The group of input objects described in this section is
used to account for non-uniform room air temperatures that may
occur within the interior air volume of a zone. Room air
modeling was added to EnergyPlus starting with Version
1.2. Although there are many types of analyses (comfort,
indoor air quality, etc) that might benefit from localized
modeling of how room air varies across space, only the
temperature distribution of room air within the zone
is currently addressed in EnergyPlus. This allows surface heat
transfer and air system heat balance calculations to be made
taking into account natural thermal stratification of air and
different types of intentional air distribution designs such
as under-floor and side-wall displacement ventilation that
purport to extract room air at higher-than-mean temperatures.
Note that EnergyPlus does not have completely
general methods of modeling room air that are applicable to
every conceivable type of airflow that might occur in a zone.
Such models (e.g. RANS-CFD) are too computationally expensive
to use with EnergyPlus for the foreseeable future. The models
that are available in EnergyPlus offer only limited modeling
capabilities for select room airflow configurations. Also note
that because the complete mixing model for room air has long
been the standard in building energy simulation, there is not
currently a consensus on how to best model non-uniform air
temperatures in buildings. Therefore, it is up to the user to
have a good understanding of when, where, and how to apply the
room air models available in EnergyPlus. The rest of this
section provides some guidance in the way of examples and
further discussion of the models available in EnergyPlus.
EnergyPlus offers the different types of air models listed
in the table below along with the input objects associated
with the use of that model.
EnergyPlus uses the RoomAirModelType
object to determine which air model is available for use in a
given zone during the simulation. If no RoomAirModelType
object is specified (for each zone or the whole building),
then EnergyPlus will run with the conventional, completely
mixing air model (for each zone or the whole building).
Include a RoomAirModelType
for each zone that the user wants modeled using a more
detailed method. Currently only a single RoomAirModelType
object can be specified for each zone; you cannot switch
between models during a simulation. However, the UCSD
Displacement, Cross Ventilation and UFAD models switch from
displacement to mixing ventilation when the operating
conditions do not give rise to unmixed flow. The following
parameters are fields required by the RoomAirModelType
object.
This alpha field indicates the unique name of a Zone
object defined elsewhere in the input file. The type of room
air model selected will be applied to this zone.
This alpha field indicates the room-air model used for the
specified zone. Currently, there are three options for
different air models. Entering the keyword ‘Mixing’ specifies
the conventional complete-mixing air model. Note that Mixing
is the default and no RoomAirModelType
object would be needed to use the complete-mixing model.
Entering the keyword ‘UserDefined ’specifies the User Defined
Room Air Temperature Patterns. Entering the keyword
’OneNodeDisplacementVentilation ’specifies the Mundt one node
displacement ventilation air model for displacement
ventilation. Entering the keyword
’ThreeNodeDisplacementVentilation’ specifies the three-node
displacement ventilation model developed by the University of
California, San Diego (UCSD DV). Entering the keyword
‘CrossVentilation’ specifies the two-zone cross ventilation
model developed by the University of California, San Diego
(UCSD CV). Entering the keyword
‘UnderFloorAirDistributionInterior’ specifies the two-node
interior zone under floor air distribution model developed by
the University of California, San Diego (UCSD UFI). Entering
the keyword ‘UnderFloorAirDistributionExterior’ specifies the
two-node exterior zone under floor air distribution model
developed by the University of California, San Diego (UCSD
UFE).
This alpha field indicates how air temperatures predicted
by the air models are used by the surface heat balance
calculation. Two different coupling schemes are available:
Direct (also known as T-couple) or Indirect
(DT-couple). In general, indirect coupling is more
suited to situations where room air is well controlled and/or
the room air model is less robust. Direct coupling is more
suited for floating zone air temperatures and/or accurate room
air models.
The Mundt model can use either coupling scheme; the UCSD
DV, UCSD CV, UCSD UFI, and UCSD UFE models ignore this field
and use direct coupling.
Input either Direct or Indirect
An example idf entry follows
RoomAirModelType,
MOD1, !- Room-Air Model Name
ZONE ONE, !- Zone Name
ThreeNodeDisplacementVentilation, !- Room-Air Modeling Type
Direct; !- Air Temperature Coupling Strategy
This object is used to explicitly define temperature
patterns that are to be applied to the mean air temperature
within a thermal zone. This Room Air modeling option is made
available for a number of reasons. It allows modeling the
consequences of air temperature variations during the design
phase when little information is available about the specifics
of the air distribution system or positioning of various
loads. This option can be used to evaluate the energy
implications of different design targets for the temperature
patterns. It also provides a method of modeling the annual
energy use implications for air temperature distributions
determined using separate analyses or measurements. For
example, this option could be used to understand the annual
energy implications of an air distribution system that has
been previously analyzed using Computational Fluid
Dynamics.
This approach differs from the other Room Air modeling in
that the static temperature pattern is not really
modeled so that it will respond to conditions that
develop during the simulation. More sophisticated dynamic Room
Air models will adjust the temperature pattern based on
various factors, such as air system flow rate, floor
temperature, or rates of internal heat gains. The user-defined
temperature distribution patterns are fixed at the beginning
and EnergyPlus simply provides results that include the
implications of those patterns. This user-defined distribution
option may also be useful for checking dynamic Room Air models
by using “bounding” analysis.
Note that using this object carries a certain degree of
responsibility. It would be very easy to define a pattern that
is non-physical and will lead to erroneous results. The
user-defined temperature distributions should (probably) be
balanced about the mean so that basic conservation of energy
laws are not violated.
This field provides the name of a schedule that will
determine if this model is available. When not available the
room air is modeled as completely mixed. When it is available,
then a user-defined temperature distribution will be applied.
This schedule should be set to “1.0” when model is available
and “0.0” when the model is not to be used. If this field is
blank, the schedule has values of 1 for all time periods.
This field provides the name of schedule that will be used
to control which user-defined RoomAir temperature pattern will
be applied at any given time. This schedule needs to have
integer values that are closely coordinated with those defined
as the second field in one of the RoomAir:TemperaturePattern:*
objects described below. These schedule values provide the
link to the actual patterns to be used throughout the day.
This allows controlling which user-defined pattern is used at
different times during the simulation. For example, one could
use one pattern when the air system is scheduled to be on, and
a different pattern when the air system is schedule to be off.
Or if the user has knowledge of how the air temperature
pattern changes over the course of day in response to changing
thermal loads, then this schedule can be used to control when
individual patterns are used. For example, a control schedule
could use a pattern designated as number 100 from 18:00 to
6:00, pattern number 200 from 6:00 to 12:00, and pattern
number 300 from 12:00 to 18:00.
An example of this object is
RoomAir:TemperaturePattern:UserDefined,
Ground Floor South Air Temp Controls, !- Name
ZN2_S_1, !- Zone Name
Always_on, !- Availability Schedule Name
Roomair Pattern 1; !- Pattern Control Schedule Name
This object is used to model room air with a fixed
temperature gradient in the vertical direction. This
fixed-slope method is about the simplest distribution
pattern.
In addition to the vertical temperature gradient, there are
three other parameters included in the pattern that are
important. The first two might affect how the air system
conditioning the room is operated. The first describes the
temperature difference between the mean air temperature and
the point where the sensor of a drybulb thermostat is
situated. The second describes the temperature difference
between the mean and the point where system air is being
extracted from the zone. This is considered important because
the changes in temperature difference between supply and
return can affect how an air system is controlled to meet the
loads. The third parameter can affect the zone air heat
balance by altering the temperature of the air leaving the
zone through exhaust fans.
One example of a source of input data for the vertical
temperature gradient is ANSI/ASHRAE Standard 55-2004 Thermal
Environmental Conditions for Human Occupancy. Table 5.2.4.3 in
this Standard specifies an allowable vertical temperature
difference between head level and ankle level of 3ºC (5ºF). If
we assume a head to ankle length scale of 1.5 m (5 ft), this
leads to a temperature gradient of 3ºC/1.5m, or 2.0 ºC/m.
This field provides a unique name for this object.
Field:
Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique
among all other RoomAir:TemperaturePattern:* objects. The
value used here needs to be in the Pattern Control Schedule
for those times when this pattern is to be used for the Room
Air Temperature Distribution.
This field specifies the gradient, or slope, of temperature
changes in the vertical direction in ºK/m.
An example of this object is:
RoomAir:TemperaturePattern:ConstantGradient,
half C per Meter, !- Name
10005, !- Control Integer for Pattern Control Schedule Name
0.0, !- Thermostat Offset (Temp at thermostat- Mean Air Temp) [C]
1.0, !- Return Air Offset (Tleaving - Mean Air Temp ) [C]
1.0, !- Exhaust Air Offset (Texhaust - Mean Air Temp) [C]
0.5; !- Temperature Gradient [K/m]
This object provides various controls over the value of the
gradient used for determining the pattern of room air
temperatures. It is similar to previous object RoomAir:TemperaturePattern:ConstantGradient
object but simplifies the potentially arduous task of
preparing and scheduling a large number of those objects. With
this object, two different gradients are entered and user is
given several options for controlling how the program will
interpolate between the two bounds. The user inputs the height
of the location of thermostat, return air, and exhaust air in
meters rather than the temperature offset.
This field provides a unique name for this object.
Field:
Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique
among all other RoomAir:TemperaturePattern:* objects. The
value used here needs to be in the Pattern Control Schedule
for those times when this pattern is to be used for the Room
Air Temperature Distribution.
This field specifies the distance above the floor where the
thermostat is situated. This height is used by the model to
determine the thermostat temperature relative to the mean air
temperature by applying the gradient.
This field specifies the distance above the floor where the
air leaves the zone and returns to the air system. and the
mean air temperature. This height is used by the model to
determine the return air temperature relative to the mean air
temperature by applying the gradient.
This field specifies the distance above the floor where the
air leaves the zone and enters and exhaust device such as an
exhaust fan. This height is used by the model to determine the
exhaust air temperature relative to the mean air temperature
by applying the gradient.
This field specifics how the program will vary between the
two gradients. Select one of the following keywords to choose
the simulation data used to scale: ‘Outdoor Environment
Drybulb Temperature’, ‘Zone
Drybulb Temperature’, ‘Delta Outdoor and Zone
Temperature’, ‘Sensible Cooling Load’, and ‘Sensible Heating
Load’. These are explained in detail below. All of these
options have several things in common. They are essentially
hard-coded. There is no support for a general method. The
interpolation scheme is based on some variable that might
reasonably be expected to correlate with gradient changes.
This variable’s current value is used to continually adjust
the value of the vertical gradient for room air
temperature.
OutdoorDryBulbTemperature: This key
directs the program to interpolate between upper and lower
values of the vertical gradient based on the outdoor air
temperature. If the outdoor temperature exceeds the upper
limit set in the next field, then the gradient entered in the
‘Temperature Gradient Upper Bound’ field is used. Similarly if
the outdoor air temperature is below the value set in the
‘Lower Temperature’ field, then the gradient entered in the
‘Temperature Gradient Lower Bound’ is used. For outdoor
temperatures that lie between the upper and lower bounds, the
gradient is determined by linear interpolation between the
two.
ZoneDryBulbTemperature: This key directs
the program to interpolate between upper and lower values of
the vertical gradient based on the mean zone air temperature.
If the mean zone air temperature exceeds the upper limit set
in the next field, then the gradient entered in the
‘Temperature Gradient Upper Bound’ field is used. Similarly if
the mean zone air temperature is below the value set in the
‘Lower Temperature’ field, then the gradient entered in the
‘Temperature Gradient Lower Bound’ is used. For mean zone air
temperatures that lie between the upper and lower bounds, the
gradient is determined by linear interpolation between the
two.
ZoneAndOutdoorTemperatureDifference: This
key directs the program to interpolate between upper and lower
values of the vertical gradient based on the difference
between the outdoor environment and the mean zone air
temperature. If the temperature difference exceeds the upper
limit set in the next field, then the gradient entered in the
‘Temperature Gradient Upper Bound’ field is used. Similarly if
the temperature difference is below the value set in the
‘Lower Temperature’ field, then the gradient entered in the
‘Temperature Gradient Lower Bound’ is used. For temperature
differences that lie between the upper and lower bounds, the
gradient is determined by linear interpolation between the
two.
SensibleCoolingLoad: This key directs the
program to interpolate between upper and lower values of the
vertical gradient based on the sensible cooling load. If the
cooling load exceeds the upper limit set in the next field,
then the gradient entered in the ‘Temperature Gradient Upper
Bound’ field is used. Similarly if the cooling load is below
the value set in the ‘Lower Temperature’ field, then the
gradient entered in the ‘Temperature Gradient Lower Bound’ is
used. For cooling loads that lie between the upper and lower
bounds, the gradient is determined by linear interpolation
between the two.
SensibleHeatingLoad: This key directs the
program to interpolate between upper and lower values of the
vertical gradient based on the sensible heating load. If the
heating load exceeds the upper limit set in the next field,
then the gradient entered in the ‘Temperature Gradient Upper
Bound’ field is used. Similarly if the heating load is below
the value set in the ‘Lower Temperature’ field, then the
gradient entered in the ‘Temperature Gradient Lower Bound’ is
used. For heating loads that lie between the upper and lower
bounds, the gradient is determined by linear interpolation
between the two.
