Zone Controls[LINK]
Thermostatic Zone
Control[LINK]
The input object ZoneControl:Thermostat
provides a way for the zone to be controlled to a specified
temperature. ZoneControl:Thermostat
references a control type schedule and one or more control
type objects which in turn reference one or more setpoint
schedules.
The control type schedule and the list of control type/name
pairs are directly related. The schedule defines the type of
control that is to be used during for each hour. Valid control
types are
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating/Cooling Setpoint
4 - Dual Setpoint (Heating and Cooling) with deadband
If the schedule referenced in the ZoneControl statement has
a value of 4 for a particular hour, this indicates that during
that hour “dual setpoint with deadband control” is to be used.
The specific “dual setpoint with deadband” control object to
be used is specified in the list of control type/name pairs.
Then the specific control type objects reference the
thermostat setpoint temperature schedule to be used. Because
only one control can be specified for each control type in a
ZoneControl statement, there are only four pairs possible in a
particular ZoneControl type/name list. This is because
individual controls can be defined hourly, thus giving the
user a full range of flexibility. Since putting in the name of
the control type directly in the schedule would be very
cumbersome, the control types are assigned a number which is
used in the hourly schedule profile.
For more information see ZoneControl:Thermostat
in the Input Output Reference and succeeding sections in this
document.
Zone Thermostats[LINK]
The schema for the current set of four zone thermostats is
given below. In each case, the keyword is accompanied by an
identifying name and either one or two schedule names
(depending on whether the control is a single or dual setpoint
control). The schedule defines a temperature setpoint for the
control type. The schedule would be defined through the
standard schedule syntax described earlier in this document.
For an uncontrolled zone no thermostat is specified or
necessary. See the Input Output Reference for more
details.
The control type schedule and the list of control type/name
pairs are directly related. The schedule defines the type of
control that is to be used during for each hour. Valid Control
Types are
| Control Type Value |
Control Type Name |
| 0 |
Uncontrolled (No specification
or default) |
| 1 |
Single Heating Setpoint (input
object ThermostatSetpoint:SingleHeating) |
| 2 |
Single Cooling SetPoint (input
object ThermostatSetpoint:SingleCooling) |
| 3 |
Single Heating/Cooling
Setpoint(input object
ThermostatSetpoint:SingleHeatingOrCooling) |
| 4 |
Dual Setpoint (Heating and
Cooling) with deadband(input object
ThermostatSetpoint:DualSetpoint) |
For the Uncontrolled case no heating or cooling requirement
is calculated for the system to meet.
CASE (0)
! Uncontrolled Zone
LoadToHeatingSetPoint = 0.0
LoadToCoolingSetPoint = 0.0
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0
For the Single Heating Setpoint there would be a heating
only thermostat. The setpoint can be scheduled and varied
throughout the simulation but only heating is allowed with
this control type.
CASE (SingleHeatingSetPoint)
! Determine zone load based on
! Qload + Qsys = 0 and Qsys = mCp(Tsys-Tzone)
! System Load Sign Convention:
! - -> Cooling required to reach setpoint
! + -> Heating required to reach setpoint
LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) *
TempZoneThermostatSetPoint(ZoneNum) –
TempIndZnLd(ZoneNum))
IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired - 1.0) < 0.0) THEN
DeadBandOrSetback(ZoneNum) = .TRUE.
ENDIF
For the Single Cooling Setpoint there would be a cooling
only thermostat. The setpoint can be scheduled and varied
throughout the simulation but only cooling is allowed with
this control type.
CASE (SingleCoolingSetPoint)
LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) *
TempZoneThermostatSetPoint(ZoneNum) –
TempIndZnLd(ZoneNum))
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
IF ((ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired + 1.0) > 0.0) THEN
DeadBandOrSetback(ZoneNum) = .TRUE.
ENDIF
For the Single Heat Cool Setpoint there would be a cooling
only thermostat there would be a heating and cooling
thermostat. The setpoint can be scheduled and varied
throughout the simulation for both heating and cooling. With
this control type only 1 setpoint profile is needed or
used.
