetbulb temperature are taken from the input. This field is only used for performance input method = ” UFactorTimesAreaAndDesignWaterFlowRate”. For other input methods this field is ignored.
Field: Low Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per degree Kelvin corresponding to the low speed design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 and less than the value specified for the field “U-Factor Times Area Value at High Fan Speed” must be defined. This field may be autocalculated, in which case it is set to a factor of the “U-Factor Times Area Value at High Fan Speed” determined in the following field. This field is only used for performance input method = ” UFactorTimesAreaAndDesignWaterFlowRate”. For other input methods this field is ignored.
Field: Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This field contains the sizing factor to use when calculating the Low Fan Speed U-Factor Times Area Value. The default is 0.6.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the fluid cooler in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the fluid cooler. This field is ignored for the “StandardDesignCapacity” performance input method. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections).
Field: High Speed User Specified Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts. Design conditions for this capacity i.e. entering air dry-bulb temperature, entering air wet-bulb temperature and entering water temperature must be provided in the input. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored.
Field: Low Speed User Specified Design Capacity[LINK]
This numeric input field contains the heat rejection capacity of the fluid cooler in watts. Design conditions for this capacity i.e. entering air dry-bulb temperature, entering air wet-bulb temperature and entering water temperature must be provided in the input. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field may be autocalculated, in which case it is set to a fraction of the “High Speed User Specified Design Capacity” determined in the following field.
Field: Low Speed User Specified Design Capacity Sizing Factor[LINK]
This field contains the sizing factor to use when calculating the Low-Speed User Specified Design Capacity. The default is 0.5.
Field:Design Entering Water Temperature[LINK]
This numeric field contains entering water temperature at nominal conditions in degrees Celsius. The design entering water temperature must be greater than the design entering air temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field is autosizable and defaults to autosize (which means it will take the value from the corresponding Sizing:Plant object).
Field:Design Entering Air Temperature[LINK]
This numeric field contains entering air dry-bulb temperature at nominal conditions in degrees Celsius. The design entering air temperature must be greater than the design entering air wet-bulb temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field defaults to 35.0C.
Field:Design Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb temperature at nominal conditions in degrees Celsius. The design entering air wet-bulb temperature must be less than the design entering air (dry-bulb) temperature. Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other performance input methods this field is ignored. This field defaults to 25.6C.
Field: High Speed Sizing Factor[LINK]
This optional numeric field allows the user to specify a sizing factor for this component. The sizing factor is used when the component design inputs are autosized: the autosizing calculations are performed as usual and the results are multiplied by the sizing factor. Sizing factor allows the user to size a component to meet part of the design load while continuing to use the autosizing feature. For this component the inputs that would be altered by the sizing factor are:
1. Design Water Flow Rate;
2. Air Flow Rate at High Fan Speed;
3. Fan Power at High Fan Speed;
4. U-Factor Times Area Value at High Fan Speed;
5. Air Flow Rate at Low Fan Speed;
6. Fan Power at Low Fan Speed;
7. U-Factor Times Area Value at Low Fan Speed;
Note that the U-Factor Times Area Value at High Fan Speed is not multiplied by the Sizing Factor. Instead the design evaporative fluid cooler load is multiplied by the sizing factor and the design UA then calculated as usual. The U-Factor Times Area Value at Low Fan Speed is set to Low Fan Speed U-Factor Times Area Sizing Factor times the full load design UA.
Field: Evaporation Loss Mode[LINK]
This field is used to choose which method is used to model the amount of water evaporated by the evaporative fluid cooler. There are two options: LossFactor or SaturatedExit. The default is SaturatedExit. The user-defined loss factor is entered in the following field. By assuming that the air leaving the evaporative fluid cooler is saturated, the evaporation can be directly calculated using moist air engineering calculations with data available within the evaporative fluid cooler model (and does not require additional user input).
Field: Evaporation Loss Factor[LINK]
This field is used to specify the rate of water evaporated from the evaporative fluid cooler and lost to the outside air [percent/K]. This field is only used if the Evaporation Calculation Mode is set to LossFactor. The evaporation loss is then calculated as a fraction of the circulating condenser water flow and varies with the temperature change in the condenser water. The value entered here is in units of percent-per-kelvin. The evaporation rate will equal this value times each degree Kelvin of temperature drop in the condenser water. Empirical correlation is used to calculate default loss factor if it not explicitly specified in the input file.
Field: Drift Loss Percent[LINK]
This field is used to specify the rate of water lost to the exiting air as entrained droplets [%]. The drift loss is a percent of the condenser water flow. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.
Field: Blowdown Calculation Mode[LINK]
This field specifies which method is used to determine blowdown rates. There two options ConcentrationRatio or ScheduledRate. The choice will determine which of the two models below is used. The default is ConcentrationRatio.
Field: Blowdown Concentration Ratio[LINK]
This field is used to dynamically adjust the rate of blowdown in the evaporative fluid cooler as a function of the rate of evaporation. Blowdown is water intentionally drained from the evaporative fluid cooler in order to offset the build up of solids in the water that would otherwise occur because of evaporation. The value entered here is dimensionless. It can be characterized as the ratio of solids in the blowdown water to solids in the make up water. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.
Field: Blowdown Makeup Water Usage Schedule Name[LINK]
This alpha field contains the name of the schedule used to define the amount of water (m3/s) flushed from the basin on a periodic basis to purge the evaporative fluid cooler of mineral scale build-up and other contaminants. This schedule is only used if the Blowdown Calculation Mode is set to ScheduledRate. The amount of water use due to blowdown depends on the makeup water quality and is specific to each geographical location. Default value is under investigation for now cooling tower’s evaporation loss factor is taken as default value.This water usage is in addition to the amount of water lost to the atmosphere due to evaporation and/or drift. Since blowdown occurs when the basin water contaminant concentration is high, blowdown only occurs when the evaporative fluid cooler is active and water is flowing through the evaporative fluid cooler (regardless of the water usage defined by this schedule).
Field: Supply Water Storage Tank Name[LINK]
This field is optional. It is used to describe where the evaporative fluid cooler obtains water used for evaporative cooling. If blank or omitted, then the evaporative fluid cooler will obtain water directly from the mains. If the name of a WaterUse:Storage object is used here, then the evaporative fluid cooler will obtain its water from that tank. If a tank is specified, the evaporative fluid cooler will attempt to obtain all the water it uses from the tank. However if the tank cannot provide all the water the evaporative fluid cooler needs, then the evaporative fluid cooler will still operate and obtain the rest of the water it needs from the mains (referred to as ‘Starved’ water).
Examples of an IDF specification for this object are shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average,Cooling Tower Inlet Temperature [C]
HVAC,Average,Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
HVAC,Average,Cooling Tower Make Up Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Make Up Water Volume [m3]
HVAC,Average,Cooling Tower Water Evaporation Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Evaporation Volume [m3]
HVAC,Average,Cooling Tower Water Drift Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Drift Volume [m3]
HVAC,Average,Cooling Tower Water Blowdown Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Water Blowdown Volume [m3]
HVAC,Sum,Cooling Tower Make Up Mains Water Volume [m3]
If Supply Water Storage Tank Name is specified:
HVAC,Average,Cooling Tower Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Storage Tank Water Volume [m3]
HVAC,Average,Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s]
HVAC,Sum,Cooling Tower Starved Storage Tank Water Volume [m3]
Cooling Tower Fan Electricity Rate [W][LINK]
The average electric power consumption of the fluid cooler fan in Watts for the timestep being reported.
Cooling Tower Fan Electricity Energy [J][LINK]
Fan energy use in Joules. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the average rate, in Watts, at which heat is removed from the condenser water loop by the fluid cooler for the time step being reported.
Cooling Tower Inlet Temperature [C][LINK]
The fluid temperature at the fluid cooler inlet in degrees Celsius.
Cooling Tower Outlet Temperature [C][LINK]
The fluid temperature at the fluid cooler outlet in degrees Celsius.
Cooling Tower Mass Flow Rate [kg/s][LINK]
The average fluid mass flow rate through the fluid cooler in kg/s for the time step being reported.
Cooling Tower Make Up Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Make Up Water Volume [m3][LINK]
These outputs are the external spray water consumed by the evaporative fluid cooler. This is the total of evaporation, drift, and blowdown.