This field is used to enter the upper bound on heat rate
values. It is required for the interpolation modes based on
load. Both heating and cooling loads are entered as positive
numbers (in watts).
This field is used to enter the lower bound on heat rate
values. It is required for the interpolation modes based on
load. Both heating and cooling loads are entered as positive
numbers (in watts).
An example of this object follows. This pattern will apply
no gradient (effectively the mixing model) if zone air
temperatures are 22.5 C or lower. It will apply a gradient of
1 K/m if zone temperatures are 26.0 C or higher. For zone air
temperatures between 22.5 and 26.0 it will determine the
gradient by linear interpolation and use a gradient between
0.0 and 1.0 K/m depending on where the zone air temperature is
in the range.
RoomAir:TemperaturePattern:TwoGradient,
Mixed to one C per M by Zone DB, !- Name
2002, !- Control Integer for Pattern Control Schedule
1.1, !- Thermostat Height meters
4.5, !- Return Air Height
3.5, !- Exhaust Air Height
0.0, !- Temperature Gradient Lower Bound K/m
1.0, !- Temperature Gradient Upper Bound K/m
ZoneDrybulbTemperature, !- Gradient Interpolation Mode
26.0, !- Upper Temperature [C]
22.5, !- Lower Temperature [C]
, !- Upper Heat Rate [W]
; !- Lower Heat Rate [W]
The user-defined air temperature pattern that interpolates
between two gradients produces the following output
variable.
HVAC,Average,Room Air Zone Vertical Temperature Gradient [K/m]
Room
Air Zone Vertical Temperature Gradient [K/m][LINK]
This output variable is the result of the interpolation
performed by the user-defined roomair model using RoomAir:TemperaturePattern:TwoGradient.
This is the temperature gradient in the vertical direction.
The units are degrees Kelvin per meter.
This object defines a distribution pattern for air
temperatures relative to the current mean air temperature as a
function of height. The height, referred to as Zeta, is
non-dimensional by normalizing with the zone ceiling height.
(The actual zone ceiling height can be explicitly entered in
the ‘Zone’
object but if not it is calculated by EnergyPlus from the
surfaces attached to the zone.) The temperature differences
are not non-dimensional and remain in units of degrees
Celsius.
An example of a vertical temperature pattern is shown in
the figure below. The pattern itself is treated as a
piecewise, linear model of air temperature as a function of
height. This Zeta-DeltaTai curve, or lookup table, is then
mapped to surfaces defined elsewhere in the file. The centroid
of each surface and zone ceiling height are used to
automatically assign Zeta values within the program. The zone
named in the referencing RoomAir:TemperaturePattern:UserDefined
object is used to determine which surfaces will be associated
with the pattern when it is applied. A single pattern object
can be reused for multiple zones and times.
In addition to the vertical temperature pattern there are
three other parameters included in the pattern that are
important. The first two might affect how the air system
conditioning the room is operated. The first describes the
temperature difference between the mean air temperature and
the point where the sensor of a drybulb thermostat is
situated. The second describes the temperature difference
between the mean and the point where system air is being
extracted from the zone. This is considered important because
the changes in temperature difference between supply and
return can affect how an air system is controlled to meet the
loads. The third parameter can affect the zone air heat
balance by altering the temperature of the air leaving the
zone through exhaust fans.
Example of a Vertical Air
Temperature Pattern [fig:example-of-a-vertical-air-temperature-pattern]
This field provides a unique name for this object.
Field:
Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique
among all other RoomAir Temperature Pattern objects. The value
used here needs to be in the Pattern Control Schedule for
those times when this pattern is to be used for the Room Air
Temperature Distribution.
The remaining fields contain pairs of values that define a
lookup table for the temperature pattern in the vertical
direction. The first value is Zeta and the second value is
DeltaTai.
Zeta is the normalized height and should be a fractional
value from 0.0 to 1.0. A value of 0.0 corresponds to the floor
and a value of 1.0 corresponds to the ceiling. The Zeta values
need to be in increasing value.
Field: Pair
<#> Delta Adjacent Air Temperature[LINK]
DeltaT\(_{ai}\) is the
temperature difference between the air temperature at the
associated Zeta (T\(_{ai}\))
and the mean air temperature and is given in degrees
Celsius.
This object is extensible, so additional pairs of these
last two fields of this type can be added to the end of this
object. An example of this object corresponding to the figure
above is:
RoomAir:TemperaturePattern:NondimensionalHeight,
Rough UFAD Approx, !- Name
3001, !- Control Integer for Pattern Control Schedule
!- note reference this entry in Schedule
-1.0, !- Thermostat Offset
1.5, !- Return Air Offset (Tleaving - Mean Air Temp ) deg C
1.75, !- Exhaust Air Offset (Texhaust - Mean Air Temp) deg C
0.05, -1.8, !- pair 1 (Zeta , DeltaTai)
0.1, -1.7, !- pair 2 (Zeta , DeltaTai)
0.2, -0.8, !- pair 3 (Zeta , DeltaTai)
0.3, -0.2, !- pair 4 (Zeta , DeltaTai)
0.4, 0.5, !- pair 5 (Zeta , DeltaTai)
0.5, 0.8, !- pair 6 (Zeta , DeltaTai)
0.6, 1.2, !- pair 7 (Zeta , DeltaTai)
0.7, 1.4, !- pair 8 (Zeta , DeltaTai)
0.8, 1.4, !- pair 9 (Zeta , DeltaTai)
0.9, 1.42, !- pair 10 (Zeta , DeltaTai)
0.95, 1.44; !- pair 11 (Zeta , DeltaTai)
This object defines a distribution pattern for the air
temperatures adjacent to individual surfaces. This object uses
the specific names of individual surfaces defined elsewhere in
the model. This pattern allows controlling the adjacent air
temperature on a surface-by-surface basis rather than by
height. This allows modeling different adjacent air
temperatures on the opposite sides of the zone.
In addition to the surface mappings there are three other
parameters included in the pattern that are important. The
first two might affect how the air system conditioning the
room is operated. The first describes the temperature
difference between the mean air temperature and the point
where the sensor of a drybulb thermostat is situated. The
second describes the temperature difference between the mean
and the point where system air is being extracted from the
zone. This is considered important because the changes in
temperature difference between supply and return can affect
how an air system is controlled to meet the loads. The third
parameter can affect the zone air heat balance by altering the
temperature of the air leaving the zone through exhaust
fans.
This field provides a unique name for this object.
Field:
Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique
among all other RoomAir Temperature Pattern objects. The value
used here needs to be in the Pattern Control Schedule for
those times when this pattern is to be used for the RoomAir
Temperature Distribution.
The name of a surface defined elsewhere in the input
file.
Field:
Delta Adjacent Air Temperature Pair <#>[LINK]
DeltaT\(_{ai}\) is the
temperature difference between the air temperature adjacent to
the associated surface (T\(_{ai}\)) and the mean air
temperature and is given in degrees Celsius.
This object is extensible, so additional pairs of fields of
these types can be added to the end of this object. An example
of this object, which might be used to elevate temperatures
near west windows in the afternoon, is:
RoomAir:TemperaturePattern:SurfaceMapping,
GroundFloor SW Corner Hot Near West Wall, !- Name
4001, !- Control Integer for Pattern Control Schedule Name
0.0, !- Thermostat Offset(Temp at thermostat- Mean Air Temp)
0.0, !- Return Air Offset deg C
0.0, !- Exhaust Air Offset
ZN1_SW_1:W_ExtWall:1 , 0.8,!- pair 1 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:2 , 0.9,!- pair 2 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:3 , 1.0,!- pair 3 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:4, 1.1,!- pair 4 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:5, 1.3,!- pair 5 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:6, 1.5,!- pair 6 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:7, 1.7,!- pair 7 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:8, 2.1,!- pair 8 (Surface Name , DeltaTai)
ZN1_SW_1:W_ExtWall:9, 2.4;!- pair 8 (Surface Name , DeltaTai)
The RoomAir:Node
object is used to define air nodes for a nodal air model. The
number of air node objects that need to be specified depends
on the nodal air model selected. (However, currently only the
Mundt model uses this object). In order to use the Mundt
model, the user must specify six or more RoomAir:Node
objects of different types for each zone. The exact number of
RoomAir:Node
in the model will vary based on the resolution of walls. If
walls (heat transfer surfaces) are split into separate
segments in the vertical direction, then more air nodes of
type ‘MundtRoom’ will be useful. At a minimum, for the Mundt
model RoomAir Nodes of the following type are required:
‘Inlet, ’Floor, ’Control, ’Ceiling, ’MundtRoom, and
’Return.’
This field indicates the name of the zone (Ref: Zone) that
this air node belongs to. This should be the unique name of a
zone object defined elsewhere in the input file.
Field:
Height of Nodal Control Volume Center[LINK]
This numeric field indicates the height of the air node
center. Air models such as the Mundt model compute the air
temperature as a function of height and the value entered here
will be used to determine a result for this node. The value
should be specified in meters and relative to the floor of the
zone.
These remaining alpha fields indicate the names of the
surfaces (Ref: Surface) that are interacting convectively with
this air node. This field is optional and related to the
previous field. Currently, at most 20 surfaces are allowed to
interact with a single air node. Only those nodes that
interact with the inside faces of surfaces need to specify
surface names. Each surface should couple to no more than 1
node.
An IDF example:
RoomAir:Node,
WESTZN:FLOORAIR, !- Node Name
Floor, !- Node Type
WEST ZONE, !- Name of Zone to Which the Air Node Belongs
0.1, !- Height of Nodal Control Volume Center {m}
WESTZN:FLOOR:LEFF, !- surface name
WESTZN:FLOOR:RIGHT; !- surface name
The RoomAirSettings:OneNodeDisplacementVentilation
object is used to specify additional input parameters required
by the Mundt model that are not available in other input
objects in EnergyPlus. A single object will be used for the
zone.
This alpha field indicates the name of the zone (Ref: Zone)
for the required input parameters as specified in the
following fields.
Field:
Fraction of Convective Internal Loads Added to Floor Air[LINK]
This numeric field indicates what fraction of the
convective part of the internal gains is added to the air near
the floor in the zone specified.
Field:
Fraction of Infiltration Internal Loads Added to Floor
Air[LINK]
This numeric field indicates what fraction of the
infiltration air enters near the floor in the zone
specified.
An IDF example:
RoomAirSettings:OneNodeDisplacementVentilation,
WEST ZONE, !- Zone Name
0.1, !- Fraction of internal loads from the convective Floor Air
0.1; !- Fraction of internal loads from the Infiltration Air
This output variable provides the drybulb air temperature
used in, or calculated by, the Mundt model. The selection key
is the name of an air node defined in a ROOMAIR Node
object.
This model is applicable to spaces that are served by a low
velocity floor-level displacement ventilation air distribution
system. Furthermore, the dominant sources of heat gain should
be from people and other localized sources located in the
occupied part of the room. The model should be used with
caution in zones which have large heat gains or losses through
exterior walls or windows or which have considerable direct
solar gain. The model predicts three temperatures in the
room:
A foot level temperature (T\(_{\rm{FLOOR}}\)). The floor
region is 0.2 meters deep and T\(_{\rm{FLOOR}}\) represents the
temperature at the mid-point of the region.
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the
temperature in the region between the floor layer and the
upper, mixed layer.
An upper node representing the mixed-layer/outflow
temperature (T\(_{\rm{MX}}\))
essential for overall energy budget calculations and for
modeling comfort effects of the upper layer
temperature.
Schematic representation of the
three temperature points and temperature gradients [fig:schematic-representation-of-the-three]
The following fields are used to define an instance of the
‘UCSD Displacement Ventilation Model Controls’ object.
This field provides the unique name of a zone described
elsewhere in the file. A single instance of the ‘UCSD
Displacement Ventilation Model Controls’ object is needed for
each zone that is to be modeled using this method.
This field specifies the unique name of schedule defined
elsewhere in the input file. The schedule values are the
fractions of the convective portion of the internal gains in
the occupied subzone that remain in the occupied subzone. The
remainder of the convective portion of the internal gains in
the occupied subzone enters the plumes and is carried to the
upper subzone. The types of internal gains that are assumed to
be located in the occupied subzone are:
people
task lights
electric equipment
gas equipment
hot water equipment
steam equipment
other equipment
baseboard heat
Types of internal gains that are assumed to be in the upper
subzone are:
general lights
tubular daylighting devices
high temperature radiant heaters
The schedule values should be between 0 and 1. A value of 1
means that all the convection gains from equipment, task
lights and people are dispersed in the lower occupied subzone.
Conversely a value of 0 puts all the lower subzone convective
gains into the plumes rising into the upper well-mixed
subzone.
This field specifies number of plumes per occupant. Plumes
are associated with localized sources of convective heat gain
from people and equipment. For example, a value of 2.0 would
be used if each occupant has a computer that generates a
separate plume that does not merge with the plume from the
occupant in the lower, occupied, subzone.
The height in meters above the floor at which air
temperature is calculated for comfort purposes. The air
temperature at this height is used in calculating the
available measures of comfort: Fanger, Pierce, KSU,
CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1
meters.