CASE (SingleHeatCoolSetPoint)
LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) *
TempZoneThermostatSetPoint(ZoneNum) –
TempIndZnLd(ZoneNum))
LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) *
TempZoneThermostatSetPoint(ZoneNum) –
TempIndZnLd(ZoneNum))
! Possible combinations:
! 1/ LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint > 0 --> Heating required
! 2/ LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint < 0 --> Not Feasible
! 3/ LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint < 0 --> Cooling Required
! 4/ LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint > 0 --> Dead Band Operation
IF (LoadToHeatingSetPoint > 0.0 .AND. LoadToCoolingSetPoint > 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
ZoneSetPoint = ZoneThermostatSetPointLo(ZoneNum)
ELSEIF (LoadToHeatingSetPoint < 0.0 .AND. LoadToCoolingSetPoint < 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
ZoneSetPoint = ZoneThermostatSetPointHi(ZoneNum)
ELSEIF (LoadToHeatingSetPoint < 0.0 .AND. LoadToCoolingSetPoint > 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0
IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
ZoneSetPoint = Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp
ENDIF
DeadBandOrSetback(ZoneNum) = .TRUE.
ENDIF
For Dual Setpoint with DeadBand there would be a heating
and cooling thermostat. For this case both a heating and
cooling setpoint can be scheduled for any given time period.
The setpoint can be scheduled and varied throughout the
simulation for both heating and cooling.
CASE (DualSetPointWithDeadBand)
LoadToHeatingSetPoint = (TempDepZnLd(ZoneNum) *
ZoneThermostatSetPointLo(ZoneNum) –
TempIndZnLd(ZoneNum))
LoadToCoolingSetPoint = (TempDepZnLd(ZoneNum) *
ZoneThermostatSetPointHi(ZoneNum) –
TempIndZnLd(ZoneNum))
! Possible combinations:
! 1/ LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint > 0 --> Heating required
! 2/ LoadToHeatingSetPoint > 0 & LoadToCoolingSetPoint < 0 --> Not Feasible
! 3/ LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint < 0 --> Cooling Required
! 4/ LoadToHeatingSetPoint < 0 & LoadToCoolingSetPoint > 0 --> Dead Band Operation
IF (LoadToHeatingSetPoint > 0.0 .AND. LoadToCoolingSetPoint > 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToHeatingSetPoint
ZoneSetPoint = ZoneThermostatSetPointLo(ZoneNum)
ELSEIF (LoadToHeatingSetPoint < 0.0 .AND. LoadToCoolingSetPoint < 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = LoadToCoolingSetPoint
ZoneSetPoint = ZoneThermostatSetPointHi(ZoneNum)
ELSEIF (LoadToHeatingSetPoint < 0.0 .AND. LoadToCoolingSetPoint > 0.0) THEN
ZoneSysEnergyDemand(ZoneNum)%TotalOutputRequired = 0.0
IF(Zone(ZoneNum)%SystemZoneNodeNumber > 0) THEN
ZoneSetPoint = Node(Zone(ZoneNum)%SystemZoneNodeNumber)%Temp
ENDIF
DeadBandOrSetback(ZoneNum) = .TRUE.
ENDIF
Operative Temperature
Control[LINK]
The input object ZoneControl:Thermostat:OperativeTemperature
provides a model where the behavior of the zone thermostats
described above can be modified to accommodate operative
temperature control. The ZoneControl:Thermostat:OperativeTemperature
input object is used to modify the behavior of any of the
thermostatic control types described above. When this object
is used, the zone can be controlled by a weighted mixture of
radiant and air temperatures (rather than just zone air
temperatures).
In EnergyPlus, operative temperature,
, is defined as ,
where,
is the radiative
fraction,
is the mean radiant
temperature for the thermal zone, and
is the mean zone air
temperature.
The radiative fraction
is
selected by the user and can be scheduled to vary during the
simulation. A typical value is 0.5. The maximum value needs to
be less than 0.9 and the minimum is 0.0. A value of 0.0 is the
same as controlling on only zone air temperature. If air
velocities are higher than 0.2 m/s, then lower values for
radiative fraction might apply. Niu and Burnett (1998) cite
International Standard ISO 77300 in recommending the values
for this fraction listed in the following table.
Operative Temperature - Radiative Fraction vs Air
Velocity
| Air Velocity (m/s) |
< 0.2 |
0.2 to 0.6 |
0.6 to 1.0 |
 |
0.5 |
0.4 |
0.3 |
The control is accomplished using the load to setpoint
formulation that is fundamental to HVAC system control in
EnergyPlus. Although real systems will not know the loads and
operate on temperature-based control, EnergyPlus needs to be
able to function at zone timesteps up to one hour and this is
too long of a timeframe for true temperature-based zone
control. Load-based control is an important method of
determining the average HVAC system response to zone
conditions over the time step. For operative temperature
control, the same methods and routines are used for
calculating loads to setpoints but the setpoints are shifted
to emulate operative temperature control rather than air
temperature control.
The user-defined setpoint for
is an input in degrees Celsius.
is continually modeled by
the full zone heat balance method and includes all the
interactions between thermal loads and HVAC systems. A new
setpoint for the zone’s
is
obtained for each zone timestep by rearranging the definition
of
to put
on the left hand side.