Cooling Tower Water Evaporation Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Evaporation Volume [m3][LINK]
Cooling Tower Water Drift Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Drift Volume [m3][LINK]
Cooling Tower Water Blowdown Volume Flow Rate [m3/s][LINK]
Cooling Tower Water Blowdown Volume [m3][LINK]
These outputs provide the breakdown of the different components of water use during fluid cooler operation.
Cooling Tower Make Up Mains Water Volume [m3][LINK]
The volume of make up water provided by the mains in cubic meters. If no Supply Water Storage Tank is specified, then all fluid cooler make up water is provided by the mains (same as Cooling Tower Make Up Water Volume). If a Supply Water Storage Tank is specified, then the make up from the mains only occurs when sufficient water supply is not available from the tank (same as Cooling Tower Starved Storage Tank Water Volume). This output variable is metered on HeatRejection:MainsWater, MainsWater:Plant and MainsWater:Facility.
Cooling Tower Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water provided by the Supply Water Storage Tank.
Cooling Tower Starved Storage Tank Water Volume Flow Rate [m3/s][LINK]
Cooling Tower Starved Storage Tank Water Volume [m3][LINK]
These are the rate and volume of water the Supply Water Storage Tank was not able to provide. The starved water is assumed to come from the mains. The fluid cooler’s operation is not affected by a lack of storage tank water.
FluidCooler:SingleSpeed[LINK]
Fluid coolers are components that may be assigned to condenser loops. The Fluid cooler is modeled as a cross flow heat exchanger (both streams unmixed) with single-speed fans (induced draft configuration). The user must define fluid cooler performance via one of the two methods: design heat transfer coefficient-area product (UA) and design water flow rate, or nominal fluid cooler capacity at a specific rating point. Regardless of which method is chosen, the design airflow rate and corresponding fan power must be specified.
The fluid cooler seeks to maintain the temperature of the water exiting the fluid cooler at (or below) a set point. The set point schedule value is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., fluid cooler fan on for the entire simulation timestep and fluid cooler fan off for the entire simulation timestep). Cyclic losses are not taken into account.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the Fluid Cooler.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the Fluid Cooler’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the Fluid Cooler’s water outlet node.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify fluid cooler performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”.
Field: Design Air Flow Rate U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the design air and water flow rates specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design fluid cooler UA value is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), the fluid cooler inlet air dry-bulb and wetbulb temperature are taken from the input. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the fluid cooler UA based on the fluid cooler capacity and nominal conditions specified in input file.
Field: Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the fluid cooler in watts, Nominal conditions i.e. entering air dry-bulb temperature, entering air wet-bulb temperature and Entering water temperature should be provided in the input.
Field:Design Entering Water Temperature[LINK]
This numeric field contains entering water temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering water temperature must be greater than the design entering air temperature.
Field:Design Entering Air Temperature[LINK]
This numeric field contains entering air dry-bulb temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering air temperature must be greater than the design entering air wet-bulb temperature.
Field:Design Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wetbulb temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering air wet-bulb temperature must be less than the design entering air (dry-bulb) temperature.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the fluid cooler in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the fluid cooler. A water flow rate greater than zero must be defined or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections).
Field: Design Air Flow Rate[LINK]
This numeric field contains the design air flow rate induced by the fluid cooler fan in m\(^{3}\)/s. A value greater than zero must be defined regardless of the fluid cooler performance input method. Alternately, this field can be autosized. See Engineering Reference document for fluid cooler autosizing.
Field: Design Air Flow Rate Fan Power[LINK]
This numeric field contains the fan power (in watts) at the design air flow rate specified in the previous field. A value greater than zero must be specified regardless of the performance input method, or this field can be autosized. See Engineering ref. for fluid cooler autosizing.
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the fluid cooler. If this field is left blank, the outdoor air conditions entering the fluid cooler are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
An IDF specification for this object is shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
Zone,Meter,HeatRejection:Electricity [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average, Cooling Tower Inlet Temperature [C]
HVAC,Average, Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
Cooling Tower Fan Electricity Rate [W][LINK]
The electric power consumption of the fluid cooler fans.
Cooling Tower Fan Electricity Energy [J][LINK]
Fan energy use. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the fluid cooler.
Cooling Tower Inlet Temperature [C][LINK]
The loop temperature at the fluid cooler inlet.
Cooling Tower Outlet Temperature [C][LINK]
The loop temperature at the fluid cooler outlet.
Cooling Tower Mass Flow Rate [kg/s][LINK]
The loop mass flow rate of the circulating condenser water loop.
FluidCooler:TwoSpeed[LINK]
The two-speed fluid cooler is modeled in a similar fashion to the single-speed fluid cooler. The fluid cooler is modeled as a cross flow heat exchanger (both stream unmixed) with two-speed fans (induced draft configuration). The user must define fluid cooler performance via one of two methods: heat transfer coefficient-area product (UA) and design water flow rate, or nominal fluid cooler capacity at a specific rating point. Regardless of which method is chosen, the airflow rate and corresponding fan power at both high and low fan speed must be specified. The Fluid Cooler seeks to maintain the temperature of the water exiting the Fluid Cooler at (or below) a set point. The set point schedule is defined by the field “Condenser Loop Temperature Setpoint Node Name or Reference” for the CondenserLoop object. The model first runs at low speed and calculates the fluid cooler exiting water temperature. If the exiting water temperature based on “low speed” is at or below the set point, then the fluid cooler fan runs at this speed or below this speed. If the exiting water temperature remains above the set point after “low speed” is modeled, then the fluid cooler fan runs at high speed to reduce the exiting water temperature.
The model assumes that part-load operation is represented by a simple linear interpolation between two steady-state regimes (i.e., fluid cooler fan at high speed for the entire simulation timestep and fluid cooler fan at low speed for the entire simulation timestep,). Cyclic losses are not taken into account.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the fluid cooler.
Field: Water Inlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water inlet node.
Field: Water Outlet Node Name[LINK]
This alpha field contains the identifying name for the fluid cooler’s water outlet node.
Field: Performance Input Method[LINK]
This alpha field contains the method by which the user will specify fluid cooler performance: “UFactorTimesAreaAndDesignWaterFlowRate” or “NominalCapacity”.
Field: High Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per degree Celsius corresponding to the high-speed air flow rate and design water flow rate specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, then a UA value greater than zero but less than or equal to 300,000 must be defined, or the field can be autosized. If autosized, a Plant Sizing object must be defined and the fluid cooler UA value at high fan speed is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections), fluid cooler water inlet temperature, fluid cooler inlet air drybulb and wetbulb are provided in the input. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the fluid cooler UA based on the capacity specified in the field “High Speed Nominal Capacity” and nominal conditions.
Field: Low Fan Speed U-factor Times Area Value[LINK]
This numeric field contains the heat transfer coefficient-area product (UA) in watts per Kelvin corresponding to the design water flow rate and low-speed air flow rate specified above. If the input field “Performance Input Method” is specified as “UFactorTimesAreaAndDesignWaterFlowRate”, this value must be greater than zero but less than or equal to 300,000, less than the value specified for the field “U-factor Times Area Value at High Fan Speed”. This field may be autocalculated, in which case it is set to a factor of the “U-factor Times Area Value at High Fan Speed” determined in the following field. If “Performance Input Method” is specified as “NominalCapacity”, then this field must be left blank since the model automatically calculates the fluid cooler UA based on the fluid cooler capacity specified in the field “Low Speed Nominal Capacity”.
Field: Low Fan Speed U-Factor Times Area Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Fan Speed U-factor Times Area Value. The default is 0.6.
Field: High Speed Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the fluid cooler in watts under high-speed fan operation, with nominal (design) inputs entering water temperature, entering air temperature and entering air wet-bulb temperature. The design water flow rate is also provided in the input.
Field: Low Speed Nominal Capacity[LINK]
This numeric input field contains the “nominal” heat rejection capacity of the Fluid Cooler in watts under low-speed fan operation, with nominal (design) inputs entering water temperature, entering air temperature and entering air wet-bulb temperature. The design water flow rate is also provided in the input. The value specified for this field must be greater than zero but less than the value specified for the field “High Speed Nominal Capacity”. This field may be autocalculated, in which case it is set to a fraction of the “High Speed Nominal Capacity” determined in the following field.
Field: Low Speed Nominal Capacity Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Speed Nominal Capacity. The default is 0.5.
Field:Design Entering Water Temperature[LINK]
This numeric field contains entering water temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering water temperature must be greater than the design entering air temperature.