Field:
Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference
between the upper mixed subzone and the occupied subzone that
will be used to trigger whether or not the displacement
ventilation auxiliary outputs will be calculated. These
outputs are Room Air Zone
Transition Height, Room Air Zone
Recommended Minimum Flow Fraction, Room Air Zone
Average Temperature Gradient and Room Air Zone
Maximum Temperature Gradient. They are set to negative
values when the temperature difference is less than the
threshold and the output Room Air Zone
Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in
units of degrees Centigrade. The default value is 0.4 degrees
C.
An example input:
RoomAirSettings:ThreeNodeDisplacementVentilation,
ZONE ONE, !- Zone Name
Constant - .2, !- Gain Distribution Schedule Name
1, !- Number of Plumes per Occupant
, !- Thermostat Height
, !- Comfort Height
.3; !- Temp. Difference Threshold for Displacement Ventilation
The height above the floor, in meters, of the boundary
between the lower occupied subzone and the upper well-mixed
subzone.
Room
Air Zone Recommended Minimum Flow Fraction [][LINK]
The ratio of the minimum recommended flow rate to the
actual flow rate. Here flow rate means the sum of
infiltration, ventilation, mixing and system air flow rates.
The minimum flow is the flow needed to establish the boundary
between the occupied and mixed subzones at 1.5 meters.
An integer flag that indicates whether the zone is mixed
(single node well-mixed zone model used) or stratified (UCSD
DV model used). The value 1 means well-mixed; 0 means
stratified.
Room
Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the floor
region and the middle of the well-mixed upper subzone in
degrees Kelvin per meter.
Room
Air Zone Maximum Temperature Gradient [K/m][LINK]
The maximum of the temperature gradient between the middle
of the floor region and the middle of the occupied subzone and
the temperature gradient between the middle of the occupied
subzone and the middle of the well-mixed subzone. The gradient
is in degrees Kelvin per meter.
Room
Air Zone Thermal Comfort Effective Air Temperature [C][LINK]
The temperature at the user specified comfort height in
degrees C.
The UCSD Cross Ventilation Room Air Model provides a simple
model for heat transfer and temperature prediction in cross
ventilated rooms. Cross Ventilation (CV) is common in many
naturally ventilated buildings, with air flowing through
windows, open doorways and large internal apertures across
rooms and corridors in the building.
The CV model is used in EnergyPlus in the context of
natural ventilation simulations using the AirflowNetwork
airflow prediction model. Typical CV room flows are
characterized by two clearly distinguishable flow regions that
have different airflow velocities and temperature:
Jet regions in front of the inflow windows
Recirculation regions in the portions of the room that
are not directly in front of the windows.
Each inflow aperture has one jet region while the
recirculation regions are treated as a whole, with a single
temperature and characteristic velocity. The default
EnergyPlus perfectly mixed single temperature node room air
approach is not suitable for these partially mixed flows. The
proposed CV model uses multiple nodes with distinct air
temperature and airflow velocity (one node for the
recirculations plus one additional node for each inflow
aperture).
Schematic representation of
room air geometry a) schematic representation of a room
geometry that generates cross ventilation airflow. b) the
proposed model distinguishes two regions in the flow: jet and
recirculation (shown here in a CFD simulation of one half of a
symmetrical room). [fig:schematic-representation-of-room-air-geometry]Schematic top view — possible
airflow patterns in cross-ventilation. [fig:schematic-top-view-possible-airflow-patterns]
The following fields are used to define an instance of the
‘UCSD Cross Ventilation Model Controls’ object.
This field provides the name of the zone to which this
object applies. A single instance of the ‘UCSD Cross
Ventilation Model Controls’ object is needed for each zone
modeled using this method.
This field specifies the unique name of schedule defined
elsewhere in the input file. The schedule values define the
fractions of the convective portion of the internal gains in
the jet and recirculation regions.
The schedule values should be between 0 and 1. A value of 1
means that all the convective gains are dispersed in the jet
region. Conversely a value of 0 puts all the convective gains
into the recirculation region.
Field:
Airflow Region Used for Thermal Comfort Evaluation[LINK]
Required field whenever thermal comfort is predicted.
Defines air temperature and mean airflow velocity that will be
used in the Fanger model. Conditions must refer to one of the
two regions defined in the model: jet or recirculation.
Average air temperature in the jet region of the flow in
degrees C. If there is more than one inflow window this output
will be the inflow-area-weighted average of the jet region
temperature.
Room
Air Zone Recirculation Region Temperature [C][LINK]
Average air temperature in the recirculation region of the
flow in degrees C.
Room
Air Zone Jet Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the jet region of the flow in
meters per second. If there is more than one inflow window
this output will be the inflow area weighted area of the jet
inflow velocities.
Room
Air Window Jet Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the jet region in front of the
window, in meters per second.
Room
Air Zone Recirculation Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the recirculation region of the
flow in meters per second.
Room
Air Zone Recirculation and Inflow Rate Ratio [][LINK]
Ratio between airflow rate in the recirculation regions and
the total inflow rate, non-dimensional.
Area of the inflow aperture in square meters. This area can
change due to variation in wind direction (as inflow aperture
changes) or variations in the opening schedule.
An integer flag that indicates whether the zone is mixed
(single node well-mixed zone model used) or significant
momentum conservation is occurring (UCSD CV model used). The
value 1 means well-mixed; 0 means cross ventilation is
present. Transition to mixed flow can occur due to three
mechanism: reduction in inflow velocity, reduction in inflow
aperture area and dominance of buoyancy effects. A value of 1
is yes, a value of 0 is no.
An integer flag that indicates whether recirculations are
present in the flow. A cross ventilation flow does not have
recirculations whenever the inflow area is similar to the room
cross section area (such as airflow in a typical corridor). A
value of 1 is yes, a value of 0 is no.
This model is applicable to interior spaces that are served
by an underfloor air distribution system. The dominant sources
of heat gain should be from people, equipment, and other
localized sources located in the occupied part of the room.
The model should be used with caution in zones which have
large heat gains or losses through exterior walls or windows
or which have considerable direct solar gain. The model
predicts two temperatures in the room:
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the
temperature in the region between the floor and the boundary
of the upper subzone.
An upper subzone temperature (T\(_{\rm{MX}}\)) essential for
overall energy budget calculations and for modeling comfort
effects of the upper layer temperature.
The following fields are used to define an instance of the
‘UCSD UFAD Interior Model Controls’ object.
This field provides the unique name of a zone described
elsewhere in the file. A single instance of the ‘RoomAirSettings:UnderFloorAirDistributionInterior’
object is needed for each zone that is to be modeled using
this method.
The total number of diffusers in this zone. This field can
allowed to Autocalculate (in which case it is set to the
design occupancy level; i.e., number of people). If the design
occupancy is low or zero but there are still heat sources that
could generate buoyancy driven plumes, the user should input a
value based on the design supply air flow rate of the zone and
the design flow rate of an individual diffuser. In the absence
of any other information, divide the zone area by 100 ft\(^{2}\). The default for this
field is Autocalculate.
The power in watts incorporated in a buoyancy driven
thermal plume. Normally we assume all the loads of a
workstation create a single plume so that this represents the
convective heat gain from a workstation – 1 person, 1 computer
terminal, plus any task lighting. A typical value would be 220
watts. However, the model assumes an “equivalent” plume
derived from the zone extraction rate normalized to the number
of workstations/occupants. This field should be allowed to
default – the program will calculate a value based upon the
occupancy and the extraction rate. The default is
Autocalculate.
This is the design air flow opening area in square meters
of a single diffuser. The default value depends on the
diffuser type. For swirl diffusers it is 0075 m\(^{2}\), for variable area
diffusers 0.035 m\(^{2}\),
for horizontal swirl diffusers 0.006 m\(^{2}\), and for linear bar
grilles 0.03 m\(^{2}\). The
default is Autocalculate..
This input describes the angle at which air emerges from
the diffusers. It should be the angle in degrees between the
vertical and the diffuser slots. The defaults depend on the
diffuser type: for swirl diffusers it is 28 degrees, for
variable area diffusers 45 degrees, for DV diffusers 73
degrees, and for linear bar grilles 15 degrees.
The height in meters above the floor at which air
temperature is calculated for comfort purposes. The air
temperature at this height is used in calculating the
available measures of comfort: Fanger, Pierce, KSU,
CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1
meters.
Field:
Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference
between the upper subzone and the occupied subzone that will
be used to trigger whether or not the UFAD auxiliary outputs
will be calculated. These outputs are Room Air Zone
Transition Height and Room Air Zone
Average Temperature Gradient. They are set to zero when
the temperature difference is less than the threshold and the
output Room Air Zone
Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in
units of degrees Centigrade. The default value is 0.4 degrees
C.
The choices for this alpha field are SwirlVariableAreaHorizontalSwirl
LinearBarGrille Custom. The swirl and displacement
diffusers are fixed area diffusers. The variable area
diffusers maintain an approximately constant exit velocity.
Linear bar grilles are normally used in exterior zones and are
fixed area diffusers. Custom is used to signify that the user
intends to input the coefficients A – E (see below) rather
than let the program set the coefficients based on diffuser
type. The default is Swirl.
An optional field to allow the user to specify the
transition height (meters above floor) rather than have the
program calculate it. The default is 1.7 meters.
The coefficient A in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient B in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient C in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient D in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient E in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
An example input is:
RoomAirModelType,
SPACE5-1 RoomAir Model, !- Name
SPACE5-1, !- Zone Name
UnderFloorAirDistributionInterior, !- Room-Air Modeling Type
DIRECT; !- Air Temperature Coupling Strategy
RoomAirSettings:UnderFloorAirDistributionInterior,
SPACE5-1, !- Zone Name
Autocalculate, !- Number of Diffusers
Autocalculate, !- Power per Plume
Autocalculate, !- Design Effective Area of Diffuser {m2}
Autocalculate, !- Diffuser Slot Angle from Vertical {deg}
, !- Thermostat Height {m}
, !- Comfort Height {m}
0.001, !- Temperature Difference Threshold for Reporting {deltaC}
Swirl, !- Diffuser Type
1.7, !- Transition Height {m}
Autocalculate, !- Coefficient A
Autocalculate, !- Coefficient B
Autocalculate, !- Coefficient C
Autocalculate, !- Coefficient D
Autocalculate; !- Coefficient E
An integer flag that indicates whether the zone is mixed
(single node well-mixed zone model used) or stratified (UCSD
UFI model used). The value 1 means well-mixed; 0 means
stratified.
Room
Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the occupied
subzone and the middle of the upper subzone in degrees Kelvin
per meter.
Room
Air Zone Effective Comfort Air Temperature [C][LINK]
The temperature at the user specified comfort height in
degrees C.
The temperature at the height of the thermostat (specified
by user input) in degrees C.
Room Air
Zone Transition Height Gamma Value [][LINK]
Value of gamma – a dimensionless “height” used in
calculating the transition height. Lower values of gamma
indicate increased stratification, higher values less.
Generally the values should be between 2 and 30.
The heat in watts driving the plumes in the occupied
subzone.
Room
Air Zone Temperature Stratification Fraction [][LINK]
This output, (Phi) is a measure of temperature
stratification in the space. It is the difference between the
occupied subzone temperature and the supply temperature
divided by difference between the return temperature and the
supply temperature. Technically it is equal to Kc. As phi
approaches 1, the space is fully mixed. As phi approaches 0,
the space becomes fully stratified. Expressed as an
equation:
This model is applicable to exterior spaces that are served
by an underfloor air distribution system. The dominant sources
of heat gain should be from people, equipment, and other
localized sources located in the occupied part of the room, as
well as convective gain coming from a warm window. The model
predicts two temperatures in the room:
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the
temperature in the region between the floor and the boundary
of the upper subzone..
An upper subzone temperature (T\(_{\rm{MX}}\)) essential for
overall energy budget calculations and for modeling comfort
effects of the upper layer temperature.
The following fields are used to define an instance of the
‘UCSD UFAD Exterior Model Controls’ object.
This field provides the unique name of a zone described
elsewhere in the file. A single instance of the ‘RoomAirSettings:UnderFloorAirDistributionExterior’
object is needed for each zone that is to be modeled using
this method.
The total number of diffusers in this zone. This field can
allowed to Autocalculate (in which case it is set to the
design occupancy level; i.e., number of people). If the design
occupancy is low or zero but there are still heat sources that
could generate buoyancy driven plumes, the user should input a
value based on the design supply air flow rate of the zone and
the design flow rate of an individual diffuser. In the absence
of any other information, divide the zone area by 100 ft\(^{2}\). The default for this
field is Autocalculate.
The power in watts incorporated in a buoyancy driven
thermal plume. Normally we assume all the loads of a
workstation create a single plume so that this represents the
convective heat gain from a workstation – 1 person, 1 computer
terminal, plus any task lighting. A typical value would be 220
watts. However, the model assumes an “equivalent” plume
derived from the zone extraction rate normalized to the number
of workstations/occupants. This field should be allowed to
default – the program will calculate a value based upon the
occupancy and the extraction rate. The default is
Autocalculate.
This is the design air flow opening area in square meters
of a single diffuser. The default value depends on the
diffuser type. For swirl diffusers it is 0075 m\(^{2}\), for variable area
diffusers 0.035 m\(^{2}\),
for horizontal swirl diffusers 0.006 m\(^{2}\), and for linear bar
grilles 0.03 m\(^{2}\). The
default is Autocalculate..