This adjustment to the target zone air drybulb temperature
is made every timestep for every zone immediately after the
setpoints are obtained from the schedule.
Reference: J. Niu and J. Burnett. 1998. Integrating
Radiant/Operative Temperature Controls into Building
Energy Simulations. ASHRAE Transactions Vol. 104. Part 2. page
210. ASHRAE. Atlanta, GA.
Temperature And
Humidity Control[LINK]
The
rate at which the cooling setpoint temperature is reduced is
dictated by the user-specified Overcool Control Ratio. The
maximum reduction in cooling setpoint temperature is defined
by the user-entered Overcool Range, although the Overcool
Range may be reduced from the user-defined value when this
TemperatureAndHumidity control is used in tandem with a dual
setpoint thermostat (see discussion below). Note that
occupants are sensitive to overcooling and can experience
discomfort if the overcool range is too large.[LINK]
This control is accomplished using the load to setpoint
formulation that is fundamental to HVAC system control in
EnergyPlus. Although real systems will not know the loads and
operate on temperature-based control, EnergyPlus needs to be
able to function at zone timesteps up to one hour and this is
too long of a timeframe for true temperature-based zone
control. Load-based control is an important method of
determining the average HVAC system response to zone
conditions over the time step. For TemperatureAndHumidity
control, the same methods and routines are used for
calculating loads to setpoints but the cooling setpoint is
shifted to emulate TemperatureAndHumidity control, as
described above.
The overcool range limits the extent of the zone air
temperature reduction below the cooling setpoint. When a dual
setpoint thermostat is being modified by this
TemperatureAndHumidity control, the maximum overcool range
must be less than or equal to the temperature difference
between the dual setpoint thermostat’s cooling and heating
setpoints:
where,
= maximum overcool range
for the zone air (°C)
= overcool range for the
zone air (°C). User input.
= temperature difference
between the cooling and heating setpoints (°C)
If a single cooling setpoint thermostat is being modified
by this control, the maximum overcool range is equal to the
user-defined overcool range.
The extent that the zone air relative humidity exceeds the
user-entered dehumidifying relative humidity setpoint is given
by:
The actual cooling setpoint reduction (overcooling) is
calculated for the condition when the zone air relative
humidity exceeds the dehumidifying setpoint (i.e.,
>0), as described below:
The cooling setpoint temperature is then adjusted as
follows:
where,
= adjusted cooling
setpoint temperature (°C)
= zone air cooling
setpoint temperature for the current time step (°C). User
input.
= user-defined overcool
control ratio (%/K)
= difference between the
zone air relative humidity and the user-defined dehumidifying
setpoint (%)
= zone air relative
humidity calculated at the last system time step (%)
= dehumidifying relative
humidity setpoint at the current time step (%). User
input.
This adjusted cooling setpoint temperature is made every
timestep for every zone immediately after the original
thermostat setpoint is obtained from the user-defined setpoint
schedule.
The input object ZoneControl:Humidistat
provides a way for the zone to be controlled to a single
relative humidity setpoint schedule, or dual humidity
schedules (humidifying and dehumidifying with deadband). The
schedules consist of relative humidities, expressed as a
percentage (0-100), to be used for the zone moisture
prediction calculation. Only one control statement can be
specified for each zone. Individual relative humidity values
can be defined for every time step, thus giving the user a
full range of flexibility. For a single setpoint humidistat,
if the control relative humidity is below the calculated load
and the equipment specified can humidify then that equipment
will try and meet the requirement. The opposite is true if the
calculated value is above the setpoint and the equipment can
dehumidify. For a dual setpoint humidistat, if the zone
relative humidity is below the humidifying
relative humidity setpoint and the equipment specified can
humidify then that equipment will try and meet the zone’s
humidification load. The opposite is true if the zone relative
humidity is above the dehumidifying relative
humidity setpoint and the equipment can dehumidify.
If the ZoneControl:Humidistat
is used by a furnace or unitary system then no other objects
are required. The signal from the humidistat is used directly
by that component. If the Zone
Control:Humidistat is used to control a Humidifier or used in
conjunction with the Controller:Simple object with control
variable “TemperatureAndHumidityRatio”, then either the
“SetpointManager:SingleZone:Humidity:Minimum”,
“SetpointManager:MultiZone:Humidity:Minimum”,
“SetpointManager:SingleZone:Humidity:Maximum” or
“SetpointManager:MultiZone:Humidity:Maximum” objects are
required to determine a setpoint for those components to meet
for the single setpoint humidistat. For a dual setpoint
humidistat, a minimum humidity setpoint manager object
(“SetpointManager:SingleZone:Humidity:Minimum” or
“SetpointManager:MultiZone:Humidity:Minimum”) and a maximum
humidity setpoint manager object
(“SetpointManager:SingleZone:Humidity:Maximum” or
“SetpointManager:MultiZone:Humidity:Maximum”) are required to
determine the setpoints for the corresponding humidification
and dehumidification components. Note that the
“SetpointManager:Scheduled” object can also be used to
directly set humidity ratio setpoints on the exit node of the
humidifier component.