Field:Design Entering Air Temperature[LINK]
This numeric field contains entering air dry-bulb temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering air temperature must be greater than the design entering air wet-bulb temperature.
Field:Design Entering Air Wet-bulb Temperature[LINK]
This numeric field contains entering air wet-bulb temperature at nominal conditions in degrees Celsius. This field must be specified for both the performance input methods. The design entering air wet-bulb temperature must be less than the design entering air (dry-bulb) temperature.
Field: Design Water Flow Rate[LINK]
This numeric field contains the design water flow rate through the fluid cooler in m\(^{3}\)/s. This value is the flow rate of the condenser loop water being cooled by the fluid cooler. A water flow rate greater than zero must be defined or the field can be autosized. If autosized, a Plant Sizing object must be defined and the design water flow rate is derived from the design load to be rejected by the condenser loop and the design loop delta T (Ref. Sizing and Input for Design Calculations and Component Autosizing sections).
Field: High Fan Speed Air Flow Rate[LINK]
This numeric field contains the fluid cooler air flow rate at high fan speed in m\(^{3}\)/s. A value greater than zero must be defined regardless of the fluid cooler performance input method. Alternately, this field can be autosized. See Engineering ref. for fluid cooler autosizing.
Field: High Fan Speed Fan Power[LINK]
This numeric field contains the fan power (in Watts) at the high-speed air flow rate specified in the previous field. A value greater than zero must be specified regardless of the fluid cooler performance input method, or this field can be autosized. See Engineering ref. for fluid cooler autosizing.
Field: Low Fan Speed Air Flow Rate[LINK]
This numeric field contains the fluid cooler air flow rate at low fan speed in m\(^{3}\)/s. This value must be greater than zero, less than the value specified for the field “Air Flow Rate at High Fan Speed”. This field may be autocalculated, in which case it is set to a fraction of the “Air Flow Rate at High Fan Speed” determined in the following field.
Field: Low Fan Speed Air Flow Rate Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Fan Speed Air Flow Rate. The default is 0.5.
Field: Low Fan Speed Fan Power[LINK]
This numeric field contains the fan power (in Watts) at the low-speed air flow rate specified in the previous field. This value must be specified greater than zero or the field may be autocalculated, in which case it is set to set to a fraction of the “Fan Power at High Fan Speed” determined in the following field.
Field: Low Fan Speed Fan Power Sizing Factor[LINK]
This numeric field contains the sizing factor to use when calculating the Low Fan Speed Fan Power. The default is 0.16.
Field: Outdoor Air Inlet Node Name[LINK]
This optional alpha field specifies the outdoor air node name used to define the conditions of the air entering the Fluid Cooler. If this field is left blank, the outdoor air conditions entering the Fluid Cooler are taken directly from the weather data. If this field is not blank, the node name specified must also be specified in an OutdoorAir:Node object where the height of the node is taken into consideration when calculating outdoor air conditions from the weather data. Alternately, the node name may be specified in an OutdoorAir:NodeList object where the outdoor air conditions are taken directly from the weather data.
Examples of an IDF specification for this object are shown below:
Outputs[LINK]
HVAC,Average,Cooling Tower Fan Electricity Rate [W]
HVAC,Sum,Cooling Tower Fan Electricity Energy [J]
HVAC,Average,Cooling Tower Heat Transfer Rate [W]
HVAC,Average, Cooling Tower Inlet Temperature [C]
HVAC,Average, Cooling Tower Outlet Temperature [C]
HVAC,Average,Cooling Tower Mass Flow Rate [kg/s]
Cooling Tower Fan Electricity Rate [W][LINK]
Average fan electric power consumed.
Cooling Tower Fan Electricity Energy [J][LINK]
Total energy used by the fan. Consumption is metered on HeatRejection:Electricity, Electricity:Plant, and Electricity:Facility.
Cooling Tower Heat Transfer Rate [W][LINK]
This is the rate at which heat is removed from the condenser water loop by the fluid cooler.
Cooling Tower Inlet Temperature [C][LINK]
Loop temperature at the fluid cooler inlet.
Cooling Tower Outlet Temperature [C][LINK]
Loop temperature at the fluid cooler outlet.
Cooling Tower Mass Flow Rate [kg/s][LINK]
Loop mass flow rate through the fluid cooler.
GroundHeatExchanger:System[LINK]
The EnergyPlus ground loop heat exchanger is a condenser component which serves the condenser supply side in addition to the cooling towers and other condensing components. Figure 2 shows the Ground Heat Exchanger in the simulation environment.
The heat exchanger response is defined by a g-function which is a non-dimensional function that is used to calculate the response to square heat pulses of different duration. (This function is not the same as ‘G-factors’ referred to in the ASHRAE Applications Handbook). This continuous function is specified by a series of data pairs (LNTTSi, GFNCi) where,
LNTTSi is the non-dimensional time: ln(T/T\(_{s}\))
GFNCi is the g-function value
The g-function is different for each borehole field configuration (i.e. a 4 \(\times\) 4 field has a different response than a 80 \(\times\) 80 field). It is also dependent on the ratio of borehole spacing to depth. g-function values, for accurate simulation, have to be computed for each specific heat exchanger design. The GroundHeatExchanger:System object will accept four different types of input in order to define the g-functions necessary for the ground heat exchanger calculations.
Use the GroundHeatExchanger:Vertical:Array object to define a rectangular borehole field.
Use one or more GroundHeatExchanger:Vertical:Single objects to define a vertical borehole field with the boreholes located arbitrarily.
Use a third-party tool such as GLHEPro to compute the g-functions, or download them from a precomputed library and pass them to EnergyPlus using the GroundHeatExchanger:ResponseFactors object.
Request borehole field design and sizing by providing a single GroundHeatExchanger:Vertical:Single object and also a GroundHeatExchanger:Vertical:Sizing:Rectangle object.
A small number of reference datasets containing example input data for 1 \(\times\) 2, 4 \(\times\) 4 and 8 \(\times\) 8 configurations and for both standard and thermally enhanced grout are provided as well.
Definitions for the input fields are provided below.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the ground heat exchanger (GHE).
Field: Inlet Node Name[LINK]
This alpha field contains the ground heat exchanger inlet node name.
Field: Outlet Node Name[LINK]
This alpha field contains the ground heat exchanger outlet node name.
Field: Design Flow Rate[LINK]
This numeric field contains the GHE design flow rate in cubic meters per second {m\(^{3}\)/s}. The flow rate specified is the total flow rate for the entire borehole field. Flow will be assumed to be evenly distributed across all boreholes.
Field: Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Ground Thermal Conductivity[LINK]
This numeric field contains the thermal conductivity of the ground in W/m-K.
FieldSet: Ground Thermal Heat Capacity[LINK]
This numeric field contains the thermal heat capacity of the ground in J/m\(^{3}\)-K.
Field: GHE:ResponseFactors object name[LINK]
The unique name of the GroundHeatExchanger:ResponseFactors object used to define the third-party response factors. If present, the GHE:Vertical:Array and GHE:Vertical:Single objects defined will be ignored.
Field: g-Function Calculation Method[LINK]
If the GHE:ResponseFactors object is not provided, this input will be relevant to the calculation method used to generate the g-function values. There are three options for this input:
“UHFcalc”
“UBHWTcalc”
“FullDesign”
The default is UHFcalc, where a g-function is computed with the uniform heat flux boundary condition. The UBHWTcalc option computes the g-function with a uniform borehole wall temperature boundary condition. The g-function computed with a uniform borehole wall temperature boundary condition is expected to be a better approximation of the borehole physics and is also expected to be faster to compute. The final option of FullDesign allows a borehole field to be designed and sized based on loads and design parameters. For a designed borehole field, the input file should include a GHE:Vertical:Sizing object matching the next field in this object, a full annual weather file sizing period to allow a year of loads to be generated, and finally hvac sizing enabled in the simulation control object.
Field: GHEVertical:Sizing object type[LINK]
For borehole field design and sizing calculations, this should be the type of an object specifying the borehole field design parameters. Currently only GroundHeatExchanger:Vertical:Sizing:Rectangle is supported.
Field: GHE:Vertical:Sizing object name[LINK]
For borehole field design and sizing calculations, this should be the name of an object specifying the borehole field design parameters. See the full documentation for GroundHeatExchanger:Vertical:Sizing:Rectangle.
Field: GHE:Vertical:Array object name[LINK]
The unique name of the GroundHeatExchanger:Vertical:Array object used to define a rectangular borehole field. If present, the GHE:Vertical:Single objects will be ignored.