This input describes the angle at which air emerges from
the diffusers. It should be the angle in degrees between the
vertical and the diffuser slots. The defaults depend on the
diffuser type: for swirl diffusers it is 28 degrees, for
variable area diffusers 45 degrees, for DV diffusers 73
degrees, and for linear bar grilles 15 degrees.
The height in meters above the floor at which air
temperature is calculated for comfort purposes. The air
temperature at this height is used in calculating the
available measures of comfort: Fanger, Pierce, KSU,
CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1
meters.
Field:
Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference
between the upper subzone and the occupied subzone that will
be used to trigger whether or not the UFAD auxiliary outputs
will be calculated. These outputs are Room Air Zone
Transition Height and Room Air Zone
Average Temperature Gradient. They are set to zero when
the temperature difference is less than the threshold and the
output Room Air Zone
Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in
units of degrees Centigrade. The default value is 0.4 degrees
C.
The value should be greater than or equal to zero and is in
units of degrees Centigrade. The default value is 0.4 degrees
C.
The choices for this alpha field are SwirlVariableAreaHorizontalSwirl
LinearBarGrille Custom. The swirl and displacement
diffusers are fixed area diffusers. The variable area
diffusers maintain an approximately constant exit velocity.
Linear bar grilles are normally used in exterior zones and are
fixed area diffusers. Custom is used to signify that the user
intends to input the coefficients A – E (see below) rather
than let the program set the coefficients based on diffuser
type. The default is Swirl.
An optional field to allow the user to specify the
transition height (meters above floor) rather than have the
program calculate it. The default is 1.7 meters.
The coefficient A in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient B in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient C in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient D in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
The coefficient E in the formula: Kc = A*Gamma**B + C +
D*Gamma + E*Gamma**2. Gamma is a variable that characterizes
the amount of stratification in a UFAD zone. Kc is the
fraction of the total internal convective heat gain that is
assigned to the lower (occupied) subzone. The coefficients in
the formula are defaulted based upon diffuser type. A user
would normally allow this field to default. The default is
autocalculate.
An example input is:
RoomAirSettings:UnderFloorAirDistributionExterior,
SPACE1-1, !- Zone Name
Autocalculate, !- Number of Diffusers per Zone
Autocalculate, !- Power per Plume
Autocalculate, !- Design Effective Area of Diffuser {m2}
Autocalculate, !- Diffuser Slot Angle from Vertical {deg}
, !- Thermostat Height {m}
, !- Comfort Height {m}
0.001, !- Temperature Difference Threshold for Reporting {deltaC}
LinearBarGrille, !- Diffuser Type
1.7, !- Transition Height {m}
Autocalculate, !- Coefficient A
Autocalculate, !- Coefficient B
Autocalculate, !- Coefficient C
Autocalculate, !- Coefficient D
Autocalculate; !- Coefficient E
An integer flag that indicates whether the zone is mixed
(single node well-mixed zone model used) or stratified (UCSD
UFE model used). The value 1 means well-mixed; 0 means
stratified.
Room
Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the occupied
subzone and the middle of the upper subzone in degrees Kelvin
per meter.
Room
Air Zone Effective Comfort Air Temperature [C][LINK]
The temperature at the user specified comfort height in
degrees C.
The temperature at the height of the thermostat (specified
by user input) in degrees C.
Room
Air Zone Transition Height Gamma Value [][LINK]
Value of gamma – a dimensionless “height” used in
calculating the transition height. Lower values of gamma
indicate increased stratification, higher values less.
Generally the values should be between 2 and 30.
The heat in watts driving the plumes in the occupied
subzone.
Room
Air Zone Window Plume Heat Transfer Rate [W][LINK]
The convective heat gain from windows in an
UnderFloorAirDistributionExterior zone.
Room
Air Zone Temperature Stratification Fraction [][LINK]
This output, (Phi) is a measure of temperature
stratification in the space. It is the difference between the
occupied subzone temperature and the supply temperature
divided by difference between the return temperature and the
supply temperature. Technically it is equal to Kc. As phi
approaches 1, the space is fully mixed. As phi approaches 0,
the space becomes fully stratified. Expressed as an
equation:
This model simulates a thermal zone using a network
approach by assuming intra-zone nodes connected by
user-defined patterns of airflows. The new model also allows
users to specify a node to be connected to surfaces to have
convective heat transfer between surfaces and the node,
portion of internal gains and supply air and return air
fractions from zone equipment. The model requires following
objects to work together:
The first five objects are described below. The last two
objects are described in the Airflow Network Model section.
This model also requires additional AirflowNetwork:* objects
to form a complete network.
This object provides inputs in a thermal zone needed for
the RoomAirflowNetwork model. The inputs specify a thermal
zone and a list of RoomAir nodes. The object gives a summary
of the model configuration in a zone.
This is the name of a RoomAir:Node:AirflowNetwork
object that contains the sensor for zone HVAC controls. The
conditions at this node will be used for thermostatic,
humidistatic, or comfort based control decisions. The zone
node defined in a Zone
object is required.
The name of a RoomAir:Node:AirflowNetwork
object defined elsewhere. This node will receive the fraction
of internal gains, and HVAC equipment, and a list of surface
names exposed to this node with convective heat transfer.
An IDF example input is:
RoomAirSettings:AirflowNetwork,
NORTH_ZONE, !- Name
NORTH_ZONE, !- Zone Name
RoomAir Schedule, !- Availability Schedule Name
NORTH_ZONE, !- Control Point RoomAir:Node Name
LeftUpper, !- RoomAir:Node:AirflowNetwork 1 Name
CentralUpper, !- RoomAir:Node:AirflowNetwork 2 Name
NORTH_ZONE, !- RoomAir:Node:AirflowNetwork 3 Name
LeftMiddle, !- RoomAir:Node:AirflowNetwork 4 Name
LeftLower, !- RoomAir:Node:AirflowNetwork 5 Name
CentralLower; !- RoomAir:Node:AirflowNetwork 6 Name
This object is used to define a node in a thermal zone. The
input specifies the fraction of zone volume and provides a
list of names to define fraction of internal gains, surface
connection and HVAC equipment.
The field specifies a fraction of the overall zone air
volume that is assigned to this RoomAir:Node:AirflowNetwork
object. The fraction will be used to calculate zone air
storage term. See corresponding sections in Engineering
Reference for its use in the node energy and moisture balance
equations.
The field specifies a name to provide a list of connected
adjacent surfaces with convective heat transfer between
surfaces and this particular node. When a moisture mode is
assigned to surfaces, convective moisture transfer will be
calculated. See corresponding sections in Engineering
Reference for its use in the node energy and moisture balance
equations.
The field specifies a name to provide a list of internal
gain objects and associated fractions assigned to this
particular node. See corresponding sections in Engineering
Reference for its use in the node energy and moisture balance
equations.
The field specifies a name to provide a list of HVAC
equipment, including AirLoop terminals and zone equipment. See
corresponding sections in Engineering Reference for its use in
the node energy and moisture balance equations.
RoomAir:Node:AirflowNetwork,
LeftUpper, !- Name
NORTH_ZONE, !- Zone Name
0.15, !- Fraction of Zone Air Volume
Surface_18_T_List, !- RoomAir:Node:AirflowNetwork:AdjacentSurfaceList Name
LeftUpper_Gain, !- RoomAir:Node:AirflowNetwork:InternalGains Name
LeftUpper_HVAC; !- RoomAir:Node:AirflowNetwork:HVACEquipment Name
This object is used to provide a list of connected adjacent
surfaces with convective heat transfer between surfaces and
this particular node. When a moisture mode is assigned to
surfaces, convective moisture transfer will be calculated. It
should be pointed out that a fraction of a surface exposed to
this particular node is not allowed.
The field specifies a fraction of the particular internal
gain object assigned to this node.
This object is extensible, so additional groups of these
last three fields can be added to the end of this object.
RoomAir:Node:AirflowNetwork:InternalGains,
CentralUpper_Gain, !- Name
People, !- Internal Gain Object 1 Type
NORTH_ZONE People, !- Internal Gain Object 1 Name
0.15, !- Fraction of Gains to Node 1
Lights, !- Internal Gain Object 2 Type
NORTH_ZONE Lights, !- Internal Gain Object 2 Name
0.15, !- Fraction of Gains to Node 2
ElectricEquipment, !- Internal Gain Object 3 Type
NORTH_ZONE Equip, !- Internal Gain Object 3 Name
0.15; !- Fraction of Gains to Node 3
Field:
ZoneHVAC or Air Terminal Equipment Object Type <#>[LINK]
The field specifies an object type of ZoneHVAC equipment or
terminal type based on the list in the Energy+.idd.
Field:
ZoneHVAC or Air Terminal Equipment Object Name <#>[LINK]
The field specifies the object name based on the object
type defined in the previous field.
Field:
Fraction of Output or Supply Air from HVAC Equipment
<#>[LINK]
The field specifies a fraction of supply air from the
particular equipment to this node.
Field:
Fraction of Input or Return Air from HVAC Equipment
<#>[LINK]
The field specifies a fraction of return air from the
particular equipment to this node.
This object is extensible, so additional groups fields of
these last four fields can be added to the end of this
object.
RoomAir:Node:AirflowNetwork:HVACEquipment,
CentralUpper_HVAC, !- Name
ZoneHVAC:PackagedTerminalAirConditioner, !- ZoneHVAC or Air Terminal Equipment Object Type 1
NORTH_ZONE PTAC, !- ZoneHVAC or Air Terminal Equipment Object Name 1
0.14, !- Fraction of Output or Supply Air from HVAC Equipment 1
0.14; !- Fraction of Input or Return Air to HVAC Equipment 1
Each room air model sets up outputs specific to that model.
The effect of room air modeling is usually to adjust the
adjacent air temperature along the inside surface of heat
transfer surfaces. The output report “Surface Int Adjacent Air
Temperature [C]” is provided for this and described under
Surface Outputs.
Zone
Predicted Sensible Load Room Air Correction Factor[LINK]
This output variable provides the value of the correction
factor applied to the predicted zone loads. Predicted zone
load to setpoint is (usually) used to control HVAC air systems
and the presence of a room air model has an impact on the
loads. The predicted loads are multiplied by the factor in
this output variable. The value is always 1.0 when there is no
Room Air model. When there is a Room Air model, this output
shows how that model is increasing or decreasing overall zone
loads experienced by the air system.
Group – Room Air Models[LINK]
Room Air Models[LINK]
The group of input objects described in this section is used to account for non-uniform room air temperatures that may occur within the interior air volume of a zone. Room air modeling was added to EnergyPlus starting with Version 1.2. Although there are many types of analyses (comfort, indoor air quality, etc) that might benefit from localized modeling of how room air varies across space, only the temperature distribution of room air within the zone is currently addressed in EnergyPlus. This allows surface heat transfer and air system heat balance calculations to be made taking into account natural thermal stratification of air and different types of intentional air distribution designs such as under-floor and side-wall displacement ventilation that purport to extract room air at higher-than-mean temperatures. Note that EnergyPlus does not have completely general methods of modeling room air that are applicable to every conceivable type of airflow that might occur in a zone. Such models (e.g. RANS-CFD) are too computationally expensive to use with EnergyPlus for the foreseeable future. The models that are available in EnergyPlus offer only limited modeling capabilities for select room airflow configurations. Also note that because the complete mixing model for room air has long been the standard in building energy simulation, there is not currently a consensus on how to best model non-uniform air temperatures in buildings. Therefore, it is up to the user to have a good understanding of when, where, and how to apply the room air models available in EnergyPlus. The rest of this section provides some guidance in the way of examples and further discussion of the models available in EnergyPlus.
EnergyPlus offers the different types of air models listed in the table below along with the input objects associated with the use of that model.
RoomAirModelType[LINK]
EnergyPlus uses the RoomAirModelType object to determine which air model is available for use in a given zone during the simulation. If no RoomAirModelType object is specified (for each zone or the whole building), then EnergyPlus will run with the conventional, completely mixing air model (for each zone or the whole building). Include a RoomAirModelType for each zone that the user wants modeled using a more detailed method. Currently only a single RoomAirModelType object can be specified for each zone; you cannot switch between models during a simulation. However, the UCSD Displacement, Cross Ventilation and UFAD models switch from displacement to mixing ventilation when the operating conditions do not give rise to unmixed flow. The following parameters are fields required by the RoomAirModelType object.
Inputs[LINK]
Field: Name[LINK]
This alpha field is the air model name selected by user. It is used as an identifier
Field: Zone Name[LINK]
This alpha field indicates the unique name of a Zone object defined elsewhere in the input file. The type of room air model selected will be applied to this zone.