For the single setpoint humidistat case, the model takes
into account all of the moisture gains and/or losses from
sources except the HVAC system contribution, and then
calculates a moisture removal or addition rate based on the
provided setpoint value, like the temperature predictor. The
algorithm uses a 3rd Order derivative to predict zone moisture
addition or removal to smooth the changes using the zone air
capacitance. Positive values of moisture load mean that this
amount of moisture must be added to the zone to reach the
setpoint. Negative values represent the amount of moisture
that must be removed by the system.
This routine also calculates the zone required humidity
ratio, Wsetpoint, which is required and takes into account the
zone multiplier. At this time the Wsp is not stored in a
derived type to make it available for SetpointManagers. It was
setup to be analogous to the temperature thermostat.
For the dual setpoint humidistat case, the model takes into
account all of the moisture gains and/or losses from sources
except the HVAC system contribution, and then calculates
moisture addition and removal rates based on the provided
humidifying and dehumidifying setpoint values, like the
temperature predictor. The algorithm uses a Third Order
Backward Difference , Analytical Solution, or Euler Method in
subroutine CalcPredictedHumidityRatio to predict zone moisture
addition and removal to smooth the changes using the zone air
capacitance. The program calculates the humidifying (addition)
and dehumidifying (removal) moisture loads based on the
specified humidifying and dehumidifying setpoints,
respectively. The calculated humidifying moisture load is
passed to subroutine CalcSingZoneMinHumSetPoint and
CalcMultiZoneMinHumSetPoint in the SetpointManager module to
calculate the requested supply air humidity ratio at the
setpoint node (Ref. SetpointManager:SingleZone:Humidity:Minimum
and SetpointManager:MultiZone:Humidity:Minimum
objects). The calculated dehumidifying moisture load is passed
to subroutine CalcSingZoneMaxHumSetPoint and
CalcMultiZoneMaxHumSetPoint in the SetpointManager module to
calculate the requested supply air humidity ratio at the
setpoint node (Ref. SetpointManager:SingleZone:Humidity:Maximum
and SetpointManager:MultiZone:Humidity:Maximum
objects). At the same time, the dehumidifying load is also
passed directly to a furnace or unitary system if it is
defined for the simulation, and that system will operate to
meet this load based on its configuration and control
settings.
Thermal Comfort Zone
Control[LINK]
The input object ZoneControl:Thermostat:ThermalComfort
provides a way for the zone to be controlled to a specified
temperature based on a selected thermal comfort model. ZoneControl:Thermostat:ThermalComfort
references a thermal comfort control type schedule and one or
more thermal comfort control type objects which in turn
reference one or more setpoint schedules.
The thermal comfort control type schedule and the list of
thermal comfort control type/name pairs are directly related.
The schedule defines the type of thermal comfort control that
is to be used during for each simulation time step. Valid
Control Types are
| Control Type |
Control Type Name/Object |
| 0 |
No thermal comfort control |
| 1 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating |
| 2 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling |
| 3 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling |
| 4 |
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint |
If the schedule referenced in the ZoneControl statement has
a value of 4 for a particular time step, this indicates that
during that time step
“ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint”
control is to be used. The specific
“ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint”
control object to be used is specified in the list of thermal
comfort control type/name pairs. Then the specific thermal
comfort control type objects reference the thermal comfort PMV
setpoint schedule to be used. Because only one thermal comfort
control can be specified for each thermal comfort control type
in a ZoneControl statement, there are only four pairs possible
in a particular ZoneControl type/name list. This is because
individual thermal comfort controls can be defined for
specific times, thus giving the user a full range of
flexibility. Since putting in the name of the thermal comfort
control type directly in the schedule would be very
cumbersome, the thermal comfort control types are assigned a
number which is used in the schedule profile.
For more information see ZoneControl:Thermostat:ThermalComfort
in the InputOutput Reference and Zone
Fanger Thermal Comfort in the Engineering Documentation.