Field: GHE:Vertical:Single names[LINK]
The unique names of all single, vertical GLHE objects which are used to define and arbitrarily shaped GHE array. This field is extensible.
The following are example inputs corresponding to the input variations allowed which were described previously. The first example uses the GroundHeatExchanger:Vertical:Array object. The g-functions will be generated automatically by EnergyPlus.
The second example uses the GroundHeatExchanger:Vertical:Single object. The g-functions will be generated automatically by EnergyPlus.
The final example uses the ResponseFactors object to provide third-party g-functions.
Outputs[LINK]
HVAC,Average,Ground Heat Exchanger Average Borehole Temperature [C]
HVAC,Average,Ground Heat Exchanger Heat Transfer Rate [W]
HVAC,Average,Ground Heat Exchanger Inlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Outlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Mass Flow Rate [kg/s]
HVAC,Average,Ground Heat Exchanger Average Fluid Temperature [C]
HVAC,Average,Ground Heat Exchanger Farfield Ground Temperature [C]
Ground Heat Exchanger Average Borehole Temperature [C][LINK]
This is the model result for the average temperature of the borehole heat exchanger.
Ground Heat Exchanger Heat Transfer Rate [W][LINK]
This is the rate of heat transfer between the working fluid and the ground heat exchanger, in Watts.
Ground Heat Exchanger Inlet Temperature [C][LINK]
This is the temperature of the working fluid entering the ground heat exchanger.
Ground Heat Exchanger Outlet Temperature [C][LINK]
This is the temperature of the working fluid leaving the ground heat exchanger.
Ground Heat Exchanger Mass Flow Rate [kg/s][LINK]
This is the mass flow rate of the working fluid through the heat exchanger.
Ground Heat Exchanger Average Fluid Temperature [C][LINK]
This is the average temperature of the working fluid inside the heat exchanger.
Ground Heat Exchanger Farfield Ground Temperature[LINK]
This is the farfield temperature used by the object which is provided by the undisturbed ground temperature object. The temperature is the average of the 5 evenly spaced points between the top of the borehole and the bottom of the borehole.
GroundHeatExchanger:Vertical:Sizing:Rectangle[LINK]
The ground loop heat exchanger can be designed and sized using the packaged GHEDesigner library. Currently the design is limited to rectangular borehole fields, with future enhancements expected to allow more flexible field design. To achieve the design, several design parameters are required, and are supplied in this object. HVAC sizing must also be enabled.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the rectangle ground heat exchanger sizing object. This name will be referenced in a GroundHeatExchanger:System object.
Field: SizingPeriod:WeatherFileDays Name[LINK]
The name of the SizingPeriod:WeatherFileDays object, used to define the design period. This object is required and must specify a period of 356 days.
Field: Design Flow Rate Per Borehole[LINK]
This is the design flow rate per borehole in m3/s. Used only for sizing the ground heat exchanger.
Field: Available Borehole Field Length[LINK]
This is the available borehole field length, in meters, as looking down from above.
Field: Available Borehole Field Width[LINK]
This is the available borehole field width, in meters, as looking down from above.
Field: Maximum Number of Boreholes[LINK]
This is the maximum number of boreholes available for the design.
Field: Minimum Borehole Spacing[LINK]
This is the minimum borehole-to-borehole spacing, in meters.
Field: Maximum Borehole Spacing[LINK]
This is the maximum borehole-to-borehole spacing, in meters.
Field: Minimum Borehole Vertical Length[LINK]
This is the minimum vertical height, or total borehole “length”, to be used when designing the borehole field.
Field: Maximum Borehole Vertical Length[LINK]
This is the maximum vertical height, or total borehole “length”, to be used when designing the borehole field.
Field: Minimum Exiting Fluid Temperature for Sizing[LINK]
This is the minimum allowable exiting fluid temperature for the borehole heat exchanger when designing the borehole field.
Field: Maximum Exiting Fluid Temperature for Sizing[LINK]
This is the maximum allowable exiting fluid temperature for the borehole heat exchanger when designing the borehole field.
Example Inputs[LINK]
This is an example input object for the sizing parameters:
Outputs[LINK]
This object does not have any specific output variables. However, by using the full design approach, there may be additional output files or sizing outputs available in the EIO.
GroundHeatExchanger:Vertical:Properties[LINK]
This object defines several borehole parameters.
Inputs[LINK]
Field: Name[LINK]
This alpha field indicates the unique name of the object.
Field: Depth of Top of Borehole[LINK]
This numeric field indicates the depth of the top of the borehole below the ground surface, in meters. The depth measured from the ground surface downward is positive.
Field: Borehole Length[LINK]
This numeric field indicates the active length of the borehole, referenced from the starting location (potentially below the ground surface), to the end of the borehole, in meters.
Field: Borehole Diameter[LINK]
This numeric field indicates the diameter of the borehole, in meters.
Field: Grout Thermal Conductivity[LINK]
This numeric field contains the thermal conductivity of the filler material in W/m-K.
Field: Grout Thermal Heat Capacity[LINK]
This numeric field contains the thermal heat capacity of the grout in J/m\(^{3}\)-K.
Field: Pipe Thermal Conductivity[LINK]
This numeric field contains the thermal conductivity of the pipe in W/m-K.
Field: Pipe Thermal Heat Capacity[LINK]
This numeric field contains the thermal heat capacity of the pipe in J/m\(^{3}\)-K.
Field: Pipe Outer Diameter[LINK]
This numeric field contains the outer diameter of the U-tube (pipe) in meters {m}.
Field: Pipe Thickness[LINK]
This numeric field contains the outer diameter of the U-tube (pipe) in meters.
Field: U-Tube Distance[LINK]
This numeric field contains the distance between the two legs of the U-tube in meters {m}. Distance is measured from the u-tube pipe center.
An example object is shown below.
GroundHeatExchanger:Vertical:Array[LINK]
This object defines the borehole locations for a rectangular array of boreholes.
Field: Name[LINK]
This alpha field indicates the unique name of the object.
Field: Properties[LINK]
This alpha field indicates the name of the GroundHeatExchanger:Vertical:Properties object referenced by the boreholes in the array.
Field: Number of Boreholes in the X-Direction[LINK]
This numeric field indicates the number of boreholes in one axis of the rectangular borehole field.
Field: Number of Boreholes in the Y-Direction[LINK]
This numeric field indicates the number of boreholes in the other axis of the rectangular borehole field.
Field: Borehole Spacing[LINK]
This numeric field indicates the center-to-center borehole spacing, in meters, which is applied to the rectangular borehole field.
An example object is shown below.
GroundHeatExchanger:Vertical:Single[LINK]
This object defines a single borehole heat exchanger.
Inputs[LINK]
Field: Name[LINK]
This alpha field indicates the unique name of the object.
Field: Properties[LINK]
This alpha field indicates the name of the GroundHeatExchanger:Vertical:Properties object referenced by the borehole.
Field: X-Location[LINK]
This numeric field indicates the x-location of this borehole.
Field: Y-Location[LINK]
This numeric field indicates the y-location of this borehole.
GroundHeatExchanger:ResponseFactors[LINK]
This object is used to provide third-party g-functions which are generated by other tools.
Inputs[LINK]
Field: Name[LINK]
This alpha field indicates the unique name of the object.
Field: Properties[LINK]
This alpha field indicates the name of the GroundHeatExchanger:Vertical:Properties object referenced g-function response factors.
Field: G-Function Reference Ratio[LINK]
The G-Functions may be formulated slightly differently based on the program which generated them. The original g-functions as defined by Eskilson are based on an borehole radius to active length ratio of 0.0005. If the physical ratio is different from this, a correction must be applied. EnergyPlus will apply the correction, based on the reference ratio entered in this field. Therefore, there are two possible input configurations.
If the g-functions have not had a correction applied, then the g-functions are still based on a reference of 0.0005, so use a value of 0.0005 in this field. EnergyPlus will adjust the g-functions internally to create the properly referenced g-function.
If the correction has already been applied, then the input g-functions are based on a reference to the actual (physical) radius/length ratio, so enter the physical radius/length in this field. Entering the actual value will nullify any internal corrections, which will avoid re-basing the g-function set.
The software GLHEPro has been making this “pre-correction” to the data sets since version 3.1 of that software, so this input field should match the actual (physical) radius/length ratio.