Field: Room-Air Modeling Type[LINK]
This alpha field indicates the room-air model used for the specified zone. Currently, there are three options for different air models. Entering the keyword ‘Mixing’ specifies the conventional complete-mixing air model. Note that Mixing is the default and no RoomAirModelType object would be needed to use the complete-mixing model. Entering the keyword ‘UserDefined ’specifies the User Defined Room Air Temperature Patterns. Entering the keyword ’OneNodeDisplacementVentilation ’specifies the Mundt one node displacement ventilation air model for displacement ventilation. Entering the keyword ’ThreeNodeDisplacementVentilation’ specifies the three-node displacement ventilation model developed by the University of California, San Diego (UCSD DV). Entering the keyword ‘CrossVentilation’ specifies the two-zone cross ventilation model developed by the University of California, San Diego (UCSD CV). Entering the keyword ‘UnderFloorAirDistributionInterior’ specifies the two-node interior zone under floor air distribution model developed by the University of California, San Diego (UCSD UFI). Entering the keyword ‘UnderFloorAirDistributionExterior’ specifies the two-node exterior zone under floor air distribution model developed by the University of California, San Diego (UCSD UFE).
Field: Air Temperature Coupling Strategy[LINK]
This alpha field indicates how air temperatures predicted by the air models are used by the surface heat balance calculation. Two different coupling schemes are available: Direct (also known as T-couple) or Indirect (DT-couple). In general, indirect coupling is more suited to situations where room air is well controlled and/or the room air model is less robust. Direct coupling is more suited for floating zone air temperatures and/or accurate room air models.
The Mundt model can use either coupling scheme; the UCSD DV, UCSD CV, UCSD UFI, and UCSD UFE models ignore this field and use direct coupling.
Input either Direct or Indirect
An example idf entry follows
RoomAir:TemperaturePattern:UserDefined[LINK]
This object is used to explicitly define temperature patterns that are to be applied to the mean air temperature within a thermal zone. This Room Air modeling option is made available for a number of reasons. It allows modeling the consequences of air temperature variations during the design phase when little information is available about the specifics of the air distribution system or positioning of various loads. This option can be used to evaluate the energy implications of different design targets for the temperature patterns. It also provides a method of modeling the annual energy use implications for air temperature distributions determined using separate analyses or measurements. For example, this option could be used to understand the annual energy implications of an air distribution system that has been previously analyzed using Computational Fluid Dynamics.
This approach differs from the other Room Air modeling in that the static temperature pattern is not really modeled so that it will respond to conditions that develop during the simulation. More sophisticated dynamic Room Air models will adjust the temperature pattern based on various factors, such as air system flow rate, floor temperature, or rates of internal heat gains. The user-defined temperature distribution patterns are fixed at the beginning and EnergyPlus simply provides results that include the implications of those patterns. This user-defined distribution option may also be useful for checking dynamic Room Air models by using “bounding” analysis.
Note that using this object carries a certain degree of responsibility. It would be very easy to define a pattern that is non-physical and will lead to erroneous results. The user-defined temperature distributions should (probably) be balanced about the mean so that basic conservation of energy laws are not violated.
Inputs[LINK]
Field: Name[LINK]
This field provides a unique name for this object.
Field: Zone Name[LINK]
This field provides the unique name of a zone described elsewhere in the file.
Field: Availability Schedule Name[LINK]
This field provides the name of a schedule that will determine if this model is available. When not available the room air is modeled as completely mixed. When it is available, then a user-defined temperature distribution will be applied. This schedule should be set to “1.0” when model is available and “0.0” when the model is not to be used. If this field is blank, the schedule has values of 1 for all time periods.
Field: Pattern Control Schedule Name[LINK]
This field provides the name of schedule that will be used to control which user-defined RoomAir temperature pattern will be applied at any given time. This schedule needs to have integer values that are closely coordinated with those defined as the second field in one of the RoomAir:TemperaturePattern:* objects described below. These schedule values provide the link to the actual patterns to be used throughout the day. This allows controlling which user-defined pattern is used at different times during the simulation. For example, one could use one pattern when the air system is scheduled to be on, and a different pattern when the air system is schedule to be off. Or if the user has knowledge of how the air temperature pattern changes over the course of day in response to changing thermal loads, then this schedule can be used to control when individual patterns are used. For example, a control schedule could use a pattern designated as number 100 from 18:00 to 6:00, pattern number 200 from 6:00 to 12:00, and pattern number 300 from 12:00 to 18:00.
An example of this object is
RoomAir:TemperaturePattern:ConstantGradient[LINK]
This object is used to model room air with a fixed temperature gradient in the vertical direction. This fixed-slope method is about the simplest distribution pattern.
In addition to the vertical temperature gradient, there are three other parameters included in the pattern that are important. The first two might affect how the air system conditioning the room is operated. The first describes the temperature difference between the mean air temperature and the point where the sensor of a drybulb thermostat is situated. The second describes the temperature difference between the mean and the point where system air is being extracted from the zone. This is considered important because the changes in temperature difference between supply and return can affect how an air system is controlled to meet the loads. The third parameter can affect the zone air heat balance by altering the temperature of the air leaving the zone through exhaust fans.
One example of a source of input data for the vertical temperature gradient is ANSI/ASHRAE Standard 55-2004 Thermal Environmental Conditions for Human Occupancy. Table 5.2.4.3 in this Standard specifies an allowable vertical temperature difference between head level and ankle level of 3ºC (5ºF). If we assume a head to ankle length scale of 1.5 m (5 ft), this leads to a temperature gradient of 3ºC/1.5m, or 2.0 ºC/m.
Inputs[LINK]
Field: Name[LINK]
This field provides a unique name for this object.
Field: Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique among all other RoomAir:TemperaturePattern:* objects. The value used here needs to be in the Pattern Control Schedule for those times when this pattern is to be used for the Room Air Temperature Distribution.
Field: Thermostat Offset[LINK]
This field specifies the temperature difference between where the thermostat is situated and the mean air temperature.
Field: Return Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and returning to the air system and the mean air temperature.
Field: Exhaust Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and being exhausted out of the building and the mean air temperature.
Field: Temperature Gradient[LINK]
This field specifies the gradient, or slope, of temperature changes in the vertical direction in ºK/m.
An example of this object is:
RoomAir:TemperaturePattern:TwoGradient[LINK]
This object provides various controls over the value of the gradient used for determining the pattern of room air temperatures. It is similar to previous object RoomAir:TemperaturePattern:ConstantGradient object but simplifies the potentially arduous task of preparing and scheduling a large number of those objects. With this object, two different gradients are entered and user is given several options for controlling how the program will interpolate between the two bounds. The user inputs the height of the location of thermostat, return air, and exhaust air in meters rather than the temperature offset.
Inputs[LINK]
Field: Name[LINK]
This field provides a unique name for this object.
Field: Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique among all other RoomAir:TemperaturePattern:* objects. The value used here needs to be in the Pattern Control Schedule for those times when this pattern is to be used for the Room Air Temperature Distribution.
Field: Thermostat Height[LINK]
This field specifies the distance above the floor where the thermostat is situated. This height is used by the model to determine the thermostat temperature relative to the mean air temperature by applying the gradient.
Field: Return Air Height[LINK]
This field specifies the distance above the floor where the air leaves the zone and returns to the air system. and the mean air temperature. This height is used by the model to determine the return air temperature relative to the mean air temperature by applying the gradient.
Field: Exhaust Air Height[LINK]
This field specifies the distance above the floor where the air leaves the zone and enters and exhaust device such as an exhaust fan. This height is used by the model to determine the exhaust air temperature relative to the mean air temperature by applying the gradient.
Field: Temperature Gradient Lower Bound[LINK]
This field specifies the gradient, or slope, of temperature changes in the vertical direction in ºC/m.
Field: Temperature Gradient Upper Bound[LINK]
This field specifies the gradient, or slope, of temperature changes in the vertical direction in ºC/m.
Field: Gradient Interpolation Mode[LINK]
This field specifics how the program will vary between the two gradients. Select one of the following keywords to choose the simulation data used to scale: ‘Outdoor Environment Drybulb Temperature’, ‘Zone Drybulb Temperature’, ‘Delta Outdoor and Zone Temperature’, ‘Sensible Cooling Load’, and ‘Sensible Heating Load’. These are explained in detail below. All of these options have several things in common. They are essentially hard-coded. There is no support for a general method. The interpolation scheme is based on some variable that might reasonably be expected to correlate with gradient changes. This variable’s current value is used to continually adjust the value of the vertical gradient for room air temperature.
OutdoorDryBulbTemperature: This key directs the program to interpolate between upper and lower values of the vertical gradient based on the outdoor air temperature. If the outdoor temperature exceeds the upper limit set in the next field, then the gradient entered in the ‘Temperature Gradient Upper Bound’ field is used. Similarly if the outdoor air temperature is below the value set in the ‘Lower Temperature’ field, then the gradient entered in the ‘Temperature Gradient Lower Bound’ is used. For outdoor temperatures that lie between the upper and lower bounds, the gradient is determined by linear interpolation between the two.
ZoneDryBulbTemperature: This key directs the program to interpolate between upper and lower values of the vertical gradient based on the mean zone air temperature. If the mean zone air temperature exceeds the upper limit set in the next field, then the gradient entered in the ‘Temperature Gradient Upper Bound’ field is used. Similarly if the mean zone air temperature is below the value set in the ‘Lower Temperature’ field, then the gradient entered in the ‘Temperature Gradient Lower Bound’ is used. For mean zone air temperatures that lie between the upper and lower bounds, the gradient is determined by linear interpolation between the two.
ZoneAndOutdoorTemperatureDifference: This key directs the program to interpolate between upper and lower values of the vertical gradient based on the difference between the outdoor environment and the mean zone air temperature. If the temperature difference exceeds the upper limit set in the next field, then the gradient entered in the ‘Temperature Gradient Upper Bound’ field is used. Similarly if the temperature difference is below the value set in the ‘Lower Temperature’ field, then the gradient entered in the ‘Temperature Gradient Lower Bound’ is used. For temperature differences that lie between the upper and lower bounds, the gradient is determined by linear interpolation between the two.
SensibleCoolingLoad: This key directs the program to interpolate between upper and lower values of the vertical gradient based on the sensible cooling load. If the cooling load exceeds the upper limit set in the next field, then the gradient entered in the ‘Temperature Gradient Upper Bound’ field is used. Similarly if the cooling load is below the value set in the ‘Lower Temperature’ field, then the gradient entered in the ‘Temperature Gradient Lower Bound’ is used. For cooling loads that lie between the upper and lower bounds, the gradient is determined by linear interpolation between the two.
SensibleHeatingLoad: This key directs the program to interpolate between upper and lower values of the vertical gradient based on the sensible heating load. If the heating load exceeds the upper limit set in the next field, then the gradient entered in the ‘Temperature Gradient Upper Bound’ field is used. Similarly if the heating load is below the value set in the ‘Lower Temperature’ field, then the gradient entered in the ‘Temperature Gradient Lower Bound’ is used. For heating loads that lie between the upper and lower bounds, the gradient is determined by linear interpolation between the two.
Field: Upper Temperature Bound[LINK]
This field is used to enter the upper bound on temperature values in Celsius. It is required for the interpolation modes based on temperature.
Field: Lower Temperature Bound[LINK]
This field is used to enter the lower bound on temperature values in Celsius. It is required for the interpolation modes based on temperature.
Field: Upper Heat Rate Bound[LINK]
This field is used to enter the upper bound on heat rate values. It is required for the interpolation modes based on load. Both heating and cooling loads are entered as positive numbers (in watts).
Field: Lower Heat Rate Bound[LINK]
This field is used to enter the lower bound on heat rate values. It is required for the interpolation modes based on load. Both heating and cooling loads are entered as positive numbers (in watts).
An example of this object follows. This pattern will apply no gradient (effectively the mixing model) if zone air temperatures are 22.5 C or lower. It will apply a gradient of 1 K/m if zone temperatures are 26.0 C or higher. For zone air temperatures between 22.5 and 26.0 it will determine the gradient by linear interpolation and use a gradient between 0.0 and 1.0 K/m depending on where the zone air temperature is in the range.
Outputs[LINK]
The user-defined air temperature pattern that interpolates between two gradients produces the following output variable.
Room Air Zone Vertical Temperature Gradient [K/m][LINK]
This output variable is the result of the interpolation performed by the user-defined roomair model using RoomAir:TemperaturePattern:TwoGradient. This is the temperature gradient in the vertical direction. The units are degrees Kelvin per meter.
RoomAir:TemperaturePattern:NondimensionalHeight[LINK]
This object defines a distribution pattern for air temperatures relative to the current mean air temperature as a function of height. The height, referred to as Zeta, is non-dimensional by normalizing with the zone ceiling height. (The actual zone ceiling height can be explicitly entered in the ‘Zone’ object but if not it is calculated by EnergyPlus from the surfaces attached to the zone.) The temperature differences are not non-dimensional and remain in units of degrees Celsius.
An example of a vertical temperature pattern is shown in the figure below. The pattern itself is treated as a piecewise, linear model of air temperature as a function of height. This Zeta-DeltaTai curve, or lookup table, is then mapped to surfaces defined elsewhere in the file. The centroid of each surface and zone ceiling height are used to automatically assign Zeta values within the program. The zone named in the referencing RoomAir:TemperaturePattern:UserDefined object is used to determine which surfaces will be associated with the pattern when it is applied. A single pattern object can be reused for multiple zones and times.
In addition to the vertical temperature pattern there are three other parameters included in the pattern that are important. The first two might affect how the air system conditioning the room is operated. The first describes the temperature difference between the mean air temperature and the point where the sensor of a drybulb thermostat is situated. The second describes the temperature difference between the mean and the point where system air is being extracted from the zone. This is considered important because the changes in temperature difference between supply and return can affect how an air system is controlled to meet the loads. The third parameter can affect the zone air heat balance by altering the temperature of the air leaving the zone through exhaust fans.