Zone
Control Based on Fanger Thermal Comfort[LINK]
The syntax for the current set (4) of zone thermal comfort
control types is given below. In each case, the keyword is
accompanied by an identifying name and either one or two
schedule names (depending on whether the control type is a
single or dual setpoint control). The schedule defines a PMV
setpoint for the control type. The schedule would be defined
through the standard schedule syntax described earlier in this
document. For an uncontrolled thermal comfort zone, no Fanger
thermal comfort object is specified or necessary. See the
Input Output Reference for more details.
The control type schedule and the list of control type/name
pairs are directly related. The schedule defines the type of
control that is to be used during for each hour. Valid Control
Types are
| Control Type |
Control Type Name/Object |
| 0 |
No thermal comfort control |
| 1 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating |
| 2 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling |
| 3 |
ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling |
| 4 |
ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint |
For the no thermal comfort control (uncontrolled) case, the
control will revert to thermostat control if specified. If the
thermal comfort control is specified as “uncontrolled” for a
particular period and thermostat control is not specified in
the input, then conditions will float.
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating
case there would be a heating only thermal comfort setpoint
temperature. The setpoint is calculated based on the selected
thermal comfort model and varied throughout the simulation but
only heating is allowed with this thermal comfort control
type.
CASE (Single Thermal Comfort Heating Setpoint:Fanger)
TempControlType(ZoneNum)= SingleHeatingSetpoint
TempZoneThermostatSetPoint(ZoneNum) = Calculated Zone Setpoint from Fanger heating setpoint PMV
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling
case there would be a cooling only thermal comfort setpoint
temperature. The setpoint is calculated based on the selected
thermal comfort model and varied throughout the simulation but
only cooling is allowed with this thermal comfort control
type.
CASE (Single Thermal Comfort Cooling Setpoint:Fanger)
TempControlType(ZoneNum)= SingleCoolingSetPoint
TempZoneThermostatSetPoint(ZoneNum) = Calculated Zone Setpoint from Fanger cooling setpoint PMV
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling
there would be heating and cooling thermal comfort zone
control objects. The setpoint is calculated based on the
selected thermal comfort model and varied throughout the
simulation for both heating and cooling. With this thermal
comfort control type only 1 setpoint profile is needed or
used.
CASE (Single Thermal Comfort Heating Cooling Setpoint:Fanger)
TempControlType(ZoneNum)= SingleHeatCoolSetPoint
TempZoneThermostatSetPoint(ZoneNum) = Calculated Zone Setpoint from Fanger heating and cooling
setpoint PMV
For ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint
there would be heating and cooling thermal comfort control
objects. For this case both a heating and cooling setpoint can
be calculated based on the selected thermal comfort model for
any given time period. The thermal comfort setpoint
temperature can be varied throughout the simulation for both
heating and cooling.
CASE (Dual Thermal Comfort Setpoint with Deadband:Fanger)
TempControlType(ZoneNum)= DualSetPointWithDeadBand
ZoneThermostatSetPointLo(ZoneNum) = Calculated Zone Setpoint from Fanger heating setpoint PMV
ZoneThermostatSetPointHi(ZoneNum) = Calculated Zone Setpoint from Fanger cooling setpoint PMV
Zone Controls[LINK]
Thermostatic Zone Control[LINK]
The input object ZoneControl:Thermostat provides a way for the zone to be controlled to a specified temperature. ZoneControl:Thermostat references a control type schedule and one or more control type objects which in turn reference one or more setpoint schedules.
The control type schedule and the list of control type/name pairs are directly related. The schedule defines the type of control that is to be used during for each hour. Valid control types are
0 - Uncontrolled (No specification or default)
1 - Single Heating Setpoint
2 - Single Cooling SetPoint
3 - Single Heating/Cooling Setpoint
4 - Dual Setpoint (Heating and Cooling) with deadband
If the schedule referenced in the ZoneControl statement has a value of 4 for a particular hour, this indicates that during that hour “dual setpoint with deadband control” is to be used. The specific “dual setpoint with deadband” control object to be used is specified in the list of control type/name pairs. Then the specific control type objects reference the thermostat setpoint temperature schedule to be used. Because only one control can be specified for each control type in a ZoneControl statement, there are only four pairs possible in a particular ZoneControl type/name list. This is because individual controls can be defined hourly, thus giving the user a full range of flexibility. Since putting in the name of the control type directly in the schedule would be very cumbersome, the control types are assigned a number which is used in the hourly schedule profile.
For more information see ZoneControl:Thermostat in the Input Output Reference and succeeding sections in this document.