Field: g-function Ln(t/ts) Value <x>[LINK]
This numeric field contains the natural log of time/steady state time: ln(t/t\(_{s}\)).
Field: g-function ‘g’ Value <x>[LINK]
This numeric field contains the g-function value of the corresponding LNTTS.
This object is extensible, so additional pairs of these last two fields can be added to the end of this object.
An example object is shown below.
GroundHeatExchanger:Slinky[LINK]
The GroundHeatExchanger:Slinky use the g-functions to calculate the GHX temperature response, similar to the GroundHeatExchanger:Vertical model, however for this model g-functions are automatically calculated by EnergyPlus without the need of external software or data.
Horizontal slinky-loop ground heat exchangers (GHXs) consist of coiled tubing, with the individual rings spread out along the direction of the trench either horizontally or vertically, as shown in Figure. A schematic of a slinky GHX can be seen in Figure. Compared to conventional straight tube horizontal GHXs, slinky loops have a higher tube density; hence, with the same cooling/heating loads, slinky-loop GHXs require less land area and excavation work than straight tube HGHXs.
Figure: Slinky Ground Heat Exchanger Configurations.
Figure: Schematic of Slinky HX.
An example GroundHeatExchanger:Slinky object is shown below.
Inputs[LINK]
Field: Name[LINK]
Alpha field used as identifying field for heat exchanger
Field: Inlet Node[LINK]
This alpha field is the name of the inlet node of the component on a plant loop.
Field: Outlet Node[LINK]
This alpha field is the name of the outlet node of the component on a plant loop.
Field: Design Flow Rate[LINK]
This numeric field is the design flow rate in m3/s for the heat exchanger. The plant loop will attempt to meet this request based on loop and flow conditions.
Field: Soil Thermal Conductivity[LINK]
This numeric field is the thermal conductivity of the soil, in W/m-K.
Field: Soil Density[LINK]
This numeric field is the density of the soil, in kg/m3.
Field: Soil Specific Heat[LINK]
This numeric field is the specific heat of the soil, in J/kg-K.
Field: Pipe Thermal Conductivity[LINK]
This numeric field is the thermal conductivity of the heat exchanger pipe.
Field: Pipe Density[LINK]
This numeric field is the density of the heat exchanger pipe, in kg/m3.
Field: Pipe Specific Heat[LINK]
This numeric field is the specific heat of the heat exchanger pipe, in J/kg-K.
Field: Pipe Outside Diameter[LINK]
This numeric field is the outside pipe diameter, in meters.
Field: Pipe Wall Thickness[LINK]
This numeric field is the pipe wall thickness, in meters.
Field: Heat Exchanger Configuration[LINK]
This alpha field is heat exchanger configuration, either Vertical or Horizontal.
Field: Coil Diameter[LINK]
This numeric is the diameter of the slinky coil, in meters.
Field: Coil Pitch[LINK]
This numeric field is the center-to-center distance between heat exchanger coils, in meters.
Field: Trench Depth[LINK]
This numeric field is the distance from the bottom of the trench to the ground surface, in meters.
Field: Trench Length[LINK]
This numeric field is the length of the heat exchanger trench, in meters. This assumes the heat exchanger runs the full length of the trench.
Field: Number of Parallel Trenches[LINK]
This numeric field is the number of parallel trenches. Design flow rate will be equally divided among all parallel trenches.
Field: Trench Spacing[LINK]
This numeric field is the center-to-center distance in between parallel trenches, in meters.
Field: Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Maximum Length of Simulation[LINK]
This numeric field contains the maximum number of years of simulation to be carried out.
Outputs[LINK]
The following output variables are available.
HVAC,Average,Ground Heat Exchanger Average Borehole Temperature [C]
HVAC,Average,Ground Heat Exchanger Heat Transfer Rate [W]
HVAC,Average,Ground Heat Exchanger Inlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Outlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Mass Flow Rate [kg/s]
HVAC,Average,Ground Heat Exchanger Average Fluid Temperature [C]
Ground Heat Exchanger Average Borehole Temperature [C][LINK]
This is the model result for the average temperature of the borehole heat exchanger.
Ground Heat Exchanger Heat Transfer Rate [W][LINK]
This is the rate of heat transfer between the working fluid and the ground heat exchanger, in Watts.
Ground Heat Exchanger Inlet Temperature [C][LINK]
This is the temperature of the working fluid entering the ground heat exchanger.
Ground Heat Exchanger Outlet Temperature [C][LINK]
This is the temperature of the working fluid leaving the ground heat exchanger.
Ground Heat Exchanger Mass Flow Rate [kg/s][LINK]
This is the mass flow rate of the working fluid through the heat exchanger.
Ground Heat Exchanger Average Fluid Temperature [C][LINK]
This is the average temperature of the working fluid inside the heat exchanger.
GroundHeatExchanger:Pond[LINK]
The pond heat exchanger model represents a shallow pond with submerged hydronic tubes through which the heat transfer fluid is circulated. The model represents a ‘shallow’ pond in that no attempt is made to model any stratification effects that may be present in deeper ponds.
This type of heat exchanger is intended to be connected to the supply side of a condenser loop, and can be used with any type of plant loop. The pond may be specified as the only heat exchanger on the condenser loop (as shown in Figure 3) or it may be connected in parallel with other condenser loop heat exchangers (such as cooling towers, ground surface heat exchangers) as shown in the second figure below.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the outside pond heat exchanger.
Field: Fluid Inlet Node Name[LINK]
This alpha field contains the fluid inlet node name.
Field: Fluid Outlet Node Name[LINK]
This alpha field contains the fluid outlet node name.
Field: Pond Depth[LINK]
This numeric field contains the pond depth {m}.
Field: Pond Area[LINK]
This numeric field contains the pond area m\(^{2}\).
Field: Hydronic Tubing Inside Diameter[LINK]
This numeric field contains the hydronic tubing inside diameter {m}.
Field: Hydronic Tubing Outside Diameter[LINK]
This numeric field contains the hydronic tubing outside diameter {m}.
Field: Hydronic Tubing Thermal Conductivity[LINK]
This numeric field contains the hydronic tubing thermal conductivity in W/mK.
Field: Ground Thermal Conductivity[LINK]
This numeric field contains the ground thermal conductivity in W/m\(^{2}\)K.
Field: Number of Tubing Circuits[LINK]
This numeric field contains the number of hydronic tubing circuits, total in parallel in this pond..
Field: Length of Each Tubing Circuit[LINK]
This numeric field contains length {m} of each hydronic tubing circuit.
An example of the IDF is shown below.
Outputs[LINK]
HVAC,Average,Pond Heat Exchanger Heat Transfer Rate [W]
HVAC,Sum,Pond Heat Exchanger Heat Transfer Energy [J]
HVAC,Average,Pond Heat Exchanger Mass Flow Rate [kg/s]
HVAC,Average,Pond Heat Exchanger Inlet Temperature [C]
HVAC,Average,Pond Heat Exchanger Outlet Temperature [C]
HVAC,Average,Pond Heat Exchanger Bulk Temperature [C]
Pond Heat Exchanger Heat Transfer Rate [W][LINK]
Pond Heat Exchanger Heat Transfer Energy [J][LINK]
These outputs are the pond ground heat exchanger heat transfer rate and total energy exchange for the timestep.
Pond Heat Exchanger Mass Flow Rate [kg/s][LINK]
Pond Heat Exchanger Inlet Temperature [C][LINK]
Pond Heat Exchanger Outlet Temperature [C][LINK]
These outputs are the pond fluid inlet and outlet temperatures and mass flow rate.
Pond Heat Exchanger Bulk Temperature [C][LINK]
This output is the pond bulk temperature.
GroundHeatExchanger:Surface[LINK]
The surface heat exchanger model is to simulate hydronic surface ground heat exchangers. This includes pavement surfaces with embedded pipes for snow-melting or heat rejection from hybrid ground source heat pump systems.
The heat exchanger may be ground coupled or not. In the latter case the bottom surface is exposed to the wind but not solar gains. This type of heat exchanger is intended to be connected to the supply side of a condenser loop, and can be used with any type of plant loop. The surface heat exchanger may be specified as the only heat exchanger on the condenser loop (as shown in the first figure below) or it may be connected in parallel with other condenser loop heat exchangers (such as cooling towers, ground surface heat exchangers) as shown in the second figure below.
Inputs[LINK]
Field: Name[LINK]
This alpha field contains the identifying name for the outside panel heat exchanger.