Inputs[LINK]
Field: Name[LINK]
This field provides a unique name for this object.
Field: Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique among all other RoomAir Temperature Pattern objects. The value used here needs to be in the Pattern Control Schedule for those times when this pattern is to be used for the Room Air Temperature Distribution.
Field: Thermostat Offset[LINK]
This field specifies the temperature difference between where the thermostat is situated and the mean air temperature.
Field: Return Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and returning to the air system and the mean air temperature.
Field: Exhaust Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and being exhausted out of the building and the mean air temperature.
Field Set Zeta and Temperature Difference[LINK]
The remaining fields contain pairs of values that define a lookup table for the temperature pattern in the vertical direction. The first value is Zeta and the second value is DeltaTai.
Field: Pair <#> Zeta non-dimensional Height[LINK]
Zeta is the normalized height and should be a fractional value from 0.0 to 1.0. A value of 0.0 corresponds to the floor and a value of 1.0 corresponds to the ceiling. The Zeta values need to be in increasing value.
Field: Pair <#> Delta Adjacent Air Temperature[LINK]
DeltaT\(_{ai}\) is the temperature difference between the air temperature at the associated Zeta (T\(_{ai}\)) and the mean air temperature and is given in degrees Celsius.
This object is extensible, so additional pairs of these last two fields of this type can be added to the end of this object. An example of this object corresponding to the figure above is:
RoomAir:TemperaturePattern:SurfaceMapping[LINK]
This object defines a distribution pattern for the air temperatures adjacent to individual surfaces. This object uses the specific names of individual surfaces defined elsewhere in the model. This pattern allows controlling the adjacent air temperature on a surface-by-surface basis rather than by height. This allows modeling different adjacent air temperatures on the opposite sides of the zone.
In addition to the surface mappings there are three other parameters included in the pattern that are important. The first two might affect how the air system conditioning the room is operated. The first describes the temperature difference between the mean air temperature and the point where the sensor of a drybulb thermostat is situated. The second describes the temperature difference between the mean and the point where system air is being extracted from the zone. This is considered important because the changes in temperature difference between supply and return can affect how an air system is controlled to meet the loads. The third parameter can affect the zone air heat balance by altering the temperature of the air leaving the zone through exhaust fans.
Inputs[LINK]
Field: Name[LINK]
This field provides a unique name for this object.
Field: Control Integer for Pattern Control Schedule Name[LINK]
This field should contain an integer value that is unique among all other RoomAir Temperature Pattern objects. The value used here needs to be in the Pattern Control Schedule for those times when this pattern is to be used for the RoomAir Temperature Distribution.
Field: Thermostat Offset[LINK]
This field specifies the temperature difference between where the thermostat is situated and the mean air temperature.
Field: Return Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and returning to the air system and the mean air temperature.
Field: Exhaust Air Offset[LINK]
This field specifies the temperature difference between the air leaving the zone and being exhausted out of the building and the mean air temperature.
Field Set: Surface Name, Temperature Difference[LINK]
Fields (6 and on): Pairs of Surface Names and Temperature Differences[LINK]
The remaining fields contain pairs that define a lookup table for the temperature pattern on a surface-by-surface basis.
Field: Surface Name Pair <#>[LINK]
The name of a surface defined elsewhere in the input file.
Field: Delta Adjacent Air Temperature Pair <#>[LINK]
DeltaT\(_{ai}\) is the temperature difference between the air temperature adjacent to the associated surface (T\(_{ai}\)) and the mean air temperature and is given in degrees Celsius.
This object is extensible, so additional pairs of fields of these types can be added to the end of this object. An example of this object, which might be used to elevate temperatures near west windows in the afternoon, is:
RoomAir:Node[LINK]
The RoomAir:Node object is used to define air nodes for a nodal air model. The number of air node objects that need to be specified depends on the nodal air model selected. (However, currently only the Mundt model uses this object). In order to use the Mundt model, the user must specify six or more RoomAir:Node objects of different types for each zone. The exact number of RoomAir:Node in the model will vary based on the resolution of walls. If walls (heat transfer surfaces) are split into separate segments in the vertical direction, then more air nodes of type ‘MundtRoom’ will be useful. At a minimum, for the Mundt model RoomAir Nodes of the following type are required: ‘Inlet, ’Floor, ’Control, ’Ceiling, ’MundtRoom, and ’Return.’
Inputs[LINK]
Field: Name[LINK]
This alpha field is a name for the air node. It should be unique and is used as an identifier
Field: Node Type[LINK]
This alpha field indicates the type of this air node. The following explains options available for use with the Mundt nodal air model.
Inlet is specified for the air node located where the system air enters the zone.
Floor is specified for the air node located near the floor.
Control is specified for the air node located near the thermostat.
Ceiling is specified for the air node located near the ceiling.
MundtRoom is specified for the air node located adjacent to the wall(s).
Return is specified for the air node located where the system air leaves the zone.
Field: Zone Name[LINK]
This field indicates the name of the zone (Ref: Zone) that this air node belongs to. This should be the unique name of a zone object defined elsewhere in the input file.
Field: Height of Nodal Control Volume Center[LINK]
This numeric field indicates the height of the air node center. Air models such as the Mundt model compute the air temperature as a function of height and the value entered here will be used to determine a result for this node. The value should be specified in meters and relative to the floor of the zone.
Field: Surface <#> Name[LINK]
These remaining alpha fields indicate the names of the surfaces (Ref: Surface) that are interacting convectively with this air node. This field is optional and related to the previous field. Currently, at most 20 surfaces are allowed to interact with a single air node. Only those nodes that interact with the inside faces of surfaces need to specify surface names. Each surface should couple to no more than 1 node.
An IDF example:
RoomAirSettings:OneNodeDisplacementVentilation[LINK]
The RoomAirSettings:OneNodeDisplacementVentilation object is used to specify additional input parameters required by the Mundt model that are not available in other input objects in EnergyPlus. A single object will be used for the zone.
Inputs[LINK]
Field: Zone Name[LINK]
This alpha field indicates the name of the zone (Ref: Zone) for the required input parameters as specified in the following fields.
Field: Fraction of Convective Internal Loads Added to Floor Air[LINK]
This numeric field indicates what fraction of the convective part of the internal gains is added to the air near the floor in the zone specified.
Field: Fraction of Infiltration Internal Loads Added to Floor Air[LINK]
This numeric field indicates what fraction of the infiltration air enters near the floor in the zone specified.
An IDF example:
Outputs[LINK]
The following output is available for the Mundt model.
Room Air Node Air Temperature [C][LINK]
This output variable provides the drybulb air temperature used in, or calculated by, the Mundt model. The selection key is the name of an air node defined in a ROOMAIR Node object.
RoomAirSettings:ThreeNodeDisplacementVentilation[LINK]
This model is applicable to spaces that are served by a low velocity floor-level displacement ventilation air distribution system. Furthermore, the dominant sources of heat gain should be from people and other localized sources located in the occupied part of the room. The model should be used with caution in zones which have large heat gains or losses through exterior walls or windows or which have considerable direct solar gain. The model predicts three temperatures in the room:
A foot level temperature (T\(_{\rm{FLOOR}}\)). The floor region is 0.2 meters deep and T\(_{\rm{FLOOR}}\) represents the temperature at the mid-point of the region.
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the temperature in the region between the floor layer and the upper, mixed layer.
An upper node representing the mixed-layer/outflow temperature (T\(_{\rm{MX}}\)) essential for overall energy budget calculations and for modeling comfort effects of the upper layer temperature.
The following fields are used to define an instance of the ‘UCSD Displacement Ventilation Model Controls’ object.
Inputs[LINK]
Field: Zone Name[LINK]
This field provides the unique name of a zone described elsewhere in the file. A single instance of the ‘UCSD Displacement Ventilation Model Controls’ object is needed for each zone that is to be modeled using this method.
Field: Gain Distribution Schedule Name[LINK]
This field specifies the unique name of schedule defined elsewhere in the input file. The schedule values are the fractions of the convective portion of the internal gains in the occupied subzone that remain in the occupied subzone. The remainder of the convective portion of the internal gains in the occupied subzone enters the plumes and is carried to the upper subzone. The types of internal gains that are assumed to be located in the occupied subzone are:
people
task lights
electric equipment
gas equipment
hot water equipment
steam equipment
other equipment
baseboard heat
Types of internal gains that are assumed to be in the upper subzone are:
general lights
tubular daylighting devices
high temperature radiant heaters
The schedule values should be between 0 and 1. A value of 1 means that all the convection gains from equipment, task lights and people are dispersed in the lower occupied subzone. Conversely a value of 0 puts all the lower subzone convective gains into the plumes rising into the upper well-mixed subzone.
Field: Number of Plumes per Occupant[LINK]
This field specifies number of plumes per occupant. Plumes are associated with localized sources of convective heat gain from people and equipment. For example, a value of 2.0 would be used if each occupant has a computer that generates a separate plume that does not merge with the plume from the occupant in the lower, occupied, subzone.
Field: Thermostat Height[LINK]
This field is the height in meters of the thermostat/temperature control sensor above the floor.
Field: Comfort Height[LINK]
The height in meters above the floor at which air temperature is calculated for comfort purposes. The air temperature at this height is used in calculating the available measures of comfort: Fanger, Pierce, KSU, CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1 meters.
Field: Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference between the upper mixed subzone and the occupied subzone that will be used to trigger whether or not the displacement ventilation auxiliary outputs will be calculated. These outputs are Room Air Zone Transition Height, Room Air Zone Recommended Minimum Flow Fraction, Room Air Zone Average Temperature Gradient and Room Air Zone Maximum Temperature Gradient. They are set to negative values when the temperature difference is less than the threshold and the output Room Air Zone Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in units of degrees Centigrade. The default value is 0.4 degrees C.
An example input:
Outputs[LINK]
HVAC,Average,Room Air Zone Mixed Subzone Temperature [C]
HVAC,Average,Room Air Zone Occupied Subzone Temperature [C]
HVAC,Average,Room Air Zone Floor Subzone Temperature [C]
HVAC,Average,Room Air Zone Transition Height [m]
HVAC,Average,Room Air Zone Recommended Minimum Flow Fraction
HVAC,Average,Room Air Zone Is Mixed Status
HVAC,Average,Room Air Zone Average Temperature Gradient [K/m]
HVAC,Average,Room Air Zone Maximum Temperature Gradient [K/m]
HVAC,Average,Room Air Zone Thermal Comfort Effective Air Temperature [C]
HVAC,Average,Room Air Zone Thermostat Temperature [C]
Room Air Zone Mixed Subzone Temperature [C][LINK]
The temperature of the upper well-mixed subzone in degrees C.
Room Air Zone Occupied Subzone Temperature [C][LINK]
The average temperature of the lower, stratified, occupied subzone in degrees C.
Room Air Zone Floor Subzone Temperature [C][LINK]
The temperature of the region near the floor in degrees C.
Room Air Zone Transition Height [m][LINK]
The height above the floor, in meters, of the boundary between the lower occupied subzone and the upper well-mixed subzone.
Room Air Zone Recommended Minimum Flow Fraction [][LINK]
The ratio of the minimum recommended flow rate to the actual flow rate. Here flow rate means the sum of infiltration, ventilation, mixing and system air flow rates. The minimum flow is the flow needed to establish the boundary between the occupied and mixed subzones at 1.5 meters.
Room Air Zone Is Mixed Status [][LINK]
An integer flag that indicates whether the zone is mixed (single node well-mixed zone model used) or stratified (UCSD DV model used). The value 1 means well-mixed; 0 means stratified.
Room Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the floor region and the middle of the well-mixed upper subzone in degrees Kelvin per meter.
Room Air Zone Maximum Temperature Gradient [K/m][LINK]
The maximum of the temperature gradient between the middle of the floor region and the middle of the occupied subzone and the temperature gradient between the middle of the occupied subzone and the middle of the well-mixed subzone. The gradient is in degrees Kelvin per meter.
Room Air Zone Thermal Comfort Effective Air Temperature [C][LINK]
The temperature at the user specified comfort height in degrees C.
Room Air Zone Thermostat Temperature [C][LINK]
The temperature at the height of the thermostat (specified by user input) in degrees C.
RoomAirSettings:CrossVentilation[LINK]
The UCSD Cross Ventilation Room Air Model provides a simple model for heat transfer and temperature prediction in cross ventilated rooms. Cross Ventilation (CV) is common in many naturally ventilated buildings, with air flowing through windows, open doorways and large internal apertures across rooms and corridors in the building.
The CV model is used in EnergyPlus in the context of natural ventilation simulations using the AirflowNetwork airflow prediction model. Typical CV room flows are characterized by two clearly distinguishable flow regions that have different airflow velocities and temperature:
Jet regions in front of the inflow windows
Recirculation regions in the portions of the room that are not directly in front of the windows.
Each inflow aperture has one jet region while the recirculation regions are treated as a whole, with a single temperature and characteristic velocity. The default EnergyPlus perfectly mixed single temperature node room air approach is not suitable for these partially mixed flows. The proposed CV model uses multiple nodes with distinct air temperature and airflow velocity (one node for the recirculations plus one additional node for each inflow aperture).