Zone Thermostats[LINK]
The schema for the current set of four zone thermostats is given below. In each case, the keyword is accompanied by an identifying name and either one or two schedule names (depending on whether the control is a single or dual setpoint control). The schedule defines a temperature setpoint for the control type. The schedule would be defined through the standard schedule syntax described earlier in this document. For an uncontrolled zone no thermostat is specified or necessary. See the Input Output Reference for more details.
The control type schedule and the list of control type/name pairs are directly related. The schedule defines the type of control that is to be used during for each hour. Valid Control Types are
For the Uncontrolled case no heating or cooling requirement is calculated for the system to meet.
For the Single Heating Setpoint there would be a heating only thermostat. The setpoint can be scheduled and varied throughout the simulation but only heating is allowed with this control type.
For the Single Cooling Setpoint there would be a cooling only thermostat. The setpoint can be scheduled and varied throughout the simulation but only cooling is allowed with this control type.
For the Single Heat Cool Setpoint there would be a cooling only thermostat there would be a heating and cooling thermostat. The setpoint can be scheduled and varied throughout the simulation for both heating and cooling. With this control type only 1 setpoint profile is needed or used.
For Dual Setpoint with DeadBand there would be a heating and cooling thermostat. For this case both a heating and cooling setpoint can be scheduled for any given time period. The setpoint can be scheduled and varied throughout the simulation for both heating and cooling.
Operative Temperature Control[LINK]
The input object ZoneControl:Thermostat:OperativeTemperature provides a model where the behavior of the zone thermostats described above can be modified to accommodate operative temperature control. The ZoneControl:Thermostat:OperativeTemperature input object is used to modify the behavior of any of the thermostatic control types described above. When this object is used, the zone can be controlled by a weighted mixture of radiant and air temperatures (rather than just zone air temperatures).
In EnergyPlus, operative temperature,
, is defined as ,
where,
The radiative fraction
is
selected by the user and can be scheduled to vary during the
simulation. A typical value is 0.5. The maximum value needs to
be less than 0.9 and the minimum is 0.0. A value of 0.0 is the
same as controlling on only zone air temperature. If air
velocities are higher than 0.2 m/s, then lower values for
radiative fraction might apply. Niu and Burnett (1998) cite
International Standard ISO 77300 in recommending the values
for this fraction listed in the following table.
The control is accomplished using the load to setpoint formulation that is fundamental to HVAC system control in EnergyPlus. Although real systems will not know the loads and operate on temperature-based control, EnergyPlus needs to be able to function at zone timesteps up to one hour and this is too long of a timeframe for true temperature-based zone control. Load-based control is an important method of determining the average HVAC system response to zone conditions over the time step. For operative temperature control, the same methods and routines are used for calculating loads to setpoints but the setpoints are shifted to emulate operative temperature control rather than air temperature control.
The user-defined setpoint for
is an input in degrees Celsius.
is continually modeled by
the full zone heat balance method and includes all the
interactions between thermal loads and HVAC systems. A new
setpoint for the zone’s
is
obtained for each zone timestep by rearranging the definition
of
to put
on the left hand side.
This adjustment to the target zone air drybulb temperature is made every timestep for every zone immediately after the setpoints are obtained from the schedule.
Reference: J. Niu and J. Burnett. 1998. Integrating Radiant/Operative Temperature Controls into Building Energy Simulations. ASHRAE Transactions Vol. 104. Part 2. page 210. ASHRAE. Atlanta, GA.
Temperature And Humidity Control[LINK]
The input object ZoneControl:Thermostat:TemperatureAndHumidity is used to modify the behavior of ZoneControl:Thermostat objects (control types ThermostatSetpoint:SingleCooling and ThermostatSetpoint:DualSetpoint only) based on zone air humidity conditions. Specifically, this TemperatureAndHumidity zone control resets the ZoneControl:Thermostat’s cooling setpoint temperature downward when the zone air relative humidity exceeds the Dehumidifying Relative Humidity Setpoint defined in this object. The reduced cooling setpoint temperature typically results in longer cooling coil runtimes and additional dehumidification. While additional dehumidification (lower absolute humidity level in the zone air) may be achieved, the resulting dry-bulb temperature and absolute humidity of the zone air will determine if the zone air relative humidity is reduced.[LINK]
The rate at which the cooling setpoint temperature is reduced is dictated by the user-specified Overcool Control Ratio. The maximum reduction in cooling setpoint temperature is defined by the user-entered Overcool Range, although the Overcool Range may be reduced from the user-defined value when this TemperatureAndHumidity control is used in tandem with a dual setpoint thermostat (see discussion below). Note that occupants are sensitive to overcooling and can experience discomfort if the overcool range is too large.[LINK]
This control is accomplished using the load to setpoint formulation that is fundamental to HVAC system control in EnergyPlus. Although real systems will not know the loads and operate on temperature-based control, EnergyPlus needs to be able to function at zone timesteps up to one hour and this is too long of a timeframe for true temperature-based zone control. Load-based control is an important method of determining the average HVAC system response to zone conditions over the time step. For TemperatureAndHumidity control, the same methods and routines are used for calculating loads to setpoints but the cooling setpoint is shifted to emulate TemperatureAndHumidity control, as described above.