Field: Construction Name[LINK]
This alpha field contains the construction name. It must contain a valid “Construction” name that is usual for Surfaces. (Ref: Group – Surface Construction Elements).
Field: Fluid Inlet Node Name[LINK]
This alpha field contains the fluid inlet node name.
Field: Fluid Outlet Node Name[LINK]
This alpha field contains the fluid outlet node name.
Field: Hydronic Tubing Inside Diameter[LINK]
This numeric field contains the hydronic tubing inside diameter in m.
Field: Number of Tubing Circuits[LINK]
This numeric field contains the number of hydronic tubing circuits.
Field: Hydronic Tube Spacing[LINK]
This numeric field contains the hydronic tube spacing in m.
Field: Surface Length[LINK]
This numeric field contains the surface length in m.
Field: Surface Width[LINK]
This numeric field contains the surface width in m.
Field: Lower Surface Environment[LINK]
This alpha field expresses the lower surface exposure: Exposed or Ground.
An example of this statement in an IDF is shown below:
Outputs[LINK]
HVAC,Average,Ground Heat Exchanger Heat Transfer Rate [W]
HVAC,Average,Ground Heat Exchanger Surface Heat Transfer Rate [W]
HVAC,Sum,Ground Heat Exchanger Heat Transfer Energy [J]
HVAC,Average,Ground Heat Exchanger Mass Flow Rate [kg/s]
HVAC,Average,Ground Heat Exchanger Inlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Outlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Top Surface Temperature [C]
HVAC,Average Ground Heat Exchanger Bottom Surface Temperature [C]
HVAC,Average,Ground Heat Exchanger Top Surface Heat Transfer Energy per Area [J/m2]
HVAC,Average,Ground Heat Exchanger Bottom Surface Heat Transfer Energy per Area[J/m2]
HVAC,Sum,Ground Heat Exchanger Surface Heat Transfer Energy [J]
HVAC,Average,Ground Heat Exchanger Source Temperature [C]
Ground Heat Exchanger Heat Transfer Rate [W][LINK]
Ground Heat Exchanger Surface Heat Transfer Rate [W][LINK]
Ground Heat Exchanger Heat Transfer Energy [J][LINK]
These outputs are the source heat transfer rate, surface heat transfer rate and the total source energy input for the timestep.
Ground Heat Exchanger Mass Flow Rate [kg/s][LINK]
Ground Heat Exchanger Inlet Temperature [C][LINK]
Ground Heat Exchanger Outlet Temperature [C][LINK]
These outputs are the surface heat exchanger fluid inlet and outlet temperatures and mass flow rate.
Ground Heat Exchanger Top Surface Temperature [C][LINK]
Ground Heat Exchanger Bottom Surface Temperature [C][LINK]
These outputs are the surface heat exchanger top and bottom surface temperatures.
Ground Heat Exchanger Top Surface Heat Transfer Energy per Area [J/m\(^{2}\)][LINK]
Ground Heat Exchanger Bottom Surface Heat Transfer Energy per Area [J/m\(^{2}\)][LINK]
These outputs are the surface heat exchanger top and bottom surface flux.
Ground Heat Exchanger Surface Heat Transfer Energy [J][LINK]
This is the total surface energy exchange for the timestep.
Ground Heat Exchanger Source Temperature [C][LINK]
This is the surface heat exchanger source temperature.
GroundHeatExchanger:HorizontalTrench[LINK]
The horizontal trench ground heat exchanger object provides an alternate interface to the detailed PipingSystem:Underground:* objects. The same underlying simulation algorithm is utilized, providing a transient numerical simulation of soil with buried pipes and a detailed surface heat balance. The input syntax is much smaller and useful for simple applications. For full flexibility, use the PipingSystem:Underground:* objects to build a detailed simulation domain and piping circuit. For information regarding the simulation algorithms, see the engineering reference document section covering the buried piping system objects.
Field: Name
This alpha field is used as an identifying field for the ground heat exchanger.
Field: Inlet Node Name
This alpha field is the name of the inlet node of this component on a plant loop, and must match other topology definitions such as branch objects.
Field: Outlet Node Name
This alpha field is the name of the outlet node of this component on a plant loop, and must match other topology definitions such as branch objects.
Field: Design Flow Rate [m3/s]
This numeric field is the designed flow rate for this heat exchanger; the plant loop solver will attempt to meet this request based on flow and loop conditions.
Field: Trench Length in Pipe Axial Direction [m]
This numeric field represents the axial length of each pipe trench. Each pipe defined for this ground heat exchanger will have the same length. If different pipes have different lengths, they must use separate GroundHeatExchanger:HorizontalTrench objects with different lengths.
Field: Number of Trenches
This integer field is the number of trenches for this heat exchanger. Since each trench has a single pipe, this defines the number of “pipe segments” for this overall heat exchanger. The total piping length is then calculated as the trench length times the number of trenches.
Field: Horizontal Spacing Between Pipes [m]
This numeric field represents the horizontal spacing (pipe centroid to pipe centroid) between pipes/trenches.
Field: Pipe Inner Diameter [m]
This numeric field is the inner diameter of the pipe. The same pipe properties are used for all pipes in this heat exchanger.
Field: Pipe Outer Diameter [m]
This numeric field is the outer diameter of the pipe. The same pipe properties are used for all pipes in this heat exchanger.
Field: Burial Depth [m]
This numeric field is the burial depth of each pipe, from ground surface to pipe cross section centroid. The same pipe depth is used for all pipes in this heat exchanger.
Field: Soil Thermal Conductivity [W/mK]
This numeric field is the soil thermal conductivity.
Field: Soil Density [kg/m3]
This numeric field is the soil density.
Field: Soil Specific Heat [J/kgK]
This numeric field is the nominal soil specific heat, but is corrected for moisture content and in freezing conditions.
Field: Pipe Thermal Conductivity [W/mK]
This numeric field is the pipe thermal conductivity.
Field: Pipe Density [kg/m3]
This numeric field is the pipe density.
Field: Pipe Specific Heat [J/kgK]
This numeric field is the pipe specific heat.
Field: Soil Moisture Content Percent [%]
This numeric field represents the volume fraction, in percent, of water content in the soil.
Field: Soil Moisture Content Percent at Saturation [%]
This numeric field represents the volume fraction, in percent, of water content in the soil which results in saturation.
Inputs[LINK]
Field: Type of Undisturbed Ground Temperature Object[LINK]
The type of undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Name of Undisturbed Ground Temperature Object[LINK]
The name of the undisturbed ground temperature object used to determine ground temperature for the farfield boundary conditions.
Field: Evapotranspiration Ground Cover Parameter [-]
This numeric field specifies the ground cover effects used in the evapotranspiration model at the ground surface heat balance. The values range from 0 (solid, non-permeable ground surface) to 1.5 (wild growth).
An example of this statement in an IDF is shown below:
Outputs[LINK]
HVAC,Average,Ground Heat Exchanger Mass Flow Rate [kg/s]
HVAC,Average,Ground Heat Exchanger Inlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Outlet Temperature [C]
HVAC,Average,Ground Heat Exchanger Fluid Heat Transfer Rate [W]
Ground Heat Exchanger Mass Flow Rate [kg/s][LINK]
The output provides the mass flow rate currently being sent through the heat exchanger.
Ground Heat Exchanger Inlet Temperature [C][LINK]
Ground Heat Exchanger Outlet Temperature [C][LINK]
Temperature of fluid at the inlet and outlet of the heat exchanger.
Ground Heat Exchanger Fluid Heat Transfer Rate [W][LINK]
Heat transfer rate for the heat exchanger, defined as positive for fluid heat loss.
HeatExchanger:FluidToFluid[LINK]
A fluid-to-fluid heat exchanger designed to couple the supply side of one plant or condenser loop to the demand side of another plant or condenser loop. This heat exchanger is fairly general and can be configured for use in any application where any two loops need to be connected together. The only constraints are that that one side must be connected to the supply side of one loop and the other side connected to the demand side of a different loop.
Because the heat exchanger is intended to be generic, its two sides are distinguished by the nature of loop side being connected. One side is called Loop Supply Side to indicate the heat exchanger is situated on the supply side of a loop. The other side is called Loop Demand Side to indicate it is on the demand side of a loop. The heat exchanger is intended to act as a supply component for the loop connected to it as the “Loop Supply Side” and as a demand component for the loop connected to it as the “Loop Demand Side.” From the point of view of the heat exchanger model itself, the Loop Demand Side fluid serves as the source/sink to supply heating/cooling to the fluid in the Loop Supply Side.