The following fields are used to define an instance of the ‘UCSD Cross Ventilation Model Controls’ object.
Inputs[LINK]
Field: Zone Name[LINK]
This field provides the name of the zone to which this object applies. A single instance of the ‘UCSD Cross Ventilation Model Controls’ object is needed for each zone modeled using this method.
Field: Gain Distribution Schedule Name[LINK]
This field specifies the unique name of schedule defined elsewhere in the input file. The schedule values define the fractions of the convective portion of the internal gains in the jet and recirculation regions.
The schedule values should be between 0 and 1. A value of 1 means that all the convective gains are dispersed in the jet region. Conversely a value of 0 puts all the convective gains into the recirculation region.
Field: Airflow Region Used for Thermal Comfort Evaluation[LINK]
Required field whenever thermal comfort is predicted. Defines air temperature and mean airflow velocity that will be used in the Fanger model. Conditions must refer to one of the two regions defined in the model: jet or recirculation.
Possible choices: Jet or Recirculation.
Outputs[LINK]
Zone,Average,Room Air Zone Jet Region Temperature [C]
Zone,Average,Room Air Zone Recirculation Region Temperature [C]
Zone,Average,Room Air Zone Jet Region Average Air Velocity [m/s]
Zone,Average,Room Air Zone Recirculation Region Average Air Velocity [m/s]
Zone,Average,Room Air Window Jet Region Average Air Velocity [m/s]
Zone,Average,Room Air Zone Recirculation and Inflow Rate Ratio
Zone,Average,Room Air Zone Inflow Opening Area [m2]
Zone,Average,Room Air Zone Room Length [m]
Zone,Average,Room Air Zone Is Mixing Status
Zone,Average,Room Air Zone Is Recirculating Status
Room Air Zone Jet Region Temperature [C][LINK]
Average air temperature in the jet region of the flow in degrees C. If there is more than one inflow window this output will be the inflow-area-weighted average of the jet region temperature.
Room Air Zone Recirculation Region Temperature [C][LINK]
Average air temperature in the recirculation region of the flow in degrees C.
Room Air Zone Jet Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the jet region of the flow in meters per second. If there is more than one inflow window this output will be the inflow area weighted area of the jet inflow velocities.
Room Air Window Jet Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the jet region in front of the window, in meters per second.
Room Air Zone Recirculation Region Average Air Velocity [m/s][LINK]
Average airflow velocity in the recirculation region of the flow in meters per second.
Room Air Zone Recirculation and Inflow Rate Ratio [][LINK]
Ratio between airflow rate in the recirculation regions and the total inflow rate, non-dimensional.
Room Air Zone Inflow Opening Area [m2][LINK]
Area of the inflow aperture in square meters. This area can change due to variation in wind direction (as inflow aperture changes) or variations in the opening schedule.
Room Air Zone Room Length [m][LINK]
Length of the room along the cross ventilation direction, in meters.
Room Air Zone Is Mixing Status [][LINK]
An integer flag that indicates whether the zone is mixed (single node well-mixed zone model used) or significant momentum conservation is occurring (UCSD CV model used). The value 1 means well-mixed; 0 means cross ventilation is present. Transition to mixed flow can occur due to three mechanism: reduction in inflow velocity, reduction in inflow aperture area and dominance of buoyancy effects. A value of 1 is yes, a value of 0 is no.
Room Air Zone Is Recirculating Status [][LINK]
An integer flag that indicates whether recirculations are present in the flow. A cross ventilation flow does not have recirculations whenever the inflow area is similar to the room cross section area (such as airflow in a typical corridor). A value of 1 is yes, a value of 0 is no.
RoomAirSettings:UnderFloorAirDistributionInterior[LINK]
This model is applicable to interior spaces that are served by an underfloor air distribution system. The dominant sources of heat gain should be from people, equipment, and other localized sources located in the occupied part of the room. The model should be used with caution in zones which have large heat gains or losses through exterior walls or windows or which have considerable direct solar gain. The model predicts two temperatures in the room:
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the temperature in the region between the floor and the boundary of the upper subzone.
An upper subzone temperature (T\(_{\rm{MX}}\)) essential for overall energy budget calculations and for modeling comfort effects of the upper layer temperature.
The following fields are used to define an instance of the ‘UCSD UFAD Interior Model Controls’ object.
Inputs[LINK]
Field: Zone Name[LINK]
This field provides the unique name of a zone described elsewhere in the file. A single instance of the ‘RoomAirSettings:UnderFloorAirDistributionInterior’ object is needed for each zone that is to be modeled using this method.
Field: Number of Diffusers[LINK]
The total number of diffusers in this zone. This field can allowed to Autocalculate (in which case it is set to the design occupancy level; i.e., number of people). If the design occupancy is low or zero but there are still heat sources that could generate buoyancy driven plumes, the user should input a value based on the design supply air flow rate of the zone and the design flow rate of an individual diffuser. In the absence of any other information, divide the zone area by 100 ft\(^{2}\). The default for this field is Autocalculate.
Field: Power per Plume[LINK]
The power in watts incorporated in a buoyancy driven thermal plume. Normally we assume all the loads of a workstation create a single plume so that this represents the convective heat gain from a workstation – 1 person, 1 computer terminal, plus any task lighting. A typical value would be 220 watts. However, the model assumes an “equivalent” plume derived from the zone extraction rate normalized to the number of workstations/occupants. This field should be allowed to default – the program will calculate a value based upon the occupancy and the extraction rate. The default is Autocalculate.
Field: Design Effective Area of Diffuser[LINK]
This is the design air flow opening area in square meters of a single diffuser. The default value depends on the diffuser type. For swirl diffusers it is 0075 m\(^{2}\), for variable area diffusers 0.035 m\(^{2}\), for horizontal swirl diffusers 0.006 m\(^{2}\), and for linear bar grilles 0.03 m\(^{2}\). The default is Autocalculate..
Field: Diffuser Slot Angle from Vertical[LINK]
This input describes the angle at which air emerges from the diffusers. It should be the angle in degrees between the vertical and the diffuser slots. The defaults depend on the diffuser type: for swirl diffusers it is 28 degrees, for variable area diffusers 45 degrees, for DV diffusers 73 degrees, and for linear bar grilles 15 degrees.
Field: Thermostat Height[LINK]
This field is the height in meters of the thermostat/temperature control sensor above the floor. The default is 1.2 meters.
Field: Comfort Height[LINK]
The height in meters above the floor at which air temperature is calculated for comfort purposes. The air temperature at this height is used in calculating the available measures of comfort: Fanger, Pierce, KSU, CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1 meters.
Field: Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference between the upper subzone and the occupied subzone that will be used to trigger whether or not the UFAD auxiliary outputs will be calculated. These outputs are Room Air Zone Transition Height and Room Air Zone Average Temperature Gradient. They are set to zero when the temperature difference is less than the threshold and the output Room Air Zone Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in units of degrees Centigrade. The default value is 0.4 degrees C.
Field: Diffuser Type[LINK]
The choices for this alpha field are Swirl VariableArea HorizontalSwirl LinearBarGrille Custom. The swirl and displacement diffusers are fixed area diffusers. The variable area diffusers maintain an approximately constant exit velocity. Linear bar grilles are normally used in exterior zones and are fixed area diffusers. Custom is used to signify that the user intends to input the coefficients A – E (see below) rather than let the program set the coefficients based on diffuser type. The default is Swirl.
Field: Transition Height[LINK]
An optional field to allow the user to specify the transition height (meters above floor) rather than have the program calculate it. The default is 1.7 meters.
Field: Coefficient A[LINK]
The coefficient A in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient B[LINK]
The coefficient B in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient C[LINK]
The coefficient C in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient D[LINK]
The coefficient D in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient E[LINK]
The coefficient E in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
An example input is:
Outputs[LINK]
HVAC,Average,Room Air Zone Mixed Subzone Temperature [C]
HVAC,Average,Room Air Zone Occupied Subzone Temperature [C]
HVAC,Average,Room Air Zone Transition Height [m]
HVAC,Average,Room Air Zone Is Mixed Status []
HVAC,Average,Room Air Zone Average Temperature Gradient [K/m]
HVAC,Average,Room Air Zone Effective Comfort Air Temperature [C]
HVAC,Average,Room Air Zone Thermostat Temperature [C]
HVAC,Average,Room Air Zone Transition Height Gamma Value []
HVAC,Average,Room Air Zone Plume Heat Transfer Rate [W]
HVAC,Average,Room Air Zone Temperature Stratification Fraction []
Room Air Zone Mixed Subzone Temperature [C][LINK]
The temperature of the upper subzone in degrees C.
Room Air Zone Occupied Subzone Temperature [C][LINK]
The temperature of the lower, occupied subzone in degrees C.
Room Air Zone Transition Height [m][LINK]
The height above the floor, in meters, of the boundary between the lower occupied subzone and the upper subzone..
Room Air Zone Is Mixed Status [][LINK]
An integer flag that indicates whether the zone is mixed (single node well-mixed zone model used) or stratified (UCSD UFI model used). The value 1 means well-mixed; 0 means stratified.
Room Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the occupied subzone and the middle of the upper subzone in degrees Kelvin per meter.
Room Air Zone Effective Comfort Air Temperature [C][LINK]
The temperature at the user specified comfort height in degrees C.
Room Air Zone Thermostat Temperature [C][LINK]
The temperature at the height of the thermostat (specified by user input) in degrees C.
Room Air Zone Transition Height Gamma Value [][LINK]
Value of gamma – a dimensionless “height” used in calculating the transition height. Lower values of gamma indicate increased stratification, higher values less. Generally the values should be between 2 and 30.
Room Air Zone Plume Heat Transfer Rate [W][LINK]
The heat in watts driving the plumes in the occupied subzone.
Room Air Zone Temperature Stratification Fraction [][LINK]
This output, (Phi) is a measure of temperature stratification in the space. It is the difference between the occupied subzone temperature and the supply temperature divided by difference between the return temperature and the supply temperature. Technically it is equal to Kc. As phi approaches 1, the space is fully mixed. As phi approaches 0, the space becomes fully stratified. Expressed as an equation:
\[\frac{T_{occ} - T_{sup}}{T_{ret} - T_{sup}}\]
RoomAirSettings:UnderFloorAirDistributionExterior[LINK]
This model is applicable to exterior spaces that are served by an underfloor air distribution system. The dominant sources of heat gain should be from people, equipment, and other localized sources located in the occupied part of the room, as well as convective gain coming from a warm window. The model predicts two temperatures in the room:
An occupied subzone temperature (T\(_{\rm{OC}}\)), representing the temperature in the region between the floor and the boundary of the upper subzone..
An upper subzone temperature (T\(_{\rm{MX}}\)) essential for overall energy budget calculations and for modeling comfort effects of the upper layer temperature.
The following fields are used to define an instance of the ‘UCSD UFAD Exterior Model Controls’ object.
Inputs[LINK]
Field: Zone Name[LINK]
This field provides the unique name of a zone described elsewhere in the file. A single instance of the ‘RoomAirSettings:UnderFloorAirDistributionExterior’ object is needed for each zone that is to be modeled using this method.
Field: Number of Diffusers[LINK]
The total number of diffusers in this zone. This field can allowed to Autocalculate (in which case it is set to the design occupancy level; i.e., number of people). If the design occupancy is low or zero but there are still heat sources that could generate buoyancy driven plumes, the user should input a value based on the design supply air flow rate of the zone and the design flow rate of an individual diffuser. In the absence of any other information, divide the zone area by 100 ft\(^{2}\). The default for this field is Autocalculate.
Field: Power per Plume[LINK]
The power in watts incorporated in a buoyancy driven thermal plume. Normally we assume all the loads of a workstation create a single plume so that this represents the convective heat gain from a workstation – 1 person, 1 computer terminal, plus any task lighting. A typical value would be 220 watts. However, the model assumes an “equivalent” plume derived from the zone extraction rate normalized to the number of workstations/occupants. This field should be allowed to default – the program will calculate a value based upon the occupancy and the extraction rate. The default is Autocalculate.
Field: Design Effective Area of Diffuser[LINK]
This is the design air flow opening area in square meters of a single diffuser. The default value depends on the diffuser type. For swirl diffusers it is 0075 m\(^{2}\), for variable area diffusers 0.035 m\(^{2}\), for horizontal swirl diffusers 0.006 m\(^{2}\), and for linear bar grilles 0.03 m\(^{2}\). The default is Autocalculate..
Field: Diffuser Slot Angle from Vertical[LINK]
This input describes the angle at which air emerges from the diffusers. It should be the angle in degrees between the vertical and the diffuser slots. The defaults depend on the diffuser type: for swirl diffusers it is 28 degrees, for variable area diffusers 45 degrees, for DV diffusers 73 degrees, and for linear bar grilles 15 degrees.
Field: Thermostat Height[LINK]
This field is the height in meters of the thermostat/temperature control sensor above the floor. The default is 1.2 meters.
Field: Comfort Height[LINK]
The height in meters above the floor at which air temperature is calculated for comfort purposes. The air temperature at this height is used in calculating the available measures of comfort: Fanger, Pierce, KSU, CoolingEffectASH55 or AnkleDraftASH55. The default is 1.1 meters.