The overcool range limits the extent of the zone air temperature reduction below the cooling setpoint. When a dual setpoint thermostat is being modified by this TemperatureAndHumidity control, the maximum overcool range must be less than or equal to the temperature difference between the dual setpoint thermostat’s cooling and heating setpoints:
where,
If a single cooling setpoint thermostat is being modified by this control, the maximum overcool range is equal to the user-defined overcool range.
The extent that the zone air relative humidity exceeds the user-entered dehumidifying relative humidity setpoint is given by:
The actual cooling setpoint reduction (overcooling) is calculated for the condition when the zone air relative humidity exceeds the dehumidifying setpoint (i.e.,
>0), as described below:
The cooling setpoint temperature is then adjusted as follows:
This adjusted cooling setpoint temperature is made every timestep for every zone immediately after the original thermostat setpoint is obtained from the user-defined setpoint schedule.
Humidistat[LINK]
The input object ZoneControl:Humidistat provides a way for the zone to be controlled to a single relative humidity setpoint schedule, or dual humidity schedules (humidifying and dehumidifying with deadband). The schedules consist of relative humidities, expressed as a percentage (0-100), to be used for the zone moisture prediction calculation. Only one control statement can be specified for each zone. Individual relative humidity values can be defined for every time step, thus giving the user a full range of flexibility. For a single setpoint humidistat, if the control relative humidity is below the calculated load and the equipment specified can humidify then that equipment will try and meet the requirement. The opposite is true if the calculated value is above the setpoint and the equipment can dehumidify. For a dual setpoint humidistat, if the zone relative humidity is below the humidifying relative humidity setpoint and the equipment specified can humidify then that equipment will try and meet the zone’s humidification load. The opposite is true if the zone relative humidity is above the dehumidifying relative humidity setpoint and the equipment can dehumidify.
If the ZoneControl:Humidistat is used by a furnace or unitary system then no other objects are required. The signal from the humidistat is used directly by that component. If the Zone Control:Humidistat is used to control a Humidifier or used in conjunction with the Controller:Simple object with control variable “TemperatureAndHumidityRatio”, then either the “SetpointManager:SingleZone:Humidity:Minimum”, “SetpointManager:MultiZone:Humidity:Minimum”, “SetpointManager:SingleZone:Humidity:Maximum” or “SetpointManager:MultiZone:Humidity:Maximum” objects are required to determine a setpoint for those components to meet for the single setpoint humidistat. For a dual setpoint humidistat, a minimum humidity setpoint manager object (“SetpointManager:SingleZone:Humidity:Minimum” or “SetpointManager:MultiZone:Humidity:Minimum”) and a maximum humidity setpoint manager object (“SetpointManager:SingleZone:Humidity:Maximum” or “SetpointManager:MultiZone:Humidity:Maximum”) are required to determine the setpoints for the corresponding humidification and dehumidification components. Note that the “SetpointManager:Scheduled” object can also be used to directly set humidity ratio setpoints on the exit node of the humidifier component.
For the single setpoint humidistat case, the model takes into account all of the moisture gains and/or losses from sources except the HVAC system contribution, and then calculates a moisture removal or addition rate based on the provided setpoint value, like the temperature predictor. The algorithm uses a 3rd Order derivative to predict zone moisture addition or removal to smooth the changes using the zone air capacitance. Positive values of moisture load mean that this amount of moisture must be added to the zone to reach the setpoint. Negative values represent the amount of moisture that must be removed by the system.
This routine also calculates the zone required humidity ratio, Wsetpoint, which is required and takes into account the zone multiplier. At this time the Wsp is not stored in a derived type to make it available for SetpointManagers. It was setup to be analogous to the temperature thermostat.