This heat exchanger can be used for a wide variety of applications including chilled water, hot water, condenser, ground source, primary-secondary systems, etc. Heat transfer is calculated and reported using a sign convention from chilled water applications where positive heat transfer indicates energy was extracted from the Loop Supply Side and added to the Loop Demand Side.
Note: Only hydronic “plant” fluids are allowed (excepting Fluid Type "Steam"), no air-side connections are possible with this heat exchanger.
Various options are available for the heat exchanger model.
The heat transfer between the two sides can be modeled using one of seven different models for different types of heat exchangers.
There are also eleven options for different ways to control the heat exchanger.
One general type of control is OnOff where the flow through the heat exchanger is either fully on or fully off.
Another type of control is Modulated where the flow through the Loop Demand Side is controlled to try and meet a target setpoint or load on the Loop Supply Side.
As of Version 8.0, this object replaces three separate objects that were available prior to version 8.0 of EnergyPlus.
The former HeatExchanger:Hydronic object corresponds to a situation where the Loop Demand Side is the demand side of condenser loop, the Loop Supply Side is a the supply side of a chilled water loop, the control type is “CoolingSetpointOnOffWithComponentOverride”, and the remote override component is a chiller.
The former HeatExchanger:WatersideEconomizer object corresponds to a situation where the Loop Demand Side is the demand side of condenser loop, the Loop Supply Side is a the supply side of a chilled water loop, and the control type is “CoolingDifferentialOnOff.”
The former HeatExchanger:Plate object corresponds to a situation where the Loop Demand Side is the demand side of a condenser loop, the Loop Supply Side is the supply side of a second condenser loop, and the control type is “UncontrolledOn.”
Inputs[LINK]
Field: Name[LINK]
This alpha field provides the unique identifying name for this heat exchanger.
Field: Availability Schedule Name[LINK]
This field specifies the name of an availability schedule that can be used for supervisory control of the device. If blank, the default is that heat exchanger is always available. If a scheduled is named here, then the heat exchanger is available for use whenever the schedule value is greater than zero. The heat exchanger is not available whenever the schedule value is zero or less.
Field: Loop Demand Side Inlet Node Name[LINK]
This field specifies the name of a plant system node that connects an inlet of the heat exchanger to the demand side of a loop. This node must be on a branch located on the demand side of a plant or condenser loop.
Field: Loop Demand Side Outlet Node Name[LINK]
This field specifies the name of a plant system node that connects an outlet of the heat exchanger to the demand side of a loop. This node must be on a branch located on the demand side of a plant or condenser loop.
Field: Loop Demand Side Design Flow Rate[LINK]
This field specifies the design flow rate, in m\(^{3}\)/s, of the hydronic fluid passing through the heat exchanger on the Loop Demand Side. This field is autosizable. When autosized, this design flow rate is set to equal the design flow rate for the Loop Supply Side.
Field: Loop Supply Side Inlet Node Name[LINK]
This field specifies the name of a plant system node that connects an inlet of the heat exchanger to the supply side of a loop. This node must be on a branch located on the supply side of a plant or condenser loop.
Field: Loop Supply Side Outlet Node Name[LINK]
This field specifies the name of a plant system node that connects an outlet of the heat exchanger to the supply side of a loop. This node must be on a branch located on the supply side of a plant or condenser loop.
Field: Loop Supply Side Design Flow Rate[LINK]
This field specifies the design flow rate, in m\(^{3}\)/s, of the fluid passing through the heat exchanger on the Loop Supply Side. This field is autosizable. When autosized, this design flow rate is set equal to the overall design flow rate of the loop that is connected. If a sizing factor is entered in the field below, then it is multiplied to modify the design flow rate.
Field: Heat Exchange Model Type[LINK]
This alpha field identifies the nature of heat exchanger. Heat exchanger model type is specified by one of the following four key word choices:
Specifies a single-pass, cross-flow heat exchanger. The effectiveness will be calculated using a cross-flow heat exchanger correlation for both streams unmixed.
Specifies a single-pass, cross-flow heat exchanger. The effectiveness will be calculated using a cross-flow heat exchanger correlation for both streams mixed.
Specifies a single-pass, cross-flow heat exchanger. The effectiveness will be calculated using a cross-flow heat exchanger correlation for flow mixed on the Loop Supply side and flow unmixed on the Loop Demand Side.
Specifies a single-pass, cross-flow heat exchanger. The effectiveness will be calculated using a cross-flow heat exchanger correlation for flow unmixed on the Loop Supply side and flow mixed on the Loop Demand Side.
Specifies a counter-flow shell and tube heat exchanger (one fluid has the opposite direction to the other fluid). The effectiveness will be calculated using a counter-flow shell and tube heat exchanger correlation.
Specifies a parallel-flow shell and tube heat exchanger (both fluids have the same direction). The effectiveness will be calculated using a parallel-flow shell and tube heat exchanger correlation.
Specifies an ideal heat exchanger. The effectiveness will be set to ‘1.0’ and the specified UA will be ignored. The heat transfer rate will be calculated as the maximum possible heat transfer rate.
For effectiveness of each heat exchanger model type in detail, See "Heat Exchangers: Plant Loop Fluid-to-Fluid Heat Exchanger" Section in Engineering Reference.
Field: Heat Exchanger U-Factor Times Area Value[LINK]
This numerical field is used to specify the overall U-Factor Times Area (UA) {W/K} for use in the calculation of the heat exchanger effectiveness using the appropriate D-NTU correlation. If Ideal is specified as the heat exchanger type, the effectiveness will be set to 1.0. When set to autosize Heat Exchanger U-Factor Times Area Value is calculated based on an effectiveness of 1.0 where capacity is such that the temperatures in the Sizing:Plant objects for the two loops can be maintained.
Field: Control Type[LINK]
This field is used to specify how the heat exchanger is to be controlled during operation. Different applications for connecting two loops will require different control behavior and different control options are needed depending on the desired behavior. There are the following eleven key choice options to choose from:
UncontrolledOn. This control mode is applicable to situations where the heat exchanger is passively running all the time and always transfers as much heat as possible between the fluid streams. However there is one aspect of control in that it will only request flow on the Loop Demand Side when there is non-zero flow into the heat exchanger on the Loop Supply Side. This control mode corresponds to that available in the HeatExchanger:Plate object prior to version 8.0.
OperationSchemeModulated. This control mode is applicable to situations where the heat exchanger is controlled by an operation scheme (see objects called PlantEquipmentOperationScheme or CondenserEquipmentOperationSchemes). When using this control mode the heat exchanger must be listed in PlantEquipmentList or a CondenserEquipmentList and it serves as a supply component. The operation scheme will dispatch a load request to the heat exchanger which it will try meet by conditioning the fluid stream connected as the Loop Supply Side. If the heat exchanger could exceed the load request, then the flow through the fluid stream connected as the Loop Demand Side will be modulated to just meet the load request.
OperationSchemeOnOff. This control mode is applicable to situations where the heat exchanger is controlled by an operation scheme (see objects called PlantEquipmentOperationScheme or CondenserEquipmentOperationSchemes). When using this control mode the heat exchanger must be listed in PlantEquipmentList or a CondenserEquipmentList and it serves as a supply component. The operation scheme will dispatch a load request to the heat exchanger which it will use as an on/off signal to decide if the heat exchange should run or not. If it runs, it will run at full capacity and may exceed the load request.
HeatingSetpointModulated. This control mode is applicable to situations where the Loop Demand Side can provide useful heating to the Loop Supply Side. A heating setpoint is obtained from a node named in the following field. If the setpoint and inlet temperatures are such that heat exchanger could transfer heat from the Loop Demand Side to the Loop Supply Side to meet the heating setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If the heat exchanger could overshoot the setpoint, then the flow through the fluid stream connected as the Loop Demand Side will be modulated to just meet the setpoint.
HeatingSetpointOnOff. This control mode is applicable to situations where the Loop Demand Side can provide useful heating to the Loop Supply Side. A heating setpoint is obtained from a node named in the following field. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Demand Side to the Loop Supply Side to meet the heating setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If it runs, it will run at full capacity and may overshoot the setpoint.