Field: Temperature Difference Threshold for Reporting[LINK]
This field specifies a minimum temperature difference between the upper subzone and the occupied subzone that will be used to trigger whether or not the UFAD auxiliary outputs will be calculated. These outputs are Room Air Zone Transition Height and Room Air Zone Average Temperature Gradient. They are set to zero when the temperature difference is less than the threshold and the output Room Air Zone Is Mixed Status is set to 1.
The value should be greater than or equal to zero and is in units of degrees Centigrade. The default value is 0.4 degrees C.
The value should be greater than or equal to zero and is in units of degrees Centigrade. The default value is 0.4 degrees C.
Field: Diffuser Type[LINK]
The choices for this alpha field are Swirl VariableArea HorizontalSwirl LinearBarGrille Custom. The swirl and displacement diffusers are fixed area diffusers. The variable area diffusers maintain an approximately constant exit velocity. Linear bar grilles are normally used in exterior zones and are fixed area diffusers. Custom is used to signify that the user intends to input the coefficients A – E (see below) rather than let the program set the coefficients based on diffuser type. The default is Swirl.
Field: Transition Height[LINK]
An optional field to allow the user to specify the transition height (meters above floor) rather than have the program calculate it. The default is 1.7 meters.
Field: Coefficient A[LINK]
The coefficient A in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient B[LINK]
The coefficient B in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient C[LINK]
The coefficient C in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient D[LINK]
The coefficient D in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
Field: Coefficient E[LINK]
The coefficient E in the formula: Kc = A*Gamma**B + C + D*Gamma + E*Gamma**2. Gamma is a variable that characterizes the amount of stratification in a UFAD zone. Kc is the fraction of the total internal convective heat gain that is assigned to the lower (occupied) subzone. The coefficients in the formula are defaulted based upon diffuser type. A user would normally allow this field to default. The default is autocalculate.
An example input is:
Outputs[LINK]
HVAC,Average,Room Air Zone Mixed Subzone Temperature [C]
HVAC,Average,Room Air Zone Occupied Subzone Temperature [C]
HVAC,Average,Room Air Zone Transition Height [m]
HVAC,Average,Room Air Zone Is Mixed Status []
HVAC,Average,Room Air Zone Average Temperature Gradient [K/m]
HVAC,Average,Room Air Zone Effective Comfort Air Temperature [C]
HVAC,Average,Room Air Zone Thermostat Temperature [C]
HVAC,Average,Room Air Zone Transition Height Gamma Value []
HVAC,Average,Room Air Zone Plume Heat Transfer Rate [W]
HVAC,Average,Room Air Zone Window Plume Heat Transfer Rate [W]
HVAC,Average,Room Air Zone Temperature Stratification Fraction []
Room Air Zone Mixed Subzone Temperature [C][LINK]
The temperature of the upper subzone in degrees C.
Room Air Zone Occupied Subzone Temperature [C][LINK]
The temperature of the lower, occupied subzone in degrees C.
Room Air Zone Transition Height [m][LINK]
The height above the floor, in meters, of the boundary between the lower occupied subzone and the upper subzone..
Room Air Zone Is Mixed Status [][LINK]
An integer flag that indicates whether the zone is mixed (single node well-mixed zone model used) or stratified (UCSD UFE model used). The value 1 means well-mixed; 0 means stratified.
Room Air Zone Average Temperature Gradient [K/m][LINK]
The temperature gradient between the middle of the occupied subzone and the middle of the upper subzone in degrees Kelvin per meter.
Room Air Zone Effective Comfort Air Temperature [C][LINK]
The temperature at the user specified comfort height in degrees C.
Room Air Zone Thermostat Temperature [C][LINK]
The temperature at the height of the thermostat (specified by user input) in degrees C.
Room Air Zone Transition Height Gamma Value [][LINK]
Value of gamma – a dimensionless “height” used in calculating the transition height. Lower values of gamma indicate increased stratification, higher values less. Generally the values should be between 2 and 30.
Room Air Zone Plume Heat Transfer Rate [W][LINK]
The heat in watts driving the plumes in the occupied subzone.
Room Air Zone Window Plume Heat Transfer Rate [W][LINK]
The convective heat gain from windows in an UnderFloorAirDistributionExterior zone.
Room Air Zone Temperature Stratification Fraction [][LINK]
This output, (Phi) is a measure of temperature stratification in the space. It is the difference between the occupied subzone temperature and the supply temperature divided by difference between the return temperature and the supply temperature. Technically it is equal to Kc. As phi approaches 1, the space is fully mixed. As phi approaches 0, the space becomes fully stratified. Expressed as an equation:
\[\frac{T_{occ} - T_{sup}}{T_{ret} - T_{sup}}\]
RoomAirflowNetwork Model[LINK]
This model simulates a thermal zone using a network approach by assuming intra-zone nodes connected by user-defined patterns of airflows. The new model also allows users to specify a node to be connected to surfaces to have convective heat transfer between surfaces and the node, portion of internal gains and supply air and return air fractions from zone equipment. The model requires following objects to work together:
RoomAirSettings:AirflowNetwork
RoomAir:Node:AirflowNetwork
RoomAir:Node:AirflowNetwork:AdjacentSurfaceList
RoomAir:Node:AirflowNetwork:InternalGains
RoomAir:Node:AirflowNetwork:HVACEquipment
AirflowNetwork:Intrazone:Node
AirflowNetwork:Intrazone:Linkage
The first five objects are described below. The last two objects are described in the Airflow Network Model section. This model also requires additional AirflowNetwork:* objects to form a complete network.
RoomAirSettings:AirflowNetwork[LINK]
This object provides inputs in a thermal zone needed for the RoomAirflowNetwork model. The inputs specify a thermal zone and a list of RoomAir nodes. The object gives a summary of the model configuration in a zone.
Inputs[LINK]
Field: Name[LINK]
This is a unique character string associated with this instance of the RoomAirSettings:AirflowNetwork object.
Field: Zone Name[LINK]
The name of the EnergyPlus thermal zone corresponding to the RoomAir model zone.
Field: Control Point RoomAir:Node Name[LINK]
This is the name of a RoomAir:Node:AirflowNetwork object that contains the sensor for zone HVAC controls. The conditions at this node will be used for thermostatic, humidistatic, or comfort based control decisions. The zone node defined in a Zone object is required.
Field: RoomAir:Node:AirflowNetwork x Name[LINK]
The name of a RoomAir:Node:AirflowNetwork object defined elsewhere. This node will receive the fraction of internal gains, and HVAC equipment, and a list of surface names exposed to this node with convective heat transfer.
An IDF example input is:
RoomAir:Node:AirflowNetwork[LINK]
This object is used to define a node in a thermal zone. The input specifies the fraction of zone volume and provides a list of names to define fraction of internal gains, surface connection and HVAC equipment.
Inputs[LINK]
Field: Name[LINK]
This is a unique character string associated with this instance of the RoomAirSettings:AirflowNetwork object.
Field: Zone Name[LINK]
The name of the EnergyPlus thermal zone and is defined in an RoomAirSettings:AirflowNetwork object.
Field: Fraction of Zone Air Volume[LINK]
The field specifies a fraction of the overall zone air volume that is assigned to this RoomAir:Node:AirflowNetwork object. The fraction will be used to calculate zone air storage term. See corresponding sections in Engineering Reference for its use in the node energy and moisture balance equations.
Field: RoomAir:Node:AirflowNetwork:AdjacentSurfaceList Name[LINK]
The field specifies a name to provide a list of connected adjacent surfaces with convective heat transfer between surfaces and this particular node. When a moisture mode is assigned to surfaces, convective moisture transfer will be calculated. See corresponding sections in Engineering Reference for its use in the node energy and moisture balance equations.
Field: RoomAir:Node:AirflowNetwork:InternalGains Name[LINK]
The field specifies a name to provide a list of internal gain objects and associated fractions assigned to this particular node. See corresponding sections in Engineering Reference for its use in the node energy and moisture balance equations.
Field: RoomAir:Node:AirflowNetwork:HVACEquipment Name[LINK]
The field specifies a name to provide a list of HVAC equipment, including AirLoop terminals and zone equipment. See corresponding sections in Engineering Reference for its use in the node energy and moisture balance equations.
RoomAir:Node:AirflowNetwork:AdjacentSurfaceList[LINK]
This object is used to provide a list of connected adjacent surfaces with convective heat transfer between surfaces and this particular node. When a moisture mode is assigned to surfaces, convective moisture transfer will be calculated. It should be pointed out that a fraction of a surface exposed to this particular node is not allowed.
Field: Name[LINK]
This is a unique character string associated with this instance of the RoomAir:Node:AirflowNetwork:AdjacentSurfaceList object.
Field: Surface <#> Name[LINK]
The field specifies a surface name. This object is extensible, so additional fields of this type can be added to the end of this object.
RoomAir:Node:AirflowNetwork:InternalGains[LINK]
This object is used to define a list of internal gains in the same zone and associated fraction assigned to this particular node.
Inputs[LINK]
Field: Name[LINK]
This is a unique character string associated with this instance of the RoomAir:Node:AirflowNetwork:InternalGains object.
Field: Internal Gain Object <#> Type[LINK]
The field specifies an internal gain object type based on the list in EnergyPlus.
Field: Internal Gain Object <#> Name[LINK]
The field specifies an internal gain object name based on the list in EnergyPlus.
Field: Fraction of Gains to Node <#>[LINK]
The field specifies a fraction of the particular internal gain object assigned to this node.
This object is extensible, so additional groups of these last three fields can be added to the end of this object.
RoomAir:Node:AirflowNetwork:HVACEquipment[LINK]
This object is used to define a list of HVAC equipment objects in the same zone and associated fractions assigned to this particular node.
Inputs[LINK]
Field: Name[LINK]
This is a unique character string associated with this instance of the RoomAir:Node:AirflowNetwork:HVACEquipment object.
Field: ZoneHVAC or Air Terminal Equipment Object Type <#>[LINK]
The field specifies an object type of ZoneHVAC equipment or terminal type based on the list in the Energy+.idd.
Field: ZoneHVAC or Air Terminal Equipment Object Name <#>[LINK]
The field specifies the object name based on the object type defined in the previous field.
Field: Fraction of Output or Supply Air from HVAC Equipment <#>[LINK]
The field specifies a fraction of supply air from the particular equipment to this node.
Field: Fraction of Input or Return Air from HVAC Equipment <#>[LINK]
The field specifies a fraction of return air from the particular equipment to this node.
This object is extensible, so additional groups fields of these last four fields can be added to the end of this object.
Outputs[LINK]
Each room air model sets up outputs specific to that model. The effect of room air modeling is usually to adjust the adjacent air temperature along the inside surface of heat transfer surfaces. The output report “Surface Int Adjacent Air Temperature [C]” is provided for this and described under Surface Outputs.
Zone Predicted Sensible Load Room Air Correction Factor[LINK]
This output variable provides the value of the correction factor applied to the predicted zone loads. Predicted zone load to setpoint is (usually) used to control HVAC air systems and the presence of a room air model has an impact on the loads. The predicted loads are multiplied by the factor in this output variable. The value is always 1.0 when there is no Room Air model. When there is a Room Air model, this output shows how that model is increasing or decreasing overall zone loads experienced by the air system.
Outputs[LINK]
HVAC,Average,RoomAirflowNetwork Node Temperature [C]
HVAC,Average,RoomAirflowNetwork Node Humidity Ratio [kgWater/kgDryAir]
HVAC,Average,RoomAirflowNetwork Node Relative Humidity [%]
HVAC,Average,RoomAirflowNetwork Node SumIntSensibleGain [W]
HVAC,Average,RoomAirflowNetwork Node SumIntLatentGain [W]
HVAC,Average,RoomAirflowNetwork Node NonAirSystemResponse [W]
HVAC,Average,RoomAirflowNetwork Node SysDepZoneLoadsLagged [W]
HVAC,Average,RoomAirflowNetwork Node HVAC Supply Fraction []
HVAC,Average,RoomAirflowNetwork Node HVAC Return Fraction []
RoomAirflowNetwork Node Temperature [C][LINK]
The temperature at a Room Air Node in a zone in degrees C.
HVAC,Average,RoomAirflowNetwork Node Humidity Ratio [kgWater/kgDryAir][LINK]
The humidity ratio at a Room Air Node in a zone in kgWater/kgDryAir.
RoomAirflowNetwork Node Relative Humidity [%][LINK]
The relative humidity ratio at a Room Air Node in a zone in percent.
HVAC,Average,RoomAirflowNetwork Node SumIntSensibleGain [W][LINK]
A sum of internal sensible gains assigned to a Room Air node in a zone.
HVAC,Average,RoomAirflowNetwork Node SumIntLatentGain [W][LINK]
A sum of internal latent gains assigned to a Room Air node in a zone.
HVAC,Average,RoomAirflowNetwork Node NonAirSystemResponse [W][LINK]
A sum of system convective gains, collected via NonAirSystemResponse, and assigned to a Room Air node in a zone.
HVAC,Average,RoomAirflowNetwork Node SysDepZoneLoadsLagged [W][LINK]
A sum of SysDepZoneLoads saved to be added to zone heat balance at the next HVAC time step. A typical system is a zone dehumidifier.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.