For the dual setpoint humidistat case, the model takes into account all of the moisture gains and/or losses from sources except the HVAC system contribution, and then calculates moisture addition and removal rates based on the provided humidifying and dehumidifying setpoint values, like the temperature predictor. The algorithm uses a Third Order Backward Difference , Analytical Solution, or Euler Method in subroutine CalcPredictedHumidityRatio to predict zone moisture addition and removal to smooth the changes using the zone air capacitance. The program calculates the humidifying (addition) and dehumidifying (removal) moisture loads based on the specified humidifying and dehumidifying setpoints, respectively. The calculated humidifying moisture load is passed to subroutine CalcSingZoneMinHumSetPoint and CalcMultiZoneMinHumSetPoint in the SetpointManager module to calculate the requested supply air humidity ratio at the setpoint node (Ref. SetpointManager:SingleZone:Humidity:Minimum and SetpointManager:MultiZone:Humidity:Minimum objects). The calculated dehumidifying moisture load is passed to subroutine CalcSingZoneMaxHumSetPoint and CalcMultiZoneMaxHumSetPoint in the SetpointManager module to calculate the requested supply air humidity ratio at the setpoint node (Ref. SetpointManager:SingleZone:Humidity:Maximum and SetpointManager:MultiZone:Humidity:Maximum objects). At the same time, the dehumidifying load is also passed directly to a furnace or unitary system if it is defined for the simulation, and that system will operate to meet this load based on its configuration and control settings.
Thermal Comfort Zone Control[LINK]
The input object ZoneControl:Thermostat:ThermalComfort provides a way for the zone to be controlled to a specified temperature based on a selected thermal comfort model. ZoneControl:Thermostat:ThermalComfort references a thermal comfort control type schedule and one or more thermal comfort control type objects which in turn reference one or more setpoint schedules.
The thermal comfort control type schedule and the list of thermal comfort control type/name pairs are directly related. The schedule defines the type of thermal comfort control that is to be used during for each simulation time step. Valid Control Types are
If the schedule referenced in the ZoneControl statement has a value of 4 for a particular time step, this indicates that during that time step “ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint” control is to be used. The specific “ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint” control object to be used is specified in the list of thermal comfort control type/name pairs. Then the specific thermal comfort control type objects reference the thermal comfort PMV setpoint schedule to be used. Because only one thermal comfort control can be specified for each thermal comfort control type in a ZoneControl statement, there are only four pairs possible in a particular ZoneControl type/name list. This is because individual thermal comfort controls can be defined for specific times, thus giving the user a full range of flexibility. Since putting in the name of the thermal comfort control type directly in the schedule would be very cumbersome, the thermal comfort control types are assigned a number which is used in the schedule profile.
For more information see ZoneControl:Thermostat:ThermalComfort in the InputOutput Reference and Zone Fanger Thermal Comfort in the Engineering Documentation.
Zone Control Based on Fanger Thermal Comfort[LINK]
The syntax for the current set (4) of zone thermal comfort control types is given below. In each case, the keyword is accompanied by an identifying name and either one or two schedule names (depending on whether the control type is a single or dual setpoint control). The schedule defines a PMV setpoint for the control type. The schedule would be defined through the standard schedule syntax described earlier in this document. For an uncontrolled thermal comfort zone, no Fanger thermal comfort object is specified or necessary. See the Input Output Reference for more details.
The control type schedule and the list of control type/name pairs are directly related. The schedule defines the type of control that is to be used during for each hour. Valid Control Types are
For the no thermal comfort control (uncontrolled) case, the control will revert to thermostat control if specified. If the thermal comfort control is specified as “uncontrolled” for a particular period and thermostat control is not specified in the input, then conditions will float.
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleHeating case there would be a heating only thermal comfort setpoint temperature. The setpoint is calculated based on the selected thermal comfort model and varied throughout the simulation but only heating is allowed with this thermal comfort control type.
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleCooling case there would be a cooling only thermal comfort setpoint temperature. The setpoint is calculated based on the selected thermal comfort model and varied throughout the simulation but only cooling is allowed with this thermal comfort control type.
For the ThermostatSetpoint:ThermalComfort:Fanger:SingleHeatingOrCooling there would be heating and cooling thermal comfort zone control objects. The setpoint is calculated based on the selected thermal comfort model and varied throughout the simulation for both heating and cooling. With this thermal comfort control type only 1 setpoint profile is needed or used.
For ThermostatSetpoint:ThermalComfort:Fanger:DualSetpoint there would be heating and cooling thermal comfort control objects. For this case both a heating and cooling setpoint can be calculated based on the selected thermal comfort model for any given time period. The thermal comfort setpoint temperature can be varied throughout the simulation for both heating and cooling.
Documentation content copyright © 1996-2026 The Board of Trustees of the University of Illinois and the Regents of the University of California through the Ernest Orlando Lawrence Berkeley National Laboratory. All rights reserved. EnergyPlus is a trademark of the US Department of Energy.
This documentation is made available under the EnergyPlus Open Source License v1.0.