CoolingSetpointModulated. This control mode is applicable to situations where the Loop Demand Side can provide useful cooling to the Loop Supply Side. A cooling setpoint is obtained from a node named in the following field. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Supply Side to the Loop Demand Side to meet the cooling setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If the heat exchanger could undershoot the setpoint, then the flow through the fluid stream connected as the Loop Demand Side will be modulated to just meet the setpoint.
CoolingSetpointOnOff. This control mode is applicable to situations where the Loop Demand Side can provide useful cooling to the Loop Supply Side. A cooling setpoint is obtained from a node named in the following field. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Supply Side to the Loop Demand Side to meet the cooling setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If it runs, it will run at full capacity and may undershoot the setpoint. This control mode corresponds to that available in the HeatExchanger:WatersideEconomizer object prior to version 8.0.
DualDeadbandSetpointModulated. This control mode is applicable to situations where the Loop Demand Side can provide either useful cooling or heating to the Loop Supply Side. A dual deadband setpoint is obtained from a node named in the following field. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Demand Side to the Loop Supply Side to meet the lower setpoint, then the heat exchanger will run. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Supply Side to the Loop Demand Side to meet the high setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If the heat exchanger could overshoot the lower setpoint, or undershoot the higher setpoint, then the flow through the fluid stream connected as the Loop Demand Side will be modulated to just meet the deadband setpoint.
DualDeadbandSetpointOnOff. This control mode is applicable to situations where the Loop Demand Side can provide either useful cooling or heating to the Loop Supply Side. A dual deadband setpoint is obtained from a node named in the following field. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Demand Side to the Loop Supply Side to meet the lower setpoint, then the heat exchanger will run. If the setpoints and inlet temperatures are such that heat exchanger could transfer heat from the Loop Supply Side to the Loop Demand Side to meet the high setpoint, then the heat exchanger will run. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. If the heat exchanger runs, it will run at full capacity and may overshoot the lower setpoint or undershoot the higher setpoint.
CoolingDifferentialOnOff. This control mode is applicable to situations where the Loop Demand Side can provide useful cooling to the Loop Supply Side. This mode is similar to CoolingSetpointOnOff except that it ignores any cooling setpoint and its control is based only on the temperature difference between Loop Demand Side and the Loop Supply Side. The inlet temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. This control mode corresponds to that available in the HeatExchanger:WatersideEconomizer object prior to version 8.0.
CoolingSetpointOnOffWithComponentOverride. This control mode is applicable to situations where the heat exchanger operation is integrated with the operation of a specific chiller. Typically the heat exchanger and chiller are in parallel on separate branches. When conditions are favorable for the heat exchanger to provide cooling to the Loop Supply Side, the heat exchanger is run and the integrated chiller is turned off. When conditions are not favorable, the heat exchanger is completely off and the chiller is allowed to run as usual. A cooling setpoint is obtained from a node named in the following field. If it runs it will run at full capacity and may undershoot the setpoint. The chiller that is integrated with the heat exchanger is identified by entering the names of the chiller’s inlet nodes in the input fields below. The control decision can be based on one of three different temperature signals selected in the field below called Component Override Cooling Control Temperature Mode. The setpoint and control signal temperatures must differ by more than the value set in the field called Minimum Temperature Difference to Activate Heat Exchanger for the heat exchanger to operate. This control mode corresponds to that available in the HeatExchanger:Hydronic object prior to version 8.0.
Field: Heat Exchanger Setpoint Node Name[LINK]
This field specifies the name of a plant system node located on loop attached to the Loop Supply Side. This field is used and required when the previous field is set to one of the “Setpoint” control types. The node must have a temperature setpoint placed on it by a setpoint manager (or EMS actuator).
If the previous field is set to DualDeadbandSetpointModulated or DeadbandSetpointOnOff then there must be a setpoint manager that places both a high and low setpoint on the node named in this field. (see SetpointManager:Scheduled:DualSetpoint).
Field: Minimum Temperature Difference to Activate Heat Exchanger[LINK]
This field specifies the value of a temperature tolerance used in control decisions, in deg. Celsius. Whenever the control logic needs to compare two temperatures, the value entered in this field is used as a threshold for comparisons.
Field: Heat Transfer Metering End Use Type[LINK]
This field specifies how the metering for heat transfer will be accounted with respect to end uses. Although the heat exchanger consumes no energy that needs to be metered, there are also meters for heat transfers that apply to the model. The nature of the end use may vary depending on the application that the heat exchanger is being used for. The available choices are FreeCooling, HeatRecovery, HeatRejection, HeatRecoveryForCooling, HeatRecoveryForHeating, and LoopToLoop.
Field: Component Override Loop Supply Side Inlet Node Name[LINK]
This field specifies the name of an inlet node for the remote component that will be integrated with this heat exchanger. This inlet should be on the supply side of a loop – typically chilled water inlet or return for a chiller. This field and the next two are only used for the control type called CoolingSetpointOnOffWithComponentOverride.
Field: Component Override Loop Demand Side Inlet Node Name[LINK]
This field specifies the name of an inlet node for the remote component that will be integrated with this heat exchanger. This inlet should be on the demand side of a loop – typically condenser water inlet or return for a water-cooled chiller. This field is only used for the control type called CoolingSetpointOnOffWithComponentOverride.
Field: Component Override Cooling Control Temperature Mode[LINK]
This field specifies which type of temperature is used to control a heat exchanger that uses the control type called CoolingSetpointOnOffWithComponentOverride. There are three options: Loop, WetBulbTemperature, and DryBulbTemperature. The option called “Loop” directs the program to use the inlet fluid temperature at the Loop Demand Side connection of heat exchanger for the temperature used as a signal to be compared with the setpoint. The option call “WetBulbTemperature” uses the outdoor air wetbulb temperature as the signal. The option called “DryBulbTemperature” uses the outdoor air drybulb temperature as the signal.
Field: Sizing Factor[LINK]
This optional field can be used to modify the results of autosize calculations. This sizing factor is used for this heat exchanger and modifies sizing results by multiplying them by the factor entered here. This factor is applied to the Loop Supply Side Design Flow rate and in turn affects the heat exchanger UA and the loop demand side flow rate which are derived from that flow rate. This allows fine control over the size of the heat exchanger when using autosize in those fields.
Field: Operation Minimum Temperature Limit[LINK]
This optional field can be used to provide supervisory control of the heat exchanger. If either of the inlet temperatures are below this limit (°C), the heat exchanger will not operate.
Field: Operation Maximum Temperature Limit[LINK]
This optional field can be used to provide supervisory control of the heat exchanger. If either of the inlet temperatures are above this limit (°C), the heat exchanger will not operate.
Some example IDF input objects follow.
Outputs[LINK]
Fluid Heat Exchanger Heat Transfer Rate [W][LINK]
Fluid Heat Exchanger Heat Transfer Energy [J][LINK]
These outputs are the rate and energy transferred from the Loop Supply Side to the Loop Demand Side. The sign convention is taken from cooling or heat rejection applications such that positive values indicate cooling of the Loop Supply Side.
Fluid Heat Exchanger Loop Supply Side Mass Flow Rate [kg/s][LINK]
This is the system mass flow of fluid through the heat exchanger side connected as the Loop Supply Side, in kg/s.
Fluid Heat Exchanger Loop Supply Side Inlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid entering the heat exchanger on the side connected as the Loop Supply Side.
Fluid Heat Exchanger Loop Supply Side Outlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid leaving the heat exchanger on the side connected as the Loop Supply Side.
Fluid Heat Exchanger Loop Demand Side Mass Flow Rate [kg/s][LINK]
This is the system mass flow of fluid through the heat exchanger side connected as the Loop Demand Side, in kg/s.
Fluid Heat Exchanger Loop Demand Side Inlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid entering the heat exchanger on the side connected as the Loop Demand Side.
Fluid Heat Exchanger Loop Demand Side Outlet Temperature [C][LINK]
This is the temperature, in degrees Celsius, of the fluid leaving the heat exchanger on the side connected as the Loop Demand Side.
Fluid Heat Exchanger Operation Status [0 = off, 1 = on][LINK]
This output is a numeric flag that indicates whether or not the heat exchanger was operating or not. If the value is 0, then the heat exchanger was not operating. If the value is 1, then the heat was operating.
Fluid Heat Exchanger Effectiveness [][LINK]
This output is the calculated heat exchanger effectiveness (non-dimensional). It is an intermediate value in the NTU model calculations for heat flow rate. Values range between 0 and 1.0. A value of 1.0 indicates ideal heat transfer.